The solicitation is for construction services to upgrade the EHRM infrastructure at the Omaha VAMC. Upgrades include mechanical, electrical, and plumbing work associated with replacing aging HVAC equipment, upgrading electrical switchgear and panels, replacing the diesel fuel system for emergency generators, and other facility improvements. The solicitation type is construction and the contracting agency is the Department of Veterans Affairs Technology Acquisition Center in Austin. The response due date is not provided but the document appears to be a duplicate of solicitation number 36C776230036.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROVIDE A SECTION OF HIGH
COMPRESSION STRENGTH INSULATION
AT EACH HANGER POINT. INSULATION
MAY BE HALF ROUND OR FULL ROUND
AND EXTEND 2" BEYOND GALV. SHIELD
EACH WAY.
GALVANIZED IRON
SHEET SHIELD
INSULATION
STEEL PIPE SADDLE,
TACK WELDED TO PIPE,
FILL SADDLE WITH
INSULATION.
OVERSIZE HANGER TO ALLOW
LONGITUDINAL PIPE EXPANSION
AND PIPE INSULATION TO PASS
THROUGH UNBROKEN. (TYP)
UNI-SIRUT OR EQUIVALENT
HIGH DENSITY INSULATION INSERT
(TYP)
THREADED ROD.(TYP)
PIPE INSULATION(TYP)
INSULATION SHIELD (TYP)
INSTALL CLAMP ON ALL
PIPES LESS THAN 4"Ø
HIGH DENSITY INSULATION INSERT OR,
FOR APPLICATIONS PERMITTED IN
SPECIFICATIONS, STEEL SADDLE FILLED
WITH INSULATION.
NOTES:
1. REFER TO SPECIFICATIONS FOR MORE INFORMATION.
2. SERVICE: RECOMMENDED FOR SUSPENSION OF INSULATED (HOT OR COLD) PIPE WHEN FLEXIBILITY OF THE CLAMP IS DESIREABLE.
½"
T=THICKNESS
STEEL PLATE
B
AC
45°
D
PIPE SIZE
A
B
C
D
T
ROD SIZE
CLEVIS SIZE
ROD TAP
PIN DIA.
PIN HOLE
GRIP
2"
1"
3 1/2"
3" 4" 6"
3 1/2" 3 1/2"
2" 2"
1" 1"
1/2" 5/8" 5/8"
3/8" 3/8" 3/8"
3/8" 1/2" 1/2"
2" 2" 2"
3/8" 1/2" 1/2"
3/8" 1/2" 1/2"
1/2" 5/8" 5/8"
1/2" 1/2" 1/2"
USE TURNBUCKLE IF BUILDING
CONNECTION DOES NOT PROVIDE
ADJUSTMENT
HEX NUT
PIPE SIZE
ROD
SIZE
GRINNELL ROD ATTACHMENT
CLEVIS FIG. 299
1/8" COTTER PIN
VERTICAL ELBOW
INSULATION
PIPE
ADJUSTABLE CLEVIS GRINNELL FIG. 65 OR
ADJUSTABLE CLEVIS GRINNELL FIG. 260
INSULATION
PIPE
HANGER ROD
INSULATION PROTECTION SHEILD: GRINNELL
FIG. 167 (SIZE RANGE 1/2" THRU 24" PIPE WITH
INSULATION THICKNESS OF 1/2", 3/4", 1", 1-1/2",
AND 2")
PIPE COVERING PROTECTION SADDLE
SINGLE PIPE ROLLER COMPLETE
GRINNELL FIG. #171
HANGER ROD
PROVIDE A SECTION OF HIGH
COMPRESSION STRENGTH INSULATION
AT EACH HANGER POINT. INSULATION
MAY BE HALF ROUND OR FULL ROUND
AND EXTEND 2" BEYOND GALV. SHIELD
EACH WAY.
PROVIDE A SECTION OF HIGH COMPRESSION
STRENGTH INSULATION AT EACH HANGER POINT.
INSULATION MAY BE HALF ROUND OR FULL ROUND
AND EXTEND 2" BEYOND GALV. SHIELD EACH WAY.
PIPE CL
PIPE ℄
PIPE ℄
8" x 8" x 3/8" [203 x 203 x 8mm] STEEL PLATE
WELD PLATE TO
PIPE
SECURE TO ROOF SLAB WITH
(4) 3/8" [10mm] EXPANSION
BOLTS OR WELD TO STEEL
DECK
CONCRETE ROOF SLAB OR
STEEL ROOF DECK
ROOF SYSTEM
INSULATION AND
MEMBRANE
PRE-MOULDED FLEXIBLE
PIPE COUNTER FLASHING
CLAMPING RING
ROOF SURFACE
WELD PIPE SADDLE
SUPPORT TO PIPE.
PROVIDE WATER TIGHT
CONNECTION.
HIGH COMPRESSIVE
STRENGTH INSULATION
INSERT UNDER SHIELD
PIPE AND
INSULATION
INSULATION PROTECTION
SHIELD
SEALANT
2" [50mm] STEEL PIPE
2-1/2" [65mm] STEEL PIPE
PROVIDE VAPOR BARRIER
AS SPECIFIED ON PIPING
CONVEYING FLUID TO
DEGREE ____°F [ ___°C]
NOTES:
1. PROVIDE RESTRAINING CLAMPS 8'-0" [2,4m] O.C.
m m
[8 m m m m
[1
M
IN
[4
PROVIDE ALUMINUM
JACKET
FULL SIZE CONNECTION
CONDENSATE
DRAIN
UNION
UNION
MAX. UNIT
TOTAL S.P. + 2"
PITCH CONDENSATE
DRAIN LINE TO NEWEST
GUTTER DRAIN
1" MIN. CLEARANCE
PIPE SLEEVE DETAIL PIPE THRU FLOOR DETAIL
INSTALL AN ESCUTCHEON AROUND PIPES
EXPOSED IN FINISHED ROOMS. FOR ALL
INSULATED PIPING INSTALL A PLASTIC JACKET
EXTENDING 6" BEYOND THE WALL TO PROTECT
INSULATION FROM DAMAGE.
MAKE A SMOOTH ROUND OPENING IN WALL
SLIGHTLY LARGER THAN OUTSIDE DIAMETER
OF THE PIPE AND INSULATION.
ADD A BEAD OF NON-HARDENING
CAULK IN THE ANNULAR SPACE.
NOTES:
1. THIS DETAIL APPLIES TO ALL PIPES. THE INTENTION IS TO CONTINUE THE INSULATION AND VAPOR BARRIER THROUGH ALL PENETRATIONS. PERMIT THERMAL EXPANSION WITHOUT DAMAGING INSULATION, AND TO SEAL
AIRTIGHT AROUND INSULATED AND UNINSULATED PIPES FOR NOISE TRANSMISSION CONTROL.
2. FLOOR OPENINGS ARE SIMILAR. SEE SPECIFICATIONS FOR DIFFERENCES BETWEEN FLOOR AND WALL
PENETRATIONS.
3. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
FIRE SEALANT
NOTE 2
NOTE 3
NOTE 4
NOTE 4
PIPE
NOTE 2
NOTE 3
FIRE RATED WALL
(CONSTRUCTION VARIES)
FIRE RATED FLOOR
(CONSTRUCTION VARIES)
NOTES:
1. THIS DETAIL APPLIES TO ALL ITEMS PENETRATING FIRE RATED WALLS OR FLOORS. THE INTENT IS TO MAINTAIN THE FIRE RATING AND TO ALLOW LONGITUDINAL MOVEMENT. REFER TO SPECIFICATIONS FOR SELECTION OF THROUGH PENETRATION FIRE
STOPPING.
2. SCHEDULE 5 PIPE SLEEVE EMBEDDED IN WALL OR FLOOR, OR SMOOTH CORE DRILL. EACH CONTRACTOR FURNISHES SLEEVE TO G.C., COORDINATES SLEEVE LOCATIONS AND DEBURS SLEEVE. G.C. BUILDS SLEEVE INTO WALL OR FLOOR ALLOWING NO GAP AROUND SLEEVE. IF SLEEVE IS NOT PROVIDED WHEN WALL OR FLOOR IS BUILT, CONTRACTOR SHALL INSTALL SLEEVE. SLEEVE
SIZE SHALL ALLOW ANNULAR SPACE REQUIRED BY THE SELECTED FIRE STOP SYSTEM.
3. INSTALL BACKING MATERIAL, SUCH AS MINERAL WOOL SAFING, AS REQUIRED FOR FIRE STOP SYSTEM. INSTALL IN ACCORDANCE WITH FIRE STOP SYSTEM APPLICATION LISTING. SECURE TO WALL OR FLOOR TO ALLOW LONGITUDINAL MOVEMENT OF
PENETRATING ITEM WITHOUT MOVEMENT OF FIRE BARRIER.
4. WATER-TIGHT WELDED 1"x1" 20 GAUGE MINIMUM GALVANIZED SHEET METAL ANGLE FRAME, BY CONTRACTOR IN EQUIPMENT ROOMS FOR WATER STOP. PLACE A BEAD OF WATERPROOF SEALANT BETWEEN FLOOR AND BOTTOM OF ANGLE FRAME. SECURE TO FLOOR WITH MASONRY ANCHORS IN CORNERS AND ON 12" MAXIMUM CENTERS. MULTIPLE PENETRATING ITEMS MAY BE
ENCLOSED IN ONE FRAME.
NON-FIRE RATED WALL(OR FLOOR)
(CONSTRUCTION VARIES)
NOTE 2
P
IP
E
FINISHED
FLOOR
INSULATION
METAL JACKET
WATERPROOF
SEALANT
BACKUP
MATERIAL
PIPE WITH
INSULATION
PIPE SLEEVE
ESCUTCHEON AT
EXPOSED AREAS
ONLY
PIPE WITHOUT
INSULATION
(±)1/8"
LUG, COUPLING,
OR HUB
RISER CLAMP
INSULATION AND
NEOPRENE MOUNTS
INSULATION
SEAL OPENING,
FIRESTOP IF
REQUIRED.
FLOOR
P
IP
E
PIPE SLEEVE
BACKUP MATERIAL
WATERPROOF
SEALANT (NOTE 1)
PIPE INSULATION
ESCUTCHEON (TYP)
INTERIOR SIDE OF
EXTERIOR WALL
INSULATED PIPE
SLEEVE THRU WALL
ABOVE GRADE
BARE PIPE SLEEVE
THRU WALL ABOVE
GRADE
WATERPROOF
SEALANT
(NOTE 1)
INTERIOR SIDE OF
EXTERIOR WALL
NOTES:
1. SEALANT-JOINT 1/4" WIDE MIN. BY 3/8" DEEP MIN.
NOTES:
1. CONTRACTOR SHALL COORDINATE EXHAUST
SILENCER HEIGHT WITH ANY ELECTRICAL CONDUIT.
STAINLESS STEEL JACKETED
EXHAUST PIPE (ASTM A53 SCH.10)
WITH 4" THICK CALCIUM SILICATE
INSULATION. PIPE SHALL BE SIZED
BY MUFFLER SELECTION.
ROOF
UNISTRUT SUPPORTS
SECURED TO Z-PURLIN
ENGINE EXHAUST SILENCER WITH
STAINLESS STEEL JACKETED 4" THICK
CALCIUM SILICATE INSULATION
MOUNTING BRACKET - SADDLE TYPE
WITH GALV. METAL PROTECTIVE SHIELD
FLANGED SPOOL WITH GASKET.
LENGTH AS REQUIRED
STAINLESS STEEL FLEXIBLE CONNECTOR
WITH GASKETS AT EACH FLANGE
Y-HEADER (IF REQUIRED)
ENGINE OUTLINE
EXHAUST FLANGE (ASTM
A53 SCH.10) OUTLET WITH
GASKET
STEEL (ASTM A53 SCH.10)
FLOATING FLANGE WITH GASKET
PROVIDE GENERATOR EXHAUST
PIPE SUPPORT
BUILDING
ALL-THREAD
HANGER RODS
WALL THIMBLE
OPTIONAL MOUNTING BRACKET -
BACK TO BACK STEEL CHANNEL
WITH WELDED STITCH PLATE
TRAPEZE TYPE
LONG SWEEP ELBOW
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/3 2"
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
G ra p h ic S ca le
/2
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
NOT FOR
PERMITTING OR
CONSTRUCTION
A/E:Consultant:
Approved: Spinklered
Office of Construction and Facilities Management FULLY SPRINKLERED
B
IM
/V
IS
N
O m a h a
E H
R M
/O m a h a
E H
R M
V
.r v t
/2
/2
:3
:5
P
M
AW RAWMAY 15, 2023
M-102
636 - OMAHA VA MEDICAL CENTER
ISSUE FOR BIDMECHANICAL DETAILS 636-21-704OMAHA EHRM INFRASTRUCTURE
UPGRADE DESIGN
NTS
PIPE SUPPORTS DETAIL
NTS
PIPE SUPPORT ON ROOF
NTS
TYPICAL CONDENSATE TRAP DETAIL
NTS
PIPE PENETRATIONS DETAIL
Revisions: Date:
1/4" = 1'-0"
EXHAUST SILENCER SUPPORT
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/3 2"
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
G ra p h ic S ca le
/2
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
NOT FOR
PERMITTING OR
CONSTRUCTION
A/E:Consultant:
Approved: Spinklered
Office of Construction and Facilities Management FULLY SPRINKLERED
B
IM
/V
IS
N
O m a h a
E H
R M
/O m a h a
E H
R M
V
.r v t
/2
/2
:3
:5
P
M
AW RAWMAY 15, 2023
M-103
636 - OMAHA VA MEDICAL CENTER
ISSUE FOR BIDMECHANICAL SCHEDULES 636-21-704OMAHA EHRM INFRASTRUCTURE
UPGRADE DESIGN
4. ELECTRICAL CONTRACTOR TO PROVIDE DISCONNECT SWTICH.
3. PROVIDE MICROPROCESSOR CONTROL, THERMOSTAT, BACNET INTERFACE, LOW AMBIENT WIND BAFFLE KIT, INTEGRAL CONDENSATE PUMP, SECONDARY DRAIN PAN WITH WATER LEAK SENSOR. CONDENSER PAD. INSTALL PER MANUFACTURER GUIDELINES.
2. LOCATIONS OF CONDENSING UNITS ARE SCHEMATIC IN NATURE. CONTRACTOR SHALL COORDINATE FINAL PLACEMENT OF CONDENSING UNITS WITH VA.
1. BASED ON LG LAU1480HYV3 OUTDOOR UNIT AND LG LAN180HYV3 INDOOR UNIT.
NOTES:
9-ASHP-1 9 B12A WALL MT. SPLIT 813 0.2 18 24 80 67 [ 95 ] [ 22 ] 70 90 [ -4 ] - TSTAT - DDC 14.81 DIRECT 19 1 208/230 R410A 164 SEE NOTES 1,2,3,4
CFM IN MBH °F °F °F MBH °F °F °F AMPS CONTROL AMPS CONTROL
Db Wb
TOTAL
CAPACITY MIN SEER
EAT OSA DESIGN
TEMP
MIN. HEAT
CAPACITY
EAT
Db
LAT
Db
OSA DESIGN
TEMP
INDOOR FAN OUTDOOR UNIT FAN
MCA PHASE VOLT
MARK BLDG ROOM TYPE
TOTAL SUPPLY
AIR FLOW
EXT STATIC
PRESSURE
CAPACITY HEATING CAPACITY ELECTRICAL DATA
REFRIG.
PIPE LENGTH
MAX. FT
REMARKS
SPLIT SYSTEM AIR CONDITIONER / EVAPORATOR SCHEDULE
1. SEE DETAIL FOR DAMPER IN BRANCH DUCT SERVING EACH DIFFUSER.
NOTES:
SD-53 150 350 0.1 DUCT MOUNTED 12x12 10x10 19 OBD WHITE SEE NOTE 1
SD-13 110 380 0.09 CEILING 24x24 10Ø 22 OBD WHITE SEE NOTE 1
SD-12 70 280 0.1 CEILING 24x24 8Ø 23 OBD WHITE SEE NOTE 1
CFM CFM IN WG IN X IN IN DB
MIN MAXMARK
AIRFLOW
MAX APD
MOUNTING
PANEL/FRAME SIZE NECK SIZE NOISE CRITERIA
DAMPER FINISH REMARKS
AIR DEVICE SCHEDULE (SUPPLY)
2. OMIT FIRE PROTECTION DUE TO SPACE LIMITATIONS AND/OR LACK OF EXISTING SPRINKLER SYSTEM. SPACE TO HAVE FIRE-SMOKE ALARM SYSTEM.
VARIANCES: 1. IT RACK COOLING LOAD PER 35% COMMENTS BY OMAHA VA AND MEETING WITH VA-OIT FEB-24-2022.
* 35% VA COMMENTS: Cooling per TR/number of racks will be as follows. We need 5kW per rack, however in aggregate we don't need 5kW for each of four racks. Update standard and TR design checklist with new language, applicable for both new construction and renovations.
1 rack TR = 5kW (e.g. single 5kW cooling unit).
2 rack TR = 7kW (e.g. 3.5kW x2 cooling units).
3 rack TR = 8.5 kW (e.g. 3.5kW + 2.5kW x2 cooling units).
4 rack TR =10kW (e.g. 2.5kW x4 or 5kW x2 cooling units).
Other designs meeting these maximum expected aggregated load levels are acceptable. Multiple smaller units will assist in avoiding equipment freeze-up in some types of equipment.
** Meeting with VA-OIT Feb-24-2022: MCR to use existing equipment with 80kw load.
ACC 2433 3 TR >96 - EXISTING DX EXISTING N 1 WS Remain as it. DDC upgrades for monitoring only.
ACC 2011 4 TR >96 - EXISTING DX EXISTING N 1 WS Remain as it. DDC upgrades for monitoring only.
ACC 1433 3 TR >96 - EXISTING DX EXISTING N 1 WS Remain as it. DDC upgrades for monitoring only.
ACC 1011 3 TR >96 - EXISTING DX EXISTING N 1 WS Remain as it. DDC upgrades for monitoring only.
ACC G433 6 TR >96 - EXISTING DX EXISTING N 1 WS Remain as it. DDC upgrades for monitoring only.
ACC G011 3 TR >96 - EXISTING DX EXISTING N 1 WS Remain as it. DDC upgrades for monitoring only.
D OFFICES 109 Telecommunications Rm 1 TE <96 5 kw (17,060 btu/hr) NONE NONE N 1 NONE Design alert eliminate fire protection and cooling.
15 Research R200A Telecommunications Rm 1 TR >96 5 kw (17,060 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser
9 DIALYSIS B12A Telecommunications Rm 1 TR >96 5 kw (17,060 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser 8 OFFICES 104A Telecommunications Rm 1 TE <96 5 kw (17,060 btu/hr) NONE NONE N 1 NONE Design alert eliminate fire protection and cooling.
6 DENTAL 109 Telecommunications Rm 1 TR >96 5 kw (17,060 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser
2 BOILER PLANT 202 Telecommunications Rm 1 TE <96 5 kw (17,060 btu/hr) NONE NONE N 1 NONE Design alert eliminate fire protection and cooling.
1 14002 Telecommunications Rm 1 TR >96 5 kw (17,060 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser 1 12018 Telecommunications Rm 1 TR >96 5 kw (17,060 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser
1 11414 Telecommunications Rm 1 TR >96 5 kw (17,060 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser
1 10414 Telecommunications Rm 1 TR >96 5 kw (17,060 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser
1 9414 Telecommunications Rm 2 TR >96 7 kw (23,884 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser
1 8414 Telecommunications Rm 2 TR >96 7 kw (23,884 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser 1 7414 Telecommunications Rm 2 TR >96 7 kw (23,884 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser
1 6414 Telecommunications Rm 2 TR >96 7 kw (23,884 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser
1 5414 Telecommunications Rm 2 TR >96 7 kw (23,884 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser
1 4374A Telecommunications Rm 2 TR >96 7 kw (23,884 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser 1 3254B Telecommunications Rm 2 TR >96 7 kw (23,884 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser
1 2448 Telecommunications Rm 1 TR >96 5 kw (17,060 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser
1 2255A Telecommunications Rm 2 TR >96 7 kw (23,884 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser
1 1656 Telecommunications Rm 2 TR >96 7 kw (23,884 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser
1 1616 Telecommunications Rm 1 TR >96 5 kw (17,060 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser 1 1510 Telecommunications Rm 1 TR >96 5 kw (17,060 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser
1 1205B Telecommunications Rm 3 TR >96 8.5 kw (29,002 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser
1 B721 Telecommunications Rm 34 TR >96 80 kw (272,960 btuh) EXISTING DX NONE N + 1 3 WS Existing CRAC units to remain. Qty (2) 105 kw cooling capacity.
1 B611 Telecommunications Rm 1 TR >96 5 kw (17,060 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser 1 B818A Telecommunications Rm 2 TR >96 7 kw (23,884 btu/hr) DX NONE N 1 WS Dedicated CRAC with air cooled condenser
1 B024C Telecommunications Rm 3 TR >96 8.5 kw (29,002 btu/hr) DX NONE N 3 WS Dedicated CRAC with air cooled condenser
NUM. NUM. NUM. QTY TE / TR <96 OR >96
PER VA COMMENTS
OIT/OMAHA VARIANCE
DX / CW / VAV
DX-Vertiv-Encl
DRY FOG /
NONE
N 1 / 2 / 3 / 4 CA (clean agent) WS (wet system)
CA-Vertiv-Encl / NONE
BLDG ROOM ROOM NAME IT RACKS ROOM TYPE
QTY WORK
AREA
OUTLETS
HEAT LOAD
BASIS OF DESIGN
HVAC SYSTEM
TYPE
HUMIDIFIER
CRITICAL
REDUNDANCY
LEVEL
ANSI/TIA-9
43-B
RATING
FIRE SUPPRESSION
SYSTEM TYPE
NOTES
OIT TR ROOM DESIGN INPUT COORDINATION SCHEDULE: *INCLUDES CHANGES FROM VARIANCES, DESIGN ALERTS, MEETINGS, AND
COMMENTS
5. INTERLOCK DAMPER OPERATION WITH EXHAUST FAN.
4. INTERLOCK DAMPER OPERATION WITH GENERATOR.
3. CONTROLS PROVIDED BY CONTROLS CONTRACTOR.
2. PROVIDE LOUVER WITH INSULATED LOW LEAKAGE DAMPER. SPRING OPEN WITH ACTUATOR POWERED CLOSED. PROVIDE 1/4" MESH BUG SCREEEN.
1. LOUVER SHALL BE BLAST AND MISSILE RATED. REFER TO SPECIFICATIONS FOR DETAILS.
NOTES:
G-IAL-3 G-ME101 GENERATOR INTAKE POTTORFF / EFD-637 114 x 104 19,000 400 0.02 SEE NOTES 1-5.
G-IAL-2 G-ME101 GENERATOR INTAKE POTTORFF / EFD-637 114 x 104 19,000 400 0.02 SEE NOTES 1-5.
G-IAL-1 G-ME101 GENERATOR INTAKE POTTORFF / EFD-637 114 x 86 19,000 459 0.02 SEE NOTES 1-5.
G-EAL-3 G-ME101 GENERATOR EXHAUST POTTORFF / EDD-637 40 x 36 3,450 655 0.05 SEE NOTES 1-5.
G-EAL-2 G-ME101 GENERATOR EXHAUST POTTORFF / EFD-637 114 x 86 28,500 689 0.02 SEE NOTES 1-5.
G-EAL-1 G-ME101 GENERATOR EXHAUST POTTORFF / EFD-637 114 x 86 28,500 689 0.02
KYNAR FINISH. REFER TO
ARCHITECTURAL
PLANS FOR COLOR.
SEE NOTES 1-5.
IN CFM F/m IN WG
MARK LOCATION SYSTEM AND/OR SERVICE MANUFACTURER / MODEL
SIZE (W x H) AIRFLOW
FREE AREA
VELOCITY
SP IN WC
FINISH REMARKS
LOUVER SCHEDULE
4. PROVIDE UNIT WITH FACTORY SUPPLIED CONDENSATE PUMP AS REQUIRED. PUMP TO BE INSTALLED IN FIELD PER MANUFACTURER'S RECOMMENDATIONS.
3. PROVIDE UNIT WITH FACTORY MOUNTED FUSED INTEGRAL DISCONNECT SWITCH.
2. RE-HEAT COIL SHALL BE WIRED AND CONTROLLED TO LOCK-OUT, TURN OFF, DURING EMERGENCY GENERATOR OPERATION.
1. PROVIDE MICROPROCESSOR CONTROL, PROGRAMMABLE THERMOSTAT, BACNET INTERFACE, DISCONNECT SWITCH, CONDENSATE PUMP, AIR FILTER BOX, WIRE MESH RETURN GRILLE, SUPPLY FLANGE, SECONDARY DRAIN PAN WITH WATER LEAK SENSOR. INSTALL PER MANUFACTURER GUIDELINES. INSULATE SUPPLY DUCTS AND TRANSITIONS WITH 2" WRAP.
NOTES:
15-CRAC-1 15 R200A DX CRAC INDOOR UNIT 750 0.3 18.5 16.5 75.0 61 12.2 208 1 Ø 60 20.2 25.3 30 54 x 30 x 20 225 LIEBERT MINI-MATE2 / MMD18E NOTES: 1-4
06-CRAC-1 06 109 DX CRAC INDOOR UNIT 750 0.3 18.5 16.5 75.0 61 12.2 208 1 Ø 60 20.2 25.3 30 54 x 30 x 20 225 LIEBERT MINI-MATE2 / MMD18E NOTES: 1-4
01-CRAC-20 01 12018 DX CRAC INDOOR UNIT 750 0.3 18.5 16.5 75.0 61 12.2 277 1 Ø 60 17.7 22.1 25 54 x 30 x 20 225 LIEBERT MINI-MATE2 / MMD18E NOTES: 1-4
01-CRAC-19 01 14002 DX CRAC INDOOR UNIT 750 0.3 18.5 16.5 75.0 61 12.2 277 1 Ø 60 17.7 22.1 25 54 x 30 x 20 225 LIEBERT MINI-MATE2 / MMD18E NOTES: 1-4
01-CRAC-18 01 11414 DX CRAC INDOOR UNIT 750 0.3 18.5 16.5 75.0 61 12.2 277 1 Ø 60 17.7 22.1 25 54 x 30 x 20 225 LIEBERT MINI-MATE2 / MMD18E NOTES: 1-4
01-CRAC-17 01 10414 DX CRAC INDOOR UNIT 750 0.3 18.5 16.5 75.0 61 12.2 277 1 Ø 60 17.7 22.1 25 54 x 30 x 20 225 LIEBERT MINI-MATE2 / MMD18E NOTES: 1-4
01-CRAC-16 01 9414 DX CRAC INDOOR UNIT 885 0.3 21.8 19.5 75.0 61 16 277 1 Ø 60 24.0 30 35 57-13/16 x 31 x 24 225 LIEBERT MINI-MATE2 / MMD24E NOTES: 1-4
01-CRAC-15 01 8414 DX CRAC INDOOR UNIT 885 0.3 21.8 19.5 75.0 61 16 277 1 Ø 60 24.0 30 35 57-13/16 x 31 x 24 225 LIEBERT MINI-MATE2 / MMD24E NOTES: 1-4
01-CRAC-14 01 7414 DX CRAC INDOOR UNIT 885 0.3 21.8 19.5 75.0 61 16 277 1 Ø 60 24.0 30 35 57-13/16 x 31 x 24 225 LIEBERT MINI-MATE2 / MMD24E NOTES: 1-4
01-CRAC-13 01 6414 DX CRAC INDOOR UNIT 885 0.3 21.8 19.5 75.0 61 16 277 1 Ø 60 24.0 30 35 57-13/16 x 31 x 24 225 LIEBERT MINI-MATE2 / MMD24E NOTES: 1-4
01-CRAC-12 01 5414 DX CRAC INDOOR UNIT 885 0.3 21.8 19.5 75.0 61 16 277 1 Ø 60 24.0 30 35 57-13/16 x 31 x 24 225 LIEBERT MINI-MATE2 / MMD24E NOTES: 1-4
01-CRAC-11 01 4374A DX CRAC INDOOR UNIT 885 0.3 21.8 19.5 75.0 61 16 277 1 Ø 60 24.0 30 35 57-13/16 x 31 x 24 225 LIEBERT MINI-MATE2 / MMD24E NOTES: 1-4
01-CRAC-10 01 3254B DX CRAC INDOOR UNIT 885 0.3 21.8 19.5 75.0 61 16 277 1 Ø 60 24.0 30 35 57-13/16 x 31 x 24 225 LIEBERT MINI-MATE2 / MMD24E NOTES: 1-4
01-CRAC-9 01 2255A DX CRAC INDOOR UNIT 885 0.3 21.8 19.5 75.0 61 16 277 1 Ø 60 24.0 30 35 57-13/16 x 31 x 24 225 LIEBERT MINI-MATE2 / MMD24E NOTES: 1-4
01-CRAC-8 01 2448 DX CRAC INDOOR UNIT 750 0.3 18.5 16.5 75.0 61 12.2 277 1 Ø 60 17.7 22.1 25 54 x 30 x 20 225 LIEBERT MINI-MATE2 / MMD18E NOTES: 1-4
01-CRAC-7 01 1656 DX CRAC INDOOR UNIT 885 0.3 21.8 19.5 75.0 61 16 277 1 Ø 60 24.0 30 35 57-13/16 x 31 x 24 225 LIEBERT MINI-MATE2 / MMD24E NOTES: 1-4
01-CRAC-6 01 1616 DX CRAC INDOOR UNIT 750 0.3 18.5 16.5 75.0 61 12.2 277 1 Ø 60 17.7 22.1 25 54 x 30 x 20 225 LIEBERT MINI-MATE2 / MMD18E NOTES: 1-4
01-CRAC-5 01 1205B DX CRAC INDOOR UNIT 1,350 0.2 32.4 28.0 75.0 61 25.2 460 3 Ø 60 11.5 14.4 15 57-13/16 x 31 x 24 328 LIEBERT MINI-MATE2 / MT036 NOTES: 1-4
01-CRAC-4 01 1510 DX CRAC INDOOR UNIT 750 0.3 18.5 16.5 75.0 61 12.2 277 1 Ø 60 17.7 22.1 25 54 x 30 x 20 225 LIEBERT MINI-MATE2 / MMD18E NOTES: 1-4
01-CRAC-3 01 B024C DX CRAC INDOOR UNIT 1,350 0.2 32.4 28.0 75.0 61 25.2 460 3 Ø 60 11.5 14.4 15 57-13/16 x 31 x 24 328 LIEBERT MINI-MATE2 / MT036 NOTES: 1-4
01-CRAC-2 01 B611 DX CRAC INDOOR UNIT 750 0.3 18.5 16.5 75.0 61 12.2 277 1 Ø 60 17.7 22.1 25 54 x 30 x 20 225 LIEBERT MINI-MATE2 / MMD18E NOTES: 1-4
01-CRAC-1 01 B818A DX CRAC INDOOR UNIT 885 0.3 21.8 19.5 75.0 61 16 277 1 Ø 60 24.0 30 35 57-13/16 x 31 x 24 225 LIEBERT MINI-MATE2 / MMD24E NOTES: 1-4
CFM IN MBH MBH °F °F MBH IN x IN x IN LBS
Db Wb
MIN. TOTAL
CAP.
MIN. SENS
CAP.
EAT ELEC. REHEAT
CAP. VOLTS PHASE HZ FLA WSA OPD
FAN COIL
DIMENSIONS WEIGHT
MANUF. / MODEL
MARK BLDG ROOM TYPE
SUPPLY
AIR FLOW
EXT.
STATIC
PRESS.
COOLING CAPACITY ELECTRICAL DATA BASIS OF DESIGN
REMARKS
FAN COIL UNIT
AIR COOLED DX CRAC INDOOR UNIT SCHEDULE
3. LOCATION OF CONDENSING UNITS ARE SCHEMATIC IN NATURE. CONTRACTOR SHALL COORDINATE FINAL PLACEMENT OF CONDENSING UNITS WITH VA.
2. ALL ENCLOSURES REQUIRE TWO POWER CONNECTIONS. ONE FOR FAN COIL UNIT AND ONE FOR CONDENSER UNIT.
1. ELECTRICAL CONTRACTOR TO PROVIDE DISCONNECT SWITCH.
NOTES:
15-CRAC-1A 15 LEVEL 2 ROOF DX CRAC CONDENSER UNIT 208 1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH020 NOTES: 1, 2, 3
06-CRAC-1A 06 LEVEL 1 GRADE DX CRAC CONDENSER UNIT 208 1 Ø 60 40 x 18 x 23-1/2 244 LIEBERT MINI-MATE2 / PFH020 NOTES: 1, 2, 3
01-CRAC-20A 01 LEVEL 12 ROOF DX CRAC CONDENSER UNIT 277 '1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH020 NOTES: 1, 2, 3
01-CRAC-19A 01 LEVEL 13 SIDEWALL DX CRAC CONDENSER UNIT 277 '1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH020 NOTES: 1, 2, 3
01-CRAC-18A 01 LEVEL 12 ROOF DX CRAC CONDENSER UNIT 277 '1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH020 NOTES: 1, 2, 3
01-CRAC-17A 01 LEVEL 12 ROOF DX CRAC CONDENSER UNIT 277 '1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH020 NOTES: 1, 2, 3
01-CRAC-16A 01 LEVEL 12 ROOF DX CRAC CONDENSER UNIT 277 '1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH027 NOTES: 1, 2, 3
01-CRAC-15A 01 LEVEL 5 ROOF DX CRAC CONDENSER UNIT 277 '1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH027 NOTES: 1, 2, 3
01-CRAC-14A 01 LEVEL 5 ROOF DX CRAC CONDENSER UNIT 277 '1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH027 NOTES: 1, 2, 3
01-CRAC-13A 01 LEVEL 5 ROOF DX CRAC CONDENSER UNIT 277 '1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH027 NOTES: 1, 2, 3
01-CRAC-12A 01 LEVEL 5 ROOF DX CRAC CONDENSER UNIT 277 '1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH027 NOTES: 1, 2, 3
01-CRAC-11A 01 LEVEL 5 ROOF DX CRAC CONDENSER UNIT 277 '1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH027 NOTES: 1, 2, 3
01-CRAC-10A 01 LEVEL 5 ROOF DX CRAC CONDENSER UNIT 277 '1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH027 NOTES: 1, 2, 3
01-CRAC-9A 01 LEVEL 2 ROOF DX CRAC CONDENSER UNIT 277 '1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH027 NOTES: 1, 2, 3
01-CRAC-8A 01 LEVEL 3 ROOF DX CRAC CONDENSER UNIT 277 '1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH020 NOTES: 1, 2, 3
01-CRAC-7A 01 LEVEL 2 ROOF DX CRAC CONDENSER UNIT 277 '1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH027 NOTES: 1, 2, 3
01-CRAC-6A 01 LEVEL 2 ROOF DX CRAC CONDENSER UNIT 277 '1 Ø 60 40 x 18 x 23-1/2 244 LIEBERT MINI-MATE2 / PFH020 NOTES: 1, 2, 3
01-CRAC-5A 01 LEVEL 2 ROOF DX CRAC CONDENSER UNIT 460 '3 Ø 60 48-1/4 x 18-5/8 x 30-3/4 244 LIEBERT MINI-MATE2 / PFD037 NOTES: 1, 2, 3
01-CRAC-4A 01 LEVEL 2 ROOF DX CRAC CONDENSER UNIT 277 '1 Ø 60 40 x 18 x 23-1/2 244 LIEBERT MINI-MATE2 / PFH020 NOTES: 1, 2, 3
01-CRAC-3A 01 LEVEL 1 GRADE DX CRAC CONDENSER UNIT 460 '3 Ø 60 48-1/4 x 18-5/8 x 30-3/5 244 LIEBERT MINI-MATE2 / PFD037 NOTES: 1, 2, 3
01-CRAC-2A 01 LEVEL 2 ROOF DX CRAC CONDENSER UNIT 277 1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH020 NOTES: 1, 2, 3
01-CRAC-1A 01 LEVEL 2 ROOF DX CRAC CONDENSER UNIT 277 1 Ø 60 40 x 18 x 23-1/2 200 LIEBERT MINI-MATE2 / PFH027 NOTES: 1, 2, 3
IN LBS
VOLT PHASE HZ
CONDENSER UNIT
DIMENSIONS
WEIGHT
MANF / MODEL
MARK BLDG LOCATION TYPE
ELECTRICAL DATA BASIS OF DESIGN
REMARKS
OUTDOOR CONDENSING UNIT
AIR COOLED DX CRAC OUTDOOR UNIT SCHEDULE
NOTES:
RR-55 320 850 0.082 SIDEWALL 20x18 18x16 19 NONE WHITE -
RG-26 420 700 0.087 CEILING 24x24 16Ø 16 NONE WHITE -
RG-22 110 170 0.1 CEILING 12x12 8Ø 13 NONE WHITE -
CFM CFM IN WG IN X IN IN DB
MIN MAXMARK
AIRFLOW
MAX APD
MOUNTING
PANEL/FRAME SIZE NECK SIZE NOISE CRITERIA
DAMPER FINISH REMARKS
AIR DEVICE SCHEDULE (RETURN)
2. TIE UNIT HEATER INTO BUILDING CONTROL SYSTEMS. UNIT HEATER SHALL RUN WHENEVER TEMPERATURE IS BELOW 55°F (ADJ).
1. ELECTRIC EXPLOSION PROOF UNIT HEATER.
NOTES:
G-UH-5 WATER ROOM ELECTRIC BERKO / RUX300812 700 10,236 38.4 1 208 3 SEE NOTE 1
G-UH-4 SUBSTATION ELECTRIC BERKO / RUX750812 840 25,590 38.4 1 208 7.5 SEE NOTE 1
G-UH-3 ELECTRIC ROOM ELECTRIC BERKO / RUX500812 700 17,060 26.3 1 208 5 SEE NOTE 1
G-UH-2 GENERATOR ROOM ELECTRIC BERKO / RUX750812 840 25,590 38.4 1 208 7.5 SEE NOTE 1
G-UH-1 GENERATOR ROOM ELECTRIC BERKO / RUX750812 840 25,590 38.4 1 208 7.5 SEE NOTE 1
CFM BTUH AMP PHASE VOLT KW
MARK LOCATION TYPE MANU / MODEL
AIRFLOW MIN CAPACITY POWER ELECTRIC HEATING WATTS
REMARKS
ELECTRIC UNIT HEATER SCHEDULE
Revisions: Date:
4. A VAULTED CONCRETE ENCLOSURE SHALL ENCASE AND PROTECT BOTH THE PRIMARY STEEL TANK AND THE SECONDARY CONTAINMENT. THE CONCRETE ENCASEMENT SHALL BE 6” THICK WITH A MINIMUM DESIGN STRENGTH OF 4000 PSI.
3. THE TANK SYSTEM SHALL INCLUDE SECONDARY CONTAINMENT CONSISTING OF AN IMPERVIOUS BARRIER OF 30 MIL (0.76 MM) HIGH-DENSITY POLYETHYLENE GEOMEMBRANE ENCLOSING THE PRIMARY STEEL TANK AND INSULATION MATERIAL TO CONTAIN LEAKS FROM THE PRIMARY TANK AND ISOLATING THE PRIMARY TANK FROM THE CONCRETE TO PROTECT AGAINST CORROSION.
2. THE PRIMARY STEEL TANK SHALL BE PRESSURE TESTED AT 5 PSIG FOR A MINIMUM OF 24 HOURS. ALL OPENINGS SHALL BE FROM THE
TOP ONLY.
1. THE PRIMARY TANK SHALL BE RECTANGULAR IN SHAPE AND LISTED PER UL STANDARD 142. STEEL TANK THICKNESS SHALL BE 3/16” THICK (7 GAUGE). WELDS SHALL BE CONTINUOUS ON ALL SIDES AND EXTERIOR SEAMS, CONFORMING TO THE AMERICAN WELDING
SOCIETY STANDARD FOR CONTINUOUS WELD.
NOTES:
DFT-1 6,000 DIESEL FUEL CONVAULT 17' 7" x 8' 0" x 8' 3-1/4" SEE NOTES 1-4
FT / IN
MARK SIZE (GALLONS)
SYSTEM AND/OR
SERVICE
MANUFACTURER
SIZE (L x W x H)
REMARKS
DIESEL FUEL TANK SCHEDULE
1. EXPLOSION PROOF FAN WITH MOTORIZED DAMPER.
NOTES:
G-EF-3 SUBSTATION GENERATOR BUILDING EXHAUST GREENHECK SDPHE-16-3-A4 1,700 0.31 SIDEWALL DIRECT DRIVE HAZARDOUS FAN DIRECT 1,750 1/4 1 120 1,750 SEE NOTE 1.
G-EF-2 ELEC ROOM GENERATOR BUILDING EXHAUST GREENHECK SDPHE-12-3-A4 1,050 0.28 SIDEWALL DIRECT DRIVE HAZARDOUS FAN DIRECT 1,750 1/4 1 120 1,750 SEE NOTE 1.
G-EF-1 GENERATOR ROOM GENERATOR BUILDING EXHAUST GREENHECK SDPHE-24-3-A5 3,450 0.28 SIDEWALL DIRECT DRIVE HAZARDOUS FAN DIRECT 1,750 1/2 1 120 1,750 SEE NOTE 1.
G-SF-3 SUBSTATION GENERATOR BUILDING OUTDOOR AIR GREENHECK AER-24-03-0315 1,700 0.31 SIDEWALL DIRECT DRIVE HAZARDOUS FAN DIRECT 1,750 1/4 1 120 1,750 SEE NOTE 1.
G-SF-2 ELEC ROOM GENERATOR BUILDING OUTDOOR AIR GREENHECK AER-24-03-0315 1,050 0.28 SIDEWALL DIRECT DRIVE HAZARDOUS FAN DIRECT 1,750 1/4 1 120 1,750 SEE NOTE 1.
G-SF-1 GENERATOR ROOM GENERATOR BUILDING OUTDOOR AIR GREENHECK AER-24-03-0315 3,450 0.28 SIDEWALL DIRECT DRIVE HAZARDOUS FAN DIRECT 1,750 1/2 1 120 1,750 SEE NOTE 1.
01-EF-1 ROOF B830 EXHAUST GREENHECK GB-220 6000 0.5 DOWNBLAST ROOFTOP FAN BELT 882 1-1/2 3 430 882 -
CFM IN.
TYPE DRIVE
FAN MAX
RPM
PHASE VOLT RPM
MARK LOCATION AREA AND/OR BLDG SERVED
SYSTEM AND/OR
SERVICE
MANUFACTURER MODEL
AIR FLOW TSP
FAN
REMARKS
FAN SCHEDULE
1. SPUN ALUMINUM GRAVITY INTAKE VENTILATOR.
NOTES:
01-RH-2 ROOF B830 INTAKE GREENHECK GRSI-30 3,000 0.09 1
01-RH-1 ROOF B830 INTAKE GREENHECK GRSI-30 3,000 0.09 1
CFM IN.
MARK LOCATION
AREA AND/OR BLDG
SERVED
SYSTEM AND/OR
SERVICE
MANUFACTURER MODEL
AIR FLOW PRESSURE DROP
REMARKS
ROOF HOOD SCHEDULE
4. INSTALL AS ONE FULL PUMP SET ASSEMBLEY.
3. PROVIDE WITH MANUFACTURER'S PUMP STARTER CONTROL BOX.
2. PUMP AND MOTOR SHALL BE SUITABLE FOR OUTDOOR INSTALLATION.
1. PROVIDE WITH INTERNAL RELIEF VALVE.
NOTES:
FOP-2 GENERATOR BUILDING DIESEL FUEL MAINTENACE SYSTEM SINGLE #2D FUEL 1.86 40 3R 1/3 1,800 1 115 60 PRYCO PYPS2100 SEE NOTES 1-4
FOP-1 GENERATOR BUILDING OUTDOOR TANK DUPLEX #2D FUEL 1.86 40 3R 1/3 1,800 1 115 60 PRYCO PYPS2205 SEE NOTES 1-4
GPM PSI
PHASE VOLT HZ MANUFACTURER MODEL
MARK LOCATION SERVICE CONFIGURATION FLUID
FUEL FLOW
HEAD
PRESSURE NEMA RATING HP RPM
ELECTRICAL DATA BASIS OF DESIGN
REMARKS
FUEL OIL PUMP SCHEDULE
P3
P1P2
FP
MP
LEGEND
P1
FP
LD FL
BOBOP1 P2
FLLD LD
FUEL DISTRIBUTION SYSTEM CONTROL SEQUENCE
LD
LEGEND
P1
BO
FL
LD
BO
FP BO
FILL GAUGE VISUAL AND
AUDIBLE ALARM
FOS
DIESEL FUEL
MAINTENANCE
SYSTEM
OVERFILL
PREVENTATION
AND DROP TUBE
FILL CONNECTION
PRESSURE RELIEF VALVE, PIPE DISCHARGE
TO DROP INTO DIESEL OIL RETURN LNE.
DIESEL OIL
SUPPLY BACK
PRESSURE VALVE
FUEL RETURN PUMP
FOS
FOR
FUEL ISOLATION VALVES
LOCATED WITHIN BUILDING
F O
S
F O
R
FUEL TANK
6,000 GAL
MANUAL FUEL PUMP
(ROTARY HAND PUMP)F
O R
F O
S
DIESEL
GENERATOR
DFMS FUEL
PUMP
FUEL OIL TANK
MONITORING
SYSTEM
FUEL OIL PUMP
XXX SYSTEM DESCRIPTION
VALVE - SHUT-OFF, NORMALLY CLOSED
VALVE - SHUT-OFF, NORMALLY OPEN
DIRECTION OF FLOW
FOS FUEL OIL SUPPLY
FOR FUEL OIL RETURN
PRESSURE GAUGE
VALVE - CONTROL 2-WAY (2-POSITION)
FLOW METER
VALVE - CHECK
VALVE - PPRESSURE REDUCING VALVE (PRV)
FUEL SUPPLY PUMPS
FUEL SUPPLY PUMP
(BUILT INTO GENERATOR)
DAY TANK
1. DESCRIPTION OF THE FUEL SYSTEM:
A. THE FUEL DISTRIBUTION SYSTEM IS COMPRISED OF AN ABOVE GROUND FUEL STORAGE TANK WITH REDUNDANT FUEL OIL PUMPS. FUEL OIL PUMPS DISTRIBUTE FUEL TO THE GENERATOR DAY TANK. FUEL RETURN PUMP FOR THE DAY TANK SHALL RETURN FUEL BACK TO THE ABOVE GROUND TANK TO PREVENT OVERFLOW CONDITION. A FUEL MANAGEMENT SYSTEM WILL MONITOR THE FUEL LEVEL AND LEAK DETECTION
ALARMS FOR EACH TANK THROUGHOUT THE FUEL SYSTEM.
2. GENERAL SEQUENCE OF OPERATION:
A. FUEL WILL BE DISTRIBUTED FROM AN ABOVE GROUND STORAGE TANK TO THE DAY TANK. THE TANK SHALL BE EQUIPPED WITH A FULL, FILL, AND LOW LEVEL FLOAT SWITCH. THE LEAD FUEL OIL PUMP OPERATION WILL BE ALTERNATED AUTOMATICALLY.
1) FUEL OIL PUMPS CONTROLLED AS INDICATED BY MOTOR STARTER HOA SWITCH
i. HAND - FUEL PUMP IS ENABLED TO RUN.
ii. OFF - FUEL PUMP IS DISABLED AND WILL NOT BE ALLOWED TO RUN.
iii. AUTO - FUEL PUMP IS ENABLED AND DISABLED BASED ON FUEL LEVEL OF TANKS.
2) DAY TANK FILL VALVES ARE:
i. OPEN, OR
ii. CLOSED
3) DIESEL FUEL MAINTENANCE SYSTEM IS:
i. ENABLED, OR
ii. DISABLED
B. FUEL MANAGEMENT SYSTEM WILL MONITOR THE FUEL LEVEL AND LEAK DETECTION SENSOR OF DAY TANK. THE FUEL MANAGEMENT SYSTEM SHALL GENERATE AN AUDIBLE AND VISUAL ALARM IF LEAK DETECTION SENSOR IS ACTIVE, OR IF FUEL LEVEL IS ABOVE THE HIGH OR LOW LEVEL
SETTING.
3. SYSTEM FUNCTIONS:
A. THE LEAD FUEL OIL PUMP WILL BE ENABLED WHENEVER DAY TANK IS BELOW THE FILL LEVEL. THE STANDBY FUEL OIL PUMP WILL BE ENABLED IF DAY TANK IS BELOW THE LOW LEVEL. FUEL OIL PUMPS WILL REMAIN RUNNING UNTIL DAY TANK IS ABOVE THE FULL LEVEL.
B. DAY TANK FILL VALVES WILL BE OPEN WHEN THE RESPECTIVE FUEL TANK IS BELOW THE FILL LEVEL. FILL VALVES WILL BE CLOSED WHEN THE
RESPECTIVE FUEL TANK IS ABOVE THE FULL LEVEL.
C. FUEL RETURN PUMP WILL BE ENABLED WHEN THE DAY TANK IS FILLED ABOVE THE HIGH LEVEL. RETURN PUMP WILL BE DISABLED WHEN
FUEL LEVEL DROPS TO BELOW THE FULL LEVEL.
D. DIESEL FUEL MAINTENANCE SYSTEM SHALL OPERATE THROUGH INTERNAL CONTROL LOGIC TO CYCLE FUEL WITHIN THE MAIN STORAGE
TANK.
E. ALARMS:
1) HIGH LEVEL ALARM SHALL BE GENERATED IF DAY TANK FUEL LEVEL IS ABOVE THE HIGH LEVEL.
2) LOW LEVEL ALARM SHALL BE GENERATED IF DAY TANK FUEL LEVEL IS BELOW THE LOW LEVEL.
3) LEAK DETECTION ALARM SHALL BE GENERATED IF FUEL IS DETECTED WITHIN DAY TANK INTERSTITAL SPACE, INSIDE THE TRANSITION
SUMP, OR WITHIN THE FUEL MAINTENANCE SYSTEM.
4) EMERGENCY OVERFLOW ALARM SHALL BE GENERATED IF FUEL IS DETECTED WITHIN THE NORMAL VENT OF DAY TANK.
TRANSITION SUMP
LEAK
DETECTION
ALARM
FUEL OIL TANK
FUEL TANK
CONTENTS AND
LEAKAGE
MONITORING PANEL
FOS
LEAK
DETECTION
ALARM
DIESEL
GENERATOR
BACK-PRESSURE
VALVE
VENT
FOS
FOR
START/STOPSTART/STOP
INTERSTITIAL
ALARM
F O
R
F O
S
XXX SYSTEM DESCRIPTION
VALVE - CONTROL 2-WAY (MODULATING)
VALVE - SHUT-OFF, NORMALLY CLOSED
VALVE - SHUT-OFF, NORMALLY OPEN
DIRECTION OF FLOW
FOS FUEL OIL SUPPLY
FOR FUEL OIL RETURN
FUEL OIL PUMP
START/STOP
PUMP STARTER
FUEL LEVEL SENSOR
LEAK DETECTION SENSOR
FOR
DAY TANK
P3
START/
STOP
FOR FOS
START/STOP
TRANSITION SUMP
DISCRIMINATING LEAK SENSOR
TEST BOOT EACH END (TYP.)
DOUBLE WALL
FUEL PIPING
DIESEL SUPPLY
DS
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/3 2"
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
G ra p h ic S ca le
/2
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
NOT FOR
PERMITTING OR
CONSTRUCTION
A/E:Consultant:
Approved: Spinklered
Office of Construction and Facilities Management FULLY SPRINKLERED
B
IM
/V
IS
N
O m a h a
E H
R M
/O m a h a
E H
R M
V
.r v t
/2
/2
:3
:5
P
M
AW MPMMAY 15, 2023
M-105
636 - OMAHA VA MEDICAL CENTER
ISSUE FOR BIDMECHANICAL CONTROLS AND FLOW
DIAGRAMS
636-21-704OMAHA EHRM INFRASTRUCTURE
UPGRADE DESIGN
Revisions: Date:
NTS
GENERATOR FUEL OIL FLOW DIAGRAM
NTS
GENERATOR FUEL OIL SYSTEM CONTROLS
NTS
TRANSITION SUMP DETAIL
FEC
FEC
FEC
KEYNOTES
SUBSTATION
750KVA 13.8KV:480V
600KW GENERATOR
(DIESEL FUEL)
GENERATOR - FUTURE
3 4 5
G-EAL-2
G-IAL-2
G-IAL-3
G-EAL-1
6 6
G-EF-1
G-SF-1
G-EF-2
G-SF-2
G-SF-3
G-EF-3
G-UH-2
G-UH-3
G-UH-4
G-IAL-1
G-UH-5
RR-55
850 CFM
(TYP 2)
G-UH-1
FD
G-EAL-3
DAY TANK
3/4" FOS DN
3/4" FOS UP
3/4" FOS
3/4" FOS DN
3/4" FOR UP
3/4" FOR
/4
F
O S
/4
F
O R
3/4" FOS
3/4" FOS
/4
F
O S
FOP-1
FOP-2
BI - FAN STATUS
BO - FAN START/STOP
EA
M
CT
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/3 2"
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
G ra p h ic S ca le
/2
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
NOT FOR
PERMITTING OR
CONSTRUCTION
A/E:Consultant:
Approved: Spinklered
Office of Construction and Facilities Management FULLY SPRINKLERED
B
IM
/V
IS
N
O m a h a
E H
R M
/O m a h a
E H
R M
V
.r v t
/2
/2
:3
:5
P
M
AW RAWMAY 15, 2023
G-ME101
636 - OMAHA VA MEDICAL CENTER
ISSUE FOR BIDBLDG. G - LEVEL 01 MECHANICAL FLOOR PLAN
G
636-21-704OMAHA EHRM INFRASTRUCTURE
UPGRADE DESIGN
1/4" = 1'-0"
ENLARGED MECHANICAL PLAN - GENERATOR BUILDING
NO. DESCRIPTION
1 DOUBLE WALL ABOVE GRADE FUEL STORAGE TANK. 6,000 GALLONS MINIMUM PER
GENERATOR FOR 96 HOURS OF OPERATION. REFER TO SPECIFICATIONS FOR DETAILS.
INSTALL PER LOCAL CODES AND MANUFACTURER'S GUIDELINES.
2 GENERATOR COMBUSTION FLUE STACK THROUGH ROOF. SIZE PER MANUFACTURER'S
RECOMMENDATIONS. REFER TO DETAIL 4 ON SHEET M-102.
3 FUEL PUMP CONTROL PANEL.
4 FUEL LEAK DETECTION SYSTEM PANEL.
5 DDC POWER AND CONTROL PANELS.
6 INTERLOCK MOTORIZED DAMPER WITH GENERATOR AND EXHAUST FAN OPERATION.
7 ELECTRICAL EQUIPMENT SHOWN FOR REFERENCE.
8 FIBERGLASS TRANSITION SUMP WITH STEEL PLATE ACCESS COVER - BRAVO B-600 OR
APPROVED EQUAL
9 18x16 TRANSFER DUCT. PROVIDE WITH FIRE DAMPER AND MOTORIZED DAMPER.
10 BOTTOM OF LOUVER SHALL BE AT MINIMUM 18 INCHES ABOVE GRADE.
11 LOUVER TO BE MOUNTED ON GRADE TO ALLOW FOR REMOVAL OF GENERATOR.
12 DUCT TRANSITION FROM GENERATOR TO LOUVER.
13 NEW 200 GALLON DOUBLE WALL DAY TANK WITH OVERFILL PREVENTION VALVE AND
INTEGRAL RETURN FUEL PUMP WITH CONTROLS. DAY TANK INCLUDES 2 GPM BRONZE
GEAR PUMP WITH STAINLESS STEEL SHAFTS. (1/3 HP THERMALLY PROTECTED 120
VAC, 1 PH, 60 HZ MOTOR) MANUFACTURER: PRYCO. MODEL: PY200ULDW (OR
APPROVED EQUAL).
14 MOUNT AT 8' - 2" ABOVE FINISHED FLOOR.
15 DIESEL FUEL MAINTENANCE SYSTEM. PROVIDE WITH:
-STAND-ALONE CONTROL AND EMERGENCY STOP FOR FUEL MAINTENANCE SYSTEM.
CONTROLLER SHALL INCLUDE DRY CONTACTS TO MONITOR GENERAL ALARM AND
LEAK DETETCTION
-WATER SEPARATION UNIT WITH MANUAL DRAIN VALVE
-NEMA-4 ENCLOSURE
16 SILENCER TO BE PROVIDED WITH GENERATOR.
17 DUPLEX FUEL OIL PUMP
Revisions: Date:
NORTH
EXHAUST FAN AND SUPPLY FAN SEQUENCE OF OPERATIONS:
THE FANS SHALL BE INTERLOCKED TO RUN WHENEVER THE AREA'S TEMPERATURE IS ABOVE
85°F (ADJ.).
FANS:
THE FANS SHALL HAVE A USER DEFINABLE (ADJ.) MINIMUM RUNTIME.
THE FANS SHALL RUN AT ALL TIMES RUNS, UNLESS SHUTDOWN ON SAFETIES. THE FAN
SPEEDS SHALL BE INDEXED AS FOLLOWS:
• SPEED SHALL MODULATE TO MAINTAIN STATIC PRESSURE SETPOINT BY A USER
DEFINABLE AMOUNT (ADJ.) DETERMINED THROUGH TESTING AND BALANCING.
EXHAUST AIR STATIC PRESSURE CONTROL:
THE FAN SHALL OPERATE AT CONSTANT VOLUME TO MAINTAIN ROOM PRESSURIZATION, BY
BALANCING SET POINT FOR SYSTEMS WITHOUT ZONE PRESSURE MONITORS, AND/OR BY
SETPOINT OF ZONE PRESSURE MONITOR.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH EXHAUST AIR STATIC PRESSURE: IF THE EXHAUST AIR STATIC PRESSURE IS 25%
(ADJ.) GREATER THAN SETPOINT.
• LOW EXHAUST AIR STATIC PRESSURE: IF THE EXHAUST AIR STATIC PRESSURE IS 25%
(ADJ.) LESS THAN SETPOINT.
• SUPPLY FAN VFD FAULT.
FAN STATUS:
THE CONTROLLER SHALL MONITOR THE FAN STATUS.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
• FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
• FAN RUNTIME EXCEEDED: FAN STATUS RUNTIME EXCEEDS A USER DEFINABLE
LIMIT (ADJ.).
HIGH STATIC PRESSURE x
LOW STATIC PRESSURE x
FAN IN HAND x
FAN FAILURE x
FAN START/STOP x x x
FAN VFD FAULT x x x
FAN VFD SPEED x x x
FAN STATUS x x x
AIRFLOW x x x
AI AO BI BO AV BV LOOP SCHED TREND ALARM
POINT NAME
HARDWARE POINTS SOFTWARE POINTS SHOW ON
GRAPHIC
POINTS MATRIX - EF - VFD
12" = 1'-0"
SEQUENCE - GENERATOR EXHAUST FANS
GENERATOR AND LOUVER SEQUENCE OF OPERATIONS:
THE GENERATOR AND MOTORIZED DAMPER CONTROLING LOUVERS SHALL BE INTERLOCKED
TO RUN WHENEVER THE GENERATOR IS IN OPERATION. COORDINATE WITH MOTORIZED
DAMPER MANUFACTURER FOR PROPER CONNECTIONS, AIRFLOW BALANCING, AND
CONTROLS INTEGRATION.
| Sheets |
| M-102 - MECHANICAL DETAILS |
| M-103 - MECHANICAL SCHEDULES |
| M-105 - MECHANICAL CONTROLS AND FLOW DIAGRAMS |
| G-ME101 - BLDG. G - LEVEL 01 MECHANICAL FLOOR PLAN |
File details come from the government source that posted it. Updated .