This transmittal document is from Bancroft Architects + Engineers, dated July 22, 2025, for the EHRM Infrastructure Upgrades – Tier 2 project at the Fargo, ND Veterans Affairs Medical Center (VAMC). The transmittal includes two electronic submittal documents for document clarification: Addendum#1_Drawing M-600, which updates the CRAC schedule to indicate -30F low ambient operation, and Addendum#1_Above Air Technologies technical manual for MC2 DX units. The document is submitted to Mr. Clifford Halvorson for VA approval, record, and file, with the contract number 36C26319D0044 and project number 437-21-210. The attached mechanical schedules detail specifications for various HVAC equipment, including duct free split systems, electric suspended heaters, exhaust/supply fans, and computer room air conditioning units, with specific requirements for low ambient operation, accessories, and performance characteristics.
View the file
Other files
Show all 37
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1471 E Business Center Dr #900 | Mt Prospect, IL 60056 California | Connecticut | Colorado | Florida | Illinois | Louisiana | Minnesota | Oklahoma | Pennsylvania | Virginia | Wisconsin
847.952.9362 | www.bancroft-ae.com
TRANSMITTAL
July 22, 2025
To: Mr. Clifford Halvorson Project Name:
EHRM Infrastructure Upgrades – Tier 2
Department of Veterans Affairs Fargo, ND VAMC Contract No.:
36C26319D0044
2101 Elm Street North Station Project No.: 437-21-210 Fargo, ND 58102
Phone: (701) 232-3241 Bancroft-AE No.:
22-113
Ext. 3905
We Transmit: For Your: Response Required:
☐ Attached ☒ Approval ☐ Yes
☐ Under Separate Cover ☐ Review/Comment ☒ No
☐ Via US Mail ☐ Use
☐ Via FedEx ☒ Record/File
☒ Electronic
Contents:
Electronic Submittal Documents for the Document Clarification
Addendum#1_Drawing M-600 – Updated CRAC schedule to indicate -30F low ambient operation.
Addendum#1_Above Air Technologies technical manual for MC2 DX units.
Action Required: Submitted for VA approval / record / file.
Please contact me directly if you have any questions or concerns regarding this submittal.
Walter Groszko wgroszko@bancroft-ae.com
Bancroft Architects + Engineers
Cc: Project File
DUCT FREE SPLIT SYSTEM SCHEDULE
EQUIPMENT
TAG BUILDING NO. LOCATION BASIS OF
DESIGN
COOLING
CAPACITY
(MBH)
HEATING
CAPACITY
(MBH)
HEATING
FLOW RATE
(GPM)
ENTERING WATER
TEMPERATURE
(°F)
INDOOR UNIT OUTDOOR UNIT
NOTES
TYPE WEIGHT
(LBS)
DIMENSIONS (IN.) AIRFLOW FILTERS ELECTRICAL DATA
EQUIPMENT
TAG LOCATION WEIGHT
(LBS)
COMPRESSOR ELECTRICAL DATA
H W D TOTAL
CFM
EAT. D.B.
(°F)
EAT. W.B.
(°F) TYPE MCA MOCP PHASE VOLTS SIZE
(TONS)
REF.
TYPE EAT (°F) MCA MOCP PHASE VOLTS
CCU-BC50A-1 46 STORAGE ROOM BC-50A MODINE 19.2 40.4 4.0 180 CSD18BACBBNDM CEILING CASSETTE 84 32.4 32.4 12 590 80 67 CLEANABLE 0.7 15 1 208 ACCU-BC-50A-1 YC2E18 ROOF 150 1.5 R-410A 90 11.8 20 1 208 1, 2, 3, 4, 5, 6, 7, 8
CCU-BC50A-2 46 STORAGE ROOM BC-50A MODINE 19.2 40.4 4.0 180 CSD18BACBBNDM CEILING CASSETTE 84 32.4 32.4 12 590 80 67 CLEANABLE 0.7 15 1 208 ACCU-BC-50A-2 YC2E18 ROOF 150 1.5 R-410A 90 11.8 20 1 208 1, 2, 3, 4, 5, 6, 7, 8
CCU-BC-50B 46 SPLICE ENCLOSURE ROOM BC-50B MODINE 19.2 40.4 4.0 180 CSD18BACBBNDM CEILING CASSETTE 84 32.4 32.4 12 590 80 67 CLEANABLE 0.7 15 1 208 ACCU-BC-50B YC2E18 ROOF 150 1.5 R-410A 90 11.8 20 1 208 1, 2, 3, 4, 5, 6, 7, 8
CCU-BC-60-1 46 TELEPHONE EQUIPMENT
ROOM BC-50B MODINE 19.2 40.4 4.0 180 CSD18BACBBNDM CEILING
CASSETTE 84 32.4 32.4 12 590 80 67 CLEANABLE 0.7 15 1 208 ACCU-BC-60-1 YC2E18 ROOF 150 1.5 R-410A 90 11.8 20 1 208 1, 2, 3, 4, 5, 6, 7, 8
CCU-BC-60-2 46 TELEPHONE EQUIPMENT
ROOM BC-50B MODINE 19.2 40.4 4.0 180 CSD18BACBBNDM CEILING
CASSETTE 84 32.4 32.4 12 590 80 67 CLEANABLE 0.7 15 1 208 ACCU-BC-60-2 YC2E18 ROOF 150 1.5 R-410A 90 11.8 20 1 208 1, 2, 3, 4, 5, 6, 7, 8
NOTES: 5. PROVIDE THE FOLLOWING FACTORY INSTALLED ACCESSORIES FOR THE OUTDOOR UNIT:
1. ACCEPTABLE MANUFACTURERS: VA APPROVED EQUALS LOW AMBIENT KIT
2. INDOOR UNIT SHALL BE INTERLOCKED TO OUTDOOR UNIT FOR POWER AND CONTROL WIRING. 6. MERV 10 FILTER AND SPARE
3. FACTORY SHROUD FOR EXPOSED CEILING APPLICATION. 7. BACNET CARD
4. PROVIDE DIGITAL WALL STAT, NON-FUSED DISCONNECT, AND CONDENSATE PUMP. 8. INDOOR UNITS PROVIDED WITH HEATING WATER COILS
ELECTRIC SUSPENDED HEATER SCHEDULE
GENERAL HEATER FAN DATA ELECTRICAL DATA
NOTES
EQUIPMENT TAG LOCATION TYPE
MANUFACTURER
BASIS OF DESIGN KW PHASE VOLT TYPE CFM AMPS PHASE VOLT
EUH-1 BUILDING 1 GENERATOR
ROOM BE-98
SUSPENDED
HORIZONTAL MODINE HER200 20 3 208 PROP. 1300 55.6 3 208 1,2,3,4
EUH-2 BUILDING 1 GENERATOR
ROOM BE-98
SUSPENDED
HORIZONTAL MODINE HER200 20 3 208 PROP. 1300 55.6 3 208 1,2,3,4
NOTES:
1. OTHER ACCEPTABLE MANUFACTURERS: VA APPROVED EQUAL
2. DISCONNECT SWITCH.
3. MOUNTING KIT TO MATCH MOUNTING REQUIREMENTS.
4. FAN DELAY SWITCH.
EXHAUST / SUPPLY FAN SCHEDULE
EQUIPMENT TAG LOCATION AREA SERVED TYPE DRIVE CFM ESP
(IN.)
MAXIMUM
SONES
FAN
RPM BHP
MOTOR WEIGHT
CONTROL TYPE NOTES
HP RPM PHASE VOLT
EFG-1 GENERATOR ROOM GENERATOR ROOM GREENHECK SBCE-3H36 WALL MOUNTED
PROPELLER BELT 17500 0.25 46.0 1200 4.6 5 - 3 208 250 BAS 1, 3, 4, 5, 7
EFG-2 GENERATOR ROOM GENERATOR ROOM GREENHECK SBE-3H36 WALL MOUNTED
PROPELLER BELT 17500 0.25 46.0 1200 4.6 5 - 3 208 250 BAS 1, 3, 4, 5, 7
SFG-1 GENERATOR ROOM GENERATOR ROOM GREENHECK SBS-3H48 WALL MOUNTED
PROPELLER BELT 25000 0.375 40.0 688 5.1 7 1/2 - 3 208 400 BAS 1, 3, 4, 5, 6
NOTES:
1. OTHER ACCEPTABLE MANUFACTURERS: SEE SPECIFICATIONS. 6. 90 DEGREE INLET HOOD
2. PROVIDE THE FOLLOWING OPTIONS: GRAVITY BACKDRAFT DAMPER AND DISCONNECT SWITCH. 7. 45 DEGREE OUTLET HOOD
3. PROVIDE GALVANIZED BIRDSCREEN, , WALL HOUSING, MOTORIZED DAMPER.
4. PROVIDE VFD AND ROOM SPACE TEMPERATURE SENSOR ON BAS.
5. PROVIDE THE FOLLOWING OPTIONS AND ACCESSORIES: ELECTRICAL DISCONNECT SWITCH, NEOPRENE
VIBRATION ISOLATORS.
COMPUTER ROOM AC UNIT SCHEDULE
GENERAL FANS REHEAT SECTION HUMIDIFIER SECTION FILTERS ELECTRICAL DATA
NOTESEQUIPMENT
TAG LOCATION AREA
SERVED MANUFACTURER
BASIS OF DESIGN
TYPE DESIGN MODEL
OR EQUIVILANT
PHYSICAL CHARACTERISTICS
CFM
MOTOR
CAPACITY STEPS REFRIG.
TYPE
NET TOTAL
CAPACITY
(MBH)
NET SENSIBLE
CAPACITY (MBH) EAT (DB°F/WB°F) TYPE STAGES CAPACITY
(kW) TYPE STEAM CAPACITY
(LBS/HR) TYPE FLA MCA MOCP PHASE VOLTDIMENSIONS (IN.) WEIGHT
(LBS.) QTY. KW
(EACH)D W H
CRAC-1 MAIN COMPUTER ROOM 4E-24 MCR
4E-24 ABOVE AIRE DOWNFRONT
FLOW MCH-105D-3-HGHERH-EC-00-DFF-2E 33 107 85 3,420 15,000 3 3.10 VARIABLE R-410a 378.3 312.1 75/62.5 ELECTRIC SCR 30 STEAM CANISTER 30.0 MERV 8 132.6 158.7 175 3 208 1, 2, 3, 4, 5, 6, 9
CRAC-2 MAIN COMPUTER ROOM 4E-24 MCR
4E-24 ABOVE AIRE DOWNFRONT
FLOW MCH-105D-3-HGHERH-EC-00-DFF-2E 33 107 85 3,420 15,000 3 3.10 VARIABLE R-410a 378.3 312.1 75/62.5 ELECTRIC SCR 30 STEAM CANISTER 30.0 MERV 8 132.6 158.7 175 3 208 1, 2, 3, 4, 5, 6, 9
CRAC-3 UPS ROOM BE-97 UPS BE-97 ABOVE AIRE UPFRONT
FLOW MCH-035D-3-HGER0-EC-00-UF1-2A 34 59 95 1,695 4,400 1 3.10 VARIABLE R-410a 89.3 89.3 75/62.5 ELECTRIC SCR 15 N/A N/A MERV 8 48.6 60.8 70 3 208 1, 2, 3, 4, 5, 6, 7, 8, 9
CRAC-4 UPS ROOM BE-97 UPS BE-97 ABOVE AIRE UPFRONT
FLOW MCH-035D-3-HGER0-EC-00-UF1-2A 34 59 95 1,695 4,400 1 3.10 VARIABLE R-410a 89.3 89.3 75/62.5 ELECTRIC SCR 15 N/A N/A MERV 8 48.6 60.8 70 3 208 1, 2, 3, 4, 5, 6, 7, 8, 9
NOTES:
1. OTHER ACCEPTABLE MANUFACTURERS: VA APPROVED EQUALS. 4. PROVIDE SMOKE SENSOR WITH UNIT ALARM AND SHUTDOWN INCLUDE SUPERVISION CONTACTS 7. EACH CRAC SHALL HAVE A LOCAL MONITORING PANEL AFFIXED TO THE UNIT ACCESSING THE FOLLOWING INFORMATION:
SYSTEM AUTOMATIC RESTART WITH PROGRAMMABLE DELAY, SEQUENTIAL LOAD ACTIVATION, SENSOR CALIBRATION, CURRENT TEMPERATURE SET POINT AND LOCATION OF THAT SET POINT, CURRENT SUPPLY AND RETURN TEMPERATURE AND HUMIDITY, UNIT DIAGNOSTICS (FAN, VALVE, ALARM), ALARM LOG HISTORY, RUNTIME LOG, AUDIBLE AND VISUAL ALARM
8. 24" FLOOR STAND
2. PROVIDE LOCKING DISCONNECT, STARTER, AND CONTROLLER WITH BACnet COMPATIBLE BY MANUFACTURER. 5. PROVIDE DUAL REFRIGERATION CIRCUITS WITH HOT GAS BYPASS AND MUFFLERS, DIGITAL SCROLL COMPRESSOR, AND
COMPRESSORS TO INLCUDE CRANKCASE HEATER.
9. LOW AMBIENT OPERATION TO -30F.
3. PROVIDE SUPPLY AIR SENSOR WITH MULTIPLE RETURN SENSORS FIELD VERIFY EXACT LOCATION. 6. BMS CARD COMPATIBLE WITH CURRENT BUILDING CONTROL SYSTEM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
2\
-1
_4
-2 1-
0_
Fa rg o, N
D _E
H R
M T ie r 2
(V
IS
N
TO
)\4
- D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\C
AD
\M ec ha ni ca l\M
-6
.d w g 7/
/2
:3
4:
ISSUE FOR BID
BUILDING FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES - TIER 2
FARGO VA HEALTH CARE SYSTEM
437-21-210
Project Director
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
01/16/2024Bancroft Project No: 22-113ISSUE FOR BID 01-16-24
ISSUE FOR BID - 01/16/2024
MECHANICAL SCHEDULES
RH MB
M-600
1-9-46
1 BIDDING ADDENDA #1 07-22-25
DESIGN MODEL
OR EQUIVILANT
DESIGN MODEL
OR EQUIVILANT
MANUFACTURER
BASIS OF DESIGN
DESIGN MODEL
OR EQUIVILANT
DESIGN MODEL
OR EQUIVILANT