This document is a Fire/Life Safety System Inspection, Testing, and Maintenance Certificate for the VA Sepulveda Building 99 located at 16111 Plummer St in North Hills, CA. The comprehensive inspection was performed in accordance with multiple NFPA standards, including NFPA 101, NFPA 72, and NFPA 904, covering life safety code, fire alarm systems, and air conditioning/ventilation systems. The inspection details test results for 127 total devices across multiple categories, including tamper switches, waterflow switches, duct detectors, heat detectors, pull stations, smoke detectors, chime/strobes, releasing devices, communicators, control panels, batteries, power supplies, and elevators. Two batteries in the first Fire Alarm Control Panel (FACP) were noted as failed/expired, requiring replacement or load testing, which represents the primary discrepancy in the report.
View the file
Other files
Show all 41
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
. 1
Executive Summary Generated by: BuildingReports.com
Building Information Building: VA Sepulveda Bldg 99 Contact: Keith Hayhurst Address: 16111 Plummer St Phone: 310.714.5379 City/State/ZIP Code: North Hills, CA 90012 Mobile:
Country: United States of America Email: Keith.Hayhurst@VA.Gov
Inspection Performed By
System Control Unit Manufacturer: Cerberus Inspection Date: 02/01/2024 IDC Style:
Model Number: Pyrotronics - MXL Install Date: 03/04/2020 SLC Style:
Software Version: Version Date: 03/04/2020 NAC Style:
Location: 1st Main Electric/Transformer Room Current Protection:
Central Station Signal Verification Type: Digital Communicator Mfg.: Detection Systems Model #: DS9471 Test Time/Date: 2/1/24 10:36:54 AM Restore Time: 41 Seconds Note:
Certification Company: Building: VA Sepulveda Bldg 99 Inspector: Contact: Keith Hayhurst
Inspection Completion Date: Feb 8, 2024 Building: VA Sepulveda Bldg 99 EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2
(17)(10)(a) & (17)(11)
Devices Tested This
Quarter Pass Fail Tested YTD
(2024) Untested YTD
(2024) Total Quantity Tamper Switch 8 8 0 8 0 8 Waterflow Switch 6 6 0 6 0 6
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Devices Tested This
Quarter Pass Fail Tested YTD
(2024) Untested YTD
(2024) Total Quantity Duct Detector 6 6 0 6 0 6 Heat Detector 1 1 0 1 0 1 Pull Station 18 18 0 18 0 18 Smoke Detector 30 30 0 30 0 30
EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)
Devices Tested This
Quarter Pass Fail Tested YTD
(2024) Untested YTD
(2024) Total Quantity Chime/Strobe 25 25 0 25 0 25 Releasing Device 12 12 0 12 0 12 Strobe 3 3 0 3 0 3
EC 02.03.05 EP 05 Annual test of fire alarm equipment for notifying off-site fire responders. NFPA 72 (2022) Table 14.4.3.2 (4)
Devices Tested This
Quarter Pass Fail Tested YTD
(2024) Untested YTD
(2024) Total Quantity Communicator 1 1 0 1 0 1
EC 02.03.05 EP 19 Annual test of automatic smoke-detection shutdown devices for air-handling equipment. NFPA 90A (2024) 6.4.1
Devices Tested This
Quarter Pass Fail Tested YTD
(2024) Untested YTD
(2024) Total Quantity Duct Detector 6 6 0 6 0 6
LS 02.01.34 EP 02 Protected master fire alarm control panel
Devices Tested This
Quarter Pass Fail Tested YTD
(2024) Untested YTD
(2024) Total Quantity Control Panel 1 1 0 1 0 1
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
Devices Tested This
Quarter Pass Fail Tested YTD
(2024) Untested YTD
(2024) Total Quantity Annunciator 3 3 0 3 0 3 Battery 8 6 2 8 0 8 Power Supply 3 3 0 3 0 3
LS 02.01.50 EP 07 Annual - Elevators are fully equipped and protected
Devices Tested This
Quarter Pass Fail Tested YTD
(2024) Untested YTD
(2024) Total Quantity Elevator 2 2 0 2 0 2 Total Device Count: 127
Discrepancy Report Generated by: BuildingReports.com
Building: VA Sepulveda Bldg 99 Control Panel: 1 - Cerberus Pyrotronics - MXL The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.
ScanID Location Problem Address Reference
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
Battery 57079187 1st FACP Date Expired 1 NFPA72 Table
14.4.3.2 (9)(5) 57079191 1st FACP Date Expired 1 NFPA72 Table
14.4.3.2 (9)(5)
Code References NFPA72 Table
14.4.3.2 (9)(5)
Replace the battery or conduct a load test of the battery capacity every 3 years.
. 4
Notes & Recommendations Generated by: BuildingReports.com
Building: VA Sepulveda Bldg 99 Control Panel: 1 - Cerberus Pyrotronics - MXL
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection.
ScanID Note Device Type Location Comment LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
57079187 1 Battery 1st FACP Date Expired Out of date.
57079191 2 Battery 1st FACP Date Expired Out of date.
Inspection & Testing Generated by: BuildingReports.com
Building: VA Sepulveda Bldg 99 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far-right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.
Passed=P, Failed=F, Replaced=R
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11)
Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(10)(a))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Tamper Switch 8 8 0 8 8 Device Type Location ScanID Address Annual 2024 Tamper Switch 1st OS&Y Outside FACU 57079167 1-01-026 Tested – 1 Turn - 02/08 - Pass Tamper Switch 1st OS&Y Outside FACU 57079166 1-01-026 Tested – 1 Turn - 02/08 - Pass Tamper Switch 1st Outside Service Room AHU 3 Room 109 57079169 1-01-011 Tested – 2 Turns - 02/01 - Pass Tamper Switch Ground G-100 Pump & Mechanical Service Room “A A” 57079102 1-01-014 Tested – 2 Turns - 02/01 - Pass Tamper Switch Ground G-100 Pump & Mechanical Service Room “A A” 57079103 1-01-013 Tested – 2 Turns - 02/01 - Pass Tamper Switch Ground Corridor By Room G-79 Above Ceiling 57079147 1-01-017 Tested – 1 Turn - 02/01 - Pass Tamper Switch Ground Corridor By G-59 Staff Breakroom Above Ceiling 57079136 1-01-019 Tested – 1 Turn - 02/01 - Pass Tamper Switch Ground Corridor By G-38 Kitchen Fire Doors Above
Ceiling 57079128 1-01-021 Tested – 1 Turn - 02/01 - Pass
Device Total: 8
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11)
Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size installed in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25-20. (NFPA 72-22 Table 14.4.3.2 (17)(11))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Waterflow Switch 6 6 0 6 6 Device Type Location ScanID Address Annual 2024 Waterflow Switch 1st Outside Service Room AHU 3 Room 109 57079168 1-01-010 Tested – 20 Seconds - 02/01 - Pass Waterflow Switch Ground G-100 Pump & Mechanical Service Room “A A” 57079104 1-01-012 Tested – 55 Seconds - 02/01 - Pass Waterflow Switch Ground Corridor By Electrical Room G-106 Above
Ceiling 57079017 1-01-016 Tested – 37 Seconds - 02/01 - Pass
Waterflow Switch Ground Corridor By G-59 Break Room 57079018 1-01-018 Tested – 55 Seconds - 02/01 - Pass Waterflow Switch Ground Corridor By G-54 Lounge Above Ceiling 57079020 1-01-020 Tested – 48 Seconds - 02/01 - Pass Waterflow Switch Ground Corridor By G-54 Lounge Above Ceiling 57079019 1-01-022 Tested – 34 Seconds - 02/01 - Pass Device Total: 6
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(7)(e))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Duct Detector 6 6 0 6 6 Device Type Location ScanID Address Annual 2024 Duct Detector 1st Outside Service Room AHU 3 Room 109 57079170 1-01-007 02/01-P Duct Detector 1st Outside Service Room AHU 3 Room 109 57079171 1-01-008 02/01-P Duct Detector Roof Service Room C AHU 1 57079161 1-02-031 02/01-P Duct Detector Roof Service Room C AHU 1 57079160 1-02-032 02/01-P Duct Detector Roof Service Room B AHU 2 57079164 1-02-033 02/01-P Duct Detector Roof Service Room B AHU 2 57079165 1-02-034 02/01-P
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions.
Non-Restorable: Do not perform heat test. Test functionality mechanically and electrically. (NFPA 72-22 Table 14.4.3.2 (17)(4)(a))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Heat Detector 1 1 0 1 1 Device Type Location ScanID Address Annual 2024 Heat Detector Ground Elevator Machine Room By Women’s Restroom G-12 57079110 1-02-016 02/02-P Device Total: 1
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-19 Table 14.4.3.2 (17)(5))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Pull Station 18 18 0 18 18 Device Type Location ScanID Address Annual 2024 Pull Station 1st Corridor By FACU Room 110 Exit Door 57079186 1-01-009 02/01-P Pull Station 1st Corridor Elevator Lobby 57079185 1-01-004 02/01-P Pull Station Ground Corridor By G-57 Social Worker Office 57079135 1-02-036 02/01-P Pull Station Ground Dining Area By Room G09 57079157 1-02-012 02/01-P Pull Station Ground Dining Area East By Fire Doors 57079154 1-02-010 02/01-P Pull Station Ground Corridor By G-65 Nurse Managers Office 57079132 1-02-024 02/01-P Pull Station Ground Corridor By G-80 MDS Nurse Office Exit 57079131 1-02-003 02/01-P Pull Station Ground Corridor By West Nurse Station 57079125 1-02-038 02/01-P Pull Station Ground Corridor By G-100 Pump & Mechanical Service Room 57079105 1-02-011 02/01-P Pull Station Ground Corridor By G-98 North Exit 57079143 1-02-004 02/01-P Pull Station Ground Corridor By G-85 Shower Room Fire Doors 57079144 1-02-037 02/01-P Pull Station Ground Corridor By East Nurse Station 57079151 1-02-007 02/01-P Pull Station Ground Corridor By Room G-53 Exit Door 57079126 1-02-002 02/01-P Pull Station Ground Corridor By G-40 Patient Room Fire Doors 57079127 1-02-025 02/01-P Pull Station Ground Corridor By G-34 Conference Room Exit 57079116 1-02-001 02/01-P Pull Station Ground Corridor By G-20 Patient Bath 57079119 1-02-029 02/01-P Pull Station Ground Corridor West Dining Area Fire Doors 57079111 1-02-018 02/01-P Pull Station Ground Corridor By Women’s Restroom G-12 57079108 1-02-039 02/01-P Device Total: 18
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72-22 Table 14.4.3.2 (17)(7)(a))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Smoke Detector 30 30 0 30 30 Device Type Location ScanID Address Annual 2024 Smoke Detector 1st Elevator Lobby 57079184 1-01-002 02/05-P Smoke Detector 1st Main Lobby TR Room 49519220 1-1-028 02/01-P Smoke Detector 1st Outside Service Room AHU 3 Room 109 57079172 1-01-006 02/01-P Smoke Detector 1st Main Electric/Transformer Room 110 57079188 1-01-005 02/01-P Smoke Detector Roof Service Room C AHU 1 57079162 1-02-030 02/01-P Smoke Detector Roof Service Room B AHU 2 57079163 1-02-035 02/01-P Smoke Detector Ground Elevator Lobby 57079158 1-02-017 02/02-P Smoke Detector Ground TR Room By G-57 Social Worker Office 49519221 1-02-046 02/01-P Smoke Detector Ground Elevator Machine Room By Women’s Restroom G-12 57079109 1-02-015 02/01-P Smoke Detector Ground Dining Area High Ceiling 57079023 1-02-049 02/01-P Smoke Detector Ground Corridor West Dining Area Fire Doors 57079112 1-02-019 02/01-P Smoke Detector Ground Dining Area East Area Fire Doors 57079153 1-02-008 02/01-P Smoke Detector Ground Corridor By G-38 Kitchen Fire Doors 57079130 1-02-021 02/01-P Smoke Detector Ground Service Tunnel Double Doors 57079106 1-02-014 02/01-P Smoke Detector Ground Corridor By G-10 57079107 1-02-013 02/01-P Smoke Detector Ground Dining Area East Fire Doors 57079152 1-02-009 02/01-P Smoke Detector Ground Corridor By G-59 Staff Breakroom Fire Doors 57079138 1-02-005 02/01-P Smoke Detector Ground Corridor By G-83 Laundry Room Fire Doors 57079146 1-02-028 02/01-P Smoke Detector Ground Dining Area By Room G05 57079155 1-02-052 02/01-P Smoke Detector Ground Dining Area By Room G09 57079156 1-02-053 02/01-P Smoke Detector Ground Dining Area High Ceiling 57079022 1-02-050 02/01-P Smoke Detector Ground Dining Area High Ceiling 57079021 1-02-051 02/01-P Smoke Detector Ground Corridor By G-85 Shower Room Fire Doors 57079145 1-02-027 02/01-P Smoke Detector Ground Corridor By G-66 Shower Fire Doors 57079137 1-02-006 02/01-P Smoke Detector Ground Corridor By G-58 Hospice Social Worker Office 57079134 1-02-043 02/01-P Smoke Detector Ground Corridor By G-57 Social Worker Office 57079133 1-02-044 02/01-P Smoke Detector Ground Corridor By G-39 Shower Fire Doors 57079129 1-02-026 02/01-P Smoke Detector Ground Corridor By G-19 Meditation Room Fire Doors 57079121 1-02-022 02/01-P Smoke Detector Ground Corridor By G-20 Patient Bath Fire Doors 57079120 1-02-023 02/01-P Smoke Detector Ground Corridor By West Nurse Station Fire Doors 57079113 1-02-020 02/01-P Device Total: 30
EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)
For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(1))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Chime/Strobe 25 25 0 25 25 Device Type Location ScanID Address Annual 2024 Chime/Strobe 1st Corridor Outside FACU Room 57079025 1 02/01-P Chime/Strobe 1st Corridor Elevator Lobby 57078994 1 02/01-P Chime/Strobe 1st Men’s Locker Room 107A 57078992 1 02/01-P Chime/Strobe Ground Corridor By G-100 Pump & Mechanical Service Room “A A” 57079015 1 02/01-P Chime/Strobe Ground Corridor By Women’s Restroom G-12 57079014 1 02/01-P Chime/Strobe Ground Corridor G-02A Pharmacy 57079013 1 02/01-P Chime/Strobe Ground Dining Area Above Vending Machines 57079012 1 02/01-P Chime/Strobe Ground Dining Area East By Fire Doors 57079011 1 02/01-P Chime/Strobe Ground G-100 Pump & Mechanical Service Room “A A” 57079016 1 02/01-P Chime/Strobe Ground Corridor By East Nurse Station 57079010 1 02/01-P Chime/Strobe Ground Corridor By G-85 Shower Room Fire Doors 57079009 1 02/01-P Chime/Strobe Ground Corridor By G-91 Exercise Therapy 57079008 1 02/01-P Chime/Strobe Ground Corridor By G-98 North Exit 57079007 1 02/01-P Chime/Strobe Ground Corridor By G-65 Nurse Managers Office 57079006 1 02/01-P Chime/Strobe Ground Corridor By-69 Patient Room 57079005 1 02/01-P Chime/Strobe Ground Corridor By G-80 MDS Nurse Office Exit 57079004 1 02/01-P Chime/Strobe Ground Corridor By G-57 Social Worker Office 57079003 1 02/01-P Chime/Strobe Ground Corridor By G-40 Patient Room Fire Doors 57079002 1 02/01-P Chime/Strobe Ground Corridor By G-45 Patient Room 57079001 1 02/01-P Chime/Strobe Ground Corridor By G-51 Patient Room 57079000 1 02/01-P Chime/Strobe Ground Corridor By West Nurse Station 57078999 1 02/01-P Chime/Strobe Ground Corridor By G-20 Patient Bath 57078998 1 02/01-P Chime/Strobe Ground Corridor By G-27 Patient Room 57078997 1 02/01-P Chime/Strobe Ground Corridor By G-34 Conference Room Exit 57078996 1 02/01-P Chime/Strobe Ground Corridor West Dining Area Fire Doors 57078995 1 02/01-P Device Total: 25
EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)
Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Releasing Device 12 12 0 12 12 Device Type Location ScanID Address Annual 2024 Releasing Device Ground Corridor By G-85 Shower Room Fire Doors 57079142 1 02/01-P Releasing Device Ground Corridor By G-83 Laundry Room Fire Doors 57079141 1 02/01-P Releasing Device Ground Corridor By G-59 Staff Breakroom Fire Doors 57079140 1 02/01-P Releasing Device Ground Corridor By G-66 Shower Fire Doors 57079139 1 02/01-P Releasing Device Ground Corridor By G-38 Kitchen Fire Doors 57079124 1 02/01-P Releasing Device Ground Corridor By G-40 Patient Room Fire Doors 57079123 1 02/01-P Releasing Device Ground Corridor By G-20 Patient Bath Fire Doors 57079118 1 02/01-P Releasing Device Ground Corridor By G-19 Meditation Room Fire Doors 57079117 1 02/01-P Releasing Device Ground Corridor By West Nurse Station Fire Doors 57079115 1 02/01-P Releasing Device Ground Corridor West Dining Area 57079114 1 02/01-P Releasing Device Ground Dining Area East Fire Doors 57079148 1 02/01-P Releasing Device Ground Dining Area East Fire Doors 57079149 1 02/01-P Device Total: 12
EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)
For periodic testing, verify that each appliance flashes. (NFPA 72-22 Table 14.4.3.2 (22)(3))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Strobe 3 3 0 3 3 Device Type Location ScanID Address Annual 2024 Strobe 1st Corridor Men’s Restroom 107 By FACU 57079024 1 02/01-P Strobe 1st Women’s Restroom 105A 57078993 1 02/01-P Strobe 1st Women’s Locker Room 105 57078991 1 02/01-P Device Total: 3
EC 02.03.05 EP 05 Annual test of fire alarm equipment for notifying off-site fire responders. NFPA 72 (2022) Table 14.4.3.2 (4)
Test all system functions and features in accordance with the equipment manufacturer's published instructions for correct operation in conformance with the applicable sections of Chapter 26. Except for DACT, actuate initiating device and verify receipt of the correct initiating device signal at the supervising station within 90 seconds. Upon completion of the test, restore the system to its functional operating condition. (NFPA 72-22 Table 14.4.3.2 (4))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Communicator 1 1 0 1 1 Device Type Location ScanID Address Annual 2024 Communicator 1st Main Electric/Transformer Room 57079190 1 02/01-P
EC 02.03.05 EP 19 Annual test of automatic smoke-detection shutdown devices for air-handling equipment. NFPA 90A (2024) 6.4.1
Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(7)(e))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Duct Detector 6 6 0 6 6 Device Type Location ScanID Address Annual 2024 Duct Detector 1st Outside Service Room AHU 3 Room 109 57079170 1-01-007 02/01-P Duct Detector 1st Outside Service Room AHU 3 Room 109 57079171 1-01-008 02/01-P Duct Detector Roof Service Room C AHU 1 57079161 1-02-031 02/01-P Duct Detector Roof Service Room C AHU 1 57079160 1-02-032 02/01-P Duct Detector Roof Service Room B AHU 2 57079164 1-02-033 02/01-P Duct Detector Roof Service Room B AHU 2 57079165 1-02-034 02/01-P
LS 02.01.34 EP 02 Protected master fire alarm control panel
Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table 14.4.3.2 (2)(1))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Control Panel 1 1 0 1 1 Device Type Location ScanID Address Annual 2024 Control Panel 1st Main Electric/Transformer Room 57079189 1 02/01-P
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
Verify the correct operation and identification of annunciators. If provided, verify the correct operation of annunciator under a fault condition. (NFPA 72-22 Table 14.4.3.2 (11))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Annunciator 3 3 0 3 3 Device Type Location ScanID Address Annual 2024 Annunciator 1st Main Lobby Entrance 57079182 1 02/01-P Annunciator Ground Corridor By East Nurse Station 57079150 1 02/01-P Annunciator Ground Corridor By West Nurse Station 57079122 1 02/01-P
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
With the batteries fully charged and connected to the charger, measure the voltage across the batteries with a voltmeter. Then, with the battery charger disconnected, load test the batteries following the manufacturer's recommendations. (NFPA 72-22 Table 14.4.3.2 (9))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Battery 8 6 2 8 8 Device Type Location ScanID Address Annual 2024 Battery 1st FACP Room BPS 3 57079173 1 02/01-P Battery 1st FACP Room BPS 3 57079174 1 02/01-P Battery 1st FACP Room BPS 2 57079176 1 02/01-P Battery 1st FACP Room BPS 2 57079177 1 02/01-P Battery 1st FACP Room BPS 1 57079179 1 02/01-P Battery 1st FACP Room BPS 1 57079180 1 02/01-P Battery 1st FACP 57079187 1 02/01-F Battery 1st FACP 57079191 1 02/01-F Device Total: 8
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table 14.4.3.2 (2)(1))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Power Supply 3 3 0 3 3 Device Type Location ScanID Address Annual 2024 Power Supply 1st Main Electric/Transformer Room BPS 3 57079175 1 02/01-P Power Supply 1st Main Electric/Transformer Room BPS 2 57079178 1 02/01-P Power Supply 1st FACP Room BPS 1 57079181 1 02/01-P
LS 02.01.50 EP 07 Annual - Elevators are fully equipped and protected
Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Elevator 2 2 0 2 2 Device Type Location ScanID Address Annual 2024 Elevator 1st Elevator Lobby 57079183 1 02/05-P Elevator Ground Elevator Lobby 57079159 1 02/02-P Device Total: 2
Battery & Power Supply Testing Generated by: BuildingReports.com
Building: VA Sepulveda Bldg 99 Control Panel: 1 - Cerberus Pyrotronics - MXL
The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Battery
Type Location Rated Ah
Rated Volts
Pre Test
Post Test
Min Ah
Tested Ah
Passed Sealed Lead Acid 1st FACP Room BPS 1 8 12 6 Sealed Lead Acid 1st FACP Room BPS 1 8 12 6 Sealed Lead Acid 1st FACP Room BPS 2 8 12 6 Sealed Lead Acid 1st FACP Room BPS 2 8 12 6 Sealed Lead Acid 1st FACP Room BPS 3 8 12 6 Sealed Lead Acid 1st FACP Room BPS 3 8 12 6
Failed/Other Sealed Lead Acid 1st FACP 18 12 Sealed Lead Acid 1st FACP 18 12
Inventory Report Generated by: BuildingReports.com
Building: VA Sepulveda Bldg 99 Control Panel: 1 - Cerberus Pyrotronics - MXL The Inventory Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years, or more are grouped together for easy reference.
Device or Type Category % of Inventory Quantity Annunciator Control 2.36% 3
Battery Control 6.30% 8 Chime/Strobe Indicating 19.69% 25 Communicator Control 0.79% 1 Control Panel Control 0.79% 1 Duct Detector Initiating 4.72% 6
Elevator Auxiliary 1.57% 2 Heat Detector Initiating 0.79% 1 Power Supply Control 2.36% 3 Pull Station Initiating 14.17% 18
Releasing Device Auxiliary 9.45% 12 Smoke Detector Initiating 23.62% 30
Strobe Indicating 2.36% 3 Tamper Switch Supervisory 6.30% 8
Waterflow Switch Initiating 4.72% 6