This document is a Basis of Design (BOD) Narrative for Structural Components, prepared by Hohbach-Lewin, Inc. for Bancroft Architects + Engineers, related to the Tier 2 Electronic Health Record Management (EHRM) Infrastructure Upgrades project at the Fargo VA Medical Center in North Dakota. The document details structural design considerations for a new Main Computer Room (MCR) located on the 4th floor of the existing hospital building, which was originally constructed in the 1920s with subsequent additions in the 1950s and 1980s.
The structural design narrative outlines key technical specifications including building codes, design criteria, existing structural materials, loading requirements, and proposed modifications. Primary structural work includes strengthening the existing steel-framed 4th floor by welding additional steel T-sections to increase floor stiffness, potentially reinforcing beam-to-column connections, constructing a concrete retaining wall near the loading dock, and installing an HSS equipment enclosure with metal deck cladding and concrete footings. The design must account for various load requirements, including live loads ranging from 40-250 psf, seismic considerations, and potential blast loading impacts, with a focus on ensuring structural integrity and serviceability for the new electronic infrastructure equipment.
View the file
Other files
Show all 37
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
x
FARGO VA MEDICAL CENTER TIER 2 -
EHRM INFRASTRUCTURE UPGRADES
Fargo, ND
BASIS OF DESIGN - STRUCTURAL
IFB Submittal
(HOHBACH-LEWIN PROJECT #: 16709)
January 16, 2024
Prepared For:
BANCROFT ARCHITECTS + ENGINEERS
3300 DUNDEE RD.
NORTHBROOK, IL 60062
Prepared By:
HOHBACH-LEWIN, INC.
909 MONTGOMERY STREET, SUITE 260
SAN FRANCISCO, CA 94133
TIER 2 – EHRM UPGRADES| FARGO, ND
BASIS OF DESIGN NARRATIVE – STRUCTURAL
IFB SUBMITTAL
JANUARY 16, 2024
PROPERTY OF THE UNITED STATES GOVERNMENT
COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS,
OR SPECIFICATIONS TO UNAUTHORIZED USERS IS PROHIBITED
Do not remove this notice
Properly destroy documents when no longer needed
Table of Contents
INTRODUCTION
BUILDING CODES & DESIGN CRITERIA
PROJECT BACKGROUND
EXISTING STRUCTURES
STRUCTURAL LOADS & SITE-SPECIFIC DESIGN
Dead Loads
Live Loads
Seismic Design
Wind Design
Snow Design
Geotechnical Criteria
Serviceability Criteria
STRUCTURAL DESIGN
IFB SUBMITTAL
JANUARY 16, 2024
PROPERTY OF THE UNITED STATES GOVERNMENT
COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS,
OR SPECIFICATIONS TO UNAUTHORIZED USERS IS PROHIBITED
Do not remove this notice
Properly destroy documents when no longer needed
INTRODUCTION
Hohbach-Lewin, Inc. (Hohbach-Lewin) has been contracted by Bancroft Architects and Engineers (BAE) for structural consulting services for the Tier 2 Electronic Health Record Management (EHRM) infrastructure upgrade project located at the Fargo Veterans Affairs Medical Center (VAMC) located in Fargo, North Dakota. The scope of this effort is to provide a 100% CD Design report that discusses the location for the Main Computer Room (MCR) on the 4th floor of the main hospital building and other supporting equipment requiring structural design.
This 100% submission will provide information and commentary about the Structural Basis of Design, an overview of key assumptions, and outlines the preliminary design concept for the building’s structural system.
BUILDING CODES & DESIGN CRITERIA
The structural design will be performed in accordance with the following building codes, design guides, and VA criteria documents:
U.S. Department of Veterans Affairs, Master Specifications PG-18-1
U.S. Department of Veterans Affairs, VHA Program Guide PG-18-3, September 2013
U.S. Department of Veterans Affairs, National CAD Standards and Detail PG-18-4
U.S. Department of Veterans Affairs, Design Manuals PG-18-10
U.S. Department of Veterans Affairs, Design Submission Requirements PG-18-15C
U.S. Department of Veterans Affairs, VA Directive 7512, August 2017
U.S. Department of Veterans Affairs, Construction Standards H-18-3
U.S. Department of Veterans Affairs, Seismic Design Requirements H-18-8
2018 IBC, International Building Code
ACI 318-19, Building Code Requirements for Reinforced Concrete
ASCE 7-16, Minimum Design Loads for Buildings and Other Structures
AISC 360-16, American Institute of Steel Construction
AISC 325-17, Steel Construction Manual, 15th Edition
AWS D1.1, Structural Welding Code
IFB SUBMITTAL
JANUARY 16, 2024
PROPERTY OF THE UNITED STATES GOVERNMENT
COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS,
OR SPECIFICATIONS TO UNAUTHORIZED USERS IS PROHIBITED
Do not remove this notice
Properly destroy documents when no longer needed
PROJECT BACKGROUND
Figure 1 shows the location of the MCR on the 4th floor of the main hospital building.
Figure 1
Figure 1: Proposed MCR Locations
IFB SUBMITTAL
JANUARY 16, 2024
PROPERTY OF THE UNITED STATES GOVERNMENT
COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS,
OR SPECIFICATIONS TO UNAUTHORIZED USERS IS PROHIBITED
Do not remove this notice
Properly destroy documents when no longer needed
EXISTING STRUCTURES
The hospital was first constructed in the 1920’s, with subsequent building additions and expansion projects through the 1950’s and 1980’s. Much of the level 4 floor framing was constructed in the 1980’s with the initial framing being constructed in 1945. Although full sets of as-built structural drawings have not yet been made available, 1980s level 4 consists of light weight concrete over metal deck supported by wide flange steel beams supported on wide flange steel columns, the 1945 level 4 framing consists of a concrete slab supported by concrete joists. The concrete joists are supported on wide flange steel beams supported by wide flange steel columns.
Sheet S1 of the 1984 structural as-built drawings that were available defines materials properties as noted below:
Concrete (Regular and Light Weight), f’c = 3000 psi per ACI code.
Reinforcing Fs = 24,000 psi ASTM A-615 Grade 60 Structural Steel = ASTM A36 Fabricated per AISC Metal Deck:
Roof = 1 ½” x 22 GA.
Corridor floor = 1 ½” x 18 GA. Composite 4th floor = 1 ½” x 22 GA Composite
Additionally, S1 provided Design Live loads as follows:
Roof – Snow Load = 90 psf (accumulated snow load) Floor (Corridor) = 100 psf Floor (4th floor) = 125 psf
STRUCTURAL LOADS & SITE-SPECIFIC DESIGN
The following provides a summary of loading and site-specific design hazard criteria applicable.
The structural loading in this section is identified for general cases throughout the buildings included in the project scope. Superimposed dead loads and live loads will be further refined for each building during Design Development.
Dead Loads Dead loads will be considered based on the self-weights of existing or new building components. Superimposed dead loads will be identified for each affected location and will be included in the Basis of Design as the design progresses. A superimposed floor dead load of 150 psf is expected to be used for the new MCR.
Live Loads Live loads vary by occupancy, and will be considered as defined by ASCE 7-16. Service-level live loads are provided below:
IFB SUBMITTAL
JANUARY 16, 2024
PROPERTY OF THE UNITED STATES GOVERNMENT
COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS,
OR SPECIFICATIONS TO UNAUTHORIZED USERS IS PROHIBITED
Do not remove this notice
Properly destroy documents when no longer needed
Occupancy Live Load (psf) Patient Rooms 40 Main Computer Room 40 Office 50 Lobbies & Corridors 100 Stairs & Exits 100 Light Storage 125 Heavy Storage 250 Roof 20
Additionally, all floors must be capable of support a 2,000-lbs concentrated load acting over a 2’- 6” x 2’-6” surface.
The cabinets will conservatively be assumed as live loads for evaluation of the structure’s capacity to support the cabinet weights. Additionally, a maximum rated weight (2000 LBS) capacity of the data cabinets will be assumed for the structural design.
Seismic Design the new MCR will be classified as “critical” per VA H-18-8. Per the VA H-18-8 section 2.4 and RP 8 Section 2.1 there is no requirement to do an ASCE 41 seismic evaluation of the existing building.
Wind Design It is not anticipated that the current project scope will trigger evaluation of the existing lateral-force-resisting-system of any building for wind loads.
Snow Design
1. Ground Snow Load (Pg) = 50 psf
2. Thermal Factor (Ct) = 1.0
3. Exposure Factor (Ce) = 1.0
4. Snow Importance Factor (Is) = 1.2
5. Flat Roof Snow Load (Pf) = 42 psf
6. Snow drift to be evaluated upon final MCR location selection by the VA
Geotechnical Criteria Allowable soil bearing pressures will be utilized where listed in available structural as-built drawing notes in the evaluation of existing shallow foundation systems for increased loads from new data equipment. Where adequate allowable soil bearing and/or skin friction values are not available, it is assumed that a Geotechnical Engineer will be contracted to perform site investigation and provide foundation design recommendations.
Allowable soil bearing pressures will be provided in subsequent design phases for each affected building.
Serviceability Criteria Allowable floor deflections will be considered relative to the 2018 IBC deflection limits (see below table).
IFB SUBMITTAL
JANUARY 16, 2024
PROPERTY OF THE UNITED STATES GOVERNMENT
COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS,
OR SPECIFICATIONS TO UNAUTHORIZED USERS IS PROHIBITED
Do not remove this notice
Properly destroy documents when no longer needed
Loading Deflection Limit Live Only L/360 Dead + Live L/240
It is assumed that no structural elements must be designed explicitly for equipment vibration.
Rather, vibration isolators will be provided as necessary and will be designed by the contractor.
STRUCTURAL DESIGN
The following table provides a high-level summary of the structural work. Note that in addition to the structural implications discussed later in this section, blast loading will impact the design of the new MCR and the new equipment necessary for its function. The primary impacts of PSRDM blast design requirements can be found in the Blast – Basis of Design Narrative.
The MCR will require strengthening of the existing steel framed 4th floor. Welding of additional steel T sections to the underside of the existing wide flange steel framing to increase the floor’s stiffness. Additionally, there is a potential that the beam to column connections may need strengthening due to the increased floor loading. Additionally, there will be a concrete retaining wall adjacent to the North loading dock and well as an HSS equipment enclosure with 16GA metal deck cladding and continuous concrete footings and a concrete slab on grade with a housekeeping pad for the required mechanical equipment. See figure 2 below for location of structural work not related to the MCR on the 4th level.
There is also to be some roof top units located adjacent to the MCR on the 3rd floor roof. Exact locations are still to be finalized and any structural retrofits and anchorage required to support that equipment will be designed once roof top equipment selection and location has been finalized.
IFB SUBMITTAL
JANUARY 16, 2024
PROPERTY OF THE UNITED STATES GOVERNMENT
COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS,
OR SPECIFICATIONS TO UNAUTHORIZED USERS IS PROHIBITED
Do not remove this notice
Properly destroy documents when no longer needed
Figure 2