Attachment 06 Omaha EHRM Structural_20230515 - Drawing.pdf
PDF 2 MB Posted
- Attached to
- Y1DA--Copy of EHRM Infrastructure Upgrades - Construction - Omaha VAMC DUPLICATE OF 36C776230036
- Solicitation number
- 36C77623B00361
About this file
This document package outlines structural requirements for an infrastructure upgrade project at the Omaha VA Medical Center. The project includes upgrades to the existing hospital building and construction of a new generator building. Structural scope involves reinforced concrete, structural steel, cold-formed metal framing, masonry, and foundations. Design criteria include applicable codes, seismic and wind load standards. Construction documents provide plans, elevations, sections, and details for foundations, floor and roof framing, and masonry walls. Specifications cover cast-in-place concrete, structural steel, metal decking, cold-formed framing, unit masonry, and general structural notes. The related federal contract opportunity is for construction services for the EHRM infrastructure upgrades at the Omaha VAMC with an anticipated award date in 2023. The contracting agency is the Department of Veterans Affairs Technology Acquisition Center in Austin.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
010000 - GENERAL REQUIREMENTS AND DESIGN CRITERIA
1. APPLICABLE BUILDING CODE AND SELECT REFERENCING STANDARDS
INTERNATIONAL BUILDING CODE, 2018.
ACI 318-14 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE
TMS 402-2016 BUILDING CODE FOR MASONRY STRUCTURES
AISC 360-16 SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS
ASCE 7-16 MINIMUM DESIGN LOADS FOR BUILDING AND OTHER STRUCTURES INCLUDING SUPPLEMENT NO. 1
AND 2, EXCLUDING CHAPTER 14 AND APPENDIX 11A
VA SEISMIC DESIGN REQUIREMENTS, H-18-8
VA PHYSICAL SECURITY AND RESILIENCY DESIGN MANUAL FOR VA FACILITIES
PHYSICAL SECURITY DESIGN STANDARDS DATA DEFINITIONS FOR PSRDM, OCTOBER 1, 2020
OTHER SELECT REFERENCED STANDARDS MAY BE INDICATED ELSEWHERE IN THE CONTRACT DOCUMENTS, AS
APPLICABLE.
THE PROVISIONS OF THE REFERENCED BUILDING CODE AND ALL REFERENCED STANDARDS THEREIN SHALL APPLY TO THIS PROJECT. WHERE THERE IS A CONFLICT BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE APPLICABLE. TYPICALLY, THE LATEST EDITION OF CONSTRUCTION STANDARDS SHALL BE UTILIZED, AS APPROVED BY THE AUTHORITY HAVING JURISDICTION.
2. INTERPRETATION OF CONFLICTS
SHOULD CONFLICTS OCCUR IN THE CONTRACT DOCUMENTS, THE CONTRACTOR SHALL REQUEST
INTERPRETATION BEFORE PROCEEDING WITH THE ASSOCIATED WORK. ALL SUCH REQUESTS SHALL FIRST BE PRECEDED BY A DILIGENT INVESTIGATION INTO THE CONTRACT DOCUMENTS. EVIDENCE OF SUCH
INVESTIGATION SHALL BE CONTAINED IN ALL REQUESTS FOR INTERPRETATION SUBMITTED.
IF THE CONTRACTOR FAILS TO MAKE SUCH A REQUEST, THE CONTRACTOR IS EXPECTED TO COMPLETE THE WORK AS INDICATED IN THE CONTRACT DOCUMENTS. SHOULD CONFLICTS OCCUR IN OR BETWEEN DRAWINGS AND SPECIFICATIONS, THE CONTRACTOR SHALL ESTIMATE THE COST OF THE WORK BASED ON THE MORE EXPENSIVE WAY OF DOING THE WORK UNLESS HAVING ASKED FOR, AND OBTAINED, WRITTEN DECISION
BEFORE SUBMISSION OF PROPOSAL AS TO WHICH METHOD OR MATERIALS WILL BE REQUIRED.
3. STRUCTURAL SYSTEMS HAVE BEEN DESIGNED TO RESIST THE FOLLOWINGS DESIGN LOADS:
A. FLOOR LIVE LOADS
THE "TYPICAL MINIMUM LIVE LOAD USED FOR DESIGN" INDICATED BELOW WAS USED FOR ALL OCCUPANCY OR USE TYPES, EXCEPT THOSE WHERE THE "CODE-SPECIFIED MINIMUM LIVE LOADS" ARE GREATER, IN WHICH CASE THE ASSOCIATED LIVE LOAD INDICATED IN THE TABLE WAS USED FOR DESIGN. SEE
ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS FOR THE DEFINITION OF SPACES.
TYPICAL MINIMUM LIVE LOAD USED FOR DESIGN = 100 PSF, 1000 LB CONCENTRATED LOAD
* UNLESS OTHERWISE INDICATED, THE CONCENTRATED LOAD INDICATED WAS DISTRIBUTED OVER AN AREA OF 2.5 FEET BY 2.5 FEET (6.25 SQUARE FEET), AND LOCATED AS TO PROVIDE THE MAXIMUM LOAD
EFFECTS IN THE STRUCTURAL MEMBERS.
B. ROOF LIVE LOADS
20 PSF MINIMUM ROOF LIVE LOAD
C. ROOF SNOW LOADS, APPLIED IN ACCORDANCE WITH THE BUILDING CODE INDICATED HEREIN.
GROUND SNOW LOAD, Pg = 25 PSF FLAT ROOF SNOW LOAD, Pf = 25 PSF SNOW EXPOSURE FACTOR, Ce = 1.0
SNOW IMPORTANCE FACTOR, I = 1.2 AT HOSPITAL AND GENERATOR BUILDING, 1.0 ALL ELSE
THERMAL FACTOR, Ct = 1.0
SNOW LOADS ARE NOT REDUCIBLE
D. INTERIOR WALLS
5 PSF LATERAL LOAD IN THE ABSENCE OF ANY WIND LOAD EFFECTS
E. WIND LOADS. APPLIED IN ACCORDANCE WITH THE BUILDING CODE INDICATED HEREIN.
BASIC WIND SPEED, Vult = 125 MPH AT HOSPITAL AND GENERATOR BUILDING, 114 MPH ALL ELSE
RISK CATEGORY = IV AT HOSPITAL AND GENERATOR BUILDING, II ALL ELSE
WIND EXPOSURE = C
INTERNAL PRESSURE COEFFICIENT, GPi = +/- 0.55 AT GENERATOR BUILDING, +/- 0.18 ALL ELSE
F. COMPONENTS AND CLADDING ULTIMATE WIND LOADS:
* PRESSURES SHOWN ARE APPLIED NORMAL TO THE SURFACE. PLUS AND MINUS SIGNS
SIGNIFY PRESSURES ACTING TOWARD AND AWAY FROM THE SURFACES, RESPECTIVELY.
** SEE ASCE 7 FOR DEFINITION. FOR EFFECTIVE WIND AREAS BETWEEN THOSE GIVEN,
VALUES MAY BE LINEARLY INTERPOLATED, OTHERWISE USE VALUES WITH THE LOWER EFFECTIVE
WIND AREA.
G. SEISMIC LOADS. APPLIED IN ACCORDANCE WITH THE BUILDING CODE INDICATED HEREIN.
SEISMIC IMPORTANCE FACTOR, Ie = 1.5 AT HOSPITAL AND GENERATOR BUILDING, 1.0 ALL ELSE
RISK CATEGORY = IV AT HOSPITAL AND GENERATOR BUILDING, II ALL ELSE
MAPPED SPECTRAL RESPONSE ACCELERATIONS
-SHORT PERIOD, Ss = 0.097g (SITE-SPECIFIC SEISMIC EVALUATION) -ONE-SECOND PERIOD, S1 = 0.045g (SITE-SPECIFIC SEISMIC EVALUATION)
SPECTRAL RESPONSE COEFFICIENTS
-SHORT PERIOD, Sds = 0.103g (SITE-SPECIFIC SEISMIC EVALUATION) -ONE-SECOND PERIOD, Sd1 = 0.072g (SITE-SPECIFIC SEISMIC EVALUATION)
SEISMIC DESIGN CATEGORY, SDC = A
BASIC SEISMIC-FORCE-RESISTING SYSTEM = ORDINARY REINFORCED MASONRY SHEAR WALLS (AT
GENERATOR BUILDING)
DESIGN BASE SHEAR, V = 25 KIPS (AT GENERATOR BUILDING)
SEISMIC RESPONSE COEFFICIENT, Cs = 0.077 (AT GENERATOR BUILDING)
RESPONSE MODIFICATION FACTOR, R = 2 (AT GENERATOR BUILDING)
LONG-PERIOD TRANSITION = 12 SEC PERIOD, TL
SITE CLASS: D
4. BLAST LOADING DESIGN CRITERIA
A. MISSION CRITICAL FACILITY
B. EXTERIOR DESIGN LEVEL THREAT = W2
C. MINIMUM STANDOFF DISTANCE = 50 FEET (SATISFIED BY SITE PLAN)
D. PRIMARY STRUCTURE = EXTERIOR LOAD BEARING WALLS AND ROOF
6. CONTRACTOR RESPONSIBILITIES
A. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS (INCLUDING FIELD VERIFICATIONS OF EXISTING
CONDITIONS AND DIMENSIONS) BEFORE STARTING WORK OR FABRICATING ANY REINFORCING STEEL, STRUCTURAL STEEL, COLD-FORMED STEEL ELEMENTS, OR PRECAST ELEMENTS. THE ARCHITECT SHALL
BE NOTIFIED OF ANY DISCREPANCIES FOUND.
B. SEE ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS FOR SIZE AND LOCATION OF WALL, ROOF, AND FLOOR OPENINGS AND SLEEVES, AND CONCRETE PADS UNDER EQUIPMENT. THE
CONTRACTOR SHALL VERIFY EXACT SIZE AND LOCATION WITH EQUIPMENT FURNISHED. OPENINGS IN
STRUCTURE TO BE HANDLED AS FOLLOWS:
OPENINGS THROUGH CONCRETE WALLS, FLOORS, AND ROOFS, WHICH MEASURE 12" OR LESS IN ALL
DIRECTIONS, SHALL BE CORE DRILLED.
OPENINGS THROUGH METAL ROOF DECK, WHICH MEASURE 6" OR LESS IN ALL DIRECTIONS, MAY BE CUT.
C. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE ADEQUATE SHORING AND BRACING OF THE STRUCTURE (NEW AND/OR EXISTING) FOR ALL LOADS THAT MAY BE IMPOSED DURING CONSTRUCTION.
D. WHEN CUTTING A NEW OPENING IN EXISTING CONCRETE OR MASONRY, THE CONTRACTOR SHALL NOT OVER CUT AT CORNERS. CORE-DRILL, CHIP AND GRIND AS REQUIRED AT CORNERS. A LAYOUT OF ALL PROPOSED OPENINGS SHALL BE REVIEWED BY THE STRUCTURAL ENGINEER PRIOR TO SAWCUTTING.
E. ALL WALL FOOTINGS SHALL BE CENTERED ON CMU WALLS UNLESS NOTED OTHERWISE.
F. CONTRACTOR SHALL ENSURE NO STRUCTURAL MEMBERS OR ELEMENTS ARE DAMAGED OR ALTERED
UNLESS SO INDICATED BY THE STRUCTURAL ENGINEER. ANY SUCH DAMAGE THAT DOES OCCUR SHALL BE BROUGHT TO THE ATTENTION OF THE STRUCTURAL ENGINEER AND SHALL BE THE RESPONSIBILITY OF
THE CONTRACTOR.
7. PROVISIONS FOR FUTURE EXPANSION
A. NO PROVISIONS FOR FUTURE EXPANSION HAVE BEEN MADE IN THE STRUCTURAL SYSTEMS.
5. DESIGN ITEMS DELEGATED TO THE CONTRACTOR
THE CONTRACTOR IS RESPONSIBLE FOR THE DESIGN OF THE FOLLOWING ITEMS. DESIGNS SHALL SATISFY
THE REQUIREMENTS OF THE CONTRACT DOCUMENTS.
A. COLD-FORMED STEEL JOIST/STUD/TRUSS FRAMING AND PRE-FABRICATED COMPONENTS
B. SEISMIC BRACING OF NON-STRUCTURAL COMPONENTS
C. ATFP/PHYSICAL SECURITY:
a. NON-STRUCTURAL COMPONENT AT/FP RESTRAINTS
b. BLAST RESISTANT WALL AND ROOF CONSTRUCTION
D. FUEL TANK CONNECTION TO FOUNDATION
BLAST-INDUCED BASE SHEAR AT FUEL TANK, V = 87 KIPS (ULTIMATE)
ALL ITEMS LISTED AS DELEGATED DESIGN ITEMS SHALL BE PERFORMED AND STAMPED BY A STRUCTURAL ENGINEER LICENSED IN THE STATE OF NEBRASKA. STAMPED ENGINEERING CALCULATIONS SHALL BE SUBMITTED FOR REVIEW AT THE SAME TIME THAT RELATED SHOP DRAWINGS ARE SUBMITTED FOR
REVIEW.
014000 - QUALITY REQUIREMENTS
1. SPECIAL INSPECTIONS AND STRUCTURAL TESTING SHALL BE PERFORMED PER CHAPTER 17 OF IBC, THE CONTRACT DOCUMENTS, AND THE STATEMENT OF SPECIAL INSPECTIONS WHICH IS INCLUDED IN THE
CONTRACT DOCUMENTS.
033000 - CAST-IN-PLACE CONCRETE (REINFORCED)
1. ALL STRUCTURAL CONCRETE SHALL BE DESIGNED FOR A 28-DAY COMPRESSIVE STRENGTH OF:
f'c EQUALS 3500 PSI (NORMAL WEIGHT) [SLAB-ON-GRADE, SLAB-ON-DECK] f'c EQUALS 4500 PSI (NORMAL WEIGHT) [FOUNDATIONS, STOOP SLABS, JAMBS & LINTELS]
2. ALL REINFORCING STEEL SHALL BE DEFORMED, NEW, AND CONFORM TO ASTM A615 GRADE 60 (DEFORMED BARS)
3. ALL PLAIN WELDED WIRE REINFORCEMENT SHALL BE NEW AND CONFORM TO ASTM A185.
4. ALL DEFORMED WELDED WIRE REINFORCEMENT SHALL BE NEW AND CONFORM TO ASTM A497.
5. DEFORMED BAR ANCHORS SHALL BE NEW AND CONFORM TO ASTM A706. WELDING OF DEFORMED BAR
ANCHORS SHALL BE DONE WITH E80XX ELECTRODES IN CONFORMANCE WITH THE AMERICAN WELDING SOCIETY (AWS) "STRUCTURAL WELDING CODE - REINFORCING STEEL" AWS D1.4 - LATEST EDITION.
6. HEADED DEFORMED BARS SHALL BE NEW AND CONFORM TO ASTM A615 GRADE 60 AND ASTM A970 INCLUDING ANNEX A1 REQUIREMENTS FOR CLASS HA HEAD DIMENSIONS. OBSTRUCTIONS OR INTERRUPTIONS OF THE BAR DEFORMATIONS, IF ANY, SHALL NOT EXTEND MORE THAN 2 BAR DIAMETERS FROM THE BEARING FACE OF THE
HEAD.
7. HEADED SHEAR STUDS SHALL CONFORM TO A.W.S. D1.1 - LATEST EDITION REQUIREMENTS FOR STANDARD
HEADED STUDS.
8. CONCRETE PROTECTIVE COVERING FOR REINFORCEMENT AT SURFACES NOT EXPOSED DIRECTLY TO EARTH OR WEATHER SHALL BE 3/4" FOR SLABS, JOISTS, AND WALLS AND 1 1/2" FOR BEAM STIRRUPS AND COLUMN TIES
OR SPIRALS, UNLESS DETAILED OTHERWISE.
9. CONCRETE PROTECTIVE COVERING FOR REINFORCEMENT AT SURFACES WHICH WILL BE EXPOSED TO THE WEATHER OR BE IN CONTACT WITH EARTH (BUT NOT CAST AGAINST) SHALL BE 2" FOR BARS LARGER THAN #5 AND 1 1/2" FOR #5 BARS OR SMALLER, PROVIDE 3" COVER FOR REINFORCEMENT CAST AGAINST AND
PERMANENTLY EXPOSED TO EARTH, UNLESS DETAILED OTHERWISE.
10. SLABS-ON-GRADE, UNLESS NOTED OTHERWISE, SHALL BE 5 INCHES THICK WITH #4 @ 18 EACH WAY OVER VAPOR BARRIER OVER 6 INCHES OF GRANULAR FILL. REINFORCING SHALL BE LAPPED AS PER TABLE BELOW.
11. CONTRACTION JOINTS IN SLABS ON GRADE SHALL BE PLACED AT COLUMN LINE INTERSECTIONS AND AS NECESSARY TO NOT EXCEED A SPACING OF 36 TIMES THE SLAB THICKNESS OR 15'-0". WHICHEVER IS LESS.
MAXIMUM ASPECT RATIO SHALL BE 1.5 TO 1.0 UNLESS NOTED OTHERWISE.
12. PROVIDE 3/4-INCH CHAMFER ON ALL EXPOSED CONCRETE CORNERS EXCEPT WHERE MASONRY WALLS ARE
LAID FLUSH WITH COLUMN OR BEAM FACE.
13. WHERE THE WEIGHT OF EQUIPMENT OR MATERIALS BEING TRANSPORTED TO LOCATION, OR TEMPORARILY STORED, EXCEEDS THE DESIGN LIVE LOAD, PLANKING SHALL BE PROVIDED ON THE FLOOR SLAB AND SHORING
PROVIDED BENEATH THE FLOOR AS REQUIRED TO SUPPORT THE LOADS.
14. NO PENETRATIONS (SUCH AS PIPE SLEEVES, ELECTRICAL CONDUITS, ETC.) THROUGH ANY STRUCTURAL
MEMBER, SHALL BE MADE WITHOUT APPROVAL BY THE STRUCTURAL ENGINEER.
15. PROVIDE EXTERIOR CORNER BARS SAME SIZE AND SPACING AS HORIZONTAL REINFORCING AT ALL CONCRETE
WALLS AND FOOTINGS - LAP AS PER TABLE BELOW.
16. PROVIDE LAP SPLICES IN CONFORMANCE WITH TABLE 033000-1, UNLESS OTHERWISE INDICATED. FOLLOW RESTRICTIONS ON LOCATIONS OF SPLICES AS INDICATED IN DETAILS, NOTES, OR SPECIFICATIONS.
050519 - POST-INSTALLED ANCHORAGE
1. POST-INSTALLED ANCHORS SHALL ONLY BE USED WHERE SPECIFIED IN THE CONTRACT DOCUMENTS. THE
CONTRACTOR SHALL OBTAIN APPROVAL FROM THE STRUCTURAL ENGINEER-OF-RECORD PRIOR TO
INSTALLING POST-INSTALLED ANCHORS IN PLACE OF MISSING OR MISPLACED CAST-IN-PLACE ANCHORS. CARE SHALL BE TAKEN IN PLACING POST-INSTALLED ANCHORS TO AVOID CONFLICTS WITH EXISTING REBAR. ALL POST-INSTALLED ANCHORS (IN CONCRETE OR CMU) ARE TO BE INSTALLED IN STRICT CONFORMANCE WITH THE MANUFACTURER'S PUBLISHED INSTALLATION INSTRUCTIONS (MPII) (INCLUDING BUT NOT LIMITED TO DRILL BIT SIZE, PROPER CLEANING OF HOLES, INSTALLATION TORQUE, AND TEMPERATURE CONSTRAINTS).
2. ANCHOR CAPACITY IS DEPENDENT UPON SPACING BETWEEN ADJACENT ANCHORS AND PROXIMITY OF
ANCHORS TO EDGE OF CONCRETE. INSTALL ANCHORS IN ACCORDANCE WITH SPACING AND EDGE
CLEARANCES INDICATED ON THE DRAWINGS.
3. EXISTING REINFORCING BARS IN THE CONCRETE STRUCTURE MAY CONFLICT WITH SPECIFIC ANCHOR LOCATIONS. UNLESS NOTED ON THE DRAWINGS THAT THE BARS CAN BE CUT, THE CONTRACTOR SHALL REVIEW THE EXISTING STRUCTURAL DRAWINGS AND SHALL UNDERTAKE TO LOCATE THE POSITION OF THE REINFORCING BARS AT THE LOCATIONS OF THE CONCRETE ANCHORS, BY FERROSCAN, GPR, X-RAY, CHIPPING
OR OTHER MEANS AS APPROVED BY THE STRUCTURAL ENGINEER OF RECORD.
051200 - STRUCTURAL STEEL FRAMING
1. ALL STRUCTURAL STEEL W SHAPES SHALL BE ASTM A992
(UNLESS NOTED OTHERWISE).
STRUCTURAL STEEL FOR CHANNELS, ANGLES AND PLATES SHALL BE ASTM A36
(UNLESS NOTED OTHERWISE).
WHERE PLATES ARE INDICATED WITH Fy = 50 KSI, THEY SHALL BE ASTM A572, GRADE 50.
2. STRUCTURAL TUBING SHALL CONFORM TO ASTM A500, GRADE C WITH A MINIMUM YIELD STRENGTH OF 46,000
PSI FOR ROUND SECTIONS, AND 50,000 PSI FOR SQUARE AND RECTANGULAR SECTIONS.
3. STEEL PIPE COLUMNS SHALL CONFORM TO ASTM A53, TYPE E OR S, GRADE B, WITH A MINIMUM YIELD
STRENGTH OF 35,000 PSI.
4. STRUCTURAL STEEL HAS BEEN DESIGNED IN ACCORDANCE WITH "AISC 360-10, SPECIFICATION FOR
STRUCTURAL STEEL BUILDINGS, 2010". ALLOWABLE STRENGTH DESIGN METHOD.
5. ALL FIELD CONNECTIONS SHALL BE MADE WITH 3/4-INCH DIAMETER ASTM A325 BOLTS (BEARING TYPE CONNECTION), UNLESS NOTED OTHERWISE. BOLTS SHALL BE TIGHTENED (SNUG-TIGHT) IN CONFORMANCE WITH "SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS" RESEARCH COUNCIL ON
STRUCTURAL CONNECTIONS OF THE ENGINEERING FOUNDATION.
6. BEAM SIZE FOLLOWED BY A NUMBER IN PARNTHESES ON THE FRAMING PLANS (E.G. W16x26(32)) SHALL BE COMPOSITE, WITH THE INDICATED NUMBER OF 3/4-INCH DIAMTER SHEAR STUDS APPROXIMATELY EQUALLY SPACED. IF NECESSARY, TWO SHEAR STUDS MAY BE PLACED IN ONE DECK FLUTE. THE HEIGHT OF THE STUDS AFTER WELDING SHALL BE 4 INCHES. STUDS ON W10X12, W10X15, W12X14, AND W12X16 BEAMS SHALL BE
PLACED DIRECTLY OVER THE BEAM WEB.
7. STEEL LINTELS, FOR OPENINGS NOT DETAILED, SHALL BE L5x5x5/16 (GALVANIZED).
8. ALL WELDING SHALL BE DONE WITH E70XX ELECTRODES IN CONFORMANCE WITH THE AMERICAN WELDING
SOCIETY (AWS) "STRUCTURAL WELDING CODE" AWS D1.1 - LATEST EDITION.
9. ALL INTERIOR EXPOSED STEEL SHALL MEET PRIMING AND PAINTING REQUIREMENTS AS DEFINED IN THE
INTERIOR PAINTING SPECIFICATION.
053100 - STEEL DECKING
1. DESIGN AND CONSTRUCTION OF STEEL ROOF DECK SHALL CONFORM TO ANSI/SDI-RD1.0.
2. STEEL DECKING SHALL BE DESIGNED FOR THE FOLLOWING MINIMUM YIELD STRENGTHS:
Fy = 33 ksi (STEEL ROOF DECK) Fy = 50 ksi (COMPOSITE STEEL DECK)
3. ALL METAL DECKING SHALL BE GALVANIZED PER THE SPECIFICATIONS.
4. STEEL ROOF DECK SHALL BE 1.5 INCH, 20 GAUGE WIDE RIB METAL DECK HAVING THE FOLLOWING MINIMUM
SECTION PROPERTIES:
Ip = 0.201 IN^4/FT In = 0.222 IN^4/FT Sp = 0.234 IN^3/FT Sn = 0.247 IN^3/FT p = FOR POSITIVE BENDING n = FOR NEGATIVE BENDING
36/7 AT ENDS AND INTERMEDIATE SUPPORTS (5/8” WELD OR EQUIV.)
5 SIDE LAP FASTENERS EQUALLY SPACED PER SPAN (#10 TEK SCREW OR EQUIV.)
5. PROVIDE ALL NECESSARY DETAILS INCLUDING RIDGE AND VALLEY PLATES, CLOSURE PLATES AND ANY OTHER
ACCESSORIES REQUIRED FOR A FINISHED SURFACE FOR FLOOR OR ROOF INSTALLATION.
6. COMPOSITE STEEL DECK SHALL BE 2 INCH, 18 GAUGE COMPOSITE METAL DECK WITH NORMAL WEIGHT CONCRETE FILL AS INDICATED ON THE PLANS AND 6x6-W1.4xW1.4 WWF HAVING THE FOLLOWING MINIMUM
SECTION PROPERTIES:
Ip = 0.558 IN^4/FT In = 0.558 IN^4/FT Sp = 0.485 IN^3/FT Sn = 0.500 IN^3/FT p = FOR POSITIVE BENDING n = FOR NEGATIVE BENDING
36/4 AT ENDS AND INTERMEDIATE SUPPORTS (5/8" PUDDLE WELD)
4 SIDE LAP FASTENERS EQUALLY SPACED PER SPAN (BUTTON PUNCH OR EQUIV.)
054000 - COLD-FORMED METAL FRAMING
1. DESIGN: ALL STUDS, JOISTS AND CONNECTIONS, NOT SPECIFICALLY DETAILED ON THE DRAWINGS, SHALL BE DESIGNED FOR THE SPACINGS AND LOADS INDICATED, BY A PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF NEBRASKA. DESIGN SHALL BE IN ACCORDANCE WITH AMERICAN IRON AND STEEL INSTITUTE (AISI) "SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS". STEEL STRUCTURAL
MEMBERS".
2. FIRE-RESISTANCE RATINGS: COMPLY WITH FIRE-RESISTANCE RATINGS AS INDICATED AND AS REQUIRED BY GOVERNING AUTHORITIES AND CODES. PROVIDE MATERIALS, ACCESSORIES, AND INSTALLATION PROCEDURES WHICH HAVE BEEN LISTED BY UL OR TESTED IN ACCORDANCE WITH ASTM E119 FOR THE TYPE
OF CONSTRUCTION SHOWN.
3. PROVIDE ALL ACCESSORIES INCLUDING TRACKS, BLOCKING, LINTELS, CLIP ANGLES, STRAP BRACING, SHOES, AND FASTENERS TO PROVIDE A COMPLETE METAL FRAMING SYSTEM.
4. INSTALL HORIZONTAL BRIDGING AS REQUIRED BY STUD DESIGNER. MINIMUM BRIDGING SPACING SHALL BE
4'-0" ON CENTER UNTIL PERMANENT INTERIOR WALL SHEATHING IS INSTALLED.
5. ALL METAL FRAMING COMPONENTS SHALL BE FORMED FROM STRUCTURAL STEEL SHEET CONFORMING TO
THE REQUIREMENTS OF ASTM A653, WITH A MINIMUM YIELD STRENGTH OF 33,000 PSI.
6. ALL METAL FRAMING COMPONENTS SHALL HAVE A GALVANIZED FINISH COMPLYING WITH ASTM A525 FOR A MINIMUM G60 COATING. FRAMING COMPONENTS SERVING AS BACK-UP FOR MASONRY VENEER EXTERIOR
WALLS SHALL HAVE A MINIMUM G90 GALVANIZED FINISH.
7. ALL METAL FRAMING COMPONENTS SHALL BE CUT SQUARELY FOR ATTACHMENT TO PERPENDICULAR
MEMBERS OR, WHEN REQUIRED, FOR AN ANGULAR FIT TO ABUTTING MEMBERS.
8. SPLICING OF AXIAL LOADED MEMBERS IS NOT PERMITTED.
9. FASTENING OF COMPONENTS SHALL BE WITH SELF-DRILLING SCREWS OR WELDING AS STANDARD WITH
MANUFACTURER. SCREWS SHALL BE OF SUFFICIENT SIZE TO INSURE STRENGTH OF THE CONNECTION. ALL WELDS SHALL BE TOUCHED UP WITH A ZINC-RICH PAINT. AT EXTERIOR WALLS THAT ARE PART OF THE BUILDING ENVELOPE, COAT SCREWS WITH BITUMINOUS OR ZINC-RICH PAINT. WIRE TYING OF COMPONENTS IS
NOT PERMITTED.
10. FRAMING COMPONENTS MAY BE PREFABRICATED INTO PANELS PRIOR TO ERECTION. FABRICATE PANELS PLUMB, SQUARE, TRUE TO LINE AND BRACED AGAINST RACKING. PERFORM LIFTING OF PREFABRICATED
PANELS IN A MANNER TO PREVENT DAMAGE OR DISTORTION.
11. INSTALL FRAMING MEMBERS AS PER MANUFACTURER'S DESIGN AND RECOMMENDATIONS.
12. PROVIDE TEMPORARY BRACING, WHEN REQUIRED, UNTIL ERECTION IS COMPLETE.
PAN JOISTS V.I.F. EXISTING JOISTS (V.I.F.)
3" MIN 3" MIN
CUT LENGTH
PARALLEL TO
JOISTS SHALL
NOT EXCEED 12"
EDGE OF CUT
FOR MECHANICAL
OPENING
CONTRACTOR SHALL NOT CUT THROUGH ANY
JOIST OR DISTRIBUTION BEAMS UNDER ANY
CIRCUMSTANCES. CONTRACTOR TO SUBMIT
LAYOUT OF PROPOSED OPENINGS PRIOR TO
SAWCUTTING.
CONTRACTOR TO FIELD LOCATE AND
COORDINATE OPENING SIZE AND LOCATION
WITH MECHANICAL/ELECTRICAL DRAWINGS
AND SUPPLIED EQUIPMENT
CONTACT EOR FOR ANY REQUIRED
PENETRATIONS THAT EXCEED THE
LIMITS OF THIS DETAIL PRIOR
TO SAW CUTTING.
DISTRIBUTION RIB
ZONE WHERE IT IS PERMISSIBLE TO
CORE DRILL THRU THE DISTRIBUTION
RIB. AT LEAST 2" OF CONRETE SHALL
REMAIN BETWEEN CORED HOLES
EXIST. JOIST CONSTRUCTION
AND TOPPING
JO
IS
T
4"
4"
4"
4"
V.I.F.
DROP PANEL
9" MIN. FROM
MIN.
4"
EXIST. SLAB LOCATE EXIST. REBAR IN SLAB
PRIOR TO CORE DRILLING
USING NON-DESTRUCTIVE
TESTING METHODS. DO NOT
CUT REBAR. CONTACT EOR
PRIOR TO DRILLING IF REBAR
MUST BE CUT.
CORE DRILL HOLES*
FOR PIPE PENETRATIONS
EXIST. DROP PANEL - VERIFY
SIZE AND LOCATION IN
FIELD (WHERE OCCURS)
EXIST. CONCRETE COLUMN
*HOLES TO BE 8" MAX DIAMETER AND
AT LEAST 4" OF CONCRETE SHALL
REMAIN BETWEEN ADJACENT HOLES.
MIN.
4"
CORE DRILL HOLES* FOR PIPE
PENETRATIONS.
IF LARGER PENETRATIONS ARE
REQUIRED, CONTACT EOR PRIOR TO
ANY DRILLING OR INSTALLATION.
*HOLES TO BE 8" MAX DIAMETER AND
AT LEAST 4" OF CONCRETE SHALL
REMAIN BETWEEN ADJACENT HOLES.
EXISTING SLAB
(WHERE OCCURS)
EXISTING CONCRETE
FOUNDATION
6" 6"
NO PENETRATIONS IN TOP 6" OR BOTTOM 6" OF FOOTING
LOCATE EXISTING REBAR IN
FOUNDATION/WALL PRIOR TO
DRILLING USING NON-
DESTRUCTIVE TESTING METHODS.
DO NOT CUT REBAR. CONTACT
EOR PRIOR TO DRILLING IF REBAR
MUST BE CUT.
BRICK BEYOND
NEW HOLES FOR CONDUIT
OPENINGS. NO REINFORCEMENT
REQUIRED FOR PENETRATIONS
LESS THAN OR EQUAL TO 8"
DIAMETER
CONTACT EOR FOR PENETRATIONS
GREATER THAN 8" IN DIAMETER
PRIOR TO ANY DRILLING OR INSTALLATION.
042000 - UNIT MASONRY
1. HOLLOW CONCRETE MASONRY UNITS SHALL CONFORM TO ASTM C90.
2. MORTAR SHALL CONFORM TO ASTM C270, TYPE N OR S.
3. NET AREA COMPRESSIVE STRENGTH OF CONCRETE MASONRY, f'm = 2000 PSI.
4. GROUT FOR REINFORCED CONCRETE MASONRY SHALL CONFORM TO ASTM C476, WITH A MINIMUM
COMPRESSIVE STRENGTH OF 2000 PSI.
5. THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY SHORING NECESSARY TO LATERALLY SUPPORT ALL
CONCRETE MASONRY WALLS AS REQUIRED.
6. PROVIDE GALVANIZED HORIZONTAL JOINT REINFORCING EVERY 16 INCHES IN HEIGHT IN ALL WALLS, NO. 9
GAGE MINIMUM, UNLESS INDICATED OTHERWISE.
7. GROUT ALL CELLS FULL UNDER STEEL BEAMS BEARING ON CONCRETE MASONRY WITHIN AN AREA 24 INCHES
WIDE BY 24 INCHES HIGH.
8. REINFORCE EXTERIOR CONCRETE MASONRY WALLS WITH (1)-#7 VERTICAL REINFORCEMENT AT EACH FACE IN
EVERY CELL. FULLY GROUT ALL CELLS. LAP AS SCHEDULED UNLESS OTHERWISE DETAILED. PLACE BOND BEAMS AT 48" MAX. VERTICAL SPACING, AT TOP OF WALL AND AS DETAILED. REINFORCE BOND BEAMS WITH (2)-#5 x CONTINUOUS UNLESS NOTED OTHERWISE.
9. REINFORCE INTERIOR NON-LOADBEARING CONCRETE MASONRY WALLS WITH (1)-#5 VERTICAL REINFORCEMENT AT 32" c/c IN GROUTED CELLS. PROVIDE REINFORCEMENT & GROUT IN ALL CORNER CELLS AND CELLS ADJACENT TO OPENINGS AND AT WALL ENDS. LAP AS SCHEDULED UNLESS OTHERWISE DETAILED.
PLACE BOND BEAMS AT TOP OF ALL INTERIOR CONCRETE MASONRY WALLS. REINFORCE BOND BEAMS WITH (2)-#5 x CONTINUOUS AND AS DETAILED.
10. LINTELS FOR OPENINGS NOT DETAILED SHALL BE 8 INCHES DEEP WITH (2)-#5 BOTTOM BARS.
11. PROVIDE LAP SPLICES OF REINFORCING STEEL IN CONFORMANCE WITH TABLE 042000-01, UNLESS OTHERWISE
INDICATED. FOLLOW RESTRICTIONS ON LOCATIONS OF SPLICES, AS INDICATED IN DETAILS, NOTES, AND
SPECIFICATIONS.
316000 - GENERAL FOUNDATIONS
1. FOUNDATION INVESTIGATION WAS MADE BY TERRACON CONULTANTS, INC. DATED AUGUST 9, 2011. THIS
REPORT IS AVAILABLE IN THE PROJECT SPECIFICATIONS.
2. EQUIVALENT FLUID PRESSURE FOR ACTIVE EARTH PRESSURE ON WALLS:
CANTILEVER (ACTIVE) RETAINING WALLS (DRAINED):
FOR STRUCTURAL DESIGN OF WALL = 40 PCF (GRANULAR), 45 PCF (LEAN CLAY)
BASEMENT (AT-REST) WALLS LATERALLY SUPPORTED TOP AND BOTTOM:
FOR STRUCTURAL DESIGN OF WALL = 55 PCF (GRANULAR), 60 PCF (LEAN CLAY)
3. BACKFILLING AGAINST WALLS AND GRADE BEAMS SHALL NOT BE DONE UNTIL CONCRETE HAS ATTAINED SUFFICIENT STRENGTH AND WALLS ARE PROPERLY SHORED OR BRACED. WHERE BACKFILL IS REQUIRED ON
BOTH SIDES OF WALLS, BACKFILL BOTH SIDES SIMULTANEOUSLY.
4. WHERE WALLS ARE SUPPORTED BY CONCRETE SLABS, SLABS SHALL HAVE CURED A MINIMUM 7 DAYS BEFORE
BACKFILLING.
5. THE SLAB-ON-GRADE SHALL BE SUPPORTED BY 6 INCHES OF FREE DRAINING GRANULAR MATERIAL AND 12 INCHES OF APPROVED STRUCTURAL FILL MATERIAL COMPACTED TO 95% OF THE MATERIAL'S MAXIMUM
STANDARD PROCTOR DRY DENSITY PER ASTM D 698.
6. SUBGRADE MATERIAL SHALL BE INSPECTED AND APPROVED BY THE GEOTECHNICAL ENGINEER. REFER TO
GEOTECHNICAL REPORT FOR MATERIAL CONSTRUCTION SPECIFICATIONS.
316100 - SPREAD FOOTINGS
1. ALL FOOTINGS SHALL BEAR ON APPROVED NATIVE SOILS OR NEW STRUCTURAL FILL. BOTTOM OF ALL EXTERIOR FOOTINGS SHALL BE AT LEAST 42" BELOW FINISHED GRADE. ELEVATIONS OF BOTTOM OF ALL FOOTINGS HAVE BEEN ESTIMATED BASED ON AVAILABLE INFORMATION AND SHALL NOT BE CONSTRUED AS WAIVING ANY OF THE MINIMUM REQUIREMENTS ON THESE DRAWINGS AND IN THE SPECIFICATIONS. ALL FOOTING EXCAVATIONS SHALL BE INSPECTED AND APPROVED BY THE SPECIAL INSPECTOR PRIOR TO CONSTRUCTION OF THE FOOTINGS. REFER
TO GEOTECHNICAL REPORT FOR MATERIAL CONSTRUCTION SPECIFICATIONS.
2. ALLOWABLE SOIL BEARING PRESSURE:
SPREAD AND CONTINUOUS FOOTINGS ON APPROVED NATIVE SOIL OR STRUCTURAL FILL = 2000 PSF (DEAD LOAD
PLUS FULL LIVE LOAD)
RETAINING WALLS = 2000 PSF (MAXIMUM TOE PRESSURE)
3. ULTIMATE FRICTION COEFFICIENT FOR SLIDING = 0.4.
4. ALLOWABLE PASSIVE SOIL PRESSURE FOR SLIDING RESISTANCE: 360 PCF (GRANULAR) 290 PCF (LEAN CLAY)
EQUIVALENT FLUID PRESSURE
1'
0.6h a = 3 ft h = 15 ft a.
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/3 2"
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
G ra p h ic S ca le
/2
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
A/E:Consultant:
Sprinklered
OMAHA EHRM INFRASTRUCTURE
UPGRADE DESIGN
636-21-704
636 - OMAHA VA MEDICAL CENTER
B
IM
/V
IS
N
O m a h a E
H R
M /E
H R
M -S tr u c tu re .r v t
/1
/2
:3
:4
P
M
STRUCTURAL GENERAL NOTES AND DETAILS
RBC CTD
ISSUED FOR BID
FULLY SPRINKLERED
May 15, 2023
Office of Construction and
Facilities Management 01-S001
SCALE: 1 1/2" = 1'-0"
D3
TYPICAL NEW MECHANICAL OPENING IN PAN CONCRETE JOIST
SCALE: 1 1/2" = 1'-0"
E3
TYPICAL PENETRATIONS THROUGH EXIST. DISTRIBUTION RIBS
SCALE: 1" = 1'-0"
C3
TYPICAL PENETRATIONS THRU EXISTING ELEVATED FLOOR FLAT SLAB
SCALE: 1" = 1'-0"
E5
TYPICAL PENETRATIONS THRU EXISTING FOUNDATION/WALLS (ELEVATION)
SCALE: 1" = 1'-0"
D5
TYPICAL OPENING THRU EXISTING EXTERIOR BRICK
TABLE 042000-1 - LAP SPLICE LENGTHS IN GROUTED CMU (GRADE 60 BARS)
BAR SIZE BARS CENTERED IN CELL BARS OFFSET IN CELL (1 1/2" MIN. CLR.) BARS OFFSET IN CELL (2" CLR.)
#3 1’-0” 1’-5” 1'-1"
#4 1’-0” 2’-6” 1'-10"
#5 1’-8” 3’-9” 2'-10"
#6 3'-1" 4'-6" 4'-6"
#7 4'-4" 5'-3" 5'-3"
TABLE 010000-2 - ULTIMATE WALL SURFACE PRESSURE AT h
WALL
AREA 10 SF 100 SF 200 SF 500 SF
NEGATIVE ZONE 4 -40 -35 -30 -30
NEGATIVE ZONE 5 -50 -35 -35 -30
POSITIVE ZONES 4 & 5 35 30 30 30
TABLE 010000-2 - ULTIMATE ROOF SURFACE PRESSURE (PSF)
ROOF
AREA 10 SF 100 SF 200 SF 500 SF
NEGATIVE ZONE 1 -55 -45 -40 -35
NEGATIVE ZONE 1' -35 -35 -30 -20
NEGATIVE ZONE 2 -75 -60 -55 -50
NEGATIVE ZONE 3 -100 -70 -60 -50
POSITIVE ALL ZONES 15 15 15 15
033000 - LAP SPLICE LENGTHS NOTES
1. TOP BARS ARE HORIZONTAL BARS WITH MORE THAN 12" OF CONCRETE CAST BELOW BARS.
2. TABULATED VALUES ARE FOR UNCOATED OR ZINC-COATED (GALVANIZED) BARS. FOR EPOXY COATED BARS, MULTIPLY LENGTH BY 1.5.
3. IF CONCRETE COVER IS LESS THAN 1.0 x db OR C-C SPACING IS LESS THAN 3.0 x db, MULTIPLY LENGTH BY 1.5. (db = BAR DIAMETER)
TABLE 033000-1 - LAP SPLICE LENGTHS (GRADE 60 BARS, NORMAL WEIGHT CONCRETE)
BAR
SIZE
f'c=3000 psi f'c=3500 psi f'c=4000 psi f'c=4500 psi f'c=5000 psi
TOP BARS OTHER BARS TOP BARS OTHER BARS TOP BARS OTHER BARS TOP BARS OTHER BARS TOP BARS OTHER BARS
#3 2'-4" 1'-10" 2'-2" 1'-8" 2'-0" 1'-7" 1'-11" 1'-6" 1'-10" 1'-5"
#4 3'-1" 2'-5" 2'-11" 2'-3" 2'-8" 2'-1" 2'-6" 2'-0" 2'-5" 1'-10"
#5 3'-11" 3'-0" 3'-8" 2'-9" 3'-4" 2'-7" 3'-2" 2'-5" 3'-0" 2'-4"
#6 4'-8" 3'-7" 4'-4" 3'-4" 4'-0" 3'-1" 3'-10" 2'-9" 3'-7" 2'-9"
#7 6'-9" 5'-3" 6'-3" 4'-10" 5'-10" 4'-6" 5'-6" 4'-3" 5'-3" 4'-1"
#8 7'-9" 6'-0" 7'-2" 5'-7" 6'-8" 5'-2" 6'-4" 4'-11" 6'-0" 4'-7"
#9 8'-9" 6'-9" 8'-1" 6'-3" 7'-7" 5'-10" 7'-2" 5'-6" 6'-9" 5'-3"
#10 9'-10" 7'-7" 9'-1" 7'-0" 8'-6" 6'-7" 8'-0" 6'-2" 7'-7" 5'-10"
#11 10'-11" 8'-5" 10'-1" 7'-10" 9'-5" 7'-3" 8'-11" 6'-10" 8'-5" 6'-6"
Revisions: Date:
01/G
5-15-2023
NEW 1 1/2" METAL ROOF DECK EXIST. CANOPY
FACE OF EXTERIOR BRICK
L6x4x5/16
(4) 3/8" Ø HILTI ALL-THREAD HAS ROD w/
HILTI HY 270 ADHESIVE (3 1/8" EMBED.)
AND HIT-SC 16x85 SLEEVE. INSTALL PER
MFR. REQ'S (DRILL SIZE. HOLE SIZE,
CLEANING PROCEDURES ETC.) TYP.
L6x4x5/16 ATTACHED TO EXISTING BRICK
WALL (SLOPE TO MATCH EXISTING)
1/4
TYP. AT ALL
FRAME WELDS
METAL STUD
-SEE ARCH.
EQ EQ EQ EQ
1/4" BENT PLATE
1 1/ 2"
SEE PLANS
2'-0"
MTL STUD
-SEE ARCH.
FACE OF BRICK
VAPOR BARRIER
NEW 5" SLAB-ON-GRADE w/ #4 BAR AT 18" c/c EA. WAY MAX SPACING
#3 BARx1'-0" w/ 4" EMBED (HILTI HY200 ADHESIVE) @ 18" c/c
STEM WALL BELOW
EXISTING STOREFRONT
FOR NEW SLAB TIE-IN
DEMO TOP 8" OF EXISTING
EXIST. SLAB-ON-GRADE
SIDEWALK
-SEE CIVIL
(2) #5xCONT.
#4 STIRRUP @ 24" c/c
8"
1/4" EXP. JT. w/ SEALANT
FREE DRAINING
GRANULAR FILL
LAP VAPOR BARRIER MINIMUM
4" w/ EXISTING VAPOR BARRIER
6"
#4 VERTx2'-6" @ 24" c/c
#4 BAR x CONT.
(3)-#5 TOP AND BOTT.
3' -0
9"
C6
01-SB101
EXISTING WALL TO BE REMOVED
- SEE ARCH.
EXISTING BRICK WALL
EXISTING BRICK WALL
10 11
T
NEW SLAB-ON-GRADE
E.L. = 100'-0"
20'-0" *
V .I.
F
7'-4 3/8" *
DOWEL CONTINUOUS FOOTING
LONGITUDINAL REBAR INTO EXISTING
FOOTING w/ 6" EMBED AND HILTI HY200
ADHESIVE. TYP BOTH ENDS
FACE OF BUILDING
EXISTING SLAB-ON-GRADE
E.L. = 100'-0"
1' -3
/4
EXISTING PIT
TO BE FILLED
A6
01-SB101
4'
-5
V .I.
F
5'-3" V.I.F.
A6
G-SB201
DEMO STEM WALL PER
TO FACILITATE CONSTRUCTION,
ABANDON WALL FOOTING
C6
01-SB101
L6 x4 x5 /1
L6x4x5/16
L6x4x5/16
L6 x4 x5 /1
EXISTING ROOF
EXISTING BRICK WALL
EXISTING BRICK WALL
NEW BRICK WALL BELOW
E6
01-SB101
10 11
T
9 1/2" * E.O.D.
V .I.
F
20'-0" *
8'-3 1/2" * 5'-9 3/8"
V .I.
F
1' -3
/4
FOUNDATION GENERAL NOTES:
1. FOR STRUCTURAL GENERAL NOTES - SEE SHEET 01-S001.
2. * INDICATES DIMENSIONS TO BE COORDINATED WITH OTHER DISCIPLINES.
COORDINATE WITH CIVIL, MECHANICAL, ELECTRICAL, AND ARCHITECTURAL DRAWINGS
AND EQUIPMENT SUPPLIED FOR OPENING SIZES AND LOCATIONS AND SUPPORT
LOCATIONS.
FRAMING GENERAL NOTES:
1. FOR STRUCTURAL GENERAL NOTES - SEE SHEET 01-S001.
2. INDICATES 1 1/2", 20 GA. ROOF DECK.
3. "E.O.D." INDICATES EDGE OF DECK DIMENSION.
4. * INDICATES DIMENSIONS TO BE COORDINATED WITH OTHER DISCIPLINES.
COORDINATE WITH CIVIL, MECHANICAL, ELECTRICAL, AND ARCHITECTURAL DRAWINGS
AND EQUIPMENT SUPPLIED FOR OPENING SIZES AND LOCATIONS AND SUPPORT
LOCATIONS.
2" COMPOSITE FLOOR DECK
WITH 4 1/2" NORMAL WEIGHT
CONCRETE TOPPING
-SEE 01-S001 FOR DECK
PROPERTIES AND REINF. AND
CONNNECTIONS TO SUPPORTS
EXISTING CONCRETE WALL L5x5x3/8xCONT. (GALVANIZED) w/
5/8" Ø HILTI KWIK BOLT TZ2
(GALVANIZED) (3 1/4" EMBED.) @ 18"
c/c MAX. AROUND ENTIRE INFILL
EXISTING SLAB-ON-GRADE
1/
2" T
Y P
4" TYP.
1/4" EXP. JOINT
w/ SEALANT
#3 DOWEL x 1'-0" @ 24" c/c w/ HILTI HY200 ADHESIVE
AROUND ENTIRE INFILL
WWF
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/3 2"
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
G ra p h ic S ca le
/2
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
A/E:Consultant:
Sprinklered
OMAHA EHRM INFRASTRUCTURE
UPGRADE DESIGN
636-21-704
636 - OMAHA VA MEDICAL CENTER
B
IM
/V
IS
N
O m a h a
E H
R M
/E H
R M
-S tr u c tu re .r v t
/1
/2
:3
:5
P
M
PLANS & DETAILS
RBC CTD
ISSUED FOR BID
FULLY SPRINKLERED
May 15, 2023
Office of Construction and
Facilities Management 01-SB101
SCALE: 1" = 1'-0"
E6
SECTION AT NEW ROOF OPENING
SCALE: 1" = 1'-0"
C6
NEW FOOTING AND SLAB
AREA OF WORK
FOR DETAILS A10
AND D10 (THIS SHEET)
SCALE: 3/8" = 1'-0"
D10
FOUNDATION PLAN
SCALE: 3/8" = 1'-0"
A10
ROOF FRAMING PLAN
A
B
D E
C
KEY PLAN
SCALE: 1" = 1'-0"
A6
PIT INFILL AT NEW STOOP
Revisions: Date:
9' -4
/2
20'-0"
(E) 16x7 WF 40
(E) 16x7 WF 45
(E x9
W F
(E x7
W F
(E x7
W F
(E
W
F
(E x7
/2
W F
EXISTING STAIR
OPENING
(E) 16x7 WF 36
G
H
(E) 16x7 WF 45
(E
B
EXISTING CONCRETE
JOIST CONSTRUCTION
(E) 4B7.5
4'-6 1/2" (V.I.F.)
E5
01-SF501
8' -0
(V
.I.
F
(E) 4B7.5
EXISTING OPENING EXISTING OPENING
8'-2"
EXISTING OPENING
TO BE FILLED IN
G
9' -4
/2
5'
-4
/2
20'-0"
4'-6 1/2" V.I.F.
H
F
12 13
(E) 16x7 WF 40
(E) 16x7 WF 45
(E x9
W F
(E x7
W F
(E x7
W F
(E
W
F
(E x7
/2
W F
(E x4
B
(E) 16x7 WF 36
(E) 16x7 WF 45
EXISTING CONCRETE
JOIST CONSTRUCTION
(E) 4B7.5
V.I.F.
EXISTING STAIR
OPENING
E5
01-SF501
8' -0
(V
.I.
F
(E) 4B7.5
EXISTING OPENING EXISTING OPENING
EXISTING OPENING
TO BE FILLED IN
V.I.F.
EXISTING CONCRETE BEAM EXISTING ENCASED W-BEAM
EXISTING SHAFT
L5x5x3/8xCONT. w/ 5/8" Ø HILTI KWIK BOLT TZ2 (3 1/4" EMBED.) @ 18" c/c
MAX. AROUND ENTIRE INFILL
1/
2" T
Y P
2" COMPOSITE FLOOR DECK
WITH 4 1/2" NORMAL WEIGHT
CONCRETE TOPPING
-SEE 01-S001 FOR DECK
PROPERTIES AND REINF.
WWF
FRAMING GENERAL NOTES:
1. FOR STRUCTURAL GENERAL NOTES - SEE SHEET 01-S001.
2. INDICATES 2", 18 GA. FLOOR DECK, w/ 4 1/2" CONCRETE TOPPING.1
FRAMING GENERAL NOTES:
1. FOR STRUCTURAL GENERAL NOTES - SEE SHEET 01-S001.
2. INDICATES 2", 18 GA. FLOOR DECK, w/ 4 1/2" CONCRETE TOPPING.1
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/3 2"
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
G ra p h ic S ca le
/2
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
A/E:Consultant:
Sprinklered
OMAHA EHRM INFRASTRUCTURE
UPGRADE DESIGN
636-21-704
636 - OMAHA VA MEDICAL CENTER
B
IM
/V
IS
N
O m a h a
E H
R M
/E H
R M
-S tr u c tu re .r v t
/1
/2
:3
:5
P
M
FRAMING PLAN
RBC CTD
ISSUED FOR BID
FULLY SPRINKLERED
May 15, 2023
Office of Construction and
Facilities Management 01-SF501
SCALE: 3/8" = 1'-0"
A10
4TH THRU 10TH FLOOR
SCALE: 3/8" = 1'-0"
D10
BASEMENT THRU 3RD FLOOR
A
B
D E
C
KEY PLAN
AREA OF WORK
FOR INFILL AT
NEW TELECOMM
ROOMS)
SCALE: NTS
E5
SECTION AT FLOOR INFILL
Revisions: Date:
LEVEL 1
0"
FULLY GROUTED CMU WALL
-SEE PLANS
WALL REINFORCING
-SEE STR GENERAL NOTES
G E
N E
R A
L N
O T
E S
LA
P
S P
LI
C
E P
E R
SLAB-ON-GRADE
-SEE PLANS
1/4" ISO JOINT w/ SEALER
(3)-#5 TOP AND BOTT.
#4 TIES @ 12" c/c
(1)-#4 EA. FACE
#7 DOWEL BAR MATCH
VERTICAL BAR SPACING
FACE OF BRICK
GRADE
11 5/8"
2'-6"
3' -0
8"
2' -6
100'-0"
E4
G-SB201
5" SLAB-ON-GRADE
EL. = 100'-0"
A6
G-SB201
E4
G-SB201
E4
G-SB201
E4
G-SB201
A10
G-SB201
A10
G-SB201
A10
G-SB201
1 2
A
B
28'-8 3/4"
'-8
/2
E8
G-SB203
APPROX. EXTENTS OF
GENERATOR
-SEE ARCH. AND ELEC.
FOR ISOLATION PAD
AT GENERATOR
-SEE
C4
G-SB202
HOUSEKEEPING PAD
-SEE
C6
G-SB202
9' -6
/8
9'
-9
7' -6
'-7
9' -6
'-1
1/ 8"
6' -0
'-8
/8
A10
G-SB201
DRAIN
-SEE CIVIL AND MECH.
FUEL CONTAINMENT
PAD
-SEE CIVIL
8" NON-LOADBEARING
CMU WALL
-SEE ARCH FOR EXTENTS
AND LOCATIONS
THICKENED SLAB AT
NON-LOADBEARING
CMU WALL TYP.
B4
G-SB202
12" CMU WALL TYP.
9" TYP.
9" T
Y P
'-1
/8
1'
-6
'-0
/4
1'
-6
5' -2
1'
-6
9' -9
1'
-6
1' -7
/8
B4
G-SB201
EXTERIOR CMU
WALL OPENING
-SEE
TYP.
2'-0" 13'-6 3/8" 1'-6" 9'-8 1/2" 2'-0"
3' -1
/8
9'
-9
1' -6
6'
-6
1' -6
9'
-9
/4
3' -3
/4
4'
-6
1' -6
9'
-9
1' -6
6'
-6
/8
1' -6
EQUIPMENT PAD
-SEE
C6
G-SB202
W16x36 (28)
W16x36 (28)
W16x36 (28)
W16x36 (28)
W16x36 (28)
6" E
.O .S
1' -5
/2
E
.O .S
1 2
A
B
C8
G-SB202
C8
G-SB202
C10
G-SB202
C10
G-SB202
TYP.
W16x36 (28)
W16x36 (28)
'-8
/2
TYP.
TOP OF 12" CMU
WALL EL. = 114'-10"
28'-8 3/4"
LINTEL
E6
G-SB202 TYP.
L-
L-
L-
L-
L-
L-
L-
L-
L-1
W16x36 (28)
W16x36 (28)
W16x36 (28)
W16x36 (28)
A10
G-SB202 TYP.
ROOF HATCH OPENING
-SEE ARCH.
A8
G-SB202
1' -5
/8
3' -1
3/
8" 3'
-4
/8
3' -9
3'
-9
3' -9
3'
-1
1/ 8"
3' -1
1/
8" 3'
-8
/8
3' -8
/8
3'
-8
/8
1' -4
3'
-4
3' -4
3'
-8
/8
3' -8
/8
3'
-8
/8
2' -5
/8
W16x36 (28)
W16x36 (28)
T Y
P . U
.N .O
6" E
.O .S
/8
E .O
.S
PROVIDE TOP OF NON-
LOADBEARING CMU
WALL ANCHORAGE
PER
D10
G-SB203 TYP.
L-2
L-2
L-
W16x36 (28)
W16x36 (28)
C8
G-SB202
C8
G-SB202
TYP.
TYP.
BEAM TO BEAM CONNECTION
E5
G-SB203
B8
G-SB202
TYP.
BEAM TO BEAM
CONNECTION w/ STD. HOLES
W x3
(6
W x3
(6
E5
G-SB203 TYP.
8"
TYP.
W16x36 (28)
L-
W x1
W x1
W16x36 (28)
1/
2" 2'
-7
/4
9"9" T
Y P
. U .N
.O
8"
FOR MECHANICAL
OPENINGS NOT SHOWN
-SEE ARCH. & MECH.
B10
G-SB202
W16x36 (28)
"T
"T
"T
"T
"T " 1"
W/ JT SEALER
1/4" EXP JT
(K.C.J.) KEYED CONSTRUCTION JOINT
A
(C.J.) CONTRACTION JOINT (I.J.) ISOLATION JOINT
PAINT FIRST POUR
WITH BOND
BREAKER
REINFORCING -
SEE STRUCTURAL
GENERAL NOTES
1 x 2 NOMINAL KEY
FREE DRAINING
GRANULAR FILL
VAPOR BARRIER
JOINT WITH SEALER
"T
M
IN
REINFORCING - SEE
STRUCTURAL GENERAL NOTES
(CUT EVERY OTHER
WIRE IF W.W.F. IS USED)
VAPOR
BARRIER
FREE DRAINING
GRANULAR FILL
JOINT FILLER
STRIPS
FACE OF WALL, COLUMN,
FOUNDATION OR OTHER
STRUCTURES
NOTES:
1. SEE PLANS AND/OR SPECIFICATIONS.
FOR LOCATION OF CONTROL JOINTS
2. SEE FOUNDATION PLAN
FOR SLAB THICKNESS "T"
B C
TOP OF S.O.G.
EL.=VARIES
(SEE PLANS)
COMPACTED
NATIVE SOIL
REINFORCING -
SEE STRUCTURAL
GENERAL NOTES
COMPACTED
NATIVE SOIL
T Y
P
2" C
LR
EXTERIOR WALL
FOOTING
-SEE
#4@12"c/c
EACH WAY
5'-0" UNLESS NOTED OTHERWISE
8"
V O
ID
6"
7" 1"
C
LR
1/
2"
1'-4"
1' -0
4"
8"
4"
SLAB ON GRADE
EL. - SEE PLAN
W.W.F. TO FIRST
SIDEWALK JT.
#4@12"c/c
MATCHING DOWELS
(ALL SIDES)
#4@12"c/c
HORIZ .
2" - 20 GAGE
METAL DECK
TOP OF FOOTING BEYOND
SEE PLANS
2-#6 CONT.
#4@12"c/c BENT
VERT.
(ALT. HK)
C
LR
1/
2"
3/8" JOINT
(LOCATE UNDER DOOR THRESHOLD)
#4 x 3'-0"@12"c/c
CONTACTOR'S OPTION TO WIDEN
WALL FOR TRENCH CONSTRUCTION
E4
G-SB201
FRAMING GENERAL NOTES:
1. FOR STRUCTURAL GENERAL NOTES - SEE SHEET 01-S001.
2. INDICATES 2", 18 GA. ROOF DECK, w/ 3" CONCRETE TOPPING.
3. * INDICATES DIMENSIONS TO BE COORDINATED WITH OTHER DISCIPLINES.
COORDINATE WITH CIVIL, MECHANICAL, ELECTRICAL, AND ARCHITECTURAL DRAWINGS
AND EQUIPMENT SUPPLIED FOR OPENING SIZES AND LOCATIONS AND SUPPORT
LOCATIONS.
4. TOP OF STEEL ELEVATION = 112'-0"
5. "E.O.S." INDICATES EDGE OF SLAB DIMENSION.
FOUNDATION GENERAL NOTES:
1. FOR STRUCTURAL GENERAL NOTES - SEE SHEET 01-S001.
2. * INDICATES DIMENSIONS TO BE COORDINATED WITH OTHER DISCIPLINES.
COORDINATE WITH CIVIL, MECHANICAL, ELECTRICAL, AND ARCHITECTURAL DRAWINGS
AND EQUIPMENT SUPPLIED FOR OPENING SIZES AND LOCATIONS AND SUPPORT
LOCATIONS.
3. EL. 100'-0" = ELEVATION 1231.50 ON CIVIL PLANS.
CORNER
BARS
SINGLE LAYER WALL REINFORCING
CORNER
BARS
DOUBLE LAYER WALL REINFORCING
0"
0"
NOTE:
CORNER BARS ARE TO BE THE SAME SIZE AND
SPACING AS HORIZ. WALL BARS.
PROVIDE CORNER BARS AT "T" INTERSECTION
OF WALLS
* LAP AS PER
STRUCTURAL
GENERAL NOTES
JAMB REINFORCING
-SEE
SLAB-ON-GRADE
-SEE PLANS
1/4" ISO JOINT w/ SEALER
PROVIDE (3)-#5
SUPPLEMENTARY BENT BARS
#4 TIES @ 12" c/c
#7 DOWEL BAR MATCH
VERTICAL BAR SPACING
FACE OF BRICK
GRADE
3'-6"
3' -0
8"
G E
N E
R A
L N
O T
E S
LA
P
S P
LI
C
E P
E R
2' -6
B6
G-SB202
2'-0" 9"
WALL FOOTING
EDGE BEYOND
LEVEL 1
100'-0"
T.O.S. AT CMU WALL
112'-0"
OPENING
CMU WALL
G-SB202
E10
B6
G-SB202
B6
G-SB202
E2
G-SB201
E4
G-SB201
CMU WALL
CMU WALL
C8
G-SB202
B8
G-SB202 CONCRETE-ON-DECK BEYOND
TYP. TYP.
E4
G-SB201
SEE PLANS
1'-6" MIN.
E6
G-SB202 G
ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/3 2"
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
G ra p h ic S ca le
/2
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
A/E:Consultant:
Sprinklered
OMAHA EHRM INFRASTRUCTURE
UPGRADE DESIGN
636-21-704
636 - OMAHA VA MEDICAL CENTER
B
IM
/V
IS
N
O m a h a
E H
R M
/E H
R M
-S tr u c tu re .r v t
/1
/2
:3
:5
P
M
PLANS AND DETAILS
RBC CTD
ISSUED FOR BID
FULLY SPRINKLERED
May 15, 2023
Office of Construction and
Facilities Management G-SB201
SCALE: 3/4" = 1'-0"
E4
TYPICAL WALL FOOTING AT CMU
SCALE: 1/4" = 1'-0"
B10
FOUNDATION PLAN AT GENERATOR BUILDING
SCALE: 1/4" = 1'-0"
B7
ROOF FRAMING PLAN AT GENERATOR BUILDING
SCALE: 1 1/2" = 1'-0"
A6
TYPICAL SLAB ON GRADE JOINT DETAILS
SCALE: 3/4" = 1'-0"
A10
CONCRETE STOOP DETAIL
A
B
D E
C
KEY PLAN
AREA OF WORK
FOR GENERATOR
BUILDING
SCALE: 3/4" = 1'-0"
A8
TYPICAL WALL CORNER REINFORCING
SCALE: 3/4" = 1'-0"
E2
TYPICAL WALL AT CONCRETE JAMB
G
SCALE: 1/2" = 1'-0"
B4
TYPICAL EXTERIOR CMU WALL OPENING
Revisions: Date: 5-15-2023
TYP.
C/C SPACING
ASTM C90 CONCRETE
MASONRY UNITS
HORIZ. LADDER TYPE JOINT
REINFORCING, MAXIMUM 16" c/c
VERTICAL SPACING - #9 GAGE MIN.
ALL CELLS FULLY GROUTED
LOCATION OF LAP
SPLICE BAR IF
REQUIRED (TYP.)
C
LR2"
(MIN.)
1/2" CLR
(T Y
P
5/ 8"
C O
V E
R
C
LR2"
CONCRETE ON DECK
-SEE PLANS
2-L4x4x1/4x0'-6"
(ONE EACH SIDE)
12" x 8" HIGH BOND BEAM
GROUT AS SHOWN OR
CUT 16" HIGH LINTEL BLOCK
(CONTRACTOR'S OPTION)
2-#5 CONT.MASONRY BEARING WALL
HORIZONTAL JOINT REINF.
SPACED VERTICALLY @ 16"c/c MAX.
BEARING PL 3/8"x5"x1'-0" w/2-1/2" Ø x 6" HEADED STUDS @ 8" c/c
VERT. WALL REINFORCING
AS PER STRUCTURAL GENERAL NOTES
6".
T.O.S.
EL. - SEE PLAN
W BEAM
GROUT POCKET FULL
3/16
BOLTED ANCHORAGE TO
CMU AS PER
PL 1/4"
C8
G-SB202
CONCRETE-ON-DECK
-SEE PLANS
VERTICAL WALL REINFORCING
PER STRUCTURAL GENERAL NOTES
CMU WALL
-SEE PLANS
BENT PL 5/16"xCONT. w/
VERT. LONG SLOTTED HOLE
W BEAM
-SEE PLANS
EL. = SEE PLANS
8" BOND BEAM
w/ (2)-#5xCONT.
#6 DEFORMED BAR ANCHOR
(WELDED TO BENT PL) ADJACENT
TO ALL-THREAD WHERE OCCURS
5/16
DBA TO PL
GENERAL NOTES
LAP SPLICE LENGTH PER
GALVANIZED PL 1"x5"x5"
1/
2"
(1) 3/4" Ø ASTM F1554
GR. 105 ALL-THREAD
AT 12" c/c MAX.
TYP.
2"
T Y
P
2"
T
Y P
TYP.
2"
S E
E P
LA
N
SEE PLAN
SEE PLAN
S E
E P
LA
N
CLR
2"
CLR
2"
2-#5 CORNER
BARS (TYP.)
2-#5 STRAIGHT
BARS (TYP.)
FULLY GROUTED AND
REINFORCED BOND
BEAM
2-#5 STRAIGHT
BARS (TYP.)
VERTICAL REINF.
IN GROUTED CELL
IF REQUIRED
STRAIGHT
BARS (TYP.)
CORNER BARS
4" O
R A
S N
O T
E D
SEE NOTE BELOW
1'-0"
MIN.
4"
2" MIN. CLR.
1/ 2"
C
LR
3"
3/4"
CHAMFER
ALL SIDES
1/2" Ø BOLTS IN
1/2" Ø DROP-IN EXPANSION
ANCHORS AT 18" c/c MAX. SPACING
AROUND PAD PERIMETER
2"
#4 @ 12"c/c
EACH WAY
SLAB ON GRADE OR
STRUCTURAL SLAB -
REINF. NOT SHOWN
NOTE:
COORDINATE SIZE AND LOCATION OF PADS WITH MECHANICAL AND ELECTRICAL
CONTRACTORS. PAD CONFIGURATION, SIZE AND LOCATION OF ANCHORS AND SLEEVES SHALL
CONFORM TO MANUFACTURER'S REQUIREMENTS
SEE PLAN
S E
E P
LA
N
S
0"
CONCRETE-ON-DECK
-SEE PLANS
(2)-#5 AROUND
ALL FLOOR OPENINGS
EXTEND 3'-0"
BEYOND OPENING
BENT PL 1/4"xCONT.
W BEAM
FINISHED FLOOR
EL. - SEE PLAN
SLAB REINF. -
SEE STRUCTURAL
GENERAL NOTES
1" C
LR
.3/16 2-12
VARIES
OPENING
-SEE PLANS
(13)-#7 VERT. EA. FACE (2 ROWS)
#4 TIES @ 6" c/c
CAST-IN-PLACE CONCRETE JAMB
2' -0
EXTERIOR FACE OF CMU WALL
0"
NOTE:
WHERE CMU BOND BEAMS OCCUR AT ELEVATIONS WHERE
OPENINGS OCCUR, PROVIDE (2)-#5 BENT BAR DOWELS INTO
CMU JAMBS.
WHERE CMU BOND BEAMS OCCUR AT ELEVATIONS WHERE
OPENINGS DO NOT OCCUR, CONTINUE BOND BEAM
REINFORCEMENT THROUGH CONCRETE JAMBS.
CONCRETE LINTEL
-FOR REINFORCING SEE
CAST-IN-PLACE
CONCRETE JAMB
VERTICAL REINFORCING
-SEE
B6
G-SB202
E6
G-SB202
OPENING
GENERAL NOTES
LAP SPLICE PER
BENT BAR w/ STD. HOOK
MATCH LINTEL BAR SIZE
AND SPACING TYP.
A S
N O
T E
D 4"
O R
SEE NOTE BELOW
MIN.
4"
2" MIN. CLR.
1/ 2"
C
LR
3/4" CHAMFER
ALL SIDES
NOTE:
COORDINATE SIZE AND LOCATION OF PADS
WITH MECH. AND ELEC. CONTRACTORS.
PAD CONFIGURATION, SIZE AND LOCATION
OF ANCHORS AND SLEEVES SHALL
CONFORM TO MFR'S. REQUIREMENTS
#6 @ 12"c/c
EACH WAY T&B
P
LA
N S
E E
C
LR
3"
SLAB REINF. -
SEE STRUCTURAL
GENERAL NOTES
SLAB ON GRADE
EL. - SEE PLAN
1/2" ISOLATION
JOINT (I.J.)
ANCHORAGE BY MFR.
SEE PLAN SEE PLAN
(3)-#5 EXTEND 3'-0"
BEYOND OPENING
BENT PL 5/16"xCONT.
W BEAM
FINISHED FLOOR
EL. - SEE PLAN
1/
2" C
LR
3/16 2-12
5/16
DBA TO PL TYP.#6 DEFORMED BAR ANCHORS
WHERE CMU WALL ATTACHMENT
OCCURS PER
C8
G-SB202
#3 TIES @ 6" c/c
E10
G-SB202
(7)-#7 EACH FACE
NOTE:
1. PROVIDE SHORING UNDER CONCRETE LINTEL FOR A MINIMUM OF
SEVEN DAYS AFTER PLACEMENT.
2. MONOLITHICALLY GROUT CMU LINTEL UNIT AND CELLS SOLID.
3. MECHANICALLY VIBRATE GROUT.
4. HORIZONTAL LINTEL REINFORCING SHALL NOT BE SPLICED.
5. GROUTING OF LINTEL SHALL BE CONTINUOUS WITHOUT
HORIZONTAL OR VERTICAL COLD JOINTS THE FULL HEIGHT
AND LENGTH OF THE LINTEL (INCLUDING END BEARING).
6. SEE DETAIL FOR CONCRETE LINTEL BEARING.
7. SEE DETAIL FOR CMU LINTEL BEARING.
(2)-#5 CONT.
8" NON-LOADBEARING CMU
CONCRETE LINTEL L-1 CMU LINTEL L-2
A6
G-SB202
1'-6"
1' -0
EXTERIOR FACE
OF CMU WALL
8"x8" CMU LINTEL
CMU VERT. REINF.
-SEE GERNERAL NOTES
CMU VERT. REINF.
-SEE GENERAL NOTES
#7 DOWEL BAR - MATCH
CMU VERT. REINF.
ROTATE STD. HOOKS AS
NECESSARY
* LAP AS PER
STRUCTURAL
GENERAL NOTES
BEARING
8" MIN.
6" MIN.
LINTEL REINFORCING
-SEE
E6
G-SB202
FOR OPENINGS 5'-0" WIDE OR LESS,
PLACE (1)-#5 FOR 8" CMU VERT. IN
ONE CELL ON EACH SIDE OF
OPENING. FOR OPENINGS GREATER
THAN 5'-0", PLACE (1)-#6 FOR 8" CMU
VERT. IN ONE CELL ON EACH SIDE
OF OPENING (TYP. UNO.) FULL
HEIGHT OF WALL
2" T
Y P
(4) GALV. 1" Ø ASTM F1554 GR.
105 ALL THREAD RODS CAST IN
WITH CONCRETE (DO NOT DRILL)
CAST-IN-PLACE
CONCRETE JAMB
-SEE
GALV. PL 1 5/8"x12"x16"
(GRADE 50)
CONCRETE-ON-DECK
-SEE PLANS
CJP
W BEAM
-SEE PLANS
5/16 12
TYP. EA. SIDE OF
WEB
PL 3/8"x4"x1'-0" EA SIDE
OF W BEAM WEB
SEE PLANS
1/2"
B6
G-SB202
1' -4
COPE BOTTOM FLANGE AS
REQUIRED FOR CONSTRUCTION
CMU WALL
-SEE PLANS
1/4" GALV. PL w/ 1" Ø GALV.
NELSON STUDS (6 1/4" MIN.
EMBED.) (2 STUDS PER CMU
CELL)
SEE ARCH. AND MECH.
28" MAX.
S E
E A
R C
H . A
N D
M E
C H
M A
X
1' -0
3"
2 x NOMINALWALL THICKNESS 8"
2-#5 CONT.
VAPOR
BARRIER
FREE DRAINING
GRANULAR FILL
SLAB ON GRADE
EL. - SEE PLAN
SLAB REINF. -
SEE STRUCTURAL
GENERAL NOTES
HORIZONTAL JOINT REINF.
SPACED VERTICALLY @ 16" c/c MAX.
VERTICAL WALL REINF.
-SEE STRUCTURAL GENERAL NOTES
THICKENED SLAB IS REQUIRED UNDER
ALL INTERIOR NON-LOAD BEARING
MASONRY WALLS UNLESS DETAILED OTHERWISE.
COORDINATE WALL LOCATIONS w/ ARCH. PLANS
S E
E P
LA
N
C
LR3"
2" C
LR
COMPACTED
NATIVE SOIL
ROTATE VERTICAL BARS AS
REQUIRED TO PROVIDE 3"
CLEAR COVER FOR END OF HOOKS
MATCH VERTICAL WALL REINF. WITH
DOWELS w/ STD. 90° HOOKS
(ALTERNATE HOOK)
LAP AS PER STRUCTURAL GENERAL NOTES
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/3 2"
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
G ra p h ic S ca le
/2
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
A/E:Consultant:
Sprinklered
OMAHA EHRM INFRASTRUCTURE
UPGRADE DESIGN
636-21-704
636 - OMAHA VA MEDICAL CENTER
B
IM
/V
IS
N
O m a h a
E H
R M
/E H
R M
-S tr u c tu re .r v t
/1
/2
:3
:5
P
M
FOUNDATION AND FRAMING DETAILS
RBC CTD
ISSUED FOR BID
FULLY SPRINKLERED
May 15, 2023
Office of Construction and
Facilities Management G-SB202
SCALE: 1" = 1'-0"
E8
TYPICAL REINFORCED CMU WALL DETAIL
SCALE: 1" = 1'-0"
C10
STEEL BEAM BEARING PERPENDICULAR AT MASONRY
SCALE: 1 1/2" = 1'-0"
C8
TOP OF CMU WALL ANCHORAGE TO DIAPHRAGM
SCALE: 1 1/2" = 1'-0"
E3
BOND BEAM UNIT AT CORNER
SCALE: 1 1/2" = 1'-0"
C6
HOUSEKEEPING EQUIPMENT PAD DETAIL
SCALE: 1 1/2" = 1'-0"
A10
TYPICAL SLAB OPENING
SCALE: 1" = 1'-0"
B6
CAST-IN-PLACE CONCRETE JAMB
SCALE: 1 1/2" = 1'-0"
E10
CONCRETE LINTEL AT OPENING JAMB
SCALE: 1 1/2" = 1'-0"
C4
ISOLATION EQUIPMENT PAD DETAIL
SCALE: 1 1/2" = 1'-0"
A8
SLAB AT ROOF HATCH OPENING
Revisions: Date:
G
SCALE: 1" = 1'-0"
E6
CONCRETE AND CMU LINTEL DETAILS
SCALE: 1" = 1'-0"
A6
TYPICAL CMU LINTEL BEARING DETAIL
SCALE: 1" = 1'-0"
B8
TOP OF JAMB SUPPORT
SCALE:NONE
B10
CMU WALL OPENING PLATE
SCALE: 1 1/2" = 1'-0"
B4
TYPICAL THICKENED SLAB
SINGLE PLATE CONNECTION SCHEDULE
BEAM
SIZE
PLATE
LENGTH
"L"
PLATE
THICK
"T"
NUMBER OF
BOLTS "n"
BOLT SIZE
AND TYPE
W8 6" 3/8" 2 3/4"Ø A325-N
W10 6" 3/8" 2 3/4"Ø A325-N
W12 9" 3 3/4"Ø A325-N
W14 9" 3 3/4"Ø A325-N
12" 4 3/4"Ø A325-N
W18 12" 4 3/4"Ø A325-N
W16
NOTES:
1. DETAIL APPLIES TO ALL SIMPLY SUPPORTED BEAMS,
FRAMING INTO BEAMS, UNLESS SPECIFIC DETAILS
FOR AN ALTERNATE CONNECTION ARE PROVIDED.
2. "k" + 1 1/2" OR 3" MIN. - "k" = DISTANCE FROM OUTER FACE OF
FLANGE TO WEB TOE OF FILLET OF ROLLED SHAPE OR
EQUIVALENT DISTANCE ON WELDED SECTION, IN.
4"
2 1/2" 1 1/2"
2"
LE
N
G T
H
1/
2"
1/ 2"
"c /c
T Y
P
S P
A C
IN
G
S E
E N
O T
E
BOLTS - SEE SCHEDULE
PL "T" x 4" x "L"
0" M
IN
4"
2 1/2" 1 1/2"
2"
S E
E N
O T
E
0" M
IN
1/4
3/8"
3/8"
3/8"
3/8"
PAVEMENT
-SEE CIVIL
3' -6
#6 @ 12" c/c EACH WAY
TOP AND BOTTOM,
HOOK TOP BARS
1/4" EXPANSION JOINT w/
SEALANT TYP.
APPROX. EXTENTS OF FUEL TANK
8" 2 1/2"2 1/2" 8"
3' -6
T
Y P
(4)-#5xCONT. EA. STEM
#4 @ 12" c/c ENTIRE TANK PERIMETER
(VERTICAL BAR CENTERED IN WALL)
SEE CIVIL
2' -8
(2)-#5 SIDE BARS TYP.
M
IN
2"
C
LR1"
NON-LOADBEARING CMU
-SEE PLANS
VERT. WALL REINFORCING
AS PER STRUCTURAL
GENERAL NOTES
(2)-L3x3x1/4"x0'-9" LONG
@ 4'-0" C/C ANCHOR TO
METAL DECK w/ (2)-3/8" Ø HILTI
KWIK BOLT TZ2 EXP. ANCHORS
(2 1/2" EMBED.)
CMU BOND BEAM
w/ (2)-#5 CONT.
BENT PL. 1/4"x0'-9" LONG .
@ 4'-0" C/C ANCHOR TO
METAL DECK w/ (2)-3/8" Ø HILTI
KWIK BOLT TZ2 EXP. ANCHORS
(2 1/2" EMBED.)
CONCRETE ON DECK
-SEE PLANS
GROUT IF REQUIRED
NON-LOADBEARING CMU
-SEE PLANS
VERT. WALL REINFORCING
AS PER STRUCTURAL
GENERAL NOTES
(2)-L3x3x1/4"x0'-9" LONG
@ 4'-0" C/C ANCHOR TO
PL w/ #12 SELF-TAPPING SCREWS
CMU BOND BEAM
w/ (2)-#5 CONT.
PL 1/4" TO BRIDGE
BETWEEN FLUTES ANCHOR TO
METAL DECK w/ (2)-3/8" Ø HILTI
KWIK BOLT TZ2 EXP. ANCHORS
(2 1/2" EMBED.)
CONCRETE ON DECK
-SEE PLANS GROUT IF REQUIRED
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/3 2"
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
G ra p h ic S ca le
/2
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
A/E:Consultant:
Sprinklered
OMAHA EHRM INFRASTRUCTURE
UPGRADE DESIGN
636-21-704
636 - OMAHA VA MEDICAL CENTER
B
IM
/V
IS
N
O m a h a
E H
R M
/E H
R M
-S tr u c tu re .r v t
/1
/2
:3
:5
P
M
FRAMING DETAILS
RBC CTD
ISSUED FOR BID
FULLY SPRINKLERED
May 15, 2023
Office of Construction and
Facilities Management
VA: Approver G-SB203
Revisions: Date:
SCALE:NONE
E5
TYPICAL BEAM TO BEAM CONNECTION AND SCHEDULE
SCALE: 1/2" = 1'-0"
E8
FUEL TANK PAD AND CONTAINMENT WALL
SCALE:NONE
D10
CMU PARTITION ANCHORAGE
| Sheets |
| 01-S001 - STRUCTURAL GENERAL NOTES AND DETAILS |
| 01-SB101 - PLANS & DETAILS |
| 01-SF501 - FRAMING PLAN |
| G-SB201 - PLANS AND DETAILS |
| G-SB202 - FOUNDATION AND FRAMING DETAILS |
| G-SB203 - FRAMING DETAILS |
File details come from the government source that posted it. Updated .