This document is a Limited Destructive Asbestos and Lead-Based Paint Sampling Report for the Jesse Brown Veterans Administration Medical Center (JBVAMC) in Chicago, prepared by Indoor Air Quality Diagnostics, Inc. on August 26, 2022. The report details a comprehensive sampling investigation conducted from July 12-14, 2022, which involved collecting 174 samples of suspect asbestos-containing materials (ACMs) and lead-based paint (LBP) across multiple buildings and locations related to the EHRM Infrastructure Upgrades project.

Key findings include the detection of asbestos in 19 out of 174 samples analyzed, with laboratory testing performed using polarized light microscopy. Additionally, XRF analysis revealed lead in 27 of 148 surface samples, with 10 surfaces classified as lead-based paint (>1.0 mg/cm2). The sampling was performed by an IDPH Certified Asbestos Inspector and conducted in accordance with EPA and Illinois Environmental Protection Agency (IEPA) regulations, focusing on identifying materials that could potentially become friable during renovation activities. The report is part of the preparation for the EHRM Infrastructure Upgrades project at the Jesse Brown VA Medical Center, which is being managed by the Department of Veterans Affairs Technology Acquisition Center Austin.

View the file

Other files

File Type Posted
36C77625B0049 0009.docx DOCX document
Attachment 2 - Abstract of Bids Chicago Pg 2 of 2.pdf PDF
Attachment 1 - Abstract of Bids Chicago Pg 1 of 2.pdf PDF
36C77625B0049 0008.docx DOCX document
Attachment 2 - Specification Section 07 27 26 - Chicago EHRM - 537-21-700.pdf PDF
Attachment 1 - RFI Responses - Chicago EHRM - 537-21-700.xlsx XLSX spreadsheet
Attachment 4 - Blast Design and Physical Security Rpts - Chicago EHRM - 537-21-700.pdf PDF
Attachment 3 - Phasing MEP Narrative and Product Data - Chicago EHRM - 537-21-700.pdf PDF
36C77625B0049 0007.docx DOCX document
S06 - 36C77625B0049 0006 - Chicago EHRM.docx DOCX document
Attachment 1 - Attachment 16 - WD - IL20250009 Rev 11 - 10-3-25.pdf PDF
36C77625B0049 0005.docx DOCX document
Attachment 2 - Attachment 16 - WD - IL20250009 Rev 10 - 9-19-25.pdf PDF
36C77625B0049 0004.docx DOCX document
Attachment 1 - 2nd Sign-In Sheet - 537-21-700 EHRM IU - Chicago 9-29-25.pdf PDF
36C77625B0049 0003.docx DOCX document
Attachment 2 - 2nd Site Visit Instructions - Jesse Brown VAMC.docx DOCX document
36C77625B0049 0002.docx DOCX document
Attachment 1 - Sign-In Sheet - 537-21-700 EHRM IU - Chicago 9-17-25.pdf PDF
Attachment 1 - Addendum 01 Jesse Brown EHRM Infrastructure Upgrades.pdf PDF
36C77625B0049 0001.docx DOCX document
Attachment 10 - 537-21-700 Site Plan - Ogden Bldg.pdf PDF
Attachment 17 - Site Visit Instructions - Jesse Brown VAMC.pdf PDF
Attachment 7 - 537-21-700 Site Plan - Atrium Bldg.pdf PDF
Attachment 6 - 537-21-700 JBMC EHRM - Drawings - Set 3.pdf PDF
Attachment 13 - Geotechnical Report JBVAMC Additions_9-21-2023.pdf PDF
Attachment 5 - 537-21-700 JBMC EHRM - Drawings - Set 2_Part2.pdf PDF
Attachment 3 - 537-21-700 JBMC EHRM Specifications - Vol 2.pdf PDF
Attachment 4 - 537-21-700 JBMC EHRM - Drawings - Set 1_Part2.pdf PDF
Attachment 5 - 537-21-700 JBMC EHRM - Drawings - Set 2_Part1.pdf PDF
Attachment 8 - 537-21-700 Site Plan - Bed Tower Bldg.pdf PDF
36C77625B0049.docx DOCX document
Attachment 16 - WD - IL20250009 Rev 9 - 8-22-25.pdf PDF
Attachment 4 - 537-21-700 JBMC EHRM - Drawings - Set 1_Part3.pdf PDF
Attachment 11 - 537-21-700 Site Plan - Taylor Bldg.pdf PDF
Attachment 12 - 537-21-700 PRA EHRM JBMC 1st FL DEMO-ICRA.pdf PDF
Attachment 9 - 537-21-700 Site Plan - Damen Bldg.pdf PDF
Attachment 15 - JA - 537-21-700 - JBMC EHRM Infra Upgrades.pdf PDF
Attachment 4 - 537-21-700 JBMC EHRM - Drawings - Set 1_Part1.pdf PDF
Attachment 4 - 537-21-700 JBMC EHRM - Drawings - Set 1_Part4.pdf PDF
Attachment 1 - VA Notice of Limitations on Subcontracting-Cert of Compliance for Construction.docx DOCX document
Attachment 2 - 537-21-700 JBMC EHRM Specifications - Vol 1.pdf PDF
Show all 42

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

www.iaqdiagnostics.com

Indoor Air Quality Diagnostics, Inc.

11611 W. North Ave; Ste 203 Office: (414) 766-0740 Wauwatosa, WI 53226 info@iaqdiagnostics.com

• Indoor Air Quality

• Mold & Allergens

• Bacteria & Chemicals

• Asbestos & Lead

• Water-Loss Consulting

• Thermal Imaging

• Industrial Hygiene

August 26, 2022

Project #: A.0038696.0622

The Reese Group Tina Reese 13615 Hwy 32/64 Mountain WI 54149

Limited Destructive Asbestos and Lead-Based Paint Sampling

(Jesse Brown VAMC EHRM Infrastructure Upgrades)

At the request of The Reese Group (‘CLIENT’), and with Tina Reese’s authorization, Indoor Air Quality Diagnostics, Inc. (‘IAQ Diagnostics’) performed limited bulk asbestos material and lead based paint (‘LPB’) sampling associated with the proposed EHRM Infrastructure Upgrades (EHRM Project) associated with the Jesse Brown Veterans Administration Buildings (JBVAMC) located at 820 S Damen Ave in Chicago (Cook County), Wisconsin (‘SITE’). The findings from that sampling are outlined in this report.

Background

SITE is a multi-building, multi-story medical complex. Prior to the EHRM Project that impacts multiple locations throughout SITE, CLIENT contracted IAQ Diagnostics to perform a limited destructive asbestos assessment to identify and sample suspect asbestos containing materials (‘ACMs’) focusing on the areas impacted by the EHRM Project

Limited Destructive Asbestos Sampling

The sampling was conducted on July 12th thru 14th, 2022, by IDPH Certified Asbestos Inspector Bret Berglund (IDPH Inspector # 100-04519). In all, one hundred seventy-four (174) samples of suspect ACMs were collected at SITE and analyzed for the presence of asbestos. The samples for each EHRM Project room/location were generally sampled from a concealed location in the aforementioned locations as depicted in the EHRM Drawings presented as Attachment A (asbestos bulk sample numbers are shown in RED and LBP samples in BLUE. Selective photographs of sampled materials are presented as Attachment B.

The sampling for building materials containing asbestos was limited to suspect ACMS that could be impacted as part of the EHRM Project. The sampling was conducted in accordance with Environmental Protection Agency, National Emissions Standards for Hazardous Air Pollutant (NESHAPS); Asbestos NESHAP revision Final Rule I the Federal Register, Volume 55, Number 224, dated November 20, 1990.

In Illinois, the asbestos NESHAP is enforced by the Illinois Environmental Protection Agency (IEPA).

Limited Asbestos & LBP Sampling EHRM Project, JBVAMC, Chicago, IL

The IEPA NESHAP rule dictates that all friable ACMs and non-friable ACMs that would become friable during renovation projects are removed from a building prior to their disturbance. A friable ACM is defined as “any material that contains asbestos in the amount greater than (>) one (1) percent and can be crumbled to powder by hand pressure.” Category II non-friable ACM, typically linoleum and transite or “slate” panels, are generally considered to “become friable” if impacted by restoration activities and must also be removed from the building prior to the restoration.

The IEPA, Illinois Department of Public Health (IDPH), and the Environmental Protection Agency (EPA) define ACM as a material which contains greater than (>) one (1) percent asbestos by qualitative or quantitative analysis techniques. Cook County also regulate asbestos inspections and abatement activities.

Bulk samples of suspect ACMs were analyzed by IAQ Diagnostics using polarized light microscopy (‘PLM’) with dispersion staining techniques in accordance with EPA/600-R-93/116. IAQ Diagnostics is an accredited IHLAP laboratory through the American Industrial Hygiene Associations (‘AIHA’) Bulk Asbestos Proficiency Analytical Testing Program (‘BAPAT’) (Lab ID: 224579). Additional information regarding the samples is presented in TABLE 1.0. Refer to the attached laboratory chain-of-custody forms and laboratory analytical reports.

Asbestos Laboratory Results

According to the laboratory results, analysis of the bulk samples showed asbestos was detected in nineteen

(19) of the one hundred seventy-four (174) samples analyzed. One (1) of the nineteen (19) samples containing asbestos were found to be less than (<) one (1) percent asbestos by point count analysis (see

TABLE 1.0).

TABLE 1.0 Asbestos PLM Results (JBVAMC)1

Sample #: Material

Samples

Locations Layer of Material Asbestos Content

Building 1A

1A-10 2'x4' White Fissured Ceiling Panel Room 1460 White/Grey Ceiling Panel ND 1A-11 2'x4' Tan Pocked Ceiling Panel Room 1460 White/Grey Ceiling Panel ND 1A-12 Drywall System Room 1460 Joint Compound ND

Tan Tape ND Drywall ND

1A-13 4"x4" White Ceramic Wall Tile Room 1460 White Ceramic Wall Tile ND White Grout ND Brown Adhesive ND

1A-14 1"x1" Grey Floor Tile Room 1460 Grey Ceramic Floor Tile ND Grey Grout ND Grey Mortar ND

Black Mastic 2%

Chrysotile (asbestos)

1A-15 Carpet Adhesive Room 2449 Green Adhesive ND 1A-16 4" Grey Vinyl Base + Adhesive Room 2449 Grey Vinyl Base ND

Yellow Adhesive ND 1A-17 2'x4' White Fissured Ceiling Panel Room 2449 White/Grey Ceiling Panel ND 1A-18 Drywall System Room 2449 Joint Compound ND

Tan Tape ND Drywall ND

1A-19 Plaster Room 2449 White Skim Coat ND

Grey Base Coat

ND

Locations Layer of Material Asbestos Content

1A-20 6"x6" White Floor Tile Room 2449 Green Adhesive ND

White Floor Tile ND Black Mastic 2%

Chrysotile 1A-21 6" Black Vinyl Base + Adhesive Room 3449 Black Vinyl Base ND

Brown Adhesive ND 1A-22 12"x12" White w/ Black Floor Tile Room 3449 White Floor Tile ND

Yellow/Black Adhesive 2% Chrysotile

1A-23 Plaster Room 3449 White Skim Coat ND Grey Base Coat ND

1A-24 Drywall System Room 3449 Joint Compound ND Tan Tape ND Drywall ND

1A-25 2'x4' White Fissured Ceiling Panel Room 3449 White/Grey Ceiling Panel ND 1A-26 6" Black Vinyl Base + Adhesive Room 4449 Black Vinyl Base ND

Brown Adhesive ND 1A-27 Carpet Adhesive Room 4449 Green Adhesive ND 1A-28 12"x12" White Floor Tile Room 4449 Green Adhesive ND

White Floor Tile ND Black Mastic ND

1A-29 Plaster Room 4449 White Skim Coat ND Grey Base Coat ND

1A-30 2'x4' White Pocked w/ Pin holed Ceiling Panel

Room 4449 White/Grey Ceiling Panel ND

1A-31 Drywall System Room 4449 Joint Compound ND Drywall ND

1A-32 Red Tile Block + Mortar Room 4449 Red Block ND Grey Mortar ND

1A-33 4" Black Vinyl Base + Adhesive Room 5449 (labeled 5502) Black Vinyl Base ND Clear Adhesive ND

1A-34 Carpet Adhesive Room 5449 (labeled 5502) Black/Brown Adhesive 3% Chrysotile

1A-35 2'x4' White Fissured Ceiling Panel Room 5449 (labeled 5502) White/Grey Ceiling Panel ND 1A-36 Plaster Room 5449 (labeled 5502) White Skim Coat ND

Grey Base Coat ND 1A-37 Drywall System Room 5449 (labeled 5502) Joint Compound ND

Tan Tape ND Drywall ND

1A-38 6" Grey Vinyl Base + Adhesive Room 6449 Grey Vinyl Base ND Tan Adhesive ND

1A-39 Carpet Adhesive Room 6449 Brown Adhesive ND 1A-40 12"x12" Tan/Brown Floor Tile Room 6449 Brown Adhesive ND

Tan Floor Tile ND Black Mastic 5%

Chrysotile 1A-41 2'x4' Fissured + Pin holed Ceiling Panel Room 6449 White/Grey Ceiling Panel ND 1A-42 Drywall System Room 6449 Joint Compound ND

Tan Tape ND Drywall ND

1A-43 Plaster Room 6449 White Skim Coat ND Grey Base Coat ND

Locations Layer of Material Asbestos Content

1A-44 4" Light Brown Vinyl Base + Adhesive Room 7449 Brown Vinyl Base ND

Tan Adhesive ND 1A-45 Carpet Adhesive Room 7449 Brown Adhesive ND 1A-46 12"x12" White w/ Grey Floor Tile Room 7449 Brown Adhesive ND

White Floor Tile ND Black Mastic 2%

Chrysotile 1A-47 2'x4' White Fissured Ceiling Panel Room 7449 White/Grey Ceiling Panel ND 1A-48 Plaster Room 7449 Brown Vinyl Base ND

Tan Adhesive ND 1A-49 Drywall System Room 7449 Joint Compound ND

Tan Tape ND Drywall ND

1A-50 4" Grey Vinyl Base + Adhesive Room 8449 Grey Vinyl Base ND Tan Adhesive ND

1A-51 12"x12" White w/ Grey Floor Tile Room 8449 White Floor Tile ND Black Mastic 2%

Chrysotile 1A-52 12"x12" Brown Floor Tile Room 8449 Brown Floor Tile 5%

Chrysotile Black Mastic 2%

Chrysotile 1A-53 2'x4' White Pocked w/ Pin holed Ceiling

Panel Room 8449 White/Grey Ceiling Panel ND

1A-54 Plaster Room 8449 White Skim Coat ND Grey Base Coat ND

1A-55 Drywall System Room 8449 Joint Compound ND Tan Tape ND Drywall ND

1A-56 Red Block + Mortar Room 8449 Red Block ND Grey Mortar ND

1A-57 4" Grey Vinyl Base + Adhesive Room 9449 Grey Vinyl Base ND Yellow Adhesive ND

1A-58 12"x12" White w/ Grey Floor Tile Room 9449 White Floor Tile ND Black Mastic 2%

Chrysotile 1A-59 2'x4' White Fissured Ceiling Panel Room 9449 White/Grey Ceiling Panel ND 1A-60 Plaster Room 9449 White Skim Coat ND

Grey Base Coat ND 1A-61 Drywall System Room 9449 Joint Compound ND

Tan Tape ND Drywall ND

1A-62 4" Grey Vinyl Base + Adhesive Room 10449 Grey Vinyl Base ND Yellow Adhesive ND

1A-63 12"x12" White w/ Grey Floor Tile Room 10449 White/Grey Floor Tile ND Black/Brown Adhesive 2%

Chrysotile 1A-64 2'x4' White Fissured Ceiling Panel Room 10449 White/Grey Ceiling Panel ND 1A-65 Plaster Room 10449 White Skim Coat ND

Grey Base Coat ND

Locations Layer of Material Asbestos Content

1A-66 Drywall System Room 10449 Joint Compound ND

Tan Tape ND Drywall ND

Building 1B 1B-10 Door Caulk Exterior o/s Room C1507 Black Caulk ND 1B-11 Door Caulk Exterior o/s Room 1573 Beige Caulk 2%

Chrysotile 1B-13 Brick + Mortar Exterior o/s Room 1573 Red Brick ND

Grey Mortar ND 1B-14 4" Grey Vinyl Base + Adhesive Room 4545 Grey Vinyl Base ND

Yellow Adhesive ND 1B-15 2'x4' White Beveled Ceiling Panel Room 4545 White/Grey Ceiling Panel ND 1B-16 Drywall System Room 4545 Joint Compound ND

Yellow Tape ND Drywall ND

1B-17 12"x12" Grey/Blue Floor Tile + Adhesive

Room 4545 Grey/Blue Floor Tile ND Yellow Adhesive ND

1B-18 Plaster Room 4545 White Skim Coat ND Grey Base Coat ND

1B-19 Interior Window Caulk - Brown Room 4545 Brown Caulk ND 1B-20 2'x2' Rough Textured Ceiling Panel Room 2537 White/Grey Ceiling Panel ND 1B-21 Drywall System Room 2537 Joint Compound ND

White Tape ND Drywall ND

1B-22 Plaster Room 2537 White Skim Coat ND Grey Base Coat ND

1B-23 Carpet Adhesive Room 2537 Green Adhesive ND 1B-24 12"x12" White w/ Tan Floor Tile Room 2537 Blue Adhesive ND

White Floor Tile ND Yellow Adhesive ND Grey Leveling Compound ND

1B-25 6" Brown Vinyl Base + Adhesive Room 2537 Brown Vinyl Base ND Yellow Adhesive ND

1B-26 Interior Window Caulk Room 2537 Black Caulk ND 1B-27 Plaster Room 3545 White Skim Coat ND

Grey Base Coat ND 1B-28 2'x2' White Holed & Pin holed Ceiling

Panel Room 3545 White/Grey Ceiling Panel ND

1B-29 4" Grey Vinyl Base + Adhesive Room 3545 Grey Vinyl Base ND Yellow Adhesive ND

1B-30 12"x12" White w/ Brown Floor Tile Room 3545 White Floor Tile ND Yellow Adhesive ND

1B-31 6"x6" White Ceramic Wall Tile Room 3545 White Ceramic Wall Tile ND White Grout ND Grey Adhesive ND

1B-32 Interior Window Caulk Room 3545 White Caulk ND 1B-33 4" Beige Vinyl Base + Adhesive Room 5544B Beige Vinyl Base ND

Yellow Adhesive ND 1B-34 Beige/Tan Sheet Flooring Room 5544B Beige/Tan Sheet Flooring ND

Clear Adhesive ND Grey Leveling Compound ND

Locations Layer of Material Asbestos Content

1B-35 Drywall System Room 5544B Joint Compound ND

Tan Tape ND Drywall ND

1B-36 2'x2' Textured Ceiling Panel Room 5544B White/Grey Ceiling Panel ND Building 11A

11A-10 Window Glazing Room 6232 Black Caulk ND 11A-11 Window Caulk Room 6232 Black Caulk ND 11A-12 Concrete Panel + Mortar Room 6232 Grey Concrete ND

Grey Mortar ND 11A-13 4" Tan Vinyl Base + Adhesive Room 6232 Tan Vinyl Base ND

White Adhesive ND 11A-14 Drywall System Room 6232 Joint Compound ND

Tan Tape ND Drywall ND

11A-15 Laminate Flooring Room 6232 Brown Laminate Flooring ND Clear Adhesive ND Grey Leveling Compound ND

11A-16 Interior Window Caulk Room 6232 Brown Caulk ND 11A-17 Green Carpet Adhesive over Black

Mastic Room 7228 Black Adhesive ND

11A-18 2'x2' White Beveled Ceiling Tile w/ Fissures

Room 7228 White/Grey Ceiling Tile ND

11A-19 Drywall System Room 7228 Joint Compound ND Tan Tape ND Drywall ND

11A-20 4" Brown Vinyl Base + Adhesive Room 7228 Brown Vinyl Base ND Yellow Adhesive ND

11A-21 Brown Carpet Adhesive over Black Mastic

Exterior o/s Room 1248 Brown/Black Adhesive ND

11A-22 2'x4' White Packed Ceiling Tile Exterior o/s Room 1248 White/Grey Ceiling Tile ND 11A-23 6" Black Vinyl Base + Adhesive Exterior o/s Room 1248 Painted Texture ND 11A-24 Drywall System Room 1249A Joint Compound ND

Tan Tape ND Drywall ND

11A-25 Green Carpet Adhesive over Black Mastic

Room 1249A Green/Black Adhesive ND

11A-26 2'x4' White Fissured Ceiling Panel Room 1249A White/Grey Ceiling Panel ND 11A-27 Drywall System Room 1249A Joint Compound ND

Tan Tape ND Drywall ND

11A-28 4" Grey Vinyl Base + Adhesive Room 2234 Grey Vinyl Base ND Tan Adhesive ND

11A-29 Interior Window Caulk Room 2234 Black Caulk ND 11A-30 Ceiling Tile Adhesive Residue Room 2234 Brown Adhesive ND 11A-31 4" Grey Vinyl Base + Adhesive Room 2234 Grey Vinyl Base ND

Tan Adhesive ND 11A-32 2'x4' White Fissured Ceiling Panel Room 3225 White/Grey Ceiling Panel ND 11A-33 Drywall System Room 3225 Joint Compound ND

Tan Tape ND Drywall ND

11A-34 12"x12" White w/ Blue Floor Tile Room 3225 White Floor Tile ND Yellow Adhesive ND Grey Leveling Compound ND

Locations Layer of Material Asbestos Content

11A-35 Interior Window Caulk Room 3225 Black Caulk ND 11A-36 Brown Carpet Adhesive over Black

Mastic Room 4245C Brown Adhesive ND

11A-37 Interior Window Caulk Room 4245C White Caulk ND 11A-38 4" Grey Vinyl Base + Adhesive Room 4245C Grey Vinyl Base ND

Tan Adhesive ND 11A-39 Drywall System Room 4245C Joint Compound ND

Tan Tape ND Drywall ND

11A-40 12"x12" Tan w/ Grey Floor Tile Room 4245C Tan/Grey Floor Tile ND Yellow Adhesive ND

11A-41 2'x4' White Fissured Ceiling Panel Room 4245C White/Grey Ceiling Panel ND 11A-42 Brown Ceiling Tile Adhesive Room 5243 Brown Adhesive ND 11A-43 Green Carpet Adhesive over Black Mastic Room 7228 Green/Yellow Adhesive ND

11A-44 4" Black Vinyl Base + Adhesive Room 7228 Black Vinyl Base ND Yellow Adhesive ND

11A-45 2'x4' White Fissured Ceiling Panel

Room 7228 White/Grey Ceiling Panel ND

11A-45 Drywall System Room 7228 Joint Compound ND Tan Tape ND Drywall ND

Building 11B 11B-10 Door Caulk Exterior 1st Floor Stairs

#8 Black Caulk ND

11B-11 Window Caulk Exterior 1st Floor Stairs #8 Black Caulk ND

11B-12 Brick + Mortar Exterior 1st Floor Stairs #8

Red Brick ND Grey Mortar ND

11B-13 Window Glazing Exterior 1st Floor Stairs #8 Black Glazing ND

11B-14 Door Caulk Interior Stairs #8 1st Floor White Caulk ND 11B-15 Window Caulk Interior Stairs #8 2nd

Floor Black Caulk ND

11B-16 Door Caulk Interior Stairs #8 4th Floor White Caulk ND 11B-17 Window Caulk Interior Stairs #8 4th Floor Black Caulk ND 11B-18 Door Caulk Interior Stairs #8 6th Floor White Caulk ND 11B-19 Window Caulk Interior Stairs #8 6th Floor Black Caulk ND 11B-20 Stair Base Caulk Interior Stairs #8 1st Floor White/Gray Caulk 3%

Chrysotile 11B-21 Stair Base Caulk Interior Stairs #8 4th Floor White/Gray Caulk 3%

Chrysotile 11B-22 Stair Base Caulk Interior Stairs #8 6th Floor White/Gray Caulk 2%

Chrysotile 11B-23 12"x12" White Perforated Fiberglass

Ceiling Tile Interior Stairs #8 7th Floor White/Yellow Ceiling Tile ND

Building 30 30-10 4" Grey Vinyl Base + Adhesive Corridor C1108 Grey Vinyl Base ND

Brown Adhesive ND 30-11 2'x4' White Fissured Ceiling Panel Corridor C1108 White/Grey Ceiling Panel ND 30-12 12"x12" Beige w/ Tan/Grey Floor Tile Corridor C1108 Beige/Grey Floor Tile ND

Black Mastic ND

Locations Layer of Material Asbestos Content

30-13 Drywall System Corridor C1108 Joint Compound ND

Tan Tape ND Drywall ND

30-14 Fire Proofing Corridor C1108 Grey Fireproofing ND 30-15 Interior Door Caulk Corridor C1108 White Caulk ND 30-16 Interior Window Caulk Corridor C1108 Black Caulk ND 30-17 Exterior Caulk (door) Exterior o/s C1108 White Caulk ND 30-18 Exterior Caulk (concrete seam) Exterior o/s C1108 Grey Caulk 2%

Chrysotile 30-19 Exterior Concrete Panel + Mortar Exterior o/s C1108 Grey Concrete ND

White Caulk <0.25% Chrysotile

Building 40 40-10 4" Grey Vinyl Base + Adhesive Room 16T1 (16T1A) Grey Vinyl Base ND

Yellow Adhesive ND 40-11 Drywall System Room 16T1 (16T1A) Joint Compound ND

Tan Tape ND Drywall ND

40-12 Red Fire Stop Room 16T1 (16T1A) Red Caulk ND 40-13 4" Grey Vinyl Base + Adhesive Room 26T1 (26T1A) Grey Vinyl Base ND

Yellow Adhesive ND 40-14 Drywall System Room 26T1 (26T1A) Joint Compound ND

Tan Tape ND Drywall ND

40-15 Red Fire Stop Room 26T1 (26T1A) Red Caulk ND 40-16 Grey Fireproofing Room 26T1 (26T1A) Grey Fireproofing ND 40-17 Drywall System Room 36T1 Joint Compound ND

Tan Tape ND Drywall ND

40-18 Red Fire Stop Room 36T1 Red Caulk ND 40-19 Grey Fireproofing Room 36T1 Grey Fireproofing ND 40-20 Drywall System Room 86T1 Joint Compound ND

Tan Tape ND Drywall ND

40-21 Red Fire Stop Room 86T1 Red Caulk ND 40-22 4" Grey Vinyl Base + Adhesive Room 86T1 Grey Vinyl Base ND

Yellow Adhesive ND 40-23 Grey Fireproofing Room 86T1 Grey Fireproofing ND 40-24 4" Grey Vinyl Base + Adhesive Room 46T1 Grey Vinyl Base ND

Yellow Adhesive ND 40-25 Drywall System Room 46T1 Joint Compound ND

Tan Tape ND Drywall ND

40-26 Red Fire Stop Room 46T1 Red Caulk ND 40-27 Grey Fireproofing Room 46T1 Grey Fireproofing ND 40-28 4" Grey Vinyl Base + Adhesive Room 56T1 Grey Vinyl Base ND

Yellow Adhesive ND 40-29 Drywall System Room 56T1 Joint Compound ND

Tan Tape ND Drywall ND

40-30 Red Fire Stop Room 56T1 Red Caulk ND 40-31 Grey Fireproofing Room 56T1 Grey Fireproofing ND

Locations Layer of Material Asbestos Content

40-32 4" Grey Vinyl Base + Adhesive Room 66T1 Grey Vinyl Base ND

Yellow Adhesive ND 40-33 Red Fire Stop Room 66T1 Red Caulk ND 40-34 Drywall System Room 66T1 Joint Compound ND

Tan Tape ND Drywall ND

40-35 Grey Fireproofing Room 66T1 Grey Fireproofing ND 40-36 4" Grey Vinyl Base + Adhesive Room 76T1 Grey Vinyl Base ND

Yellow Adhesive ND 40-37 Drywall System Room 76T1 Joint Compound ND

Tan Tape ND Drywall ND

40-38 Red Fire Stop Room 76T1 Red Caulk ND 40-39 Grey Fireproofing Room 76T1 Grey Fireproofing ND

Data provided by IAQ Diagnostics ND = none detected PC = point count 1 For complete results, see Asbestos PLM Report (see Attachment C)

Limited Non-Destructive LBP Sampling

The LBP sampling was conducted on July 12th thru 14th, 2022, by Lead Risk Assessor Bret Berglund (Lead Risk Assessor #LRA-1560). Suspect LBP was tested on a limited basis by IAQ Diagnostics using a Thermo Scientific Niton XLp 300 XRF Analyzer (serial #87763). The Thermo Scientific Niton XLp 300 XRF Analyzer is a field portable x-ray fluorescence (‘XRF’) spectrum analyzer capable of identifying lead concentrations in paint which is expressed in milligrams per centimeter squared (mg/cm2). The XRF is calibrated as per manufacturer recommendations before and after use.

The WDNR and WDHS define LBP as a coating with greater than (>) 1.0 mg/cm2 lead by XRF analysis.

XRF Results

According to the XRF results of the coated surfaces evaluated, twenty-seven (27) of one hundred forty-eight (148) samples contained lead. Ten (10) of these surfaces were considered to be LBP (> 1.0 mg/cm2) (see TABLE 2.0)

TABLE 2.0 Lead-Based Paint Results (JBVAMC)

Sample

Location Component Substrate Side1 Color

XRF

Results mg/cm2

Calibration - 7/12/22 2051 --- Pre-Cal --- --- --- 1.0 2052 --- Pre-Cal --- --- --- <0.02 2053 --- Pre-Cal --- --- --- <0.02 2104 --- Post Cal --- --- --- 1.1 2105 --- Post Cal --- --- --- <0.02 2106 --- Post Cal --- --- --- <0.02

Calibration - 7/13/22 2108 --- Pre-Cal --- --- --- 1.0 2109 --- Pre-Cal --- --- --- <0.02 2110 --- Pre-Cal --- --- --- <0.02

Location Component Substrate Side1 Color

XRF

Results mg/cm2

2168 --- Post Cal --- --- --- 1.1 2169 --- Post Cal --- --- --- <0.02 2170 --- Post Cal --- --- --- <0.02

Calibration - 7/14/22 2171 --- Pre-Cal --- --- --- 1.0 2172 --- Pre-Cal --- --- --- <0.02 2173 --- Pre-Cal --- --- --- <0.02 2213 --- Post Cal --- --- --- 1.1 2214 --- Post Cal --- --- --- <0.02 2215 --- Post Cal --- --- --- <0.02

Building 1A 2059 Room 1460 Wall Drywall A Grey <0.02 2060 Room 1460 Wall Ceramic A White 1.0 2061 Room 1460 Floor Ceramic --- Grey <0.02 2062 Room 1460 Door Metal A Grey <0.02 2063 Room 2449 Wall Drywall A Green <0.02 2065 Room 2449 Wall Drywall D Blue <0.02 2066 Room 2449 Wall Plaster B Blue <0.02 2067 Room 2449 Window Trim Wood C Blue 3.8 2068 Room 2449 Window Metal C Brown <0.02 2069 Room 2449 Door Wood A Varnish <0.03 2070 Room 3449 Window Casing Wood C Beige <0.02 2071 Room 3449 Window Metal C Brown <0.02 2072 Room 3449 Wall Drywall D White <0.04 2073 Room 3449 Wall Plaster B White <0.05 2074 Room 4449 Door Metal A White 0.18 2075 Room 4449 Wall Plaster A White <0.02 2076 Room 4449 Wall Drywall D White <0.02 2077 Room 4449 Window Casing Wood C White <0.02 2088 Room 4449 Window Metal C Brown <0.02 2089 Room 5449 (Labeled 5502) Window Casing Wood C White 0.3 2090 Room 5449 (Labeled 5502) Window Metal C Brown <0.02 2091 Room 5449 (Labeled 5502) Wall Plaster A White <0.03 2092 Room 5449 (Labeled 5502) Wall Drywall D White <0.02 2093 Room 5449 (Labeled 5502) Door Frame Metal A White 0.60 2094 Room 6449 Windowsill Wood C White <0.02 2095 Room 6449 Window Metal C Brown <0.02 2096 Room 6449 Wall Plaster A White <0.02 2097 Room 6449 Wall Drywall D White <0.02 2098 Room 6449 Door Wood A White <0.02 2099 Room 7449 Window Casing Wood C White 0.17 2100 Room 7449 Window Metal C Brown <0.02 2101 Room 7449 Wall Plaster A White 0.06 2102 Room 7449 Wall Drywall D White <0.02 2103 Room 7449 Door Wood A White <0.03 2104 Room 8449 Window Casing Wood C White 0.5 2105 Room 8449 Window Metal C Brown <0.02 2106 Room 8449 Wall Plaster A White 0.05 2107 Room 8449 Wall Drywall D White <0.02

Location Component Substrate Side1 Color

XRF

Results mg/cm2

2108 Room 8449 Door Wood A White <0.02 2109 Room 9449 Wood Casing Wood C White 1.6 2110 Room 9449 Window Metal C Brown <0.02 2111 Room 9449 Wall Plaster A White 0.12 2112 Room 9449 Wall Drywall C White <0.02 2113 Room 9449 Door Wood A White <0.02 2114 Room 10449 Window Casing Wood C White 0.16 2115 Room 10449 Window Metal C Brown <0.02 2116 Room 10449 Wall Plaster A White <0.02 2117 Room 10449 Wall Drywall D White <0.02 2118 Room 10449 Door Wood A Tan <0.02

Building 1B 2174 Room 4545 Wall Drywall C Grey <0.02 2175 Room 4545 Windowsill Wood C White 2.3 2176 Room 4545 Window Metal C Brown <0.02 2177 Room 4545 Radiator Metal C Grey <0.02 2178 Room 2537 Wall Drywall B Grey <0.02 2179 Room 2537 Wall Plaster C Grey 0.09 2180 Room 2537 Window Casing Wood C Grey 3.4 2181 Room 2537 Window Metal C Brown <0.02 2182 Room 2537 Door Casing Metal A Grey <0.02 2183 Room 3545 Wall Plaster C Grey 0.13 2184 Room 3545 Wall Ceramic C White 0.2 2185 Room 3545 Window Metal C Brown <0.02 2186 Room 3545 Window Casing Wood C White 0.5 2187 Room 5544B Wall Drywall B White <0.02 2188 Room 5544B Window Metal B Brown <0.02 2189 Room 5544B Door Wood A Varnish <0.02 2101 Exterior o/s 1573 Rail Metal --- Brown <0.02 2102 Exterior o/s 1573 Overhang Metal --- Red <0.02 2103 Exterior o/s 1573 Post Metal --- Red 0.05

Building 11A 2052 Room 1249A Wall Drywall B Beige <0.02 2054 Room 1249A Window Metal B Brown <0.02 2055 Room 1249A Ceiling Drywall --- White <0.02 2056 Room 2234 Wall Drywall D White <0.02 2057 Room 2234 Window Metal C Brown <0.02 2058 Room 2234 Radiator Metal C White <0.02 2059 Room 2234 Door Wood A Varnish <0.02 2060 Room 2234 Door Frame Metal A Blue <0.02 2061 Room 3225 Wall Drywall C Grey <0.02 2062 Room 3225 Wall Drywall B Purple <0.02 2063 Room 3225 Window Metal C Brown <0.02 2064 Room 3225 Window Casing Wood C Grey <0.02 2065 Room 3225 Radiator Metal C Grey 0.10 2066 Room 3225 Door Wood B Varnish <0.02 2067 Room 3225 Door Casing Metal B Purple <0.02 2191 Room 4245C Wall Drywall C Beige <0.02 2192 Room 4245C Window Casing Wood C White <0.02

Location Component Substrate Side1 Color

XRF

Results mg/cm2

2193 Room 4245C Window Metal A Brown <0.02 2194 Room 4245C Radiator Metal A White <0.02 2195 Room 4245C Door Wood D Varnish <0.02 2196 Room 4245C Door Casing Metal D Beige <0.02 2197 Room 5243 Wall Drywall C Grey <0.02 2198 Room 5243 Window Casing Wood C Grey <0.02 2199 Room 5243 Window Metal C Brown <0.02 2200 Room 5243 Door Wood A Varnish <0.02 2201 Room 5243 Door Casing Metal A Grey <0.02 2202 Room 6232 Wall Drywall A White <0.02 2203 Room 6232 Window Casing Wood B White <0.02 2204 Room 6232 Window Metal B Brown <0.02 2205 Room 6232 Door Wood A Varnish <0.02 2206 Room 6232 Door Casing Metal A Grey <0.02 2207 Room 6232 Radiator Metal A Grey <0.02 2208 Room 7229 Wall Drywall A White <0.02 2209 Room 7229 Window Casing Wood B White <0.02 2210 Room 7229 Door Wood A Varnish <0.02 2211 Room 7229 Door Casing Metal A Grey <0.02 2212 Room 7229 Radiator Metal C Grey <0.02 2011 Exterior Window Metal C Brown <0.02

Building 11B 2012 Stair 8 – 7th Floor Ceiling Tile --- White <0.02 2013 Stair 8 - 1st Floor Door Metal A Grey <0.02 2014 Stair 8 - 1st Floor Door Metal C Grey <0.02 2015 Stair 8 - 1st Floor Door Casing Metal C Grey <0.02 2016 Stair 8 - 1st Floor Wall Block B Grey <0.02 2017 Stair 8 - 1st Floor Rail Metal C Grey 4.2 2018 Stair 8 - 1st Floor Riser Metal D Grey 1.5 2019 Stair 8 - 1st Floor Stringer Metal C Grey 5.5 2020 Stair 8 - 1st Floor Post Metal C Grey 6.1 2021 Stair 8 - 1st Floor Wall Concrete D Grey <0.02 2022 Stair 8 – 2nd Floor Window Metal C Brown <0.02 2023 Stair 8 – 2nd Floor Window Casing Wood C Grey 0.7 2024 Stair 8 – 2nd Floor Pipe Metal B Red 14.2 2025 Stair 8 – 2nd Floor Radiator Metal B Grey 0.13

Building 30 2099 Corridor C1108 Wall Drywall B White <0.02 2100 Corridor C1108 Door Metal C Cream <0.02

Building 40 2126 16T1 Wall Drywall C White <0.02 2127 16T1 Floor Concrete --- Grey <0.02 2128 16T1 Door Casing Metal A Grey <0.02 2129 26T1 Wall Drywall C White <0.02 2130 26T1 Floor Concrete --- Grey <0.02 2131 26T1 Door Casing Metal A Grey <0.02 2132 36T1 Wall Drywall C White <0.02 2133 36T1 Floor Concrete --- Grey <0.02 2134 36T1 Door Casing Metal A Grey <0.02

Location Component Substrate Side1 Color

XRF

Results mg/cm2

2135 36T1 Wall Black B White <0.02 2136 86T1 Wall Block A Grey <0.02 2137 86T1 Wall Drywall D Grey <0.02 2138 86T1 Floor Concrete -- Grey <0.02 2139 86T1 Door Metal A Grey <0.02 2140 46T1 Wall Drywall C White <0.02 2141 46T1 Floor Concrete --- Grey <0.02 2142 46T1 Door Casing Metal A Grey <0.02 2143 56T1 Wall Drywall C White <0.02 2144 56T1 Floor Concrete --- Grey <0.02 2145 56T1 Door Varnish A Grey <0.02 2146 66T1 Wall Drywall C White <0.02 2147 66T1 Floor Concrete --- Grey <0.02 2148 66T1 Door Casing Metal A Grey <0.02 2149 76T1 Wall Drywall C White <0.02 2150 76T1 Floor Concrete --- Grey <0.02 2151 76T1 Door Casing Metal A Grey <0.02

1 The “A” side is the entry door side. The “B”, “C” and “D” sides move clockwise around the room or area

Findings

Asbestos

Building 1A

Samples of the following materials did not contain asbestos:

• 2'x4' White Fissured Ceiling Panel

• 2'x4' Tan Pocked Ceiling Panel

• Drywall System

• 4"x4" White Ceramic Wall Tile

• Green Carpet Adhesive

• 4" Grey Vinyl Base + Adhesive

• Plaster

• 6" Black Vinyl Base + Adhesive

• 12"x12" White Floor Tile

• 2'x4' White Pocked w/ Pin holed Ceiling Panel

• Red Tile Block + Mortar

• 4" Black Vinyl Base + Adhesive

• 6" Grey Vinyl Base + Adhesive

• 2'x4' Fissured + Pin holed Ceiling Panel

• Drywall System

• 4" Light Brown Vinyl Base + Adhesive

• Brown Carpet Adhesive

• 4" Grey Vinyl Base + Adhesive

Samples of the following materials contained less than (<) 1% asbestos verified in accordance with WDNR by PLM point count methodologies:

• None Sampled

Samples of the following friable materials contained greater than (>) 1% asbestos (or were assumed to contain asbestos):

Samples of the following Category II non-friable materials contained greater than (>) 1% asbestos (or were assumed to contain asbestos):

• Transite (assumed/not accessible) - Approximately twenty (20) to twenty-five (25) square feet is assumed to be behind radiator cover beneath each window within each room of the Building 1A project area.

Samples of the following Category I non-friable materials contained greater than (>) 1% asbestos (or were

• Black Mastic Beneath 1"x1" Grey Ceramic Floor Tile/Grout/Mortar – Approximately one hundred seventy (170) square feet in Room 1460.

• Black/Yellow Mastic Beneath 6” by 6” White Floor Tile - Approximately one hundred fifty (150) square feet in Room 2449.

• Black/Yellow Mastic Beneath 12"x12" White w/ Black Floor Tile - Approximately one hundred fifty (150) square feet in Room 3449.

• Black/Brown Carpet Adhesive - Approximately one hundred fifty (150) square feet in Room 5449.

• Black Mastic Beneath 12"x12" Tan/Brown Floor Tile - Approximately one hundred fifty (150) square feet in Room 6449.

• Black Mastic Beneath 12"x12" White w/ Grey Floor Tile - Approximately one hundred fifteen

(115) square feet in Room 8449, approximately one hundred fifty (150) square feet in Room 9449, and approximately one hundred fifty (150) square feet in Room 10449.

• 12” x 12” Brown Floor Tile and Black Mastic - Approximately thirty-five (35) square feet in Room 8449.

Building 1B

• Black Exterior Door Caulk

• Brick + Mortar

• 4" Grey Vinyl Base + Adhesive

• 2'x4' White Beveled Ceiling Panel

• Drywall System

• 12"x12" Grey/Blue Floor Tile +

Adhesive

• Plaster

• Interior Window Caulk - Brown

• 2'x2' Rough Textured Ceiling Panel

• Green Carpet Adhesive

• 12"x12" White w/ Tan Floor Tile

• 6" Brown Vinyl Base + Adhesive

• Interior Window Caulk

• 2'x2' White Holed & Pin holed Ceiling

Panel

• 12"x12" White w/ Brown Floor Tile

• 6"x6" White Ceramic Wall Tile

• Interior Window Caulk

• 4" Beige Vinyl Base + Adhesive

• Beige/Tan Sheet Flooring

• 2'x2' Textured Ceiling Panel

Samples of the following materials contained less than (<) 1% asbestos verified in accordance with WDNR

Samples of the following friable materials contained greater than (>) 1% asbestos (or were assumed to

Samples of the following Category II non-friable materials contained greater than (>) 1% asbestos (or were

Samples of the following Category I non-friable materials contained greater than (>) 1% asbestos (or were

• Beige Exterior Door Caulk – Approximately four (4) square feet associated with the Room 1248 Exterior Door

Building 11A

• Window Glazing

• Window Caulk

• Concrete Panel + Mortar

• 4" Tan Vinyl Base + Adhesive

• Drywall System

• Brown Laminate Flooring

• Interior Window Caulk

• Green Carpet Adhesive over Black

Mastic

• 2'x2' White Beveled Ceiling Tile w/

Fissures

• Drywall System

• 4" Brown Vinyl Base + Adhesive

• Brown Carpet Adhesive over Black

Mastic

• 2'x4' White Pocked Ceiling Tile

• 6" Black Vinyl Base + Adhesive

• 4" Grey Vinyl Base + Adhesive

• Interior Window Caulk

• Ceiling Tile Adhesive Residue

• 4" Grey Vinyl Base + Adhesive

• 2'x4' White Fissured Ceiling Panel

• 12"x12" White w/ Blue Floor Tile

• 12"x12" Tan w/ Grey Floor Tile

• Brown Ceiling Tile Adhesive

• Green Carpet Adhesive over Black

Mastic

• 4" Black Vinyl Base + Adhesive

Samples of the following materials contained less than (<) 1% asbestos verified in accordance with WDNR

Samples of the following friable materials contained greater than (>) 1% asbestos (or were assumed to

Samples of the following Category II non-friable materials contained greater than (>) 1% asbestos (or were

Samples of the following Category I non-friable materials contained greater than (>) 1% asbestos (or were

Building 11B

• Exterior & Interior Door Caulk

• Exterior & Interior Window Caulk

• Brick + Mortar

• Exterior Window Glazing

• 12"x12" White Perforated Fiberglass

Ceiling Tile

Samples of the following materials contained less than (<) 1% asbestos verified in accordance with WDNR

Samples of the following friable materials contained greater than (>) 1% asbestos (or were assumed to

Samples of the following Category II non-friable materials contained greater than (>) 1% asbestos (or were

Samples of the following Category I non-friable materials contained greater than (>) 1% asbestos (or were

• Caulk Applied to Stair Base - Approximately one hundred twenty-five (125) square feet.

Building 30

• 4" Grey Vinyl Base + Adhesive

• 2'x4' White Fissured Ceiling Panel

• 12"x12" Beige w/ Tan/Grey Floor Tile

• Fire Proofing

• Interior Door Caulk

• Interior Window Caulk

• Exterior Caulk (door)

Samples of the following materials contained less than (<) 1% asbestos verified in accordance with WDNR

• Exterior Concrete Panel + Mortar

Again, an ACM is defined as a material that contains greater than (>) 1% asbestos by laboratory PLM analysis. According to the IEPA and IDPH materials containing 1% asbestos or less by standard PLM must be verified by PLM point count analysis.

Materials containing less than (<) 1% asbestos may not be regulated (either the removal or waste disposal) by the IEPA or IDPH. However, at least portions of the OSHA Asbestos in Construction Standard (1926.1101) still apply when these materials are disturbed.

Samples of the following friable materials contained greater than (>) 1% asbestos (or were assumed to

• None sampled

Samples of the following Category II non-friable materials contained greater than (>) 1% asbestos (or were

• None sampled

Samples of the following Category I non-friable materials contained greater than (>) 1% asbestos (or were

• Exterior Caulk (concrete seam) Not Quantified

Building 40

• 4" Grey Vinyl Base + Adhesive

• Drywall System

• Red Fire Stop

• Grey Fireproofing

Samples of the following materials contained less than (<) 1% asbestos verified in accordance with WDNR

Samples of the following friable materials contained greater than (>) 1% asbestos (or were assumed to

Samples of the following Category II non-friable materials contained greater than (>) 1% asbestos (or were

Samples of the following Category I non-friable materials contained greater than (>) 1% asbestos (or were

Friable, Category I and Category II non-friable ACMs must be removed from the building prior to being disturbed if they are going to be impacted by the renovation project.

Lead Base Paint

Building 1A

According to the XRF results, three (3) of forty-nine (49) coated samples analyzed were considered to be Lead Based Paint (> 1.0 mg/cm2). This included ceramic wall tile (Room 1460) and wood window components in (Rooms 2449, 9449).

Building 1B

According to the XRF results, two (2) of sixteen (16) coated samples analyzed were considered to be Lead Based Paint (> 1.0 mg/cm2). This included wood window components in Rooms 2537 & 4545

Building 11A

None of the building coating sampled were found to be lead-based paint.

Building 11B

None of the building coating sampled were found to be lead-based paint.

Building 30

According to the XRF results, five (5) of seventeen (17) coated samples analyzed were considered to be Lead Based Paint (> 1.0 mg/cm2) This included painted metal stair components (risers, rails, stringer & posts) and the red painted water pipe.

Building 40

None of the building coating sampled were found to be lead-based paint.

Currently the IEPA allows the disposal of building materials bearing LBP in C & D landfills provided the LBP is intact and securely affixed to the substrate to which it was applied. Deteriorated LBP should be removed and/or stabilized (encapsulated) prior to being impacted by demolition activities. Removed paint wastes should be profiled (for potentially hazardous waste disposal requirements) and properly disposed of if they are to be impacted by demolition activities.

If building materials bearing LBP are going to be recycled or used as “clean” fill (such as the ceramic tiles) the lead coatings must be removed prior to recycling or their use as “clean” fill.

Remarks & Limitations

Please note that this sampling event was not part of an asbestos inspection (either limited or comprehensive) of SITE. No other suspected asbestos containing building materials were sampled. Building materials other than wood, glass, metal or fiberglass that were not sampled by IAQ Diagnostics should be presumed to contain asbestos.

Inspections, assessments, and testing performed by IAQ Diagnostics are often non-invasive; therefore, IAQ Diagnostics cannot be held responsible for hidden ACMs.

SITE is not a residential dwelling constructed before 1978 and does not meet the IDPH definition of a child occupied facility. The disturbance of LPB by past and planned renovation activities therefore it is not regulated by the IDPH.

Additionally, it should be noted that undamaged LBP may be present on untested building materials and that further testing of these surfaces may be necessary based on demolition techniques and potential lead exposures. In accordance with OSHA regulations, sampling results should be provided to the contractor completing activities that will disturb any paint or other coated surfaces potentially containing lead so potential lead exposure assessment can be completed. Where lead is present, it should be assumed that workers will be exposed to lead above the action level and personal protective measures should be implemented until an exposure assessment is completed in accordance with OSHA regulation 29 CFR 1926.62.

The findings documented in this report are only valid at the time of its design.

IAQ Diagnostics may have used information supplied by CLIENT, SITE staff, etc. for the design of this report; therefore, IAQ Diagnostics cannot be held responsible for any damages (indirect or consequential) as a result of that misinformation or omissions of information.

No warranty is either expressed or implied in this document.

Please see attached sampling and certification data. Feel free to contact me at 262.227.3722 if you should have questions.

Submitted by:

Bret D. Berglund Asbestos Inspector AII-1560 Lead Risk Assessor LRA-1560

Attachments: Figures Photographs Laboratory Reports (Asbestos PLM Reports) Copies of IDPH Asbestos Inspector and Lead Risk Assessor Certification Cards

ATTACHMENT A

FIGURES

CONFERENCE

LUNCH RM

LOCKERS

1264A

STAFF

TOILET

CLEAN

STORAGE

(DRY)

CLEAN

STORAGE

(WET)

WAREHOUSE

MAIL ROOM

SHAFT

NURSE MGR

SOCIAL

WORKER

CHAIR

STATION

CUBICLES

CLEAN

STORAGE

ALCOVE

1266A

CHAIR

STATION

CUBICLES

1259A

CORRIDOR

TEMPORARY

NURSES

STATION

TEMPORARY

SOILED

UTILITY

PATIENT

TOILET

CHIEF

PHYSICIAN

IRM

12T1MECH ROOM

MAIN

ENTRANCE

WATER

TREATMENT

STORAGE

PATIENT

WAITING

AREA

WHEELCHAIR

STORAGE

1249A

BIO-MED

REPAIR

IRM

STORAGE

MECH

FAC

ELECTRICAL

12E2

TELEPHONE

CANTEEN

STORAGE

REFR

REFR

STORAGE

1210B

CONFERENCE

RM

OFFICE

STAFF

OFFICE

STAFF

OFFICE

STAFF

OFFICE

OUTPATIENT

PHARMACY

NARCOTIC

VAULT

TOILET

STORAGE

1213A

CORRIDOR

C1203

STORAGE

DISH

WASHING

HAC

CANTEEN

STORAGE

CORRIDOR

C1204

CORRIDOR

C1205

LOADING

DOCK

1280A

VESTIBULE

1275A

Office

ELECTRICAL

ELECTRICAL

LOUNGE

HAC

SUPERVISOR

OFFICE

TELECOM

12T2

PHARMACY

CONSULTATION

1195A

CORRIDOR

C1115

OFFICE

CONSULT

OFFICE

DIETICIAN

OFFICE

SUPV CLINIC

SUPPORT

OFFICE

STORAGE/

COPIER

DERMLITE

RM

RN OFFICE

1200A

BEHAVIORAL

HEALTH LAB

1200B

DERMATOLOGY

EXAM ROOM

URGENT

CARE EXAM

1182A

URGENT

CARE EXAM

1182B

URGENT

CARE EXAM

1162A

STORAGE

OFFICE

OFFICE

102A

CORRIDOR

MEN'S

TOILET

WOMEN'S

TOILET

EXERCISE

AREA

CORRIDOR

PAINT

STORAGE

CARPENTRY

STORAGE

ELECTRICAL

STORAGE

PLUMBING

STORAGE

HVAC

STORAGE

AUDITORIUM

RESIDENT

TEAM

1225A ELECTRICAL

1210C

CORRIDOR

C1207

CHIEF

1238 COPIER/STORAGE

PHARMACY/OFFICE

STAFF

OFFICE

MANAGER

PROCUREMENT

PHARMACIST

OFFICE

EMS HAC

STORAGE

FEMALE

TOILET

MALE TOILET

CORRIDOR

C1203

CORRIDOR

C1206

FAC

1210ASTAIR

STAIR

ELEVATOR

P1A

ELEVATOR

P2A

ELEVATOR

S3A

ELEVATOR

FUTURE

P4A

ELEVATOR

5A

STAIR

KITCHEN

KITCHEN

COOKING

AREA

FOOD SVC

VENDING

CANTEEN

DINING AREA

CORRIDOR

1294A

DERMATOLOGY

EXAM RM

DERMATOLOGY

EXAM RM

DERMATOLOGY

EXAM RM

DERMATOLOGY

EXAM RM

DERMATOLOGY

EXAM RM

EXAM RM

EXAM RM

EXAM RM

EXAM RM

EXAM RM

1181B

EXAM RM

1189A

EXAM RM

URGENT

CARE

CONSULTATION

RM

CORRIDOR

C1112

CORRIDOR

C1111

EXAM RM

URGENT

CARE

EXAM RM

GREEN

CLINIC

1170ELECTRICAL

11E3

EXAM RM

GREEN

CLINIC

EXAM RM

EXAM RM

EXAM RM

GREEN

CLINIC

EXAM RM

EXAM RM

WOMEN'S

TOILET

MEN'S

TOILET

NURSE

OFFICE

NURSE

OFFICE

EXAM RM

EXAM RM

EXAM RM

ELECTRICAL

11E2

EXAM RM

EXAM RM

EXAM RM

EXAM RM

EXAM RM

EXAM RM

CONSULTATION

RM

CORRIDOR

C1110

CORRIDOR

C1109

CORRIDOR

C1107

CORRIDOR

C1106

CORRIDOR

C1108

CASHIER

STORAGE

AGENT

CASHIER

NURSE

OFFICE

NURSE

OFFICE

NURSE

OFFICE

DERMATOLOGY

EXAM RM

ELECTRICAL

11E4

PHARMACY

STAFF

1195B

CLINIC

BREAK RM

EXAM RM

EXAM RM

1161B

EXAM RM

1161A

EXAM RM

EXAM RM

EXAM RM

EXAM RM

EXAM RM

UROLOGY

NURSE

OFFICE

NURSE

OFFICE

EXAM/

SCREENING

EXAM/

SCREENING

EXAM/

SCREENING

ELECTRICAL

11E1

UROLOGY

EXAM RM

EXAM/

SCREENING

GU CLINIC

EXAM RM

EXAM/

SCREENING

GU CLINIC

EXAM RM

C1120

CONSULTATION

RM

URGENT

MAINT

VACANT

TOILET

1139A

URODYNAMIC/

ULTRASOUND

UROLOGY

TREATMENT

PROCEDURE

EXAM/

SCREENING

UROLOGY

OFFICE

HAC

TOILET

CLEAN

SUPPLY

ELECTRICAL

TOILET

DIRTY

UTILITIES

STERILE RM

MINOR OR

SURGY RM

GU CLINIC

EXAM RM

PHARMACIST

EXAM RM

NURSE

OFFICE

TELECOM

11T1

TOILET

DRESSING

RM

LOCKER

CORRIDOR

C1105

RECOVERY

RM

SUPPLY RM

UROLOGY

OFFICE

CLINICS

WOMEN'S

TOILET

MEN'S

TOILET

FLAMABLE

STORAGE

RADIOACTIVE

STORAGE

GENERATOR

RM

1300A

CORRIDOR

CANTEEN

CORRIDOR

C1202

CORRIDOR

C1201

STAIR

OFFICE

1302A

TRANSFORMER

RM

CHIEF

OFFICE

STORAGE

ELEVATOR

P-7B

FUTURE

ELEVATOR

P-6B

ELEVATOR

P-8B

ELEVATOR

P-9B

RESTROOM

ELEVATOR

S-10B

STAIR

TEL PHONE

DATA RM

13T1

TOILET

1345B

CLERICAL

SUPPORT

WAITING

CORRIDOR

INTAKE

NURSE

EXAM RM

EXAM RM

PROC

EXAM RM

EXAM RM

PROC

EXAM RM

ACCESIBLE

STAFF

TOILET

EXAM RM

CORRIDOR

PHYSICIAN

OFFICE

STAIR

STORAGE

ELECTRICAL

CLOSET

FIRE CLOSET

CORRIDOR

SOILED

UTILITY RM

ELECTRICAL

CORRIDOR

C1305

CORRIDOR

C1303

CORRIDOR

C1304

CORRIDOR

C1306

CORRIDOR

C1301

MRI SUITE

STAGING

1345F

HOLDING

1345E

VIEW

1345C

IMAGING

SUPV OFFICE

1345A

OFFICE

MOHS LAB

PHOTO

THERAPY

EQUIP

CLOSET

1345J

MRI EQUIP

1390D

MRI GANTRY

RM

1345I

MALE REST

RM

REST RM

REST RM

STORAGE

HAC

WOMEN'S

TOILET

ELECTRICAL

ELECT.

CORRIDOR

C1302

HAC

PHONE

CLOSET

CORRIDOR

PATHOLOGY

LAB

OUTPATIENT

SPECIMEN

LAB

WAITING RM

SUPV BLOOD

DRAW

OFFICE

1363A

PATH

SUPPLY

1363B

MULTI

PURPOSE

RM

MED CENTER

SAFETY

OFFICER

OFFICE

1363C

OUTPATIENT

RADIOLOGY

WAITING

AREA

REST RM

CONTROL

RM

1379A

ELECTRICAL

STORAGE

STORAGE

STORAGE

STORAGE

1390B

STORAGE

1390C

STAIR

OUTPATIENT

RADIOLOGY

EXAM/TREATMENT

READING RM

COMPUTER

ASST /

ADPAC RPA

OFFICE

DRESSING

RM

DRESSING

RM

OUTPATIENT

RADIOLOGY

EXAM/TREATMENT

CORRIDOR

1376A

DRESS

1345D

SUPPORT

ALCOVE

1345H

CONTROL

RM

1345G

CORRIDOR

C1608

CORRIDOR

C1202B

ENTRANCE

C1101

CORRIDOR

C1102

MEN'S

TOILET

WOMEN'S

TOILET

HEALTH VET

CO-ORDR

CREDIT

UNION

WAITING RM

ELECTRICAL

PHYSICIAN

ASSIST

TRIAGE

TRIAGE

STORAGE

FIRE

CONTROL

PATIENT

ADVOCATE

OFFICE

OPTICAL

WAITING RM

1410B

OPTICAL

DISPENSARY

1410A

ELECTRICAL

SWITCH RM

STAIR

TRIAGE

RECEPTION

AND

ADMISSION

AMBULATORY

CARE SUPV

OFFICE

CHIEF

AMBULATORY

TRAVEL

OFFICE

VTS

MANAGER

ER HALLWAY

1431 MEDICAL

SUPPORT

1431C

ER STORAGE

1431B

TRIAGE

ICE MACH

E D

ATTENDING

TRIAGE

EMS

STORAGE

1431A

TELEPHONE

TRIAGE

NEGATIVE

PRESSURE

TOILET

CLEAN LINEN

EMS

TOILET

CLEAN

SUPPLY

AMBULANCE

DROP-OFF

VESTIBULE

C1408

CORRIDOR

C1407

HAC

CONSULT RM

PAC

CO-ORDR

CHIEF

CONSULT RM

CONSULT RM

CONSULT RM

CONSULT RM

CONSULT RM

ADDICTION

RECEPTION

VIST

CO-ORDR

ER OFFICE

TOILET

EXAM RM

1470A

VEST/STAIR

2B

CORRIDOR

C1445

CORRIDOR

C1406

ELECTRICAL

ER MGR

VESTIBULE

C1116

ER OFFICE

1459A

STAIR

CORRIDOR

C1409

ELEVATOR

P7

ELEVATOR

P8

ELEVATOR

P1

ELEVATOR

P2

ELEVATOR

P3

ELEVATOR

P4

ELEVATOR

S5

ELEVATOR

S6

KEEPING

EQUIP

STORAGE

CORRIDOR

C1404

CORRIDOR

C1402

ROOM

STAIR

5A

NURSE

STATION

EMERGENCY

RM

EXAM RM

1470B

EXAM RM

1470C

EXAM RM

1470D

EXAM RM

1470E

EXAM RM

1470F

EXAM RM

1470G

MEDS

1470H

EXAM RM

1470J

EXAM RM 9

1470KEXAM RM 10

1470L

ON CALL

1491B

EXAM RM 11

1470M

EXAM RM 12

1470N

SOILED

UTILITY

EXAM RM 13

1470P

EXAM RM 14

1470Q

EXAM RM

1470R

ELECTRICAL

14E6

COMM

14T3

OFFICE

1475A

LOUNGE

ELECTRICAL

CLOSET

14E4

TOILET

1491A

WAITING RM

LOGISTICS

AREA

MECH RM

OFFICE

TOILET

1472B

ON CALL

SECRET

OFFICE

MEN'S

TOILET

1473 DOCTOR

OFFICE

TELECOMMUNICATION

STAFF

OFFICE

ELEVATOR

FOYER

ELEVATOR

MECH

STAIR

GAS

STORAGE

1503 TELECOMMUNICATION

RM

14T4

BIOHAZARD

CONTAINER

CORRIDOR

C1401

PHARMACY

IV STORAGE

DONATED

CLOTHING

STORAGE

MORGUE

ELEVATOR

EMS LINEN

RM

EMS

STORAGE

FIRE HOSE

CONTROL

RM

1528B

FIRE ALARM

WAITING RM

CLEAN

SUPPLY

TOILET

1530B

CONSULT RM

TECH WORK

HAC

CONSULT RM

TOILET

GOWNED

WAITING

CONTROL

RM

1530A

CT IMAGING

RM

TOILET

1528A

CLEAN

GAS

CYLINDER

STORAGE

MEN'S

CHANGING

WOMEN'S

CHANGING

CORRIDOR

C1503

CORRIDOR

C1501

CORRIDOR

C1502

CORRIDOR

C1505B

CORRIDOR

C1405

CORRIDOR

C1504

ELECTRICAL

1541B

SECY OFFICE

INPT

HOLDING

CT IMAGING

RM

DIGITAL

RADIOLOGY

CORRIDDOR

C1506

RADIOLOGY /

FLUOROSCOPIC

RM

READING RM

ELECTRICAL

15E4

DIGITAL

RADIOLOGY

ULTRASOUND

PREP/

RECOVERY

RADIOLOGY

SUPPLY

I R READING

RM

1539A

ANTE RM

1538B

CONTROL

RM

1538D

SPECIAL

PROCEDURES

INTERVENTIONAL

1538C

EQUIP RM

1538E

COMMUNICATIONS

1538F

STAIR

TOILET

1538A

CORRIDOR

C1506A

TOILET

1533A

MECH

SWITCHGEAR

RM

STAIRWELL

C1506B

VESTIBULE

1570A

ATS RM

1570C

ELECTRICAL

RM

HAC

TELEPHONE

CLOSET

15T1

SPD SUPV

OFFICE

ELECTRICAL

CLOSET

15E2

SPD

RECEIVING

STORAGE

CHIEF

RADIOLOGY

SECY OFFICE

RADIOLOGY

SVC

OPERATION

MGR

RADIOLOGY

SVC

CONFERENCE

RM

STORAGE

COMPUTER

CABINET

1581A

FAN RM

VESTIBULE

C1507

CORRIDOR

C1510

STAIR

RADIOLOGY

OFFICE

CORRIDOR

C1509

RADIOLOGY

READING RM

RADIOLOGY

OFFICE

RADIOLOGY

OFFICE

RADIOLOGY

OFFICE

RADIOLOGY

OFFICE

RADIOLOGY

SCHEDULING

RADIOLOGY

SVC

UTRASOUND

CORRIDOR

C1505

TOILET

CORRIDOR

C1505C

CORRIDOR

C1511

EVIDENCE

OFFICE VIEW

VESTIBULE

PHYSICAL

SECURITY

1540A

PHYSICAL

SECURITY

1540B

SQUAD RM

OFFICE

CONFERENCE

/ TRAINING

DEPUTY

CHIEF

POLICE

OPERATION

OPERATION

CAPTAIN

STORAGE

1554B

EVIDENCE

STORAGE

1542A

CLOSET

1544A

HOLD CELL

HOLD CELL

POLICE

INVESTIGATION

OFFICE

POLICE

CHIEF

TOILET

1555B

TEL CLOSET

14T2

TOILET

1499A

VESTIBULE

1499B

STAFF

LOCKER

TOILET

STAFF

LOCKER

TOILET

1628 STAFF

LOUNGE

MANUAL

EQUIP WASH

HAC

16H5

SALLY PORT

1635AELEVATOR

P-26

SACRISTY

SOILED

RECEIVING /

DECONTAM

STEAM

STERILIZER

CART WASH

ETO SVC

ETO RM

1639A

PREPARATION

SECURED

ITEMS

CART

STAGING

AREA

1640A

STERILE

SUPPLY

STORAGE

AND DIST

1640B

VESTIBULE

CHAPEL

VESTIBULE

1602A

SECY

BLESSED

SACRAMENT

ELEVATOR

PIT

P-27

FIRE

COMMAND

CENTER

1608 ELEVATOR

MACH RM

STAIR

ESCORT

WAITING RM

WHEELCHAIR

WASH

CHIEF

CHAPLAIN

CHAPLAIN

OFFICE

VENDING

MACH

ELECTRICAL

RM

16E1A

CORRIDOR

C1607

HAC

16H4

MALE TOILET

WOMEN'S

TOILET

TELEPHONE

ALCOVE

HAC

16H6

TOILET

1643A

SPD STAFF

OFFICE

TOILET

1646A

STAFF

LOCKER

SPD CHIEF

STAFF

LOUNGE

STAFF

LOCKER

DINNING

SPACE

VESTIBULE

1652A

EMS

STORAGE

1652B

HAC

16H2

GAS

CYLINDER

STORAGE

EMS OFFICE

STAIR

WASTE RM

STAFF

LOUNGE

STAFF

TOILET

VESTIBULE

WOMEN

STAFF

LOCKER

LINEN CHUTE

RM

16L1

COMM RM

VESTIBULE

MEN STAFF

LOCKER

SHOWER

1662B

TOILET

1662A

PAT TOILET

HOLDING RM

HOLDING RM

HOLDING RM

HOLDING RM

HOLDING RM

HOLDING RM

HOLDING RM

HOLDING RM

HOLDING RM

PAT CLINIC

PAT CLINIC

PAT CLOTH

CLOSET

STORAGE

CLEAN

SUPPLY

PANTRY

PAT TOILET

OFFICE

HOLDING RM

HOLDING RM

SOILED

UTILITY

HOLDING RM

ELEVATOR

OFFICE

PAT TOILET

VESTIBULE

CLEAN

SUPPLY

MINOR

PROCEDURE

MINOR

PROCEDURE

CLEAN LINEN

COMPUTER

TRAINING

SURGY

FAMILY

WAITING

VESTIBULE

BULK

STORAGE

VESTIBULE

1661A

VESTIBULE

1657A

EMS CLEAN

SUPPLY

RECEIVING

16H1

LOBBY

C1606

ELEVATOR

ELEVATOR

ELEVATOR

ELECTRICAL

RM

16E2

COMM RM

16T1

ELEVATOR

ELEVATOR

DISCHARGE

LOUNGE

ELEVATOR

REGISTRATION

SURGY

RECEPTION

HAC

16H3

CONSULT RM

1697B

ELEVATOR

MACH RM

1696A

CONSULT RM

1697A

MED RM

1687A

ELEVATOR

STAIR

15 ELEVATOR

LOBBY

C1604

NURSE

STATION

CORRIDOR

C1603

ELEVATOR

LOBBY

C1602

CORRIDOR

C1601

ELEVATOR

LOBBY

C1605

STAIR

ELECTRICAL

RM

16E1B

FIRE PUMP

RM

MECH PUMP

RM

CORRIDOR

C1113

CORRIDOR

C1114

FAC

ELECCLOSET

14E5

COPY

VESTIBULE

1521A

CORRIDOR

C1508

RECEPTION

ARMORY RM

CLOSET

1541A

CLOSET

1545A

CORRIDOR

C1411

1.1

1.2

1.3

1.5

1.6

1.7

1.10

1.11

1.12

1.13

1.14

1.15

1.20

1.21

1.V

1.O

1.N1.M

1.4

1.J

1.J

2.4

2.4

2.3

2.3

2.2

2.2

2.1

2.1

2.5

2.6

2.7

2.8

2.10

2.9

X8

X8.1

X7

X6.6

X6.5

X9

X10

X11

2.11

X12

2.12

2.13

2.14

2.A

2.C1

X13

X14

2.D

2.C52.A5 2.B

2.B

2.C

2.D9 2.G2.F2.E

3.P

3.N

3.M

3.L

3.K

3.J

3.H

3.G

3.F

3.E

3.A

3.B

3.C

3.D

3.1 3.2 3.3 3.5 3.7 3.8 3.9 3.10 3.11 3.12 3.13 3.173.163.153.14 3.18 3.19 3.20 3.21 3.22 3.23 3.24

5.J1

5.N1

5.U

5.S

5.C

5.10 5.12 5.14 5.16 5.19 5.21 5.23 5.25 5.27 5.30 5.32 5.35 5.38 5.435.41

4.4

4.5

4.3

4.2

4.1

4.D54.C54.A 4.B 4.C 4.D 4.E 4.F

5.N

5.G

5.34 5.37 5.40 5.44 5.44.5 5.49

5.Y

5.BB

1.22

1.I1.H1.G1.F 1.K 1.P 1.Q 1.R 1.S 1.T 1.U

1.19

1.18

1.17

1.16

1.8

1.A 1.B 1.C 1.D 1.E

1.L

VESTIBULE

ELECTRICAL

14E7

EXIT

CORRIDOR

1679A

TOOL

STORAGE

A202

D1

A202 A1

A201

E1

A201C1

TOILET

1472A

ROOM

1479B

ADMIN

OFFICES

1479C

STAIR

OFFICE

1479D

TOTAL CABLE COUNT TO BE SERVED

FROM CLOSET: 312

2 RACKS WILL BE PROVIDED WITH A MIN.

CLOSET SIZE OF 10' X 10'

TOTAL CABLE COUNT TO BE SERVED

FROM CLOSET: 495

2 RACKS WILL BE PROVIDED WITH A MIN.

CLOSET SIZE OF 10' X 17'

TOTAL CABLE COUNT TO BE SERVED

FROM CLOSET: 16

2 RACKS WILL BE PROVIDED WITH A MIN.

CLOSET SIZE OF 10' X 10'

TOTAL CABLE COUNT TO BE SERVED

FROM CLOSET: 477

2 RACKS WILL BE PROVIDED WITH A MIN.

CLOSET SIZE OF 10' X 17'

TOTAL CABLE COUNT TO BE SERVED

FROM CLOSET: 650

3 RACKS WILL BE PROVIDED USING

EXISTING CLOSET SPACE

TOTAL CABLE COUNT TO BE SERVED

FROM CLOSET: 480

2 RACKS WILL BE PROVIDED WITH A MIN.

CLOSET SIZE OF 10' X 17'

TOTAL CABLE COUNT TO BE SERVED

FROM CLOSET: 442

2 RACKS WILL BE PROVIDED WITH A MIN.

CLOSET SIZE OF 10' X 10'

TOTAL CABLE COUNT TO BE SERVED

FROM CLOSET: TBD

2 RACKS WILL BE PROVIDED WITH A MIN.

CLOSET SIZE OF 10' X 17'

1. THE PURPOSE OF THIS OPTION IS TO UTILIZE A COMBINATION OF INTERIOR

AND EXTERIOR TR'S TO MAXIMIZE THEIR COVERAGE WITH THE FEWEST

NUMBER OF ROOMS, AND MINIMIZE THE COST AND OVERALL IMPACT TO

EXISTING FACILITY OPERATIONS. THE NEW TR'S WILL HAVE, PER THE VA OIT

GUIDELINES FOR NEW CONSTRUCTION, A MINIMUM SIZE OF 11' x 17". IT IS

ANTICIPATED THAT THE FOLLOWING QUANTITY OF TR'S WILL BE NEEDED

PER FLOOR:

2. ONE NEW TR IN THE FOLLOWING FLOORS FOR EACH BUILDING:

a. BLDG 11A (TAYLOR): 1ST, 2ND 3RD, 4TH, 5TH, 6TH, AND 7TH FLOORS

b. BLDG 11B (OGDEN): 1ST, 2ND, 3RD, 4TH, 5TH, 6TH, AND 7TH FLOORS.

c. BLDG 30: 1ST FLOOR

d. BLDG 1B (DAMEN WEST): 1ST, 2ND 3RD, 4TH, 5TH, AND 6TH FLOORS

e. BLDG 1A (DAMEN EAST): 1ST, 2ND 3RD, 4TH, 5TH, 6TH, 7TH, 8TH, 9TH, AND 10TH FLOORS

3. IT IS ANTICIPATED THAT THE EXISTING TR'S WILL REMAIN IN THE FOLLOWING

FLOORS FOR EACH BUILDING:

a. BLDG 40: 1ST, 2ND 3RD, 4TH, 5TH, 6TH, 7TH, AND PENTHOUSE

FLOORS

4. THIS OPTION WILL REQUIRE STRUCTURAL AND ARCHITECTURAL CHANGES

TO THE EXTERIOR OF THE BUILDING. IT WILL ALSO REQUIRE INTERIOR

ARCHITECTURAL CHANGES IN ADDITION TO THE MECHANICAL, ELECTRICAL,

AND TECHNOLOGY DUE TO THE ADDITION OF NEW CORRIDORS TO GET

ACCESS TO THE NEW TRs.

TR LOCATION FOR VA REVIEW

ZONE BOUNDARY

EXTERIOR TR TOWER W/RACK

INTERIOR TR

PROPOSED EXIT STAIR

PROPOSED CORRIDOR

T/O NEW TOWER

AREA OUT OF REACH

OF CABLING

DIAMOND OUTLINE COVERAGE

(VA OIT DESIGN GUIDE)

CONCEPT LEGEND

40A

NORTH

1B

1A 11A

11B

TR AREAS

30A

BUILDING 1B CLINICAL

BUILDING 1B NON-CLINICAL

BUILDING 1A CLINICAL

BUILDING 1A NON-CLINICAL

BUILDING 40 CLINICAL

BUILDING 40 NON-CLINICAL

BUILDING 11B CLINICAL

BUILDING 11B NON-CLINICAL

BUILDING 11A CLINICAL

BUILDING 11A NON-CLINICAL

BUILDING 30 CLINICAL

BUILDING 32 CLINICAL

SPACE IDENTIFICATION LEGEND

13890 Bishops Drive, Suite 250 Brookfield, WI 53005

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

NAGEL

project number:

NOT FOR CONSTRUCTIONC

U s e rs

\a le x r\

D o c u m e n ts

\J e s s e B ro w n E

H R

M I n fr a s tr u c tu re U p g ra d e s a le x .r o s n o .r v t

/2

/2

:2 :4

P

M

A101

LEVEL 1 - ARCHITECTURAL JESSE BROWN VAMC EHRM

INFRASTRUCTURE UPGRADES

820 S DAMEN AVE, CHIGAGO, IL 60612

537-21-700

VA BLDG

18 FEB 2022 DE AR, RF

65% DESIGN

DEVELOPMENT

FULLY SPRINKLERED

21011

N O

R T

H

Revisions: Date:

REVISED TOWER LOCATION PER VA 3/28/2022

REVISED TOWER LOCATION FOR REVIEW 4/14/2022

FINAL REVISED TOWER LOCATION FOR…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .