Attachment 01 Additional Questions and Answers.pdf

PDF 111 KB Posted

Attached to
Y1DA--Copy of EHRM Infrastructure Upgrades - Construction - Omaha VAMC DUPLICATE OF 36C776230036
Solicitation number
36C77623B00361
Issued by

About this file

This document contains additional questions and answers pertaining to a federal solicitation for infrastructure upgrades at the Omaha Veterans Affairs Medical Center. The solicitation seeks a contractor to supply and install a backup generator meeting specifications, provide training on new equipment including the generator, and review proposed UPS and electrical configurations to determine if they meet intended requirements. No additional network equipment will be provided by the VA. The related federal contract opportunity is for EHRM infrastructure upgrades and construction at the Omaha VAMC with solicitation number 36C77623B00361 from the Department of Veterans Affairs Technology Acquisition Center in Austin.

View the file

Other files

File Type Posted
Attachment 01 Question and Answer.docx DOCX document
36C77623B0036-1 0008.docx DOCX document
Attachment 02 Spec 01 00 00 -2 POP Rev1.pdf PDF
Attachment 04 Additional Drawings.pdf PDF
36C77623B0036-1 0007.docx DOCX document
Attachment 03 Additional Drawing Sheet List.pdf PDF
ATTACHMENT 01 - SPECIFICATIONS SECTION 27 COMMUNICATIONS.zip ZIP file
36C77623B0036-1 0006.docx DOCX document
ATTACHMENT 02 - 09 65 19 19 STATIC DISSIPATIVE TILE.pdf PDF
Attachment 01 Omaha EHRM V21 - RFI Responses.pdf PDF
36C77623B0036-1 0005.docx DOCX document
Attachment 03 Tech Notes 636 704.B01.00 TN001.T.20230726.pdf PDF
Attachment 04 Omaha EHRM Addendum Mech Drawings.pdf PDF
Attachment 02 09 65 16 Resiliant Tile Flooring.pdf PDF
36C77623B0036-1 0004.docx DOCX document
Davis Bacon Wage Determinations.pdf PDF
36C77623B0036-1 0003.docx DOCX document
36C77623B0036-1 0002.docx DOCX document
Attachment 1 Site Visit Sign In EHRM Infrastructure Upgrades Construction.pdf PDF
36C77623B0036-1 0001.docx DOCX document
Attachment 09 VA-Omaha EHRM Civil_20230515 - Drawing.pdf PDF
Attachment 06 Omaha EHRM Structural_20230515 - Drawing.pdf PDF
Attachment 03 Specification vol 1 Rev1.pdf PDF
Attachment 07 OMAHA VA EHRM_BID SET_ELECTRICAL - Drawing.pdf PDF
Attachment 04 OMAHA VA EHRM_BID SET_ARCHITECTURAL - drawings.pdf PDF
Attachment 05 OMAHA VA EHRM_BID SET_MECHANICAL - Drawing (1).pdf PDF
Attachment 14 Specification Vol 2 Rev1.pdf PDF
Attachment 08 OMAHA VA EHRM_BID SET_TECHNOLOGY - Drawing.pdf PDF
Attachment 02 Omaha EHRM 100 Narrative Mechanical (2).pdf PDF
Attachment 02 Omaha EHRM 100 Narrative Mechanical.pdf PDF
Attachment 01 Omaha EHRM 100 Narrative Elec Revised.pdf PDF
Attachment 16 Service Contract Wage Determinations.gov.pdf PDF
Attachment 10 DBA Wage Determination 4.13.2023.gov.pdf PDF
Attachment 15 HEFP SEP SOP Process Flow Data Center Phase v1.0.pdf PDF
Attachment 13 - Site Visit EHRM Minor Construction Project- Omaha.docx DOCX document
Attachment 11 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 12 - Limitations on Subcontracting - Construction.docx DOCX document
36C77623B0036-1_1.docx DOCX document
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Addendum Additional Questions and Answers: Omaha EHRM 636-21-704

Q1. Will the Generator be government provided contractor installed equipment?

A1. No, contractor will supply the generator per specifications.

Q2. What will be the duration for training/certification, and will there be any costs?

A2. Training shall be supplied on any new equipment, especially generator. Exact duration is not available.

Q3. Does the VA have extra network equipment (Switch gear, routers, UPS's) to keep the network connected during construction and cut over between the old network room and the new network room?

A3. No

Q4. Input Breaker (600A) and to the Bypass Input Breaker (600A). This is not needed as we would be supplying the configuration as a dual-input UPS with a Maintenance Bypass cabinet that has the two

(2) needed sub feed breakers (for both Server and Phone PDU’s) integrated. Please confirm this configuration will be acceptable.

A4. VA would need to review the equipment proposed to use to determine if it met the intended requirements to delete circuit breakers.

Q5. Refer to Drawing Sheet 01-EP110. The UPS System is equipped with EPO (Emergency Power Off)

Dry contacts. The breakers feeding the UPS in UPSDPA and UPSDPB will not need to be shunt-tripped. Please confirm this configuration will be acceptable.

A5. VA would need to review the equipment proposed to use to determine if it met the intended requirements.

File details come from the government source that posted it. Updated .