Attachment 20 - Supplemental Drawings - MECH.pdf
PDF 1 MB Posted
- Attached to
- Y1AZ--36C77621B0013 - Construct Administration Bldg. POD 1A (Minor) - Gainesville Federal contract opportunity
- Solicitation number
- 36C77621B0013
About this file
This is a solicitation for a firm-fixed-price construction contract to build a new 26,000 square foot administration building at the Malcom Randall VA Medical Center in Gainesville, Florida. The project involves architectural, site, structural, fire protection, HVAC, plumbing, electrical, earthwork, exterior utilities, and other construction work required by the contract drawings and specifications. It also includes demolition of existing architectural, site, plumbing, fire protection, mechanical and electrical systems. The Department of Veterans Affairs intends to award a single contract for design-bid-build project delivery. The contracting activity is the VA Technology Acquisition Center located in Austin, Texas.
View the file
Other files for this federal contract opportunity
Show all 32
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT
BD
P
M
TS
SYMBOL DESCRIPTIONSYMBOL DESCRIPTIONSYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION
-SPIN-IN TAKE-OFF
-DUCT ELBOW UP THROUGH ROOF OR SLAB ABOVE
-RECTANGLE-TO-ROUND TAKE-OFF
-TRANSITION, SQUARE TO ROUND
UP W/IN FLOORDOWN
-CEILING EXHAUST
-CEILING RETURN
-STANDARD BRANCH TAKE-OFF
-RADIUS ELBOW
-TRANSITION, ECCENTRIC
-FLEXIBLE DUCT
-DUCT ELBOW, NEGATIVE PRESSURE, RETURN
-DUCT ELBOW, EXHAUST
DIMENSION INDICATES SIDE TO WHICH ARROW IS POINTING
-DUCT ELBOW, POSITIVE PRESSURE (SUPPLY), FIRST
-NEW DUCTWORK, FIRST DIMENSION IS SIDE SHOWN
-TRANSITION, CONCENTRIC
-SQUARE THROAT ELBOW
W/TURNING VANES
-RECTANGULAR/ROUND BRANCH TAKE-OFF
OR ROUND/ROUND BRANCH TAKE-OFF
-SQUARE THROAT TEE
-RADIUS TEE
-ROUND DIFFUSER
-SUPPLY REGISTER OR GRILLE
-RETURN/EXHAUST REGISTER OR GRILLE
(VERTICAL MOUNT, SIDEWALL)
(VERTICAL MOUNT, SIDEWALL)
(CEILING DIFFUSERS ARE 4-WAY THROW UNO)
-CEILING DIFFUSER, ROUND NECK
-CEILING DIFFUSER, RECTANGULAR OR
SQUARE NECK (CEILING DIFFUSERS
ARE 4-WAY THROW UNO)
M-1
-TEMPERATURE SENSOR
-MOTORIZED CONTROL DAMPER
-HUMIDISTAT/HUMIDITY SENSOR
-THERMOSTAT/TEMPERATURE SENSOR
-REVISION REFERENCE
-DETAIL REFERENCE: TOP-DETAIL#,
BOTTOM-DRAWING# SHOWN ON
-PRESSURE SENSOR
-DUCT SMOKE DETECTOR
-CONNECT TO EXISTING
-DEMOLISH TO POINT INDICATED
FF -FINAL FILTERS
DDC -DIRECT DIGITAL CONTROLS
PRS -PRESSURE REDUCING STATION
SP -STATIC PRESSURE
-CFM (CUBIC FEET PER MINUTE)
P -CHANGE IN PRESSURE
CV -CONSTANT AIR VOLUME
-ROOFTOP AIR HANDLING UNITRTU
RS/L -REFRIGERANT SUCTION & LIQUID LINES
CL
-OUTSIDE AIR LOUVEROAL
-VARIABLE AIR VOLUMEVAV
-SUPPLY AIRSA
-ROOFTOP HEAT PUMPRHP
-REHEAT COILRHC
-REVOLUTIONS PER MINUTERPM
-RETURN AIRRA
-POLYVINYL CHLORIDE PIPEPVC
-PSI GAUGEPSIG
-POUNDS PER SQUARE INCHPSI
-PRESSURE REDUCING VALVEPRV
-OUTSIDE AIROA
-NOT TO SCALENTS
-NORMALLY OPENNO
-NORMALLY CLOSEDNC
-LINEAR DIFFUSERLD
-LEAVING WATER TEMPERATURELWT
-LEAVING AIR TEMPERATURELAT
-GALLONS PER MINUTEGPM
-FEET PER MINUTE
-FIRE DAMPER
-FAN COIL UNIT
-ENTERING WATER TEMPERATURE
-ENTERING AIR TEMPERATURE
-DOWN
-CONDENSING UNIT
-CUBIC FEET PER MINUTE
-CHANGE IN TEMPERATURE
-COOLING TOWER
-CEILING DIFFUSER
-CENTER LINE
-BRITISH THERMAL UNIT
-BRAKE HORSEPOWER
-BOTTOM OF PIPE
-ACCESS PANEL
-ABOVE FINISHED FLOOR
FPM
FD
FCU
EWT
EAT
DN
CU
CFM
T
CT
CD
BTU
BOP
BHP
AP
AFF
-AIR HANDLING UNITAHU
MBH -THOUSAND BTUs PER HOUR
AFD -ADJUSTABLE FREQUENCY DRIVE
ESP -EXTERNAL STATIC PRESSURE
KW -KILOWATT
MCA -MINIMUM CIRCUIT AMPS
MOCP -MAXIMUM OVER CURRENT PROTECTION
UNO
TSP -TOTAL STATIC PRESSURE
-VOLTS/PHASEV/PH
VFD -VARIABLE FREQUENCY DRIVE
-UNLESS NOTED OTHERWISE
FLA -FULL LOAD AMPS
-CONDENSATE
-REFRIGERANT LIQUID
-REFRIGERANT SUCTION
-CAP
-CONNECTION, BOTTOM
-CONNECTION, TOP
-COUPLING
-ELBOW, 90°
-ELBOW, 45°
-ELBOW, TURNED DOWN
-ELBOW, TURNED UP
-TEE, OUTLET DOWN
-TEE, OUTLET UP
RL
RS
-NEGATIVE RELATIVE PRESSURE
-POSITIVE RELATIVE PRESSURE
-NEUTRAL RELATIVE PRESSURE
-BACKDRAFT DAMPER
MOD -MOTOR OPERATED CONTROL DAMPER (MOD)
-PACKAGED TERMINAL AIR CONDITIONERPTAC
-SHEET NOTE CALLOUT
-SHEET NOTE CALLOUT
-SHEET NOTE CALLOUT
-EXHAUST DUCT UP THROUGH SLAB W/
-EXHAUST FAN ON ROOF W/ DUCT DOWN
THROUGH ROOF
-CEILING MOUNTED ACCESS DOOR
-RECTANGULAR DUCT SECTION UP, EXHAUST
-RECTANGULAR DUCT SECTION UP,
-RECTANGULAR DUCT SECTION UP, POSITIVE PRESSURE,
-ROUND DUCT SECTION UP
SUPPLY OR OUTSIDE AIR
NEGATIVE PRESSURE, RETURN
FAN ON ROOF ABOVE
-ABOVE FINISHED ROOFAFR
HVAC GENERAL NOTESHVAC ABBREVIATIONSHVAC SYMBOL LEGEND HVAC PIPING SYMBOL LEGEND
8Ø10x8
24x12
12x8
CD
H
1. CONNECTION TO EQUIPMENT SHALL BE VERIFIED WITH MANUFACTURER'S CERTIFIED
DRAWINGS. TRANSITIONS TO ALL EQUIPMENT SHALL BE VERIFIED AND PROVIDED
FOR EQUIPMENT FURNISHED.
2. DIMENSIONS SHALL BE FIELD-VERIFIED AND COORDINATED PRIOR TO PROCUREMENT OR
FABRICATION. COORDINATE THE WORK WITH OTHER TRADES INVOLVED. FIELD MODIFICATIONS
SUCH AS OFFSETS IN PIPING OR DUCTWORK (INCLUDING DIVIDED DUCTWORK) NEEDED DUE TO
OBSTRUCTIONS OR INTERFERENCES SHALL BE PROVIDED AT NO ADDITIONAL COST. FOR PROJECTS
INVOLVING RENOVATION, COORDINATE NEW WORK WITH EXISTING ELEMENTS SUCH AS THE
BUILDING STRUCTURE AND ARCHITECTURAL FEATURES, SPRINKLER PIPING, LIGHTS, PLUMBING, AND
ELECTRICAL CONDUIT.
3. DUCT CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE
SMACNA HVAC DUCT CONSTRUCTION STANDARD.
4. SEE SPECIFICATIONS FOR GAUGES, THICKNESS, BRACING, REQUIREMENTS, ETC., OF DUCTWORK.
5. PROVIDE AIR TURNING VANES IN ALL 90 DEGREE RECTANGULAR DUCT ELBOWS.
6. DUCT SIZES AND ALL OPENINGS THROUGH BUILDING CONSTRUCTION SHALL SUIT EQUIPMENT
FURNISHED.
7. COORDINATE DIFFUSER, GRILLE AND REGISTER LOCATIONS WITH ARCHITECTURAL
REFLECTED CEILING PLANS AND EQUIPMENT OF ALL TRADES.
8. LOCATE THERMOSTATS, TEMPERATURE SENSORS, HUMIDISTATS, AND HUMIDITY SENSORS AT 48"
ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE. COORDINATE LOCATIONS WITH OTHER
EQUIPMENT, FURNITURE, AND DOOR SWINGS.
9. ALL EQUIPMENT, DUCTWORK, ETC., SHALL BE SUPPORTED AS DETAILED AND/OR SPECIFIED. PROVIDE
ADDITIONAL SUPPORTS AS REQUIRED TO PROVIDE A VIBRATION-FREE, RIGID INSTALLATION.
10. ALL DUCT SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS.
11. DAMPERS AND INSIDES OF DUCTS VISIBLE THROUGH GRILLES, REGISTERS AND DIFFUSERS SHALL BE
PAINTED FLAT BLACK.
12. REFER TO TYPICAL DETAILS FOR PIPING AND INSTALLATION OF EQUIPMENT.
13. TRAPPED CONDENSATE DRAINS FROM ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED FOR
PROPER DRAINAGE TO SUIT EQUIPMENT FURNISHED.
14. ACCESS PANELS IN DUCTWORK AND CEILINGS SHALL BE PROVIDED WHERE REQUIRED FOR
OPERATION, BALANCING OR MAINTENANCE OF ALL MECHANICAL EQUIPMENT.
15. ALL DUCTWORK AND PIPING IS SHOWN SCHEMATICALLY. PROVIDE ALL TRANSITIONS, TURNING VANES, ELBOWS, FITTINGS, ETC., TO ALLOW SMOOTH FLOWS. ALL SPLIT DUCT FITTINGS SHALL
TRANSITION TO FULL SIZE OF THE SUM OF BOTH BRANCHES, UPSTREAM OF SPLIT.
16. PROVIDE CONCRETE HOUSEKEEPING PAD UNDER ALL FLOOR-MOUNTED EQUIPMENT. REFER TO
SPECIFICATIONS FOR DETAILED REQUIREMENTS.
17. VERIFY FINISH WITH ARCHITECT PRIOR TO PURCHASING GRILLES, REGISTERS, DIFFUSERS, LOUVERS
AND OTHER AIR DISTRIBUTION DEVICES.
18. PROVIDE FLEXIBLE DUCT CONNECTIONS ON ALL DUCTWORK CONNECTING TO EACH FAN, AIR
HANDLING UNITS, AND FAN COIL UNITS.
19. PROVIDE TRANSITIONS AT DIFFUSER NECKS AS REQUIRED TO MATCH SIZES OF FLEX DUCTS TO BE
CONNECTED.
20. INTERRUPTIONS TO EXISTING SERVICES SHALL BE SCHEDULED FOR TIMES OTHER THAN NORMAL OPERATING HOURS (SUCH AS NIGHTS AND WEEKENDS). SUCH INTERRUPTIONS TO SERVICES SHALL
NOT BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER'S REPRESENTATIVE AND
PROPER COORDINATION WITH OTHER TRADES. PRE-WORK SHALL BE PERFORMED TO MAKE THE
SHUTDOWN PERIOD AS BRIEF AS POSSIBLE.
21. ALL EQUIPMENT, DUCTWORK, ETC., TO BE REMOVED SHALL REMAIN PROPERTY OF THE OWNER OR
DISPOSED OF LEGALLY, AS DIRECTED BY OWNER.
22. MAINTAIN CLEARANCE OF A MINIMUM OF 6" BETWEEN DUCTWORK, PIPING, EQUIPMENT, ETC., AND ALL FIRE RATED AND FIRE/SMOKE RATED PARTITIONS, TO ALLOW FOR INSPECTIONS OF RATED WALLS.
23. LOCATE ALL OUTSIDE AIR INTAKES A MINIMUM OF 10' CLEAR FROM ALL PLUMBING VENTS AND
EXHAUST AIR DISCHARGE LOCATIONS.
24. DUCT RUNOUTS TO DIFFUSERS SHALL MATCH THE SIZE OF THE DIFFUSER NECK.
25. WATER PRESSURE DROPS THROUGH COIL CONTROL VALVES SHALL NOT EXCEED 5 PSI.
26. UNLESS OTHERWISE NOTED, ALL EQUIPMENT AND VALVE DRAINS SHALL BE INDEPENDENTLY PIPED
FULL SIZE TO THE NEAREST PLUMBING DRAIN.
27. SLEEVE AND SEAL ALL PIPING PENETRATIONS THROUGH BUILDING PARTITIONS. PROVIDE MANUAL AIR
VENTS AT ALL HIGH POINTS IN CHILLED WATER AND HOT WATER PIPING.
28. PIPING, DUCTWORK, LEAK PROTECTION APPARATUS, OR OTHER EQUIPMENT FOREIGN TO ELECTRICAL SWITCHBOARDS, PANELBOARDS, DISTRIBUTION BOARDS, OR MOTOR CONTROL CENTERS SHALL NOT BE INSTALLED WITHIN THE REQUIRED SPACE FOR WORKING CLEARANCES OR DEDICATED SPACES OF THE ELECTRICAL EQUIPMENT, EXTENDING IN FRONT OF AND FROM FLOOR TO STRUCTURAL CEILING WITH A WIDTH AND DEPTH OF THE ELECTRICAL EQUIPMENT IN ACCORDANCE WITH NEC-110.26.
29. PROVIDE REMOTE DAMPER OPERATORS FOR AIR TERMINALS ABOVE HARD CEILINGS.
30. PROVIDE ISOLATION VALVES AT ALL EQUIPMENT CONDENSATE DRAIN CONNECTIONS.
T
CFM
HVAC CONTROLS NOTES
PROVIDE DIRECT DIGITAL CONTROL SYSTEM INCLUDING ALL ENGINEERING, PROGRAMMING, CONTROLS AND INSTALLATION MATERIALS, INSTALLATION LABOR, COMMISSIONING AND START UP, TRAINING, FINAL
PROJECT DOCUMENTATION AND WARRANTY.
THE DDC SYSTEM SHALL BE NATIVE BACNET, ALL COMPONENTS SHALL BE ACCESSIBLE USING A WEB
BROWSER INTERFACE AND SHALL COMMUNICATE EXCLUSIVEY USING ASHARE 135 BACNET
COMMUNICATIONS PROTOCOL.
CONTROL ALL PIECES OF EQUIPMENT INSTALLED UNDER THIS CONTRACT.
PROVIDE CONNECTION TO THE FACILITY’S EXISTING BUILDING AUTOMATION SYSTEM (BAS) DIRECT- DIGITAL CONTROL SYSTEM IS MANUFACTURED BY SIEMENS, AND THE MAIN INTERFACE ENGINEERING CONTROL CENTER (ECC) IS THE NEW BOILER PLANT WITH ADDITIONAL WORKSTATIONS IN THE HVAC SHOP AND THE 6TH FLOOR MECHANICAL SPACE IN THE BED TOWER. ANY DIRECT DIGITAL CONTROLS
(CONFORMING WITH BACNET AUTOMATION PROTOCOL STANDARDS) INSTALLED AS PART OF THIS
PROJECT MUST SEAMLESSLY INTEGRATE WITH THE EXISTING SIEMENS DESIGO BAS. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR RETAINING THE SYSTEMS INTEGRATOR AND COORDINATING THE CONTROL POINTS AND SEQUENCE OF OPERATIONS WITH THE SYSTEMS INTEGRATOR. THE FACILITY’S SYSTEMS INTEGRATOR IS SIEMENS CONTROLS; THEY ARE RESPONSIBLE FOR, AND ARE TO BE RETAINED BY THE GENERAL CONTRACTOR, FOR GENERATING REQUIRED SYSTEM GRAPHICS, DEVELOPING POINTS, TRENDS, ALARMS, ETC. THE GENERAL CONTRACTOR SHALL REVIEW THE CAPABILITIES, COMMUNICATION NETWORK, SERVICES, SPARE CAPACITY OF THE EXISTING CONTROL SYSTEM AND ITS ECC PRIOR TO
BEGINNING THIS PROJECT.
SEE SPECIFICATION SECTION 230923, DIRECT DIGITAL CONTROLS SYSTEM FOR HVAC FOR ADDITIONAL
INFORMATION.
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
7370 Cabot Court, Ste. 103 Melbourne, FL 32940
COA #15 TLC NO:
Phone: 321-636-0274
Fax: 321-639-8986 www.tlc-engineers.com
Copyright 2021 TLC Engineering Solutions, Inc.c
P.O. Box 1296, Winter Park, FL 32790 Tel 407.467.8833 - Fax 407.926.0701 o n e e ig h t h i n c h o n e f o o t 16
B
A
C
D
E
F t h r e e i n c h e s o n e f o o t o n e a n d o n e h a l f i n c h e s o n e f o o t o n e i n c h o n e f o o t t h r e e q u a r t e r s i n c h o n e f o o t o n e h a l f i n c h o n e f o o t t h r e e e ig h t h s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t
VA FORM 08−6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
1 2 3 4 5 6 87 9
MALCOM RANDAL VA HOSPITAL
ADMINISTRATION BUILDING
VAWPBMC PLANNING AND ENGINEERING
IF THIS DRAWING IS LESS THAN 30" X
42" IT IS A REDUCED SIZE DRAWING
CONSTRUCTION DOCUMENTS
FLGAINESVILLE
BLDG #
573-360
AWEBKG
MECHANICAL SYMBOLS,
LEGEND, NOTES & INDEX
518056 06/18/2021
JAMES T. WAMSLEY, P.E.
Florida License #50343
06/18/2021
M001
HVAC DRAWING INDEX
SHEET DESCRIPTION
M001 MECHANICAL SYMBOLS, LEGEND, NOTES & INDEX
M100 MECHANICAL FLOOR PLANS
M501 MECHANICAL DETAILS
M502 MECHANICAL DETAILS
M503 MECHANICAL DETAILS
M504 MECHANICAL DETAILS
M601 MECHANICAL SCHEDULES
MZ101 ALTERNATE 1 - BRIDGE MECHANICAL PLAN
# Revisions: Date:
1 ADDENDUM 1 10/19/21
UP
UP
UP
UP
A B C D E
6' - 0" 4 7/8"
LOBBY
1-100
OFFICE
1-101
MECHANICAL
1-102
CORRIDOR
1-103
WOMEN
1-104
MEN
1-105
HAC ROOM
1-106
PUMP ROOM
1-107
STAIR B
1-108
BREAK ROOM
1-110
WOMEN
1-112
MEN
1-113
TELE/COM
1-115
VESTIBULE
1-114
STAIR A
1-118
BUILDING 12 ENTRANCE
RECEIVING
1-117
CORRIDOR
1-116
LOADING DOCK
ELECTRICAL ROOM
1-109
3' - 0"
/2
/2
0.9
FCU-1-4
FCU-1-4
FCU-1-4
FCU-1-4
FCU-1-4
FCU-1-4
FCU-1-4 FCU-1-4
FCU-1-4FCU-1-4
FCU-1-3
FCU-1-1
FCU-1-2
A 75 A 75
A 175
A 75
B 550
A 250 A 250 A 250
A 250
B 250 B 250 B 250
B 250
A 200 A 200 A 200 A 200
B 200 B 200 B 200 B 200
UH-1
UH-2
T
T
EF-152
B 75 B 75
EF-151
B 210 B 210
12x128x12 12x12
10x106x8 10x10
W 420
12x12
12x12
12x14 12x14
12x12 12x12
12x14 12x14
T
T
T
T
T
T
T
H
ERV-1
FCU-1-4
FCU-1-4
A 520
A 520
A 520
A 520
A 520
A 450
22x20 x x x x x
10x10 x
FCU-1-4
FCU-1-4
FCU-1-4
FCU-1-4
FCU-1-4
A 75
T
AHU-57
T x
B 555
B 555
B 555
B 555
1 1/4" CND
1 1/4" CND
1 1/4" CND
1 1/4" CND 1 1/4" CND
1 1/4" CND 1 1/4" CND
1/
4" C
N D
1/
4" C
N D
1/
2" C
N D
1/
2" C
N D
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
1 1/2" CND
1 1/2" CND
1 1/4" CND
1 1/4" CND
AHU-57
CCU-3
CCU-4
CCU-6
CCU-5
B 150
T A 50
CRAC-1
ACC-1
ACC-2
1 1/4" CND
A 200
B 200
FCU-1-3
B 185 B 185
B 185 B 185 A 185A 185A 185A 185
FCU-1-4
12x12
12x12
1 1/4" CND
FCU-2-4
FCU-2-4
20x16
20x16
CCU-6-A
MCU-1
MCU-2
MCU-3
MCU-4
A B C D E
MEETING ROOM
2-100
OFFICE
2-101
STAIR B
2-108
WOMEN
2-104 ELEC ROOM
2-107
OIT IT
2-115
WOMEN
2-112 MEN
2-113
VESTIBULE
2-114
CORRIDOR
2-116
STAIR A
2-118
MEN
2-105
BREAK/COPY
2-117
TRAINING
2-110
0.9
FCU-2-2
FCU-2-4
FCU-2-1
FCU-2-5
12x12
12x14
12x12 x
12x1212x12
12x14 12x14
46x14
46x16
B 570
12x14
12x12
A 230 A 230
A 230
A 230
B 230 B 230 B 230 B 230
B 185
A 185
A 185
A 185 B 185 B 185
A 185
B 185
A 75
A 75 A 75
46x14
46x16
EF-154
B 75 B 75
EF-153
B 210 B 210
12x128x12 12x12
10x106x8 10x10
FCU-2-3
FCU-2-3
FCU-2-3 FCU-2-3
FCU-2-3FCU-2-3
FCU-2-3 FCU-2-3
FCU-2-3FCU-2-3
FCU-2-3
FCU-2-3
FCU-2-3
FCU-2-3
FCU-2-3
FCU-2-3
FCU-2-3 FCU-2-3
A 520
A 520
A 520
A 520
A 520
A 450
22x20 x x x x x
A 75
A 75
A 195
HT
AHU-58
T
T
T
T
T
T
B 580
B 580
B 580
B 580
T
T
T
T
T T
T
T
T
T
T
T
T
T
T
T
T
1 1/4" CND 1 1/4" CND
1 1/2" CND
1 1/2" CND
1 1/2" CND
1 1/2" CND
1/
2" C
N D
1 1/4" CND1 1/4" CND
1 1/4" CND
1 1/4" CND
1/
2" C
N D
1 1/4" CND 1 1/4" CND
1/
4" C
N D
1 1/4" CND 1 1/4" CND
1/
4" C
N D
1 1/4" CND
AHU-58
ERV-2
x
FCU-2-3
T
T
FCU-2-3
B 120
A 50
CRAC-2
1 1/4" CND
B 185
A 185
FCU-2-5
B 145 B 145
B 145 B 145 A 145A 145A 145A 145
12x12
12x12
B 30
20x16
20x16
MCU-5
MCU-6
MCU-7
MCU-8
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
7370 Cabot Court, Ste. 103 Melbourne, FL 32940
COA #15 TLC NO:
Phone: 321-636-0274
Fax: 321-639-8986 www.tlc-engineers.com
Copyright 2021 TLC Engineering Solutions, Inc.c
P.O. Box 1296, Winter Park, FL 32790 Tel 407.467.8833 - Fax 407.926.0701 o n e e ig h t h i n c h o n e f o o t 16
B
A
C
D
E
F t h r e e i n c h e s o n e f o o t o n e a n d o n e h a l f i n c h e s o n e f o o t o n e i n c h o n e f o o t t h r e e q u a r t e r s i n c h o n e f o o t o n e h a l f i n c h o n e f o o t t h r e e e ig h t h s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t
VA FORM 08−6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
1 2 3 4 5 6 87 9
MALCOM RANDAL VA HOSPITAL
ADMINISTRATION BUILDING
VAWPBMC PLANNING AND ENGINEERING
IF THIS DRAWING IS LESS THAN 30" X
42" IT IS A REDUCED SIZE DRAWING
CONSTRUCTION DOCUMENTS
FLGAINESVILLE
BLDG #
573-360
AWEBKG
MECHANICAL FLOOR PLANS
518056 06/18/2021
JAMES T. WAMSLEY, P.E.
Florida License #50343
06/18/2021
M100
1/8" = 1'-0"
FIRST FLOOR PLAN - MECHANICAL
1/8" = 1'-0"
SECOND FLOOR PLAN - MECHANICAL
KEYED NOTES:
DOWN TO HUB DRAIN. SEE PLUMBING DRAWINGS.
TIE OUTSIDE AIR DUCT INTO ARCHITECTURAL LOUVER WITH FIELD-BUILT PLENUM.
CEILING MOUNTED THERMOSTAT.
REFRIGERANT VALVE BOX LOCATED ABOVE CEILING. CONTRACTOR SHALL FIELD VERIFY AND COORDINATE ALL FINAL LOCATIONS AND CONFIGURATIONS PRIOR TO SUBMITTING SHOP DRAWINGS. COORDINATE WITH
ELECTRICIAN UNITS CURRENTLY CIRCUITED AT 120 VOLT SINGLE PHASE.
# Revisions: Date:
m m 1"
M A
X
SIDE VIEW TRAPEZE HANGER FOR UP TO
453KG [1000 LB.] UNIFORM LOAD
ADJUSTABLE CLEVIS HANGER TYPE 1 -
SEE SPECIFICATIONS
ADJUSTABLE CLEVIS HANGER TYPE 43 -
SEE SPECIFICATIONS
MAXIMUM PIPE/TUBING SUPPORT SPACING
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
NOM. SIZE
PIPE
TUBING
mm [IN] mm
[FT]
mm
[FT]
THRU 20
[THRU 3/4]
[7]
[5]
[1]
[7]
[6]
[1 1/4]1
[7]
[7]
[1 1/2]1
[9]
[8]
[2]
[10]
[8]
[2 1/2]
[11]
[9]
[3]
[12]
[10]
[4]
[14]
[12]
[5]
[16]
[13]
[6]
[17]
[14]
[8]
[19]
[16]
[10]
[22]
[12]
[23]
[14]
[25]
[16]
[27]
[18]
[28]
[20]
[30]
[24]
[32]
PROVIDE INSULATION
SHIELD
& INSERT FOR ALL PIPING
(200mm [8"] MIN.)
BAND
43mm [1-5/8"] 12 GAUGE CHANNEL OR 50x50x6.4mm
[2"X2"X1/4"] ANGLE
15mm [1/2"] DIA.
HANGER RODS
WITH
900mm [36"] MAX.
SPACING ON EACH
CHANNEL
WELD
SADDLE
INSULATION
SHIELD
AT HANGER
PROVIDE HIGH COMPRESSIVE
STRENGTH INSULATION (9 PSF
MIN. DENSITY) UNDER INSULATION
SHIELD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE
PIPE)
HANGER ROD
NOTE:
SEE SPECIFER FOR DETAILED HANGER REQUIREMENTS
SILL DETAIL
HEAD & JAMB DETAIL
NOTE: LOUVER SHALL BE MIAMI-DADE COUNTY APPROVED.
BASIS OF DESIGN: RUSKIN ELF6375DXD, MIAMI-DADE
COUNTY, FLORIDA NOTICE OF ACCEPTANCE NUMBER:
01-0328.04 (EXP. 7/9/06)
CONCRETE WALL
SEALANT ALL AROUND
5/8"x6" (16x152) HILTI
KBII
#00045372 THRU JAMB
FRAMES, 18" (457) O/C
12" (305) FROM ENDS.
LOUVER REF W/
SCREEN ON
REAR
HIDDEN VERTICAL
BLADE
SUPPORT (HVBS)
DEPTH
MAY VARY.
2"x2"x4"x1/4" (51x51x102x6)
STL. CLIP ANGLE W/2 #
12x1"
(25) TEKS INTO LOUVER
FRAME.
3"x3"x3/16" (76x76x5) x CONT
STEEL
ANGLE W/ 1/4"-20 (6) x 1" (25)
HHB
@ 18" (457) O/C & 6" (152) FROM
ENDS. (2"x2"x 1/4" x CONT. STEEL
ANGLE @ JAMBS & SILL ONLY)
1/2" X 2-3/4" (13 x 70) HILTI
KBII
#00045366 18" (457) O/C & 6"
(152) FROM ENDS
#ELF6375DXD LOUVER
W/ SCREEN ON REAR
5/8" X 6" (16 X 152)
HILTI
KBII #00045372 THRU
JAMB FRAMES, 18"
(457) O/C & 12" (305)
FROM ENDS.
SEALANT ALL AROUND
EXTENDED SILL
FLASHING
CONCRETE WALL 1/2"x2-3/4" (13x70)
HILTI
KBII #00045366 18"
(457) O/C & 12"
(305) FROM ENDS
2"x2"x1/4" (51x51x6) x CONT STEEL ANGLE W/ 1/4"-20x1" (25)
HHB @ 18" (457) O/C & 6" (152)
FROM ENDS.
2"x2"x4"x1/4" (51x51x102x6) STL CLIP ANGLE W/2 #12x1"
(25)TEKS INTO LOUVER
FRAME.
HIDDEN VERTICAL
BLADE
SUPPORT (HVBS) DEPTH
MAY VARY.
NOTE: FOR USE IN NON-ACCESSIBLE CEILINGS
DAMPER INSTALLED
UP
TO 30' FROM
CONTROL
BOTTOM TO BE PLACED AT
CEILING LEVEL WITH
PLATED
COVER ON CEILING
SOCKET WRENCH USED TO
ENLARGE OPERATOR
SHAFT
FOR DAMPER ADJUSTMENT
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
7370 Cabot Court, Ste. 103 Melbourne, FL 32940
COA #15 TLC NO:
Phone: 321-636-0274
Fax: 321-639-8986 www.tlc-engineers.com
Copyright 2021 TLC Engineering Solutions, Inc.c
P.O. Box 1296, Winter Park, FL 32790 Tel 407.467.8833 - Fax 407.926.0701 o n e e ig h t h i n c h o n e f o o t 16
B
A
C
D
E
F t h r e e i n c h e s o n e f o o t o n e a n d o n e h a l f i n c h e s o n e f o o t o n e i n c h o n e f o o t t h r e e q u a r t e r s i n c h o n e f o o t o n e h a l f i n c h o n e f o o t t h r e e e ig h t h s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t
VA FORM 08−6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
1 2 3 4 5 6 87 9
MALCOM RANDAL VA HOSPITAL
ADMINISTRATION BUILDING
VAWPBMC PLANNING AND ENGINEERING
IF THIS DRAWING IS LESS THAN 30" X
42" IT IS A REDUCED SIZE DRAWING
CONSTRUCTION DOCUMENTS
FLGAINESVILLE
BLDG #
573-360
AWEBKG
MECHANICAL DETAILS
518056 06/18/2021
JAMES T. WAMSLEY, P.E.
Florida License #50343
06/18/2021
M501
N.T.S.
PIPE HANGERS
N.T.S.
LOUVER - HURRICANE / IMPACT RESISTANT
N.T.S.
CABLE CONTROL VOLUME DAMPER
# Revisions: Date:
DRAW THRU
BLOW THRU
2" [50mm] PLUS X
1" [25mm] MINIMUM
X
2X
UNIT TYPE A B
WHERE X = STATIC PRESSURE IN PAN
DRAIN LINE SHALL BE AT LEAST THE
SAME SIZE AS THE NIPPLE ON THE DRAIN
PAN
PIPING SHALL BE RIGID COPPER TYPE L
OR TYPE M UNLESS NOTE BELOW IS MET
PITCH DOWN
TOWARD DRAIN
CLEAN OUT
FLOOR SINK
DRAIN
PAN
NOTE: 1. CPVC PIPE MAY BE USED ONLY IF APPROVED BY
LOCAL VA AND IS INDOORS AND DOES NOT PASS THROUGH
RATED BARRIERS.
2. DIELECTRIC FITTING TO BE USED WHEN TWO DISSIMILAR
METALS ARE TO BE CONNECTED.
[2 5m m
DIELECTRIC
FITTING
A B
1"
A
A
BB
SECTION A-A (BASE NOT POURED WITH SLAB)
SECTION A-A (BASE POURED WITH FLOOR
SLAB)
PLAN
TYPICAL ANCHOR
BOLT NUT &
WASHER
SECTION B-B
EQUIPMENT BASE PLATE
PROVIDE #3 BARS 12"
[300mm] O.C. EACH WAY IN
THE BASE & DOWEL BASE TO
FLOOR
EQUIPMENT BASE PLATE
PROVIDE DOUBLE SLAB
REINFORCING IN BASE AREA
WELD HEAD TO PLATE
OR BEND OVER END 5D
FLOOR
PIPE SLEEVE (5D, 3"
[75mm] MIN.)
ANCHOR
BOLT (TYP)
CONCRETE BASE
NOTE:
L & W DIMENSIONS
SHALL BE 6" [150mm]
GREATER THAN THE
EQUIPMENT BASE PLATE.
[400mm]
5" M
IN
[1 m m
5"
M
IN
[1 m m
TYPICAL ANCHOR
BOLT NUT &
WASHER
[2 5m m
L/
L/
5D
1"
16"
2D
L
W
D
5D
NOTE:
1.
2.
3.
4.
ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY
SMACNA.
WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE
TYPE REGARDLESS OF W DIMENSION.
ALL SINGLE THICKNESS VANES SHALL HAVE A 2" [50mm] RADIUS, 1 1/2"
[40mm] MAXIMUM SPACE BETWEEN VANES AND A 3/4" [20mm] TRAILING EDGE.
WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500mm] VANES SHALL
BE DOUBLE VANE TYPE.
W
W1
NOTE:
UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOWN SHALL APPLY.
MAX.
M A
X
E Q
U
IP
M E
N T
AIR
FLOW
AIR
FLOW
TYPICAL DUCTWORK TRANSITION
PLAN OR SIDE VIEWTYPICAL DUCTWORK TRANSITION WITH
EQUIPMENT MOUNTED IN DUCT
PLAN OR SIDE VIEW
MAX.
M A
X.
M A
X
M A
X
30°
15°
MAIN EXHAUST OR RETURN
PLAN VIEW
AIR
FLOW AIR
FLOW
PROVIDE VOLUME
DAMPER
AT EACH BRANCH DUCT
1/4W OR 4"
[100mm] MIN.
BRANCH
DUCT
VD
W
FROM STRUCTURE
SAME AS DIFFUSER
INLET: 5'-0" MAX
FLEXIBLE DUCT SIZE
LENGTH.
12"
CEILING
SUPPORT SADDLE
VOLUME DAMPER W/
LOCKING QUADSADDLE
SHEET METAL
CONICAL OUTLET
BRANCH DUCT
FOR CHANGE OF
DIRECTION GREATER
USE RIGID ELBOWS
THAN 45°
[300mm]
SEE SPECIFICATIONS FOR
CLAMPS AND SEALANT (TYP.)
NOTE:
THE USE OF FLEXIBLE AIR DUCT CONNECTORS ARE NOT
PERMITTED FOR THE DEDICATED AHU SERVING THE SURGICAL SUITE.
TYPICAL
DIFFUSER OR
REGISTER IN
LAY-IN CLG.
THERMAL INSULATION
SEE SPECIFICATIONS
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
7370 Cabot Court, Ste. 103 Melbourne, FL 32940
COA #15 TLC NO:
Phone: 321-636-0274
Fax: 321-639-8986 www.tlc-engineers.com
Copyright 2021 TLC Engineering Solutions, Inc.c
P.O. Box 1296, Winter Park, FL 32790 Tel 407.467.8833 - Fax 407.926.0701 o n e e ig h t h i n c h o n e f o o t 16
B
A
C
D
E
F t h r e e i n c h e s o n e f o o t o n e a n d o n e h a l f i n c h e s o n e f o o t o n e i n c h o n e f o o t t h r e e q u a r t e r s i n c h o n e f o o t o n e h a l f i n c h o n e f o o t t h r e e e ig h t h s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t
VA FORM 08−6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
1 2 3 4 5 6 87 9
MALCOM RANDAL VA HOSPITAL
ADMINISTRATION BUILDING
VAWPBMC PLANNING AND ENGINEERING
IF THIS DRAWING IS LESS THAN 30" X
42" IT IS A REDUCED SIZE DRAWING
CONSTRUCTION DOCUMENTS
FLGAINESVILLE
BLDG #
573-360
AWEBKG
MECHANICAL DETAILS
518056 06/18/2021
JAMES T. WAMSLEY, P.E.
Florida License #50343
06/18/2021
M502
N.T.S.
AIR HANDLING UNIT DRAIN TRAP DETAIL
1 N.T.S.
CONCRETE EQUIPMENT BASES
2 N.T.S.
DUCTWORK SQUARE VANE ELBOWS
N.T.S.
DUCTWORK TRANSITIONS (WITH EQUIPMENT MOUNTED IN DUCT)
4 N.T.S.
EXHAUST OR RETURN BRANCH DUCTWORK
5 N.T.S.
FLEXIBLE AIR DUCT CONNECTOR
# Revisions: Date:
ROUND FLEXIBLE CONNECTION
RECTANGULAR FLEXIBLE CONNECTION
FLANGED
CONNECTION ON
FAN SIDE
WASHER 1-1/2" [40mm] MIN. TO 3" [75mm] MAX. INSTALLED. 6" [150mm] NOMINAL WITH MATERIAL
TAUT
FLEXIBLE
MATERIAL AS
SPECIFIED
1"x1/8" [25x3mm] DRAW
BAND
1"x1/8" [25x3mm] BAND
IRON
BOLT ON 4" [100mm]
CENTERS
5/16" [8mm] FLANGE
DUCT
SHEET METAL SCREWS
ON 12" [300mm]
CENTERS
RIVET ON 4"
[100mm]
CENTERS
SHEET METAL AS
SPECIFIED FOR
DUCTWORK.
1"x1/8" [25x3mm] BAND
IRON
BOLT ON 4" [100mm] CENTERS
1" [25mm] FLANGE & HEMALTERNATE POSITION OF BOLT
1 1/2" [40mm]
POCKET SLIP
DUCT
SHEET METAL AS
SPECIFIED FOR
DUCTWORK.
[15mm] [15mm] [40mm]
1 1/2" [40mm] MIN. TO 3" [75mm] MAX. INSTALLED. 6" [150mm] NOMINAL WITH MATERIAL
TAUT
FLANGED
CONNECTION
ON FAN SIDE
WASHER
FLEXIBLE MATERIAL
AS SPECIFIED
1/2" 1/2" 1 1/2"
2500 [1133]
1320 [598]
420 [190]ONE 1 [25] x 18 GA STRAP36 [900]
TWO 1/2 [13]∅ RODS
TWO 3/8 [10]∅. RODS
ONE 1 [25] x 16 GA STRAP
84 [2100]
60 [1500]
50 [1250] 700 [317]
ONE 1 [25] x 22 GA STRAP
QUANTITY/SIZEMAX. DUCT ∅
26 [650]
HANGER STRAPS OR RODS
MAX. LOAD
LBS. [kg]
260 [119]
MAX.
144 [3600]
IN. [mm]
SPACING
IN. [mm] IN. [mm]
144 [3600]
144 [3600]
144 [3600]
144 [3600]
NOTE:
TABULATED DATA FROM SMACNA
ALLOWS FOR DUCT REINFORCING
AND INSULATION, BUT NO
EXTERNAL LOAD.
BAND
OVER
50"
[1250mm]∅
HANGER RODS
BAND OF
SAME SIZE AS
HANGER STRAP
LOAD RATED
FASTENERS
50"
[1250mm]∅
& UNDER
SMACNA FIGURE 4-6
45° LEED IN
RIGID DUCT TO AIR
TERMINAL UNIT.
MAIN SUPPLY
PLAN VIEW
FLOW
F
LO
W
DESIGNER'S NOTES:
1. THE SUPPLY REGISTER TAKE-OFF MAY BE USED FOR UP UP TO 25% OF THE
MAIN DUCT CFM. THE BRANCH DUCT TAKE-OFF MAY BE USED FOR UP TO 15%
OF THE MAIN DUCT CFM ANYTIME AND UP TO 40% WHEN THE MAIN DUCT
VELOCITY IS 1000 FPM [5.1 M/S] OR LESS. THE AIR SPLIT DUCT TAKE-OFF
SHALL BE USED IN ALL OTHER CASES AND MAY BE USED AT ANYTIME.
2. SHOW ALL VOLUME DAMPERS ON FLOOR PLANS.
AIR SPLIT DUCT TAKE-OFF
PLAN VIEW
BRANCH DUCT TAKE-OFF PLAN VIEW
SUPPLY REGISTER
TAKE-OFF PLAN VIEW
AIR
FLOW
AIR
FLOW
A
IR
F
LO
W
SUPPLY REGISTER
OR BRANCH DUCT
TURNING VANES
MAIN
SUPPLY
DUCT
SEE FLOOR PLAN
FOR SPLIT DIMENSION
PROVIDE VOLUME
DAMPER
PROVIDE
VOLUME
DAMPER
ADJUSTABLE
METAL ROD
OR LINKAGE
TOP REGISTER
MAIN
SUPPLY
DUCT
VOLUME EXTRACTOR; ADJUSTABLE
FROM FULLY CLOSED POSITION TO
CFM NOTED ON FLOOR PLANS
AIR
FLOW
AIR
FLOW
1/4 W OR 4"
[100mm] MIN.
AIR
FLOW
MAIN SUPPLY
DUCT
A
IR
F
LO
W
W
NOTE:
1.
2.
DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR
FOR MULTI-BLADE DAMPERS & ROUND DAMPERS.
INSULATION
SEE
SPECIFICATION
DAMPER BLADE
1/8" [6mm]
CLEARANCE
ALL AROUND
OUTSIDE END BEARING
INSIDE END BEARING
HANDLE WITH
LOCKING
QUADRANT
INSULATION STAND-OFF
1/2" [15mm]
ROUND ROD PIN
DUCT
STIFFEN
BLADE AS
REQUIRED
SIDE ELEVATION SECTION
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
7370 Cabot Court, Ste. 103 Melbourne, FL 32940
COA #15 TLC NO:
Phone: 321-636-0274
Fax: 321-639-8986 www.tlc-engineers.com
Copyright 2021 TLC Engineering Solutions, Inc.c
P.O. Box 1296, Winter Park, FL 32790 Tel 407.467.8833 - Fax 407.926.0701 o n e e ig h t h i n c h o n e f o o t 16
B
A
C
D
E
F t h r e e i n c h e s o n e f o o t o n e a n d o n e h a l f i n c h e s o n e f o o t o n e i n c h o n e f o o t t h r e e q u a r t e r s i n c h o n e f o o t o n e h a l f i n c h o n e f o o t t h r e e e ig h t h s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t
VA FORM 08−6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
1 2 3 4 5 6 87 9
MALCOM RANDAL VA HOSPITAL
ADMINISTRATION BUILDING
VAWPBMC PLANNING AND ENGINEERING
IF THIS DRAWING IS LESS THAN 30" X
42" IT IS A REDUCED SIZE DRAWING
CONSTRUCTION DOCUMENTS
FLGAINESVILLE
BLDG #
573-360
AWEBKG
MECHANICAL DETAILS
518056 06/18/2021
JAMES T. WAMSLEY, P.E.
Florida License #50343
06/18/2021
M503
N.T.S.
FLEXIBLE DUCT CONNECTIONS
N.T.S.
ROUND DUCT HANGERS
2 N.T.S.
SUPPLY DUCT TAKEOFF - AIR TERMINAL UNITS
N.T.S.
SUPPLY DUCTWORK TAKE-OFFS
N.T.S.
VOLUME DAMPER DETAIL
FANSA RA
CONCRETE SLABREFRIGERANT LINES
STEEL RODS W/THREADED ENDS (TYP.
4 PLACES) SUPPORT FROM
STRUCTURE ABOVE AS REQUIRED
VIB. ISOLATORS
FLEX CONN. (TYP.)
FLOAT SWITCH
ROUTE MAIN CONDENSATE
LINE TO PLUMBING COND.
SYSTEM. SEE PLUMBING
DRAWINGS FOR LOCATION
AND SIZE
GALVANIZED SHEET METAL
SECONDARY DRAIN PAN TO EXTEND 3"
BEYOND UNIT ON ALL SIDES BY 1-1/2"
DEEP
CEILING (IF NOT IN MECHANICAL ROOM)
PROVIDE SHEET METAL
BLANK-OFF TO SEAL
ORIGINAL FILTER
ACCESS
IN-LINE FAN AIR FLOW
PROVIDE w" RODS AND
VIBRATION ISOLATORS, (4
REQUIRED)
SEAL DUCTWORK AIR
TIGHT FROM DISCHARGE
OF FAN TO DISCHARGE
LOUVER
EXHAUST
DUCTWORK W/
TRANSITIONS AS
REQUIRED (TYP.)
FLEXIBLE CONNECTION (TYP.)
MOTOR OUT OF
AIRSTREAM
TO INDOOR UNIT COIL
INSULATION
(SUCTION LINE ONLY)
PROVIDE UV
PROTECTION PAINT
FOR PVC CARRIER
PIPE
LIQUID AND SUCTION LINES ENCASED
IN SCHEDULE 40 PVC PIPE CONDUIT.
REFRIGERANT LINES IN PVC PIPE
SHALL BE SOFT COPPER, SEAMLESS
WITHOUT JOINTS.
CONDENSING UNIT ON
REINFORCED CONCRETE
PAD, BASIS OF DESIGN
DIVERSITECH: HURRICANE
PAD
14 GAUGE GALVANIZED STEEL
ANGLE, 1" WIDE MIN, 2-MIN PER
4'-0". SECURE TO CONCRETE PAD
AND UNIT WITH 1/4"x1-1/2"
STAINLESS STEEL CONCRETE
SCREWS OR ANCHORS.
SEAL AT FLOOR WITH UL
LISTED EXTERIOR GRADE
HVAC SEALANT CAULK.
TEMPERATURE RANGE:
0-140° F.
NOTE: MAXIMUM 2 PIPES PER 6"
PERMISSIBLE TO ROUTE UP TO
3 LINESETS IN CONDUIT
ROUTE REFIRGERANT
LINES BELOW WALL AND
UP THROUGH INTERIOR
FLOOR ADJACENT TO
POINT OF ENTRY.
GAUGESPR (RADIUS)
SMALL
LARGE
RUNNER TYPE 1
SINGLE VANE
VANE SUPPORT
* MAXIMUM UNSUPPORTED VANE LENGTH
SMALL SINGLE VANE 36"
LARGE SINGLE VANE 36"
SMALL DOUBLE VANE 48"
LARGE DOUBLE VANE 72"
NOTE:
INSTALL VANES IN SECTIONS OR USE TIE
RODS TO LIMIT THE UNBRACED VANE
LENGTH
R
SINGLE VANE SCHEDULE
2" (51 mm)
NOTE:
SEE MECHANICAL SPECIFICATIONS FOR ADDITIONAL INFORMATION.
NOTES:
1. VANES SHALL BE SECURELY FASTENED TO
RUNNERS
2. ALL VANES SHALL BE SECURE AND STABLE
IN INSTALLED OPERATING POSITION.
RUNNER TYPE 2
VANE
TIE ROD
VANE
DUCT
RUNNER
METAL
SCREWS 12"
O.C.
22 GA. TAB TAB
BOLT, SCREW OR
WELD RUNNER TO
DUCT
SCREW EVERY
6TH VANE TO
TAB
1-1/2" (38 mm)
(0.70 mm)
4-1/2" (114 mm)
3-1/4" (83 mm)
(0.85 mm)
S P
45.00° 45.00°
-1
/2
O R
1-1/2" MIN.
UNLESS FOOT OF STRAP IS
PLACED UNDER A BOTTOM
REINFORCEMENT
MINIMUM SPACING OF HANGERS TO BE
4FT. MAXIMUM SPACING TO BE 8FT.
INSTALL IN ACCORDANCE WITH
SMACNA. HVAC DUCT CONSTRUCTION
STANDARDS. LATEST VERSION, TABLE
4-1,RECTANGULAR DUCT HANGERS.
DUCT
MINIMUM 20
GAUGE STEEL
60" MAX
(1524 mm)
1"MIN
SCREWS
SCREWS MAY BE
OMITTED IF
HANGER LOOPS
HANGER
STRAPS
MINIMUM 1"
WIDE
CONNECT TO STRUCTURE ABOVE USING SIMPSON
PDPH SERIES FASTENERS FOR SUPPORT INTO POST
TENSION SLAB. FASTENERS SHALL NOT PENETRATE
SLAB MORE THAN 3 /4 " (TYPICAL)
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
7370 Cabot Court, Ste. 103 Melbourne, FL 32940
COA #15 TLC NO:
Phone: 321-636-0274
Fax: 321-639-8986 www.tlc-engineers.com
Copyright 2021 TLC Engineering Solutions, Inc.c
P.O. Box 1296, Winter Park, FL 32790 Tel 407.467.8833 - Fax 407.926.0701 o n e e ig h t h i n c h o n e f o o t 16
B
A
C
D
E
F t h r e e i n c h e s o n e f o o t o n e a n d o n e h a l f i n c h e s o n e f o o t o n e i n c h o n e f o o t t h r e e q u a r t e r s i n c h o n e f o o t o n e h a l f i n c h o n e f o o t t h r e e e ig h t h s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t
VA FORM 08−6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
1 2 3 4 5 6 87 9
MALCOM RANDAL VA HOSPITAL
ADMINISTRATION BUILDING
VAWPBMC PLANNING AND ENGINEERING
IF THIS DRAWING IS LESS THAN 30" X
42" IT IS A REDUCED SIZE DRAWING
CONSTRUCTION DOCUMENTS
FLGAINESVILLE
BLDG #
573-360
AWEBKG
MECHANICAL DETAILS
518056 06/18/2021
JAMES T. WAMSLEY, P.E.
Florida License #50343
06/18/2021
M504
N.T.S.
DUCTED SUSPENDED UNIT
N.T.S.
INLINE FAN - SMALL
4 N.T.S.
REFRIGERANT PIPING
5N.T.S.
TURNING VANES
N.T.S.
TYPICAL RECTANGULAR DUCT SUPPORT
AIR TERMINAL SCHEDULE
MARK TYPE MANUFACTURER MODEL MAX N.C.
AIRFLOW
(CFM)
FACE
SIZE (IN)
NECK
SIZE (IN)
FLEX DUCT
(IN) REMARKS
A CEILING
SUPPLY
DIFFUSER
TITUS OMNI-AA 30 0-95 12X12 6Ø 6Ø 1,2,4
0-95 24X24 6Ø 6Ø
100-175 8Ø 8Ø
180-275 10Ø 10Ø
280-395 12Ø 12Ø
400-535 14Ø 14Ø
B,C CEILING
EXHAUST,
RETURN
GRILLE
TITUS PAR-AA 30 0-80 12X12 6Ø 6Ø 1,2,3,4
0-80 24X24 6Ø 6Ø
85-100 8Ø 8Ø
105-220 10Ø 10Ø
225-315 12Ø 12Ø
320-430 14Ø 14Ø
435-560 16Ø 16Ø
W WALL
LOUVER
GREENHECK ESD-635DE N/A 0-190 12X12 12X12 N/A 5
200-800 18X18 18X18 N/A
TAG SHOWN ON PLANS DENOTES TYPE, NUMBER DENOTES CFM.
PROVIDE ALL AIR DEVICES WITH FACTORY FURNISHED GASKETS. ALL AIR DEVICES CONSTRUCTED OF
ALUMINUM WITH FACTORY APPLIED OFF-WHITE PAINTED FINISH.
PROVIDE SHEET METAL PLENUM ON TOP OF EXHAUST AND RETURN GRILLES AND CONNECT TO WITH
FLEXIBLE DUCT RATED FOR 2" W.G. STATIC PRESSURE.
FOR ALL GRILLE TYPES: GRILLE SIZE SHOWN TO TAKE PREFERENCE OVER THOSE NOTED ABOVE.
REFER TO DETAIL 5 ON SHEET M-501 FOR WALL LOUVER INSTALLATION INSTRUCTIONS.
REMARKS
1.
2.
3.
4.
5.
B.O.D. B.O.D.
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
7370 Cabot Court, Ste. 103 Melbourne, FL 32940
COA #15 TLC NO:
Phone: 321-636-0274
Fax: 321-639-8986 www.tlc-engineers.com
Copyright 2021 TLC Engineering Solutions, Inc.c
P.O. Box 1296, Winter Park, FL 32790 Tel 407.467.8833 - Fax 407.926.0701 o n e e ig h t h i n c h o n e f o o t 16
B
A
C
D
E
F t h r e e i n c h e s o n e f o o t o n e a n d o n e h a l f i n c h e s o n e f o o t o n e i n c h o n e f o o t t h r e e q u a r t e r s i n c h o n e f o o t o n e h a l f i n c h o n e f o o t t h r e e e ig h t h s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t
VA FORM 08−6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
1 2 3 4 5 6 87 9
MALCOM RANDAL VA HOSPITAL
ADMINISTRATION BUILDING
VAWPBMC PLANNING AND ENGINEERING
IF THIS DRAWING IS LESS THAN 30" X
42" IT IS A REDUCED SIZE DRAWING
CONSTRUCTION DOCUMENTS
FLGAINESVILLE
BLDG #
573-360
AWEBKG
MECHANICAL SCHEDULES
518056 06/18/2021
JAMES T. WAMSLEY, P.E.
Florida License #50343
06/18/2021
M601
BASEBOARD HEATER SCHEDULE
MARK
BASIS OF DESIGN
MANUFACTURER
BASIS OF
DESIGN MODEL
CAPACITY
(W)
VOLT /
PHASE
UH-1 STELPRO B41001 1000 208/1
UH-2 STELPRO B41001 1000 208/1
FAN SCHEDULE
MARK
BASIS OF
DESIGN
MANUFACTURER
BASIS OF
DESIGN
MODEL FAN TYPE
AIRFLOW
(CFM)
ELECTRICAL DATA
HP BHP FLA
VOLT /
PHASE
EF-151 RUPP AIR RA-SIF11BD INLINE, BELT 420 1/4 0.157 4.8 120/1
EF-152 RUPP AIR RA-SIF10DD INLINE, DIRECT 300 1/4 0.157 4.8 120/1
EF-153 RUPP AIR RA-SIF11BD INLINE, BELT 420 1/4 0.157 4.8 120/1
EF-154 RUPP AIR RA-SIF10DD INLINE, DIRECT 300 1/4 0.157 4.8 120/1
OUTSIDE AIR HANDLING UNIT SCHEDULE
MARK
BASIS OF DESIGN
MANUFACTURER
BASIS OF DESIGN
MODEL
AIRFLOW
(CFM)
NOM
TONS
INDOOR HEAT PUMP COIL
HOT GAS
REHEAT
COIL
CAPACIT
Y (MBH)
SUPPLY FAN
VOLT /
PHASE MCA
MOC
P DIMENSIONS (HxWxL IN.)
COOLING DATA HEATING DATA
ESP
(IN.WG.) W
CAPACITY
(MBH) EAT (°F) LAT (°F) CAPACITY
(MBH)
EAT
(°F)
DB
LAT
(°F)
DBTOTAL DB WB DB WB
AHU-57 SAMSUNG AM300NNDDCV/AA 3000 25 221.9 78.3 73.8 55 55 108 51.2 72 108 1 1460 208/1 7 20 26.01x51.02x97.12
AHU-58 SAMSUNG AM300NNDDCV/AA 3000 25 221.9 78.3 73.8 55 55 108 51.2 72 108 1 1460 208/1 7 20 26.01x51.02x97.12
VRF FAN COIL UNIT SCHEDULE
MARK
BASIS OF DEISGN
MANUFACTURER BASIS OF DESIGN MODEL UNIT TYPE
AIRFLOW
(CFM)
NOM
TONS
COOLING COIL HEATING COIL ELECTRICAL DATA
QTY
Notes
CAPACITY (MBH) EAT (°F) LAT (°F)
CAPACIT
Y (MBH)
EAT
(°F)
DB
LAT
(°F)
DB
SUPPLY FAN
VOLT /
PHASE MCA
MOC
PSENSIBLE TOTAL DB WB DB WB
ESP
(IN.WG.) W
FCU-1-1 SAMSUNG AM036ANHDCH/AA DUCTED 1000 3.0 27.5 36 76.4 63.1 55 55 40 67.4 85 0.75 224 208/1 2 15 1
FCU-1-2 SAMSUNG AM036ANHDCH/AA DUCTED 1000 3.0 27.5 36 76.4 63.1 55 55 40 67.4 85 0.75 224 208/1 2 15 1
FCU-1-3 SAMSUNG AM024ANHDCH/AA DUCTED 550 2.0 18.3 24 76.4 63.1 55 55 27 67.4 85 0.5 153 208/1 2 15 2
FCU-1-4 SAMSUNG AM018NNNDCH/AA CEILING 450 1.5 20.4 27 76.4 63.1 55 55 30 67.4 85 0 65 208/1 2 15 18
FCU-1-4-A SAMSUNG AM018NNNDCH/AA CEILING 450 1.5 20.4 27 76.4 63.1 55 55 30 67.4 85 0 65 208/1 2 15 7
FCU-2-1 SAMSUNG AM030ANHDCH/AA DUCTED 920 2.5 23 30 77.1 63.8 55 55 34 68.8 85 0.75 153 208/1 2 15 1
FCU-2-2 SAMSUNG AM030ANHDCH/AA DUCTED 920 2.5 23 30 77.1 63.8 55 55 34 68.8 85 0.75 153 208/1 2 15 1
FCU-2-3 SAMSUNG AM018NNNDCH/AA CEILING 450 1.5 13.6 18 76.1 62.6 55 55 20 68.3 85 0 65 208/1 2 15 20
FCU-2-4 SAMSUNG AM018TNVDCH/AA WALL MOUNTED 600 1.5 12.1 18 75.1 64.1 55 55 20 67.1 85 0 65 208/1 2 15 3
FCU-2-5 SAMSUNG AM024ANHDCH/AA DUCTED 570 2.0 18.3 24 77.1 63.8 55 55 30 68.8 85 0.5 153 208/1 2 15 2
VRF COMPRESSOR UNIT SCHEDULE
MARK
BASIS OF DESIGN
MANUFACTURER
BASIS OF DESIGN
MODEL
NOM
TONS REFRIGERANT
COMPRESSORS OUTDOOR FAN ELECTRICAL DATA
DIMENSIONS (HxWxL
IN.)
Notes
QTY
KW
(EA.)
KW
(EA.) CFM QTY MCA MOCP
VOLT /
PHASE
CCU-3 SAMSUNG AM480JXVAJR2AA 40 R-410A 6 5.18 620 31428 4 92 120 480/3 66.73x90.36x50.98
CCU-4 SAMSUNG AM432KXVGJR2AA 36 R-410A 4 6.39 620 24012 2 86 120 480/3 70.67x60.24x53.66
CCU-5 SAMSUNG AM240JXVAJR2AA 20 R-410A 3 5.18 1870 3 50 60 480/3 66.73x60.24x85.63
CCU-6 SAMSUNG AM240JXVAJR2AA 20 R-410A 3 5.18 1870 3 50 60 480/3 66.73x60.24x85.63
CCU-6-A SAMSUNG AM240JXVAJR2AA 20 R-410A 3 5.18 1870 3 50 60 480/3 66.73x60.24x85.63
ENERGY RECOVERY VENTILATOR SCHEDULE
MARK
BASIS OF DESIGN
MANUFACTURER BASIS OF DESIGN MODEL
SUPPLY (TO OUTSIDE AIR UNIT) EXHAUST (FROM SPACE) ELECTRICAL DATA
DIMENSIONS
(HxWxL IN.)
WEIGHT
(LB)
AIRFLOW
(CFM)
EAT (°F) LAT (°F) SUPPLY FAN
AIRFLOW
(CFM)
EAT (°F) EXHAUST FAN
MCA
MOC
P
VOLT /
PHASE
SUMMER WINTER SUMMER WINTER
ESP
(IN.WG.) HP BHP
SUMMER WINTER ESP
(IN.WG.
) HP BHPDB WB DB DB WB DB DB WB DB
ERV-1 GREENHECK ECV-30H 3100 82.6 79.2 29.6 78.3 73.8 51.2 0.25 2 1.71 2220 76.4 63.1 68.3 0.5 1.5 1.09 16 20 208/3 60.7x61.4x69.0 1111
ERV-2 GREENHECK ECV-30H 3100 82.6 79.2 29.6 78.3 73.8 51.2 0.25 2 1.71 2220 76.4 63.1 68.3 0.5 1.5 1.09 16 20 208/3 60.7x61.4x69.0 1111
1. PROVIDE DISCONNECT SWITCH.
2. PROVIDE GRAVITY DAMPER.
3. FANS SHALL BE CONSTANTLY OPERATING DURING OCCUPIED HOURS.
4. PROVIDE VIBRATION ISOLATOR.
1. HEATERS SHALL MAINTAIN STAIRWELLS AT 50°F DURING WINTER.
1. PROVIDE ISOLATION VALVES AT EACH REFRIGERANT PIPING CONNECTION.
2. PROVIDE TRAP AT CONDENSATE LINE CONNECTION.
3. INTERLOCK VRF SYSTEM PACKAGED CONTROLS WITH CAMPUS BACNET SYSTEM.
4. INSULATE ALL DUCTED UNITS.
5. ADHERE TO MANUFACTURER'S PIPING AND HEAT RECOVERY UNIT REQUIREMENTS.
6. PROVIDE CONDENSATE PUMP.
1. PLACE UNITS ON 4" CONCRETE PAD.
2. INTERLOCK VRF SYSTEM PACKAGED CONTROLS WITH CAMPUS BACNET SYSTEM.
3. PROVIDE DISCONNECT SWITCH.
1. PROVIDE SINGLE POINT FUSED DISCONNECT SWITCH.
2. PROVIDE TRAP AT CONDENSATE LINE CONNECTION.
3. INTERLOCK UNITS WITH CAMPUS BACNET SYSTEM. UNIT SHALL NOT OPERATE DURING UNOCCUPIED HOURS.
4. PROVIDE 2" MERV-8 FILTER.
5. PROVIDE SMOKE DETECTOR ON SUPPLY DUCT.
1. PROVIDE 8" MERV-8 FILTER AT OUTDOOR AIR AND RETURN AIR INLET.
2. PROVIDE AND INTERLOCK LOW-LEAK MOTORIZED DAMPERS AT OUTDOOR AIR AND RETURN AIR INLET. INTERLOCK WITH OAHUS.
BID ALTERNATE
BID ALTERNATE
COMPUTER ROOM AIR CONDITIONER (CRAC) UNIT SCHEDULE (DX)
MARK MANUFACTURER MODEL
AIR FLOWS
COOLING COIL
DATA ELECTRICAL DATA
WEIGHT
(LBS)
TOTAL
CFM
O.A.
CFM
CAPACITY
FAN HP FLA MCA MOCP VOLT/PHASETOTAL MBH
CRAC-1 LIEBERT PX029 4300 0 98.3 4.15 34.8 43 50 460/3 700
CRAC-2 LIEBERT PX029 4300 0 98.3 4.15 34.8 43 50 460/3 700
CRAC/CRAH CONDENSER UNIT SCHEDULE
MARK MANUFACTURER MODEL TONS FLA
REFRIGERANT
DATA ELECTRICAL DATA
WEIGHT (LBS)TYPE MCA MOCP VOLT/PHASE
ACC-1 LIEBERT MCM040 8 1.4 R-410A 2 15 460/3 231
ACC-2 LIEBERT MCM040 8 1.4 R-410A 2 15 460/3 231
NOTES:
1. PROVIDE WITH 2" MERV-8 PRE FILTERS.
2. CONDENSATE PAN SHALL BE DOUBLE SLOPED & NON-CORROSIVE MATERIALS.
3. PROVIDE AN AUXILLARY DRAIN CONNECTION AT CONDENSATE DRAIN.
4. UNITS TO INCLUDE 7.7 LB/HR INFARRED HUMIDIFIER AND 15.1 KW ELECTRIC REHEAT.
5. PROVIDE WITH CONDENSATE PUMP.
NOTES:
1. PROVIDE WITH MANUFACTURER 18 INCH STANDS. .
2. PROVIDE WITH MANUFACTURER CONTROLS FOR SERVER ROOM.
3. PROVIDE WITH HAIL GUARDS AND SEACOAST CORROSION RESISTANT COATINGS.
4. EXTERIOR ROUTED PIPING SHALL BE PROTECTED BY METAL JACKET.
# Revisions: Date:
1 ADDENDUM 1 10/19/21
VRF BRANCH BOX SCHEDULE
MARK MANUFACTURER MODEL UNIT TYPE
NUMBER
OF UNITS TOT. MBH
VOLT /
PHASE
MCU-1 SAMSUNG MCU-S6NEK2N DISTRIBUTION BOX 1 216 120/1
MCU-2 SAMSUNG MCU-S6NEK2N DISTRIBUTION BOX 1 216 120/1
MCU-3 SAMSUNG MCU-S6NEK2N DISTRIBUTION BOX 1 216 120/1
MCU-4 SAMSUNG MCU-S6NEK2N DISTRIBUTION BOX 1 216 120/1
MCU-5 SAMSUNG MCU-S6NEK2N DISTRIBUTION BOX 1 216 120/1
MCU-6 SAMSUNG MCU-S6NEK2N DISTRIBUTION BOX 1 216 120/1
MCU-7 SAMSUNG MCU-S6NEK2N DISTRIBUTION BOX 1 216 120/1
MCU-8 SAMSUNG MCU-S6NEK2N DISTRIBUTION BOX 1 216 120/1
M M
M M
M M
M
J
.9
.6
.3
.1
V E
R
IF
Y A
L L
E X
IS
T
IN
G
D
IM
E N
S
IO
N S
EXISTING BUILDING
B-12
EXISTING HOSPITAL
BUILDING
T
T
T
T
T
T
FCU-1-4-A
FCU-1-4-A
FCU-1-4-A
FCU-1-4-A
FCU-1-4-A
FCU-1-4-A
FCU-1-4-A
1/
4" C
N D
1/
4" C
N D
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
7370 Cabot Court, Ste. 103 Melbourne, FL 32940
COA #15 TLC NO:
Phone: 321-636-0274
Fax: 321-639-8986 www.tlc-engineers.com
Copyright 2021 TLC Engineering Solutions, Inc.c
P.O. Box 1296, Winter Park, FL 32790 Tel 407.467.8833 - Fax 407.926.0701 o n e e ig h t h i n c h o n e f o o t 16
B
A
C
D
E
F t h r e e i n c h e s o n e f o o t o n e a n d o n e h a l f i n c h e s o n e f o o t o n e i n c h o n e f o o t t h r e e q u a r t e r s i n c h o n e f o o t o n e h a l f i n c h o n e f o o t t h r e e e ig h t h s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t
VA FORM 08−6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
1 2 3 4 5 6 87 9
MALCOM RANDAL VA HOSPITAL
ADMINISTRATION BUILDING
VAWPBMC PLANNING AND ENGINEERING
IF THIS DRAWING IS LESS THAN 30" X
42" IT IS A REDUCED SIZE DRAWING
CONSTRUCTION DOCUMENTS
FLGAINESVILLE
BLDG #
573-360
BKGBKG
ALTERNATE 1 - BRIDGE
MECHANICAL PLAN
518056 06/18/2021
JAMES T. WAMSLEY, P.E.
Florida License #50343
06/18/2021
MZ101
1/8" = 1'-0"
BRIDGE PLAN - MECHANICAL
N
PLAN NOTES:
1 ROUTE CONDENSATE DRAIN DOWN TO ULTIMATE DISCHARGE INTO STORM SYSTEM.
ROUTE REFIRGERANT LINES DOWN TO PAD MOUNTED CCU-6-A AT GRADE.2
| Sheets |
| M001 - MECHANICAL SYMBOLS, LEGEND, NOTES & INDEX |
| M100 - MECHANICAL FLOOR PLANS |
| M501 - MECHANICAL DETAILS |
| M502 - MECHANICAL DETAILS |
| M503 - MECHANICAL DETAILS |
| M504 - MECHANICAL DETAILS |
| M601 - MECHANICAL SCHEDULES |
| MZ101 - ALTERNATE 1 - BRIDGE MECHANICAL PLAN |
File details come from the government source that posted it. Updated .