Attachment 04 Omaha EHRM Addendum Mech Drawings.pdf

PDF 608 KB Posted

Attached to
Y1DA--Copy of EHRM Infrastructure Upgrades - Construction - Omaha VAMC DUPLICATE OF 36C776230036
Solicitation number
36C77623B00361
Issued by

About this file

This document is a solicitation for infrastructure upgrades at the Omaha VA Medical Center. Key details include the following:

The solicitation is for construction services to upgrade the EHRM infrastructure at the Omaha VAMC. Upgrades include mechanical, electrical, and plumbing work associated with replacing aging HVAC equipment, upgrading electrical switchgear and panels, replacing the diesel fuel system for emergency generators, and other facility improvements. The solicitation type is construction and the contracting agency is the Department of Veterans Affairs Technology Acquisition Center in Austin. The response due date is not provided but the document appears to be a duplicate of solicitation number 36C776230036.

View the file

Other files

File Type Posted
Attachment 01 Question and Answer.docx DOCX document
36C77623B0036-1 0008.docx DOCX document
Attachment 01 Additional Questions and Answers.pdf PDF
Attachment 02 Spec 01 00 00 -2 POP Rev1.pdf PDF
Attachment 04 Additional Drawings.pdf PDF
36C77623B0036-1 0007.docx DOCX document
Attachment 03 Additional Drawing Sheet List.pdf PDF
ATTACHMENT 01 - SPECIFICATIONS SECTION 27 COMMUNICATIONS.zip ZIP file
36C77623B0036-1 0006.docx DOCX document
ATTACHMENT 02 - 09 65 19 19 STATIC DISSIPATIVE TILE.pdf PDF
Attachment 01 Omaha EHRM V21 - RFI Responses.pdf PDF
36C77623B0036-1 0005.docx DOCX document
Attachment 03 Tech Notes 636 704.B01.00 TN001.T.20230726.pdf PDF
Attachment 02 09 65 16 Resiliant Tile Flooring.pdf PDF
36C77623B0036-1 0004.docx DOCX document
Davis Bacon Wage Determinations.pdf PDF
36C77623B0036-1 0003.docx DOCX document
36C77623B0036-1 0002.docx DOCX document
Attachment 1 Site Visit Sign In EHRM Infrastructure Upgrades Construction.pdf PDF
36C77623B0036-1 0001.docx DOCX document
Attachment 09 VA-Omaha EHRM Civil_20230515 - Drawing.pdf PDF
Attachment 06 Omaha EHRM Structural_20230515 - Drawing.pdf PDF
Attachment 03 Specification vol 1 Rev1.pdf PDF
Attachment 07 OMAHA VA EHRM_BID SET_ELECTRICAL - Drawing.pdf PDF
Attachment 04 OMAHA VA EHRM_BID SET_ARCHITECTURAL - drawings.pdf PDF
Attachment 05 OMAHA VA EHRM_BID SET_MECHANICAL - Drawing (1).pdf PDF
Attachment 14 Specification Vol 2 Rev1.pdf PDF
Attachment 08 OMAHA VA EHRM_BID SET_TECHNOLOGY - Drawing.pdf PDF
Attachment 02 Omaha EHRM 100 Narrative Mechanical (2).pdf PDF
Attachment 02 Omaha EHRM 100 Narrative Mechanical.pdf PDF
Attachment 01 Omaha EHRM 100 Narrative Elec Revised.pdf PDF
Attachment 16 Service Contract Wage Determinations.gov.pdf PDF
Attachment 10 DBA Wage Determination 4.13.2023.gov.pdf PDF
Attachment 15 HEFP SEP SOP Process Flow Data Center Phase v1.0.pdf PDF
Attachment 13 - Site Visit EHRM Minor Construction Project- Omaha.docx DOCX document
Attachment 11 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 12 - Limitations on Subcontracting - Construction.docx DOCX document
36C77623B0036-1_1.docx DOCX document
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROVIDE A SECTION OF HIGH

COMPRESSION STRENGTH INSULATION

AT EACH HANGER POINT. INSULATION

MAY BE HALF ROUND OR FULL ROUND

AND EXTEND 2" BEYOND GALV. SHIELD

EACH WAY.

GALVANIZED IRON

SHEET SHIELD

INSULATION

STEEL PIPE SADDLE,

TACK WELDED TO PIPE,

FILL SADDLE WITH

INSULATION.

OVERSIZE HANGER TO ALLOW

LONGITUDINAL PIPE EXPANSION

AND PIPE INSULATION TO PASS

THROUGH UNBROKEN. (TYP)

UNI-SIRUT OR EQUIVALENT

HIGH DENSITY INSULATION INSERT

(TYP)

THREADED ROD.(TYP)

PIPE INSULATION(TYP)

INSULATION SHIELD (TYP)

INSTALL CLAMP ON ALL

PIPES LESS THAN 4"Ø

HIGH DENSITY INSULATION INSERT OR,

FOR APPLICATIONS PERMITTED IN

SPECIFICATIONS, STEEL SADDLE FILLED

WITH INSULATION.

NOTES:

1. REFER TO SPECIFICATIONS FOR MORE INFORMATION.

2. SERVICE: RECOMMENDED FOR SUSPENSION OF INSULATED (HOT OR COLD) PIPE WHEN FLEXIBILITY OF THE CLAMP IS DESIREABLE.

½"

T=THICKNESS

STEEL PLATE

B

AC

45°

D

PIPE SIZE

A

B

C

D

T

ROD SIZE

CLEVIS SIZE

ROD TAP

PIN DIA.

PIN HOLE

GRIP

2"

1"

3 1/2"

3" 4" 6"

3 1/2" 3 1/2"

2" 2"

1" 1"

1/2" 5/8" 5/8"

3/8" 3/8" 3/8"

3/8" 1/2" 1/2"

2" 2" 2"

3/8" 1/2" 1/2"

3/8" 1/2" 1/2"

1/2" 5/8" 5/8"

1/2" 1/2" 1/2"

USE TURNBUCKLE IF BUILDING

CONNECTION DOES NOT PROVIDE

ADJUSTMENT

HEX NUT

PIPE SIZE

ROD

SIZE

GRINNELL ROD ATTACHMENT

CLEVIS FIG. 299

1/8" COTTER PIN

VERTICAL ELBOW

INSULATION

PIPE

ADJUSTABLE CLEVIS GRINNELL FIG. 65 OR

ADJUSTABLE CLEVIS GRINNELL FIG. 260

INSULATION

PIPE

HANGER ROD

INSULATION PROTECTION SHEILD: GRINNELL

FIG. 167 (SIZE RANGE 1/2" THRU 24" PIPE WITH

INSULATION THICKNESS OF 1/2", 3/4", 1", 1-1/2",

AND 2")

PIPE COVERING PROTECTION SADDLE

SINGLE PIPE ROLLER COMPLETE

GRINNELL FIG. #171

HANGER ROD

PROVIDE A SECTION OF HIGH

COMPRESSION STRENGTH INSULATION

AT EACH HANGER POINT. INSULATION

MAY BE HALF ROUND OR FULL ROUND

AND EXTEND 2" BEYOND GALV. SHIELD

EACH WAY.

PROVIDE A SECTION OF HIGH COMPRESSION

STRENGTH INSULATION AT EACH HANGER POINT.

INSULATION MAY BE HALF ROUND OR FULL ROUND

AND EXTEND 2" BEYOND GALV. SHIELD EACH WAY.

PIPE CL

PIPE ℄

PIPE ℄

8" x 8" x 3/8" [203 x 203 x 8mm] STEEL PLATE

WELD PLATE TO

PIPE

SECURE TO ROOF SLAB WITH

(4) 3/8" [10mm] EXPANSION

BOLTS OR WELD TO STEEL

DECK

CONCRETE ROOF SLAB OR

STEEL ROOF DECK

ROOF SYSTEM

INSULATION AND

MEMBRANE

PRE-MOULDED FLEXIBLE

PIPE COUNTER FLASHING

CLAMPING RING

ROOF SURFACE

WELD PIPE SADDLE

SUPPORT TO PIPE.

PROVIDE WATER TIGHT

CONNECTION.

HIGH COMPRESSIVE

STRENGTH INSULATION

INSERT UNDER SHIELD

PIPE AND

INSULATION

INSULATION PROTECTION

SHIELD

SEALANT

2" [50mm] STEEL PIPE

2-1/2" [65mm] STEEL PIPE

PROVIDE VAPOR BARRIER

AS SPECIFIED ON PIPING

CONVEYING FLUID TO

DEGREE ____°F [ ___°C]

NOTES:

1. PROVIDE RESTRAINING CLAMPS 8'-0" [2,4m] O.C.

m m

[8 m m m m

[1

M

IN

[4

PROVIDE ALUMINUM

JACKET

FULL SIZE CONNECTION

CONDENSATE

DRAIN

UNION

UNION

MAX. UNIT

TOTAL S.P. + 2"

PITCH CONDENSATE

DRAIN LINE TO NEWEST

GUTTER DRAIN

1" MIN. CLEARANCE

PIPE SLEEVE DETAIL PIPE THRU FLOOR DETAIL

INSTALL AN ESCUTCHEON AROUND PIPES

EXPOSED IN FINISHED ROOMS. FOR ALL

INSULATED PIPING INSTALL A PLASTIC JACKET

EXTENDING 6" BEYOND THE WALL TO PROTECT

INSULATION FROM DAMAGE.

MAKE A SMOOTH ROUND OPENING IN WALL

SLIGHTLY LARGER THAN OUTSIDE DIAMETER

OF THE PIPE AND INSULATION.

ADD A BEAD OF NON-HARDENING

CAULK IN THE ANNULAR SPACE.

NOTES:

1. THIS DETAIL APPLIES TO ALL PIPES. THE INTENTION IS TO CONTINUE THE INSULATION AND VAPOR BARRIER THROUGH ALL PENETRATIONS. PERMIT THERMAL EXPANSION WITHOUT DAMAGING INSULATION, AND TO SEAL

AIRTIGHT AROUND INSULATED AND UNINSULATED PIPES FOR NOISE TRANSMISSION CONTROL.

2. FLOOR OPENINGS ARE SIMILAR. SEE SPECIFICATIONS FOR DIFFERENCES BETWEEN FLOOR AND WALL

PENETRATIONS.

3. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

FIRE SEALANT

NOTE 2

NOTE 3

NOTE 4

NOTE 4

PIPE

NOTE 2

NOTE 3

FIRE RATED WALL

(CONSTRUCTION VARIES)

FIRE RATED FLOOR

(CONSTRUCTION VARIES)

NOTES:

1. THIS DETAIL APPLIES TO ALL ITEMS PENETRATING FIRE RATED WALLS OR FLOORS. THE INTENT IS TO MAINTAIN THE FIRE RATING AND TO ALLOW LONGITUDINAL MOVEMENT. REFER TO SPECIFICATIONS FOR SELECTION OF THROUGH PENETRATION FIRE

STOPPING.

2. SCHEDULE 5 PIPE SLEEVE EMBEDDED IN WALL OR FLOOR, OR SMOOTH CORE DRILL. EACH CONTRACTOR FURNISHES SLEEVE TO G.C., COORDINATES SLEEVE LOCATIONS AND DEBURS SLEEVE. G.C. BUILDS SLEEVE INTO WALL OR FLOOR ALLOWING NO GAP AROUND SLEEVE. IF SLEEVE IS NOT PROVIDED WHEN WALL OR FLOOR IS BUILT, CONTRACTOR SHALL INSTALL SLEEVE. SLEEVE

SIZE SHALL ALLOW ANNULAR SPACE REQUIRED BY THE SELECTED FIRE STOP SYSTEM.

3. INSTALL BACKING MATERIAL, SUCH AS MINERAL WOOL SAFING, AS REQUIRED FOR FIRE STOP SYSTEM. INSTALL IN ACCORDANCE WITH FIRE STOP SYSTEM APPLICATION LISTING. SECURE TO WALL OR FLOOR TO ALLOW LONGITUDINAL MOVEMENT OF

PENETRATING ITEM WITHOUT MOVEMENT OF FIRE BARRIER.

4. WATER-TIGHT WELDED 1"x1" 20 GAUGE MINIMUM GALVANIZED SHEET METAL ANGLE FRAME, BY CONTRACTOR IN EQUIPMENT ROOMS FOR WATER STOP. PLACE A BEAD OF WATERPROOF SEALANT BETWEEN FLOOR AND BOTTOM OF ANGLE FRAME. SECURE TO FLOOR WITH MASONRY ANCHORS IN CORNERS AND ON 12" MAXIMUM CENTERS. MULTIPLE PENETRATING ITEMS MAY BE

ENCLOSED IN ONE FRAME.

NON-FIRE RATED WALL(OR FLOOR)

(CONSTRUCTION VARIES)

NOTE 2

P

IP

E

FINISHED

FLOOR

INSULATION

METAL JACKET

WATERPROOF

SEALANT

BACKUP

MATERIAL

PIPE WITH

INSULATION

PIPE SLEEVE

ESCUTCHEON AT

EXPOSED AREAS

ONLY

PIPE WITHOUT

INSULATION

(±)1/8"

LUG, COUPLING,

OR HUB

RISER CLAMP

INSULATION AND

NEOPRENE MOUNTS

INSULATION

SEAL OPENING,

FIRESTOP IF

REQUIRED.

FLOOR

P

IP

E

PIPE SLEEVE

BACKUP MATERIAL

WATERPROOF

SEALANT (NOTE 1)

PIPE INSULATION

ESCUTCHEON (TYP)

INTERIOR SIDE OF

EXTERIOR WALL

INSULATED PIPE

SLEEVE THRU WALL

ABOVE GRADE

BARE PIPE SLEEVE

THRU WALL ABOVE

GRADE

WATERPROOF

SEALANT

(NOTE 1)

INTERIOR SIDE OF

EXTERIOR WALL

NOTES:

1. SEALANT-JOINT 1/4" WIDE MIN. BY 3/8" DEEP MIN.

NOTES:

1. CONTRACTOR SHALL COORDINATE EXHAUST

SILENCER HEIGHT WITH ANY ELECTRICAL CONDUIT.

STAINLESS STEEL JACKETED

EXHAUST PIPE (ASTM A53 SCH.10)

WITH 4" THICK CALCIUM SILICATE

INSULATION. PIPE SHALL BE SIZED

BY MUFFLER SELECTION.

ROOF

UNISTRUT SUPPORTS

SECURED TO Z-PURLIN

ENGINE EXHAUST SILENCER WITH

STAINLESS STEEL JACKETED 4" THICK

CALCIUM SILICATE INSULATION

MOUNTING BRACKET - SADDLE TYPE

WITH GALV. METAL PROTECTIVE SHIELD

FLANGED SPOOL WITH GASKET.

LENGTH AS REQUIRED

STAINLESS STEEL FLEXIBLE CONNECTOR

WITH GASKETS AT EACH FLANGE

Y-HEADER (IF REQUIRED)

ENGINE OUTLINE

EXHAUST FLANGE (ASTM

A53 SCH.10) OUTLET WITH

GASKET

STEEL (ASTM A53 SCH.10)

FLOATING FLANGE WITH GASKET

PROVIDE GENERATOR EXHAUST

PIPE SUPPORT

BUILDING

ALL-THREAD

HANGER RODS

WALL THIMBLE

OPTIONAL MOUNTING BRACKET -

BACK TO BACK STEEL CHANNEL

WITH WELDED STITCH PLATE

TRAPEZE TYPE

LONG SWEEP ELBOW

G ra p h ic S ca le

/1 6"

0"

G ra p h ic S ca le

/1 6"

0"

G ra p h ic S ca le

/8

0"

G ra p h ic S ca le

/3 2"

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

G ra p h ic S ca le

/2

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

NOT FOR

PERMITTING OR

CONSTRUCTION

A/E:Consultant:

Approved: Spinklered

Office of Construction and Facilities Management FULLY SPRINKLERED

B

IM

/V

IS

N

O m a h a

E H

R M

/O m a h a

E H

R M

V

.r v t

/2

/2

:3

:5

P

M

AW RAWMAY 15, 2023

M-102

636 - OMAHA VA MEDICAL CENTER

ISSUE FOR BIDMECHANICAL DETAILS 636-21-704OMAHA EHRM INFRASTRUCTURE

UPGRADE DESIGN

NTS

PIPE SUPPORTS DETAIL

NTS

PIPE SUPPORT ON ROOF

NTS

TYPICAL CONDENSATE TRAP DETAIL

NTS

PIPE PENETRATIONS DETAIL

Revisions: Date:

1/4" = 1'-0"

EXHAUST SILENCER SUPPORT

G ra p h ic S ca le

/1 6"

0"

G ra p h ic S ca le

/1 6"

0"

G ra p h ic S ca le

/8

0"

G ra p h ic S ca le

/3 2"

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

G ra p h ic S ca le

/2

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

NOT FOR

PERMITTING OR

CONSTRUCTION

A/E:Consultant:

Approved: Spinklered

Office of Construction and Facilities Management FULLY SPRINKLERED

B

IM

/V

IS

N

O m a h a

E H

R M

/O m a h a

E H

R M

V

.r v t

/2

/2

:3

:5

P

M

AW RAWMAY 15, 2023

M-103

636 - OMAHA VA MEDICAL CENTER

ISSUE FOR BIDMECHANICAL SCHEDULES 636-21-704OMAHA EHRM INFRASTRUCTURE

UPGRADE DESIGN

4. ELECTRICAL CONTRACTOR TO PROVIDE DISCONNECT SWTICH.

3. PROVIDE MICROPROCESSOR CONTROL, THERMOSTAT, BACNET INTERFACE, LOW AMBIENT WIND BAFFLE KIT, INTEGRAL CONDENSATE PUMP, SECONDARY DRAIN PAN WITH WATER LEAK SENSOR. CONDENSER PAD. INSTALL PER MANUFACTURER GUIDELINES.

2. LOCATIONS OF CONDENSING UNITS ARE SCHEMATIC IN NATURE. CONTRACTOR SHALL COORDINATE FINAL PLACEMENT OF CONDENSING UNITS WITH VA.

1. BASED ON LG LAU1480HYV3 OUTDOOR UNIT AND LG LAN180HYV3 INDOOR UNIT.

NOTES:

9-ASHP-1 9 B12A WALL MT. SPLIT 813 0.2 18 24 80 67 [ 95 ] [ 22 ] 70 90 [ -4 ] - TSTAT - DDC 14.81 DIRECT 19 1 208/230 R410A 164 SEE NOTES 1,2,3,4

CFM IN MBH °F °F °F MBH °F °F °F AMPS CONTROL AMPS CONTROL

Db Wb

TOTAL

CAPACITY MIN SEER

EAT OSA DESIGN

TEMP

MIN. HEAT

CAPACITY

EAT

Db

LAT

Db

OSA DESIGN

TEMP

INDOOR FAN OUTDOOR UNIT FAN

MCA PHASE VOLT

MARK BLDG ROOM TYPE

TOTAL SUPPLY

AIR FLOW

EXT STATIC

PRESSURE

CAPACITY HEATING CAPACITY ELECTRICAL DATA

REFRIG.

PIPE LENGTH

MAX. FT

REMARKS

SPLIT SYSTEM AIR CONDITIONER / EVAPORATOR SCHEDULE

1. SEE DETAIL FOR DAMPER IN BRANCH DUCT SERVING EACH DIFFUSER.

NOTES:

SD-53 150 350 0.1 DUCT MOUNTED 12x12 10x10 19 OBD WHITE SEE NOTE 1

SD-13 110 380 0.09 CEILING 24x24 10Ø 22 OBD WHITE SEE NOTE 1

SD-12 70 280 0.1 CEILING 24x24 8Ø 23 OBD WHITE SEE NOTE 1

CFM CFM IN WG IN X IN IN DB

MIN MAXMARK

AIRFLOW

MAX APD

MOUNTING

PANEL/FRAME SIZE NECK SIZE NOISE CRITERIA

DAMPER FINISH REMARKS

AIR DEVICE SCHEDULE (SUPPLY)

2. OMIT FIRE PROTECTION DUE TO SPACE LIMITATIONS AND/OR LACK OF EXISTING SPRINKLER SYSTEM. SPACE TO HAVE FIRE-SMOKE ALARM SYSTEM.

VARIANCES: 1. IT RACK COOLING LOAD PER 35% COMMENTS BY OMAHA VA AND MEETING WITH VA-OIT FEB-24-2022.

* 35% VA COMMENTS: Cooling per TR/number of racks will be as follows. We need 5kW per rack, however in aggregate we don't need 5kW for each of four racks. Update standard and TR design checklist with new language, applicable for both new construction and renovations.

1 rack TR = 5kW (e.g. single 5kW cooling unit).

2 rack TR = 7kW (e.g. 3.5kW x2 cooling units).

3 rack TR = 8.5 kW (e.g. 3.5kW + 2.5kW x2 cooling units).

4 rack TR =10kW (e.g. 2.5kW x4 or 5kW x2 cooling units).

Other designs meeting these maximum expected aggregated load levels are acceptable. Multiple smaller units will assist in avoiding equipment freeze-up in some types of equipment.

** Meeting with VA-OIT Feb-24-2022: MCR to use existing equipment with 80kw load.

ACC 2433 3 TR >96 - EXISTING DX EXISTING N 1 WS Remain as it. DDC upgrades for monitoring only.

ACC 2011 4 TR >96 - EXISTING DX EXISTING N 1 WS Remain as it. DDC upgrades for monitoring only.

ACC 1433 3 TR >96 - EXISTING DX EXISTING N 1 WS Remain as it. DDC upgrades for monitoring only.

ACC 1011 3 TR >96 - EXISTING DX EXISTING N 1 WS Remain as it. DDC upgrades for monitoring only.

ACC G433 6 TR >96 - EXISTING DX EXISTING N 1 WS Remain as it. DDC upgrades for monitoring only.

ACC G011 3 TR >96 - EXISTING DX EXISTING N 1 WS Remain as it. DDC upgrades for monitoring only.

D OFFICES 109 Telecommunications Rm 1 TE <96 5 kw (17,060 btu/hr) NONE NONE N 1 NONE Design alert eliminate fire protection and cooling.

15 Research R200A Telecommunications Rm 1 TR >96 5 kw (17,060 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser

9 DIALYSIS B12A Telecommunications Rm 1 TR >96 5 kw (17,060 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser 8 OFFICES 104A Telecommunications Rm 1 TE <96 5 kw (17,060 btu/hr) NONE NONE N 1 NONE Design alert eliminate fire protection and cooling.

6 DENTAL 109 Telecommunications Rm 1 TR >96 5 kw (17,060 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser

2 BOILER PLANT 202 Telecommunications Rm 1 TE <96 5 kw (17,060 btu/hr) NONE NONE N 1 NONE Design alert eliminate fire protection and cooling.

1 14002 Telecommunications Rm 1 TR >96 5 kw (17,060 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser 1 12018 Telecommunications Rm 1 TR >96 5 kw (17,060 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser

1 11414 Telecommunications Rm 1 TR >96 5 kw (17,060 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser

1 10414 Telecommunications Rm 1 TR >96 5 kw (17,060 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser

1 9414 Telecommunications Rm 2 TR >96 7 kw (23,884 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser

1 8414 Telecommunications Rm 2 TR >96 7 kw (23,884 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser 1 7414 Telecommunications Rm 2 TR >96 7 kw (23,884 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser

1 6414 Telecommunications Rm 2 TR >96 7 kw (23,884 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser

1 5414 Telecommunications Rm 2 TR >96 7 kw (23,884 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser

1 4374A Telecommunications Rm 2 TR >96 7 kw (23,884 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser 1 3254B Telecommunications Rm 2 TR >96 7 kw (23,884 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser

1 2448 Telecommunications Rm 1 TR >96 5 kw (17,060 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser

1 2255A Telecommunications Rm 2 TR >96 7 kw (23,884 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser

1 1656 Telecommunications Rm 2 TR >96 7 kw (23,884 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser

1 1616 Telecommunications Rm 1 TR >96 5 kw (17,060 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser 1 1510 Telecommunications Rm 1 TR >96 5 kw (17,060 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser

1 1205B Telecommunications Rm 3 TR >96 8.5 kw (29,002 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser

1 B721 Telecommunications Rm 34 TR >96 80 kw (272,960 btuh) EXISTING DX NONE N + 1 3 WS Existing CRAC units to remain. Qty (2) 105 kw cooling capacity.

1 B611 Telecommunications Rm 1 TR >96 5 kw (17,060 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser 1 B818A Telecommunications Rm 2 TR >96 7 kw (23,884 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser

1 B024C Telecommunications Rm 3 TR >96 8.5 kw (29,002 btu/hr) DX NONE N 3 WS Dedicated CRAC with air cooled condenser

NUM. NUM. NUM. QTY TE / TR <96 OR >96

PER VA COMMENTS

OIT/OMAHA VARIANCE

DX / CW / VAV

DX-Vertiv-Encl

DRY FOG /

NONE

N 1 / 2 / 3 / 4 CA (clean agent) WS (wet system)

CA-Vertiv-Encl / NONE

BLDG ROOM ROOM NAME IT RACKS ROOM TYPE

QTY WORK

AREA

OUTLETS

HEAT LOAD

BASIS OF DESIGN

HVAC SYSTEM

TYPE

HUMIDIFIER

CRITICAL

REDUNDANCY

LEVEL

ANSI/TIA-9

43-B

RATING

FIRE SUPPRESSION

SYSTEM TYPE

NOTES

OIT TR ROOM DESIGN INPUT COORDINATION SCHEDULE: *INCLUDES CHANGES FROM VARIANCES, DESIGN ALERTS, MEETINGS, AND

COMMENTS

5. INTERLOCK DAMPER OPERATION WITH EXHAUST FAN.

4. INTERLOCK DAMPER OPERATION WITH GENERATOR.

3. CONTROLS PROVIDED BY CONTROLS CONTRACTOR.

2. PROVIDE LOUVER WITH INSULATED LOW LEAKAGE DAMPER. SPRING OPEN WITH ACTUATOR POWERED CLOSED. PROVIDE 1/4" MESH BUG SCREEEN.

1. LOUVER SHALL BE BLAST AND MISSILE RATED. REFER TO SPECIFICATIONS FOR DETAILS.

NOTES:

G-IAL-3 G-ME101 GENERATOR INTAKE POTTORFF / EFD-637 114 x 104 19,000 400 0.02 SEE NOTES 1-5.

G-IAL-2 G-ME101 GENERATOR INTAKE POTTORFF / EFD-637 114 x 104 19,000 400 0.02 SEE NOTES 1-5.

G-IAL-1 G-ME101 GENERATOR INTAKE POTTORFF / EFD-637 114 x 86 19,000 459 0.02 SEE NOTES 1-5.

G-EAL-3 G-ME101 GENERATOR EXHAUST POTTORFF / EDD-637 40 x 36 3,450 655 0.05 SEE NOTES 1-5.

G-EAL-2 G-ME101 GENERATOR EXHAUST POTTORFF / EFD-637 114 x 86 28,500 689 0.02 SEE NOTES 1-5.

G-EAL-1 G-ME101 GENERATOR EXHAUST POTTORFF / EFD-637 114 x 86 28,500 689 0.02

KYNAR FINISH. REFER TO

ARCHITECTURAL

PLANS FOR COLOR.

SEE NOTES 1-5.

IN CFM F/m IN WG

MARK LOCATION SYSTEM AND/OR SERVICE MANUFACTURER / MODEL

SIZE (W x H) AIRFLOW

FREE AREA

VELOCITY

SP IN WC

FINISH REMARKS

LOUVER SCHEDULE

4. PROVIDE UNIT WITH FACTORY SUPPLIED CONDENSATE PUMP AS REQUIRED. PUMP TO BE INSTALLED IN FIELD PER MANUFACTURER'S RECOMMENDATIONS.

3. PROVIDE UNIT WITH FACTORY MOUNTED FUSED INTEGRAL DISCONNECT SWITCH.

2. RE-HEAT COIL SHALL BE WIRED AND CONTROLLED TO LOCK-OUT, TURN OFF, DURING EMERGENCY GENERATOR OPERATION.

1. PROVIDE MICROPROCESSOR CONTROL, PROGRAMMABLE THERMOSTAT, BACNET INTERFACE, DISCONNECT SWITCH, CONDENSATE PUMP, AIR FILTER BOX, WIRE MESH RETURN GRILLE, SUPPLY FLANGE, SECONDARY DRAIN PAN WITH WATER LEAK SENSOR. INSTALL PER MANUFACTURER GUIDELINES. INSULATE SUPPLY DUCTS AND TRANSITIONS WITH 2" WRAP.

NOTES:

15-CRAC-1 15 R200A DX CRAC INDOOR UNIT 750 0.3 18.5 16.5 75.0 61 12.2 208 1 Ø 60 20.2 25.3 30 54 x 30 x 20 225 LIEBERT MINI-MATE2 / MMD18E NOTES: 1-4

06-CRAC-1 06 109 DX CRAC INDOOR UNIT 750 0.3 18.5 16.5 75.0 61 12.2 208 1 Ø 60 20.2 25.3 30 54 x 30 x 20 225 LIEBERT MINI-MATE2 / MMD18E NOTES: 1-4

01-CRAC-20 01 12018 DX CRAC INDOOR UNIT 750 0.3 18.5 16.5 75.0 61 12.2 277 1 Ø 60 17.7 22.1 25 54 x 30 x 20 225 LIEBERT MINI-MATE2 / MMD18E NOTES: 1-4

01-CRAC-19 01 14002 DX CRAC INDOOR UNIT 750 0.3 18.5 16.5 75.0 61 12.2 277 1 Ø 60 17.7 22.1 25 54 x 30 x 20 225 LIEBERT MINI-MATE2 / MMD18E NOTES: 1-4

01-CRAC-18 01 11414 DX CRAC INDOOR UNIT 750 0.3 18.5 16.5 75.0 61 12.2 277 1 Ø 60 17.7 22.1 25 54 x 30 x 20 225 LIEBERT MINI-MATE2 / MMD18E NOTES: 1-4

01-CRAC-17 01 10414 DX CRAC INDOOR UNIT 750 0.3 18.5 16.5 75.0 61 12.2 277 1 Ø 60 17.7 22.1 25 54 x 30 x 20 225 LIEBERT MINI-MATE2 / MMD18E NOTES: 1-4

01-CRAC-16 01 9414 DX CRAC INDOOR UNIT 885 0.3 21.8 19.5 75.0 61 16 277 1 Ø 60 24.0 30 35 57-13/16 x 31 x 24 225 LIEBERT MINI-MATE2 / MMD24E NOTES: 1-4

01-CRAC-15 01 8414 DX CRAC INDOOR UNIT 885 0.3 21.8 19.5 75.0 61 16 277 1 Ø 60 24.0 30 35 57-13/16 x 31 x 24 225 LIEBERT MINI-MATE2 / MMD24E NOTES: 1-4

01-CRAC-14 01 7414 DX CRAC INDOOR UNIT 885 0.3 21.8 19.5 75.0 61 16 277 1 Ø 60 24.0 30 35 57-13/16 x 31 x 24 225 LIEBERT MINI-MATE2 / MMD24E NOTES: 1-4

01-CRAC-13 01 6414 DX CRAC INDOOR UNIT 885 0.3 21.8 19.5 75.0 61 16 277 1 Ø 60 24.0 30 35 57-13/16 x 31 x 24 225 LIEBERT MINI-MATE2 / MMD24E NOTES: 1-4

01-CRAC-12 01 5414 DX CRAC INDOOR UNIT 885 0.3 21.8 19.5 75.0 61 16 277 1 Ø 60 24.0 30 35 57-13/16 x 31 x 24 225 LIEBERT MINI-MATE2 / MMD24E NOTES: 1-4

01-CRAC-11 01 4374A DX CRAC INDOOR UNIT 885 0.3 21.8 19.5 75.0 61 16 277 1 Ø 60 24.0 30 35 57-13/16 x 31 x 24 225 LIEBERT MINI-MATE2 / MMD24E NOTES: 1-4

01-CRAC-10 01 3254B DX CRAC INDOOR UNIT 885 0.3 21.8 19.5 75.0 61 16 277 1 Ø 60 24.0 30 35 57-13/16 x 31 x 24 225 LIEBERT MINI-MATE2 / MMD24E NOTES: 1-4

01-CRAC-9 01 2255A DX CRAC INDOOR UNIT 885 0.3 21.8 19.5 75.0 61 16 277 1 Ø 60 24.0 30 35 57-13/16 x 31 x 24 225 LIEBERT MINI-MATE2 / MMD24E NOTES: 1-4

01-CRAC-8 01 2448 DX CRAC INDOOR UNIT 750 0.3 18.5 16.5 75.0 61 12.2 277 1 Ø 60 17.7 22.1 25 54 x 30 x 20 225 LIEBERT MINI-MATE2 / MMD18E NOTES: 1-4

01-CRAC-7 01 1656 DX CRAC INDOOR UNIT 885 0.3 21.8 19.5 75.0 61 16 277 1 Ø 60 24.0 30 35 57-13/16 x 31 x 24 225 LIEBERT MINI-MATE2 / MMD24E NOTES: 1-4

01-CRAC-6 01 1616 DX CRAC INDOOR UNIT 750 0.3 18.5 16.5 75.0 61 12.2 277 1 Ø 60 17.7 22.1 25 54 x 30 x 20 225 LIEBERT MINI-MATE2 / MMD18E NOTES: 1-4

01-CRAC-5 01 1205B DX CRAC INDOOR UNIT 1,350 0.2 32.4 28.0 75.0 61 25.2 460 3 Ø 60 11.5 14.4 15 57-13/16 x 31 x 24 328 LIEBERT MINI-MATE2 / MT036 NOTES: 1-4

01-CRAC-4 01 1510 DX CRAC INDOOR UNIT 750 0.3 18.5 16.5 75.0 61 12.2 277 1 Ø 60 17.7 22.1 25 54 x 30 x 20 225 LIEBERT MINI-MATE2 / MMD18E NOTES: 1-4

01-CRAC-3 01 B024C DX CRAC INDOOR UNIT 1,350 0.2 32.4 28.0 75.0 61 25.2 460 3 Ø 60 11.5 14.4 15 57-13/16 x 31 x 24 328 LIEBERT MINI-MATE2 / MT036 NOTES: 1-4

01-CRAC-2 01 B611 DX CRAC INDOOR UNIT 750 0.3 18.5 16.5 75.0 61 12.2 277 1 Ø 60 17.7 22.1 25 54 x 30 x 20 225 LIEBERT MINI-MATE2 / MMD18E NOTES: 1-4

01-CRAC-1 01 B818A DX CRAC INDOOR UNIT 885 0.3 21.8 19.5 75.0 61 16 277 1 Ø 60 24.0 30 35 57-13/16 x 31 x 24 225 LIEBERT MINI-MATE2 / MMD24E NOTES: 1-4

CFM IN MBH MBH °F °F MBH IN x IN x IN LBS

Db Wb

MIN. TOTAL

CAP.

MIN. SENS

CAP.

EAT ELEC. REHEAT

CAP. VOLTS PHASE HZ FLA WSA OPD

FAN COIL

DIMENSIONS WEIGHT

MANUF. / MODEL

MARK BLDG ROOM TYPE

SUPPLY

AIR FLOW

EXT.

STATIC

PRESS.

COOLING CAPACITY ELECTRICAL DATA BASIS OF DESIGN

REMARKS

FAN COIL UNIT

AIR COOLED DX CRAC INDOOR UNIT SCHEDULE

3. LOCATION OF CONDENSING UNITS ARE SCHEMATIC IN NATURE. CONTRACTOR SHALL COORDINATE FINAL PLACEMENT OF CONDENSING UNITS WITH VA.

2. ALL ENCLOSURES REQUIRE TWO POWER CONNECTIONS. ONE FOR FAN COIL UNIT AND ONE FOR CONDENSER UNIT.

1. ELECTRICAL CONTRACTOR TO PROVIDE DISCONNECT SWITCH.

NOTES:

15-CRAC-1A 15 LEVEL 2 ROOF DX CRAC CONDENSER UNIT 208 1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH020 NOTES: 1, 2, 3

06-CRAC-1A 06 LEVEL 1 GRADE DX CRAC CONDENSER UNIT 208 1 Ø 60 40 x 18 x 23-1/2 244 LIEBERT MINI-MATE2 / PFH020 NOTES: 1, 2, 3

01-CRAC-20A 01 LEVEL 12 ROOF DX CRAC CONDENSER UNIT 277 '1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH020 NOTES: 1, 2, 3

01-CRAC-19A 01 LEVEL 13 SIDEWALL DX CRAC CONDENSER UNIT 277 '1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH020 NOTES: 1, 2, 3

01-CRAC-18A 01 LEVEL 12 ROOF DX CRAC CONDENSER UNIT 277 '1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH020 NOTES: 1, 2, 3

01-CRAC-17A 01 LEVEL 12 ROOF DX CRAC CONDENSER UNIT 277 '1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH020 NOTES: 1, 2, 3

01-CRAC-16A 01 LEVEL 12 ROOF DX CRAC CONDENSER UNIT 277 '1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH027 NOTES: 1, 2, 3

01-CRAC-15A 01 LEVEL 5 ROOF DX CRAC CONDENSER UNIT 277 '1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH027 NOTES: 1, 2, 3

01-CRAC-14A 01 LEVEL 5 ROOF DX CRAC CONDENSER UNIT 277 '1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH027 NOTES: 1, 2, 3

01-CRAC-13A 01 LEVEL 5 ROOF DX CRAC CONDENSER UNIT 277 '1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH027 NOTES: 1, 2, 3

01-CRAC-12A 01 LEVEL 5 ROOF DX CRAC CONDENSER UNIT 277 '1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH027 NOTES: 1, 2, 3

01-CRAC-11A 01 LEVEL 5 ROOF DX CRAC CONDENSER UNIT 277 '1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH027 NOTES: 1, 2, 3

01-CRAC-10A 01 LEVEL 5 ROOF DX CRAC CONDENSER UNIT 277 '1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH027 NOTES: 1, 2, 3

01-CRAC-9A 01 LEVEL 2 ROOF DX CRAC CONDENSER UNIT 277 '1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH027 NOTES: 1, 2, 3

01-CRAC-8A 01 LEVEL 3 ROOF DX CRAC CONDENSER UNIT 277 '1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH020 NOTES: 1, 2, 3

01-CRAC-7A 01 LEVEL 2 ROOF DX CRAC CONDENSER UNIT 277 '1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH027 NOTES: 1, 2, 3

01-CRAC-6A 01 LEVEL 2 ROOF DX CRAC CONDENSER UNIT 277 '1 Ø 60 40 x 18 x 23-1/2 244 LIEBERT MINI-MATE2 / PFH020 NOTES: 1, 2, 3

01-CRAC-5A 01 LEVEL 2 ROOF DX CRAC CONDENSER UNIT 460 '3 Ø 60 48-1/4 x 18-5/8 x 30-3/4 244 LIEBERT MINI-MATE2 / PFD037 NOTES: 1, 2, 3

01-CRAC-4A 01 LEVEL 2 ROOF DX CRAC CONDENSER UNIT 277 '1 Ø 60 40 x 18 x 23-1/2 244 LIEBERT MINI-MATE2 / PFH020 NOTES: 1, 2, 3

01-CRAC-3A 01 LEVEL 1 GRADE DX CRAC CONDENSER UNIT 460 '3 Ø 60 48-1/4 x 18-5/8 x 30-3/5 244 LIEBERT MINI-MATE2 / PFD037 NOTES: 1, 2, 3

01-CRAC-2A 01 LEVEL 2 ROOF DX CRAC CONDENSER UNIT 277 1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH020 NOTES: 1, 2, 3

01-CRAC-1A 01 LEVEL 2 ROOF DX CRAC CONDENSER UNIT 277 1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH027 NOTES: 1, 2, 3

IN LBS

VOLT PHASE HZ

CONDENSER UNIT

DIMENSIONS

WEIGHT

MANF / MODEL

MARK BLDG LOCATION TYPE

ELECTRICAL DATA BASIS OF DESIGN

REMARKS

OUTDOOR CONDENSING UNIT

AIR COOLED DX CRAC OUTDOOR UNIT SCHEDULE

NOTES:

RR-55 320 850 0.082 SIDEWALL 20x18 18x16 19 NONE WHITE -

RG-26 420 700 0.087 CEILING 24x24 16Ø 16 NONE WHITE -

RG-22 110 170 0.1 CEILING 12x12 8Ø 13 NONE WHITE -

CFM CFM IN WG IN X IN IN DB

MIN MAXMARK

AIRFLOW

MAX APD

MOUNTING

PANEL/FRAME SIZE NECK SIZE NOISE CRITERIA

DAMPER FINISH REMARKS

AIR DEVICE SCHEDULE (RETURN)

2. TIE UNIT HEATER INTO BUILDING CONTROL SYSTEMS. UNIT HEATER SHALL RUN WHENEVER TEMPERATURE IS BELOW 55°F (ADJ).

1. ELECTRIC EXPLOSION PROOF UNIT HEATER.

NOTES:

G-UH-5 WATER ROOM ELECTRIC BERKO / RUX300812 700 10,236 38.4 1 208 3 SEE NOTE 1

G-UH-4 SUBSTATION ELECTRIC BERKO / RUX750812 840 25,590 38.4 1 208 7.5 SEE NOTE 1

G-UH-3 ELECTRIC ROOM ELECTRIC BERKO / RUX500812 700 17,060 26.3 1 208 5 SEE NOTE 1

G-UH-2 GENERATOR ROOM ELECTRIC BERKO / RUX750812 840 25,590 38.4 1 208 7.5 SEE NOTE 1

G-UH-1 GENERATOR ROOM ELECTRIC BERKO / RUX750812 840 25,590 38.4 1 208 7.5 SEE NOTE 1

CFM BTUH AMP PHASE VOLT KW

MARK LOCATION TYPE MANU / MODEL

AIRFLOW MIN CAPACITY POWER ELECTRIC HEATING WATTS

REMARKS

ELECTRIC UNIT HEATER SCHEDULE

Revisions: Date:

4. A VAULTED CONCRETE ENCLOSURE SHALL ENCASE AND PROTECT BOTH THE PRIMARY STEEL TANK AND THE SECONDARY CONTAINMENT. THE CONCRETE ENCASEMENT SHALL BE 6” THICK WITH A MINIMUM DESIGN STRENGTH OF 4000 PSI.

3. THE TANK SYSTEM SHALL INCLUDE SECONDARY CONTAINMENT CONSISTING OF AN IMPERVIOUS BARRIER OF 30 MIL (0.76 MM) HIGH-DENSITY POLYETHYLENE GEOMEMBRANE ENCLOSING THE PRIMARY STEEL TANK AND INSULATION MATERIAL TO CONTAIN LEAKS FROM THE PRIMARY TANK AND ISOLATING THE PRIMARY TANK FROM THE CONCRETE TO PROTECT AGAINST CORROSION.

2. THE PRIMARY STEEL TANK SHALL BE PRESSURE TESTED AT 5 PSIG FOR A MINIMUM OF 24 HOURS. ALL OPENINGS SHALL BE FROM THE

TOP ONLY.

1. THE PRIMARY TANK SHALL BE RECTANGULAR IN SHAPE AND LISTED PER UL STANDARD 142. STEEL TANK THICKNESS SHALL BE 3/16” THICK (7 GAUGE). WELDS SHALL BE CONTINUOUS ON ALL SIDES AND EXTERIOR SEAMS, CONFORMING TO THE AMERICAN WELDING

SOCIETY STANDARD FOR CONTINUOUS WELD.

NOTES:

DFT-1 6,000 DIESEL FUEL CONVAULT 17' 7" x 8' 0" x 8' 3-1/4" SEE NOTES 1-4

FT / IN

MARK SIZE (GALLONS)

SYSTEM AND/OR

SERVICE

MANUFACTURER

SIZE (L x W x H)

REMARKS

DIESEL FUEL TANK SCHEDULE

1. EXPLOSION PROOF FAN WITH MOTORIZED DAMPER.

NOTES:

G-EF-3 SUBSTATION GENERATOR BUILDING EXHAUST GREENHECK SDPHE-16-3-A4 1,700 0.31 SIDEWALL DIRECT DRIVE HAZARDOUS FAN DIRECT 1,750 1/4 1 120 1,750 SEE NOTE 1.

G-EF-2 ELEC ROOM GENERATOR BUILDING EXHAUST GREENHECK SDPHE-12-3-A4 1,050 0.28 SIDEWALL DIRECT DRIVE HAZARDOUS FAN DIRECT 1,750 1/4 1 120 1,750 SEE NOTE 1.

G-EF-1 GENERATOR ROOM GENERATOR BUILDING EXHAUST GREENHECK SDPHE-24-3-A5 3,450 0.28 SIDEWALL DIRECT DRIVE HAZARDOUS FAN DIRECT 1,750 1/2 1 120 1,750 SEE NOTE 1.

G-SF-3 SUBSTATION GENERATOR BUILDING OUTDOOR AIR GREENHECK AER-24-03-0315 1,700 0.31 SIDEWALL DIRECT DRIVE HAZARDOUS FAN DIRECT 1,750 1/4 1 120 1,750 SEE NOTE 1.

G-SF-2 ELEC ROOM GENERATOR BUILDING OUTDOOR AIR GREENHECK AER-24-03-0315 1,050 0.28 SIDEWALL DIRECT DRIVE HAZARDOUS FAN DIRECT 1,750 1/4 1 120 1,750 SEE NOTE 1.

G-SF-1 GENERATOR ROOM GENERATOR BUILDING OUTDOOR AIR GREENHECK AER-24-03-0315 3,450 0.28 SIDEWALL DIRECT DRIVE HAZARDOUS FAN DIRECT 1,750 1/2 1 120 1,750 SEE NOTE 1.

01-EF-1 ROOF B830 EXHAUST GREENHECK GB-220 6000 0.5 DOWNBLAST ROOFTOP FAN BELT 882 1-1/2 3 430 882 -

CFM IN.

TYPE DRIVE

FAN MAX

RPM

PHASE VOLT RPM

MARK LOCATION AREA AND/OR BLDG SERVED

SYSTEM AND/OR

SERVICE

MANUFACTURER MODEL

AIR FLOW TSP

FAN

REMARKS

FAN SCHEDULE

1. SPUN ALUMINUM GRAVITY INTAKE VENTILATOR.

NOTES:

01-RH-2 ROOF B830 INTAKE GREENHECK GRSI-30 3,000 0.09 1

01-RH-1 ROOF B830 INTAKE GREENHECK GRSI-30 3,000 0.09 1

CFM IN.

MARK LOCATION

AREA AND/OR BLDG

SERVED

SYSTEM AND/OR

SERVICE

MANUFACTURER MODEL

AIR FLOW PRESSURE DROP

REMARKS

ROOF HOOD SCHEDULE

4. INSTALL AS ONE FULL PUMP SET ASSEMBLEY.

3. PROVIDE WITH MANUFACTURER'S PUMP STARTER CONTROL BOX.

2. PUMP AND MOTOR SHALL BE SUITABLE FOR OUTDOOR INSTALLATION.

1. PROVIDE WITH INTERNAL RELIEF VALVE.

NOTES:

FOP-2 GENERATOR BUILDING DIESEL FUEL MAINTENACE SYSTEM SINGLE #2D FUEL 1.86 40 3R 1/3 1,800 1 115 60 PRYCO PYPS2100 SEE NOTES 1-4

FOP-1 GENERATOR BUILDING OUTDOOR TANK DUPLEX #2D FUEL 1.86 40 3R 1/3 1,800 1 115 60 PRYCO PYPS2205 SEE NOTES 1-4

GPM PSI

PHASE VOLT HZ MANUFACTURER MODEL

MARK LOCATION SERVICE CONFIGURATION FLUID

FUEL FLOW

HEAD

PRESSURE NEMA RATING HP RPM

ELECTRICAL DATA BASIS OF DESIGN

REMARKS

FUEL OIL PUMP SCHEDULE

P3

P1P2

FP

MP

LEGEND

P1

FP

LD FL

BOBOP1 P2

FLLD LD

FUEL DISTRIBUTION SYSTEM CONTROL SEQUENCE

LD

LEGEND

P1

BO

FL

LD

BO

FP BO

FILL GAUGE VISUAL AND

AUDIBLE ALARM

FOS

DIESEL FUEL

MAINTENANCE

SYSTEM

OVERFILL

PREVENTATION

AND DROP TUBE

FILL CONNECTION

PRESSURE RELIEF VALVE, PIPE DISCHARGE

TO DROP INTO DIESEL OIL RETURN LNE.

DIESEL OIL

SUPPLY BACK

PRESSURE VALVE

FUEL RETURN PUMP

FOS

FOR

FUEL ISOLATION VALVES

LOCATED WITHIN BUILDING

F O

S

F O

R

FUEL TANK

6,000 GAL

MANUAL FUEL PUMP

(ROTARY HAND PUMP)F

O R

F O

S

DIESEL

GENERATOR

DFMS FUEL

PUMP

FUEL OIL TANK

MONITORING

SYSTEM

FUEL OIL PUMP

XXX SYSTEM DESCRIPTION

VALVE - SHUT-OFF, NORMALLY CLOSED

VALVE - SHUT-OFF, NORMALLY OPEN

DIRECTION OF FLOW

FOS FUEL OIL SUPPLY

FOR FUEL OIL RETURN

PRESSURE GAUGE

VALVE - CONTROL 2-WAY (2-POSITION)

FLOW METER

VALVE - CHECK

VALVE - PPRESSURE REDUCING VALVE (PRV)

FUEL SUPPLY PUMPS

FUEL SUPPLY PUMP

(BUILT INTO GENERATOR)

DAY TANK

1. DESCRIPTION OF THE FUEL SYSTEM:

A. THE FUEL DISTRIBUTION SYSTEM IS COMPRISED OF AN ABOVE GROUND FUEL STORAGE TANK WITH REDUNDANT FUEL OIL PUMPS. FUEL OIL PUMPS DISTRIBUTE FUEL TO THE GENERATOR DAY TANK. FUEL RETURN PUMP FOR THE DAY TANK SHALL RETURN FUEL BACK TO THE ABOVE GROUND TANK TO PREVENT OVERFLOW CONDITION. A FUEL MANAGEMENT SYSTEM WILL MONITOR THE FUEL LEVEL AND LEAK DETECTION

ALARMS FOR EACH TANK THROUGHOUT THE FUEL SYSTEM.

2. GENERAL SEQUENCE OF OPERATION:

A. FUEL WILL BE DISTRIBUTED FROM AN ABOVE GROUND STORAGE TANK TO THE DAY TANK. THE TANK SHALL BE EQUIPPED WITH A FULL, FILL, AND LOW LEVEL FLOAT SWITCH. THE LEAD FUEL OIL PUMP OPERATION WILL BE ALTERNATED AUTOMATICALLY.

1) FUEL OIL PUMPS CONTROLLED AS INDICATED BY MOTOR STARTER HOA SWITCH

i. HAND - FUEL PUMP IS ENABLED TO RUN.

ii. OFF - FUEL PUMP IS DISABLED AND WILL NOT BE ALLOWED TO RUN.

iii. AUTO - FUEL PUMP IS ENABLED AND DISABLED BASED ON FUEL LEVEL OF TANKS.

2) DAY TANK FILL VALVES ARE:

i. OPEN, OR

ii. CLOSED

3) DIESEL FUEL MAINTENANCE SYSTEM IS:

i. ENABLED, OR

ii. DISABLED

B. FUEL MANAGEMENT SYSTEM WILL MONITOR THE FUEL LEVEL AND LEAK DETECTION SENSOR OF DAY TANK. THE FUEL MANAGEMENT SYSTEM SHALL GENERATE AN AUDIBLE AND VISUAL ALARM IF LEAK DETECTION SENSOR IS ACTIVE, OR IF FUEL LEVEL IS ABOVE THE HIGH OR LOW LEVEL

SETTING.

3. SYSTEM FUNCTIONS:

A. THE LEAD FUEL OIL PUMP WILL BE ENABLED WHENEVER DAY TANK IS BELOW THE FILL LEVEL. THE STANDBY FUEL OIL PUMP WILL BE ENABLED IF DAY TANK IS BELOW THE LOW LEVEL. FUEL OIL PUMPS WILL REMAIN RUNNING UNTIL DAY TANK IS ABOVE THE FULL LEVEL.

B. DAY TANK FILL VALVES WILL BE OPEN WHEN THE RESPECTIVE FUEL TANK IS BELOW THE FILL LEVEL. FILL VALVES WILL BE CLOSED WHEN THE

RESPECTIVE FUEL TANK IS ABOVE THE FULL LEVEL.

C. FUEL RETURN PUMP WILL BE ENABLED WHEN THE DAY TANK IS FILLED ABOVE THE HIGH LEVEL. RETURN PUMP WILL BE DISABLED WHEN

FUEL LEVEL DROPS TO BELOW THE FULL LEVEL.

D. DIESEL FUEL MAINTENANCE SYSTEM SHALL OPERATE THROUGH INTERNAL CONTROL LOGIC TO CYCLE FUEL WITHIN THE MAIN STORAGE

TANK.

E. ALARMS:

1) HIGH LEVEL ALARM SHALL BE GENERATED IF DAY TANK FUEL LEVEL IS ABOVE THE HIGH LEVEL.

2) LOW LEVEL ALARM SHALL BE GENERATED IF DAY TANK FUEL LEVEL IS BELOW THE LOW LEVEL.

3) LEAK DETECTION ALARM SHALL BE GENERATED IF FUEL IS DETECTED WITHIN DAY TANK INTERSTITAL SPACE, INSIDE THE TRANSITION

SUMP, OR WITHIN THE FUEL MAINTENANCE SYSTEM.

4) EMERGENCY OVERFLOW ALARM SHALL BE GENERATED IF FUEL IS DETECTED WITHIN THE NORMAL VENT OF DAY TANK.

TRANSITION SUMP

LEAK

DETECTION

ALARM

FUEL OIL TANK

FUEL TANK

CONTENTS AND

LEAKAGE

MONITORING PANEL

FOS

LEAK

DETECTION

ALARM

DIESEL

GENERATOR

BACK-PRESSURE

VALVE

VENT

FOS

FOR

START/STOPSTART/STOP

INTERSTITIAL

ALARM

F O

R

F O

S

XXX SYSTEM DESCRIPTION

VALVE - CONTROL 2-WAY (MODULATING)

VALVE - SHUT-OFF, NORMALLY CLOSED

VALVE - SHUT-OFF, NORMALLY OPEN

DIRECTION OF FLOW

FOS FUEL OIL SUPPLY

FOR FUEL OIL RETURN

FUEL OIL PUMP

START/STOP

PUMP STARTER

FUEL LEVEL SENSOR

LEAK DETECTION SENSOR

FOR

DAY TANK

P3

START/

STOP

FOR FOS

START/STOP

TRANSITION SUMP

DISCRIMINATING LEAK SENSOR

TEST BOOT EACH END (TYP.)

DOUBLE WALL

FUEL PIPING

DIESEL SUPPLY

DS

G ra p h ic S ca le

/1 6"

0"

G ra p h ic S ca le

/1 6"

0"

G ra p h ic S ca le

/8

0"

G ra p h ic S ca le

/3 2"

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

G ra p h ic S ca le

/2

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

NOT FOR

PERMITTING OR

CONSTRUCTION

A/E:Consultant:

Approved: Spinklered

Office of Construction and Facilities Management FULLY SPRINKLERED

B

IM

/V

IS

N

O m a h a

E H

R M

/O m a h a

E H

R M

V

.r v t

/2

/2

:3

:5

P

M

AW MPMMAY 15, 2023

M-105

636 - OMAHA VA MEDICAL CENTER

ISSUE FOR BIDMECHANICAL CONTROLS AND FLOW

DIAGRAMS

636-21-704OMAHA EHRM INFRASTRUCTURE

UPGRADE DESIGN

Revisions: Date:

NTS

GENERATOR FUEL OIL FLOW DIAGRAM

NTS

GENERATOR FUEL OIL SYSTEM CONTROLS

NTS

TRANSITION SUMP DETAIL

FEC

FEC

FEC

KEYNOTES

SUBSTATION

750KVA 13.8KV:480V

600KW GENERATOR

(DIESEL FUEL)

GENERATOR - FUTURE

3 4 5

G-EAL-2

G-IAL-2

G-IAL-3

G-EAL-1

6 6

G-EF-1

G-SF-1

G-EF-2

G-SF-2

G-SF-3

G-EF-3

G-UH-2

G-UH-3

G-UH-4

G-IAL-1

G-UH-5

RR-55

850 CFM

(TYP 2)

G-UH-1

FD

G-EAL-3

DAY TANK

3/4" FOS DN

3/4" FOS UP

3/4" FOS

3/4" FOS DN

3/4" FOR UP

3/4" FOR

/4

F

O S

/4

F

O R

3/4" FOS

3/4" FOS

/4

F

O S

FOP-1

FOP-2

BI - FAN STATUS

BO - FAN START/STOP

EA

M

CT

G ra p h ic S ca le

/1 6"

0"

G ra p h ic S ca le

/1 6"

0"

G ra p h ic S ca le

/8

0"

G ra p h ic S ca le

/3 2"

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

G ra p h ic S ca le

/2

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

NOT FOR

PERMITTING OR

CONSTRUCTION

A/E:Consultant:

Approved: Spinklered

Office of Construction and Facilities Management FULLY SPRINKLERED

B

IM

/V

IS

N

O m a h a

E H

R M

/O m a h a

E H

R M

V

.r v t

/2

/2

:3

:5

P

M

AW RAWMAY 15, 2023

G-ME101

636 - OMAHA VA MEDICAL CENTER

ISSUE FOR BIDBLDG. G - LEVEL 01 MECHANICAL FLOOR PLAN

G

636-21-704OMAHA EHRM INFRASTRUCTURE

UPGRADE DESIGN

1/4" = 1'-0"

ENLARGED MECHANICAL PLAN - GENERATOR BUILDING

NO. DESCRIPTION

1 DOUBLE WALL ABOVE GRADE FUEL STORAGE TANK. 6,000 GALLONS MINIMUM PER

GENERATOR FOR 96 HOURS OF OPERATION. REFER TO SPECIFICATIONS FOR DETAILS.

INSTALL PER LOCAL CODES AND MANUFACTURER'S GUIDELINES.

2 GENERATOR COMBUSTION FLUE STACK THROUGH ROOF. SIZE PER MANUFACTURER'S

RECOMMENDATIONS. REFER TO DETAIL 4 ON SHEET M-102.

3 FUEL PUMP CONTROL PANEL.

4 FUEL LEAK DETECTION SYSTEM PANEL.

5 DDC POWER AND CONTROL PANELS.

6 INTERLOCK MOTORIZED DAMPER WITH GENERATOR AND EXHAUST FAN OPERATION.

7 ELECTRICAL EQUIPMENT SHOWN FOR REFERENCE.

8 FIBERGLASS TRANSITION SUMP WITH STEEL PLATE ACCESS COVER - BRAVO B-600 OR

APPROVED EQUAL

9 18x16 TRANSFER DUCT. PROVIDE WITH FIRE DAMPER AND MOTORIZED DAMPER.

10 BOTTOM OF LOUVER SHALL BE AT MINIMUM 18 INCHES ABOVE GRADE.

11 LOUVER TO BE MOUNTED ON GRADE TO ALLOW FOR REMOVAL OF GENERATOR.

12 DUCT TRANSITION FROM GENERATOR TO LOUVER.

13 NEW 200 GALLON DOUBLE WALL DAY TANK WITH OVERFILL PREVENTION VALVE AND

INTEGRAL RETURN FUEL PUMP WITH CONTROLS. DAY TANK INCLUDES 2 GPM BRONZE

GEAR PUMP WITH STAINLESS STEEL SHAFTS. (1/3 HP THERMALLY PROTECTED 120

VAC, 1 PH, 60 HZ MOTOR) MANUFACTURER: PRYCO. MODEL: PY200ULDW (OR

APPROVED EQUAL).

14 MOUNT AT 8' - 2" ABOVE FINISHED FLOOR.

15 DIESEL FUEL MAINTENANCE SYSTEM. PROVIDE WITH:

-STAND-ALONE CONTROL AND EMERGENCY STOP FOR FUEL MAINTENANCE SYSTEM.

CONTROLLER SHALL INCLUDE DRY CONTACTS TO MONITOR GENERAL ALARM AND

LEAK DETETCTION

-WATER SEPARATION UNIT WITH MANUAL DRAIN VALVE

-NEMA-4 ENCLOSURE

16 SILENCER TO BE PROVIDED WITH GENERATOR.

17 DUPLEX FUEL OIL PUMP

Revisions: Date:

NORTH

EXHAUST FAN AND SUPPLY FAN SEQUENCE OF OPERATIONS:

THE FANS SHALL BE INTERLOCKED TO RUN WHENEVER THE AREA'S TEMPERATURE IS ABOVE

85°F (ADJ.).

FANS:

THE FANS SHALL HAVE A USER DEFINABLE (ADJ.) MINIMUM RUNTIME.

THE FANS SHALL RUN AT ALL TIMES RUNS, UNLESS SHUTDOWN ON SAFETIES. THE FAN

SPEEDS SHALL BE INDEXED AS FOLLOWS:

• SPEED SHALL MODULATE TO MAINTAIN STATIC PRESSURE SETPOINT BY A USER

DEFINABLE AMOUNT (ADJ.) DETERMINED THROUGH TESTING AND BALANCING.

EXHAUST AIR STATIC PRESSURE CONTROL:

THE FAN SHALL OPERATE AT CONSTANT VOLUME TO MAINTAIN ROOM PRESSURIZATION, BY

BALANCING SET POINT FOR SYSTEMS WITHOUT ZONE PRESSURE MONITORS, AND/OR BY

SETPOINT OF ZONE PRESSURE MONITOR.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

• HIGH EXHAUST AIR STATIC PRESSURE: IF THE EXHAUST AIR STATIC PRESSURE IS 25%

(ADJ.) GREATER THAN SETPOINT.

• LOW EXHAUST AIR STATIC PRESSURE: IF THE EXHAUST AIR STATIC PRESSURE IS 25%

(ADJ.) LESS THAN SETPOINT.

• SUPPLY FAN VFD FAULT.

FAN STATUS:

THE CONTROLLER SHALL MONITOR THE FAN STATUS.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

• FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.

• FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.

• FAN RUNTIME EXCEEDED: FAN STATUS RUNTIME EXCEEDS A USER DEFINABLE

LIMIT (ADJ.).

HIGH STATIC PRESSURE x

LOW STATIC PRESSURE x

FAN IN HAND x

FAN FAILURE x

FAN START/STOP x x x

FAN VFD FAULT x x x

FAN VFD SPEED x x x

FAN STATUS x x x

AIRFLOW x x x

AI AO BI BO AV BV LOOP SCHED TREND ALARM

POINT NAME

HARDWARE POINTS SOFTWARE POINTS SHOW ON

GRAPHIC

POINTS MATRIX - EF - VFD

12" = 1'-0"

SEQUENCE - GENERATOR EXHAUST FANS

GENERATOR AND LOUVER SEQUENCE OF OPERATIONS:

THE GENERATOR AND MOTORIZED DAMPER CONTROLING LOUVERS SHALL BE INTERLOCKED

TO RUN WHENEVER THE GENERATOR IS IN OPERATION. COORDINATE WITH MOTORIZED

DAMPER MANUFACTURER FOR PROPER CONNECTIONS, AIRFLOW BALANCING, AND

CONTROLS INTEGRATION.

Sheets
M-102 - MECHANICAL DETAILS
M-103 - MECHANICAL SCHEDULES
M-105 - MECHANICAL CONTROLS AND FLOW DIAGRAMS
G-ME101 - BLDG. G - LEVEL 01 MECHANICAL FLOOR PLAN