VA LAACC_351 E Temple St_REG4 ANN FA_01-30-24_Redacted 1.pdf
PDF 61 KB Posted
- Attached to
- H912--Fire Alarm Inspections - One Year Contract
- Solicitation number
- 36C26225Q0850
About this file
This is a Los Angeles Fire Department Fire Protection Equipment Performance Report for a fire alarm initial test conducted on January 30, 2024, at 351 E Temple St in Los Angeles. The report details a comprehensive fire alarm system inspection for a 5-story, 105,000 square foot business occupancy building constructed in 1973, which failed the initial inspection primarily due to battery replacement issues.
The report identifies multiple deficiencies across the building's fire alarm system, specifically noting that battery replacement dates are less than 5 years from the manufacturer's date. Batteries requiring replacement were found on multiple floors (5th, 4th, 3rd, 2nd, and 1st floor electrical rooms), with a total of 28 batteries (4, 6, 6, 4, and 8 batteries per floor respectively) needing replacement. The system uses a Notifier AFP 1000 addressable fire alarm control unit located in the ground floor lobby, with a central station monitoring account through Valley Alarm Co. The report indicates that all notification appliances, initiating devices, and emergency functions were largely operational, with only minor communication and monitoring system components marked as not applicable.
View the file
Other files
Show all 41
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TEST SITE INFORMATION
TEST SITE ADDRESS: (STREET) (CITY) (STATE) (ZIP) TEST SITE PHONE:
351 E TEMPLE ST LOS ANGELES CA 90012-3328
OCCUPANCY TYPE: NUMBER OF STORIES: YEAR BUILT: CONSTRUCTION TYPE: SQUARE FOOTAGE:
B - Business 5 1973 Type II 105000
RESPONSIBLE PARTY
NAME: (LAST, FIRST, MI) TITLE: FIRM OR D.B.A.:
HUNT, EDWARD RESPONSIBLE PERSON VA LAACC
MAILING ADDRESS: (STREET) (CITY) (STATE) (ZIP) PHONE:
351 E TEMPLE LOS ANGELES CA 90012 (818) 891-7711
TEST INFORMATION
INITIAL TEST DATE: TESTING AGENCY: PHONE:
01/30/2024 (
MAILING ADDRESS: (STREET) (CITY) (STATE) (ZIP)
TEST RESULTS
☐ PASS ☒ FAIL
All sections below shall be found in the following pages of this report.
SECTIONS:
I. BUILDING DESCRIPTION
II. SYSTEM DESCRIPTION
III. FINDINGS
IV. TESTING PROCEDURES/WORKSHEETS
I HEREBY CERTIFY THAT THE FIRE PROTECTION EQUIPMENT LISTED ABOVE HAS BEEN FULLY TESTED IN ACCORDANCE WITH THE CHIEF'S REGULATION NO. 4 OF THE LOS ANGELES FIRE CODE AND THAT THE RESULTS ARE ACCURATELY LISTED ABOVE AND THE
EQUIPMENT IS FULLY OPERABLE EXCEPT AS NOTED.
TESTER'S NAME: CERTIFICATE #: EXPIRATION DATE: SIGNATURE:
05/31/2026
REPAIR AND RETEST: IF DEFECTS ARE FOUND IN EQUIPMENT TESTED, CORRECTION OF SUCH DEFECTS SHALL COMMENCE FORTHWITH AND SHALL BE COMPLETED AS SOON AS
POSSIBLE, BUT IN EVERY CASE WITHIN 30 DAYS OF INITIAL TEST. THE F-340RT SHALL BE USED TO DOCUMENT THE RETEST OF DEFECTS FOUND IN SCTION III. A COPY OF
SECTION III OF THIS REPORT SHALL BE ATTACHED TO THE F-340RT PRIOR TO SUBMITTING TO THE FIRE DEPARTMENT.
REPORT SUBMITTAL INFORMATION:
ALL REPORTS ARE REQUIRED TO BE SUBMITTED TO THE LOS ANGELES CITY FIRE DEPARTMENT VIA THE COMPLIANCE ENGINE
WITHIN 7 DAYS OF TEST COMPLETION.
ENTERED BY: ENTERED DATE: ENTERED TIME:
02/06/2024 5:35 PM
LOS ANGELES FIRE DEPARTMENT
FIRE PROTECTION EQUIPMENT PERFORMANCE REPORT
Fire Alarm - Initial Test
Test Report Number
5364932
TRN 5364932 Printed Tue Feb 06 12:31:13 CST 2024
Section I - Building Description:
CHARACTERISTICS
PRIMARY OCCUPANCY TYPE B - Business FIRE CONTROL ROOM: ☐YES ☒NO
SECONDARY OCCUPANCY TYPE I-2 ELEVATOR INFORMATION: CARS BANKS
TYPE OF BUSINESS CONDUCTED PASSENGER 4 1
☐ Apartment/Condo ☐ Museum
☐ Bar/Restaurant ☐ Parking Structure
☐ Church ☒ Office Space
☐ Schools ☐ Repair Garage
☐ Day Care ☐ Retail
☐ Detention Facility ☐ Skilled Nursing
☐ Group Home ☐ Telecommunications
☐ Hospital ☐ Theatre
☐ Hotel/Motel ☐ Warehouse
☒ Medical Office/Clinic ☒ Other: VETERANS
OUTPATIENT CLINIC
FREIGHT
PARKING 2 1
NUMBER OF STAIRWAYS: 5
FIRE PUMP(S): ☒YES ☐NO
LOCATION: P-2
EMERGENCY GENERATOR(S): ☒YES ☐NO
LOCATION: P-1
PARKING STRUCTURE:
☒ UNDERGROUND ☐ DETACHED ☒ ATTACHED
NUMBER OF LEVELS BELOW GROUND: 2
UNIQUE PROPERTY FEATURES: TYPES OF OCCUPANCIES BELOW GROUND:
FULLY SPRINKLERED OUTPATIENT VETERNAS CLINIC
WITH RISER AT SOUTH STAIR #5.
S-2, PARKING
LOS ANGELES FIRE DEPARTMENT
FIRE PROTECTION EQUIPMENT PERFORMANCE REPORT
THIS PAGE BY ITSELF IS NOT A COMPLETE REPORT
Test Report Number
5364932
INITIAL TEST DATE: TEST SITE ADDRESS: (STREET NUMBER AND STREET NAME)
01/30/2024 351 E TEMPLE ST
EQUIPMENT TESTED:
Fire Alarm - Initial Test
The owner/owner(s) representative shall ensure that the appropriate permits have been secured prior to any repairs being performed.
A copy of this section shall accompany the F-340RT in all cases.
Section III - Findings: ☒SYSTEM DEFECTS FOUND ☐NO SYSTEM DEFECTS FOUND
GRAY AREAS SHALL BE FILLED OUT BY CERTIFIED TESTER PERFORMING RETEST
DEFECT # ITEM #
(SECTION IV) DESCRIPTION LOCATION RETEST
ONLY
1 3.2 Battery replacement date is less than 5 years from the date of manufacturer.
Fail
5TH FLOOR ELECTRICAL ROOMS
POWER SUPPLY BATTERIES
OUTDATED @ 2020, NEED TO
REPLACE 4) 12VDC 7AH
BATTERIES
☐PASS
2 4TH FLOOR ELECTRICAL ROOMS
POWER SUPPLY BATTERIES
OUTDATED @ 2020, NEED TO
REPLACE 6) 12VDC 7AH
BATTERIES
☐PASS
3 3RD FLOOR ELECTRICAL ROOMS
POWER SUPPLY BATTERIES
OUTDATED @ 2020, NEED TO
REPLACE 6) 12VDC 7AH
BATTERIES
☐PASS
4 2ND FLOOR ELECTRICAL ROOMS
POWER SUPPLY BATTERIES
OUTDATED @ 2020, NEED TO
REPLACE 4) 12VDC 7AH
BATTERIES
☐PASS
5 1ST FLOOR ELECTRICAL ROOMS
POWER SUPPLY BATTERIES
OUTDATED @ 20202, NEED TO
REPLACE 8) 12VDC 7AH
BATTERIES
☐PASS
6 SEE FA WORD DOCUMENT REPORT
FOR REFERENCE. NFPA CODE
REFERENCE BATTERIES REQUIRE
REPLACING AFTER 3 YEARS OF
MANUFACTURE DATE.
☐PASS
INITIAL TEST PERFORMED BY
TESTER'S NAME: CERTIFICATE #: EXPIRATION DATE: SIGNATURE:
05/31/2026
PHONE NUMBER OF TESTING AGENCY: TESTING AGENCY: STATE: ZIP:
RETEST DATE: RETEST PERFORMED BY
RE-TESTER'S NAME: CERTIFICATE #: EXPIRATION DATE: RE-TESTER'S SIGNATURE: PHONE NUMBER:
LOS ANGELES FIRE DEPARTMENT
FIRE PROTECTION EQUIPMENT PERFORMANCE REPORT
THIS PAGE BY ITSELF IS NOT A COMPLETE REPORT
Test Report Number
5364932
INITIAL TEST DATE: TEST SITE ADDRESS: (STREET NUMBER AND STREET NAME)
01/30/2024 351 E TEMPLE ST
EQUIPMENT TESTED:
Fire Alarm - Initial Test
All testing procedures below were performed in accordance with the Los Angeles Fire Department Chief's Regulation No. 4 requirements, applicable sections of NFPA 72 and other approved publications.
ITEM # DESCRIPTION
SECTION II - SYSTEM DESCRIPTION: FIRE ALARM
Fire Alarm Control Unit (F.A.C.U.) Information.
Manufacturer:
NOTIFIER
Model #:
AFP 1000 ADDRESSABLE SYSTEM
Location:
GROUND FLOOR LOBBY/ENTRANCE
Fire Alarm Annunciator Panel Location(s) (FAAP):
MAIN ENTRANCE SECURITY STATION
Fire department connection (FDC) locations:
STREETSIDE
Fire Alarm Serves:
☒Entire Building
☐Multiple Buildings
☐Partial Areas
If the Fire Alarm serves multiple buildings, give addresses:
NA
Emergency Voice/Alarm Communication:
No
Built-in Supervising Station Communicator? (If yes, see Item #12)
No
Type of Supervising Station:
☒Central Station
☐Proprietary
Supervising Station Account Information
Account #:
VALLEY ALARM CO. ACT #LZ6303
Phone #:
(818) 787-0999
Address:
804 PICO ST
City:
SAN FERNANDO
State:
TESTER'S NAME: CERTIFICATE #: EXPIRATION DATE: PHONE NUMBER OF TESTING AGENCY:
05/31/2026
LOS ANGELES FIRE DEPARTMENT
FIRE PROTECTION EQUIPMENT PERFORMANCE REPORT
THIS PAGE BY ITSELF IS NOT A COMPLETE REPORT
Test Report Number
5364932
INITIAL TEST DATE: TEST SITE ADDRESS: (STREET NUMBER AND STREET NAME)
01/30/2024 351 E TEMPLE ST
EQUIPMENT TESTED:
Fire Alarm - Initial Test
ITEM # DESCRIPTION
CA
Zip code:
91340
Type of Communication Pathway(s): (Check all that apply)
☒Digital Alarm Communicator Transmitter (D.A.C.T.)
☒Digital Cellular (Global Ssytem for Mobile /GSM)
☐Internet Protocol (I.P. D.A.C.T.)
☐Other
Two-Way Telephone Communication (Firefighter Phones):
☐Sound Powered
☐Amplified
Types of Initiating Devices:
☒Smoke Detector
☒Heat Detector
☐Beam Detector
☒Duct Detector
☒Manual Pull
☒Water Flow
☒Tamper Switch
Types of Notification Appliances:
☒Strobes
☐Horns
☐Bells
☐Horn/Strobe
☒Speaker/Strobe
☐Speaker
☐Chimes
☐Mini Horn
☐Chime/Strobe
Fire Alarm Control Auxiliary Function(s):
☒Elevator Recall
☐Fan Shutdown
☒Heating/Ventilation/Air Conditioning (HVAC) Shutdown
☒Magnetic Door Hold Open Device Release
☐Stairwell Pressurization
☐Smoke Management
☐Activation of Stairwell Door(s)
☐Activation of Other Automatic Closing Fire Assemblies tied to Fire Alarm
☐Special Extinguishing Systems
☐Foam Systems
☐Other Systems
TESTER'S NAME: CERTIFICATE #: EXPIRATION DATE: PHONE NUMBER OF TESTING AGENCY:
05/31/2026
LOS ANGELES FIRE DEPARTMENT
FIRE PROTECTION EQUIPMENT PERFORMANCE REPORT
THIS PAGE BY ITSELF IS NOT A COMPLETE REPORT
Test Report Number
5364932
INITIAL TEST DATE: TEST SITE ADDRESS: (STREET NUMBER AND STREET NAME)
01/30/2024 351 E TEMPLE ST
EQUIPMENT TESTED:
Fire Alarm - Initial Test
Automatic Closing Fire Assemblies Type(s) & Locations:
24VDC MAGNETICALLY HELD FIRE DOORS THROUGHOUT CORRIDORS
Special Extinguishing Systems Types & Locations:
NA
Foam Systems Type & Locations:
NA
Other Systems Type and Locations:
NA
1.0 NOTIFICATION PASS FAIL N/A
1.1 Fire Department dispatch, supervising station, & building occupants notified prior to the start of the test.
Yes
2.0 INSPECTION - If item 2.3 indicates "fail", the test shall not be performed
PASS FAIL N/A
2.1 An Accurate Sequence of Operation Matrix is provided at the Fire Control Panel. ☒ ☐
2.2 Fire alarm operating instructions within 3 feet of FACP/FACU. ☒ ☐
2.3 Fire alarm control panel free of troubles OR the trouble condition is known. ☒ ☐
3.0 POWER SUPLLIES PASS FAIL N/A
Total Amount:
15)
Amount Tested:
15) THROUGHOUT ALL FLOORS IDF/ELECTRICAL ROOMS
3.1 Batteries are free of physical damage, leaks, loose connection, and corrosion. ☒ ☐ ☐
3.2 Battery replacement date is less than 5 years from the date of manufacturer. ☐ ☒ ☐
3.3 All batteries labeled with manufacture date. ☒ ☐ ☐
3.4 Approved artificial LOAD TESTER may be used. Make:
A.C.T
Model:
INTELLIGENT TESTER
3.5 System was tested on secondary battery power in general alarm for 5 minutes at full load or 15 minutes at full load for systems with voice evacuation. An approved battery load tester may be used instead of testing the system on secondary battery.
3.6 Primary power disconnected and trouble signal verified for loss of power. ☒ ☐ ☐
3.7 Dedicated fire alarm circuit verified and identified. ☒ ☐
3.8 Dedicated fire alarm circuit locked or in a secured room. ☒ ☐
4.0 CONTROL PANEL(S) PASS FAIL N/A
TESTER'S NAME: CERTIFICATE #: EXPIRATION DATE: PHONE NUMBER OF TESTING AGENCY:
05/31/2026
LOS ANGELES FIRE DEPARTMENT
FIRE PROTECTION EQUIPMENT PERFORMANCE REPORT
THIS PAGE BY ITSELF IS NOT A COMPLETE REPORT
Test Report Number
5364932
INITIAL TEST DATE: TEST SITE ADDRESS: (STREET NUMBER AND STREET NAME)
01/30/2024 351 E TEMPLE ST
EQUIPMENT TESTED:
Fire Alarm - Initial Test
4.1 The correct identification and location indicated for alarms, supervisory, & trouble signals. ☒ ☐
4.2 Correct receipt of power supply supervision (AC power loss and secondary power loss). ☒ ☐ ☐
4.3 Correct receipt of subsequent alarms. ☒ ☐ ☐
4.4 Signals at remote annunciator panel consistent with the fire alarm panel. ☒ ☐ ☐
4.5 Other Panel Functions: Panel Silence, Lamp test, Signal Silence, Etc. ☒ ☐ ☐
5.0 INITIATING DEVICES TESTED - Initiating devices shall be
tested as intended to operate.
PASS FAIL N/A
Any devices not tested requires an explanation at the end of Section IV. (Minimum of 90% required)
5.1 Manual Pull Stations ☒ ☐ ☐
5.2 System Smoke Detectors ☒ ☐ ☐
5.3 Duct Detector(s) ☒ ☐ ☐
5.4 Air Sampling Detectors ☐ ☐ ☒
5.5 Projected Beam Detectors ☐ ☐ ☒
5.6 Heat Detector: Restorable ☒ ☐ ☐
5.7 Heat Detector: Non Restorable ☐ ☐ ☒
5.8 Water Flow Devices ☒ ☐ ☐
5.9 Valve Supervisory Switches ☒ ☐ ☐
5.10 Water Flow (interior audible) within 20-60 seconds. ☒ ☐ ☐
5.11 Outside Electric Sprinkler Bell Within 90 Seconds. ☒ ☐ ☐
6.0 AUDIBLE AND VISUAL NOTIFICATION APPLIANCES TESTED PASS FAIL N/A
Any devices not tested requires an explanation at the end of Section IV. (Minimum of 90% required).
Prior to 1993 - 10 dba above ambient sound level in the area.
1993 to 2000 - 15 dba above ambient (minimum 75 dba, maximum 120 dba).
2001 and later - 15 dba above ambient (minimum 75 dba, maximum 110dba).
Non-ADA strobes installed prior to 1998 may not have the capability to b synchronized.
6.1 Bells ☒ ☐ ☐
6.2 Chimes ☐ ☐ ☒
6.3 Speakers ☐ ☐ ☒
6.4 Horns ☐ ☐ ☒
6.5 Horn/Strobes ☐ ☐ ☒
6.6 Speaker/Strobes ☒ ☐ ☐
6.7 Mini Horns ☐ ☐ ☒
TESTER'S NAME: CERTIFICATE #: EXPIRATION DATE: PHONE NUMBER OF TESTING AGENCY:
05/31/2026
LOS ANGELES FIRE DEPARTMENT
FIRE PROTECTION EQUIPMENT PERFORMANCE REPORT
THIS PAGE BY ITSELF IS NOT A COMPLETE REPORT
Test Report Number
5364932
INITIAL TEST DATE: TEST SITE ADDRESS: (STREET NUMBER AND STREET NAME)
01/30/2024 351 E TEMPLE ST
EQUIPMENT TESTED:
Fire Alarm - Initial Test
6.8 ADA Strobes flashed in synchronization when more than 2 are visible in the field of view. ☒ ☐ ☐
6.9 Non-ADA Strobes ☐ ☐ ☒
6.10 Other ☐ ☐ ☒
6.11 Flash rate between 60 and 120 times per minute. ☒ ☐ ☐
7.0 EMERGENCY VOICE/ALARM COMMUNICATIONS FUNCTION/EQUIPMENT PASS FAIL N/A
7.1 Required Voice communication is clear in all occupiable areas within the structure. ☒ ☐ ☐
7.2 Elevator Lobbies ☒ ☐ ☐
7.3 Elevators ☒ ☐ ☐
7.4 Storage Areas ☒ ☐ ☐
7.5 Mechanical Rooms ☒ ☐ ☐
7.6 Electrical Rooms ☒ ☐ ☐
7.7 Conference Rooms ☒ ☐ ☐
7.8 Restrooms ☒ ☐ ☐
7.9 Balconies & Patios above 1st floor ☐ ☐ ☒
7.10 When microphone is activated voice communications overrides fire alarm audible signals. ☐ ☐ ☒
7.11 A.D.A. Strobes (continue or discontinue) to flash when audible signals are silenced in accordance with approved sequence of operation. ☒ ☐ ☐
☐Continue
☒Discontinue
7.12 Selective Paging Function ☐ ☐ ☒
7.13 All Call Function ☐ ☐ ☒
8.0 TWO-WAY TELEPHONE COMMUNICATION SERVICE (FIREFIGHTER
PHONES)
PASS FAIL N/A
8.1 Minimum six (6) handheld phones. ☒ ☐ ☐
8.2 Five (5) amplified telephone stations were operated simultaneously in common talk mode, voice quality and clarity verified. ☐ ☐ ☒
8.3 "Off-Hook" condition initiated a notification signal at the command center. ☐ ☐ ☒
8.4 Selective Talk Telephone initiated a distinctive visible indicator for each selectable circuit. ☐ ☐ ☒
8.5 Three (3) sound powered telephone stations were operated simultaneously in common talk mode, voice quality and clarity verified. ☒ ☐ ☐
9.0 TWO-WAY TELEPHONE COMMUNICATION SERVICE (TELEPHONE JACKS) PASS FAIL N/A
9.1 In each enclosed stairway at entry-level. ☒ ☐ ☐
9.2 Is the exterior of enclosed exit stairway exiting to a public way. ☒ ☐ ☐
Total # of Elevator Cars. ☐
TESTER'S NAME: CERTIFICATE #: EXPIRATION DATE: PHONE NUMBER OF TESTING AGENCY:
05/31/2026
LOS ANGELES FIRE DEPARTMENT
FIRE PROTECTION EQUIPMENT PERFORMANCE REPORT
THIS PAGE BY ITSELF IS NOT A COMPLETE REPORT
Test Report Number
5364932
INITIAL TEST DATE: TEST SITE ADDRESS: (STREET NUMBER AND STREET NAME)
01/30/2024 351 E TEMPLE ST
EQUIPMENT TESTED:
Fire Alarm - Initial Test
6.0
9.3 Total # of the elevator car jacks tested. ☒ ☐ ☐
6.0
9.4 In elevator machine room. ☒ ☐ ☐
Total # of elevator lobbies. ☐
2.0
9.5 Total # of elevator lobby jacks tested. ☒ ☐ ☐
2.0
9.6 In each lobby exiting to a public way. ☒ ☐ ☐
9.7 In the Fire Control Room. ☐ ☐ ☒
9.8 At the Fire Pump Room. ☐ ☐ ☒
9.9 At the Generator Room. ☐ ☐ ☒
10.0 LIFE SAFETY CONTROL FUNCTIONS PASS FAIL N/A
10.1 Elevator lobby smoke detector recalled elevator. ☒ ☐ ☐
10.2 Elevator recalled to the predetermined primary & alternate recall floors. ☒ ☐ ☐
10.3 Elevator machine room smoke detector recalled elevator. ☒ ☐ ☐
10.4 Elevator machine room shunt trip reported back to fire alarm panel. ☒ ☐ ☐
10.5 Elevator hoist-way smoke detector recalled elevator. ☐ ☐ ☒
10.6 Stairwell pressurization activated. ☐ ☐ ☒
10.7 Smoke control system activated. ☐ ☐ ☒
10.8 Heating, ventilation, and air conditioning system and damper control activated. ☒ ☐ ☐
10.9 Fan control activated. ☐ ☐ ☒
10.10 Stairwell doors unlocked. ☐ ☐ ☒
10.11 Magnetic door holders released. ☒ ☐ ☐
10.12 Other activating devices & control functions. ☐ ☐ ☒
11.0 SUPERVISORY SIGNAL INDICATION PASS FAIL N/A
11.1 Fire pump not in automatic mode. ☒ ☐ ☐
11.2 Water tank level indicator switch. ☐ ☐ ☒
11.3 Water tank temperature indicator switch. ☐ ☐ ☒
11.4 Air pressure switch(s). ☐ ☐ ☒
11.5 Valve supervisory switch(s) within 2 turns or 1/5 travel. ☒ ☐ ☐
11.6 Special extinguishing system(s). ☐ ☐ ☒
11.7 Emergency generator not in automatic mode. ☒ ☐ ☐
TESTER'S NAME: CERTIFICATE #: EXPIRATION DATE: PHONE NUMBER OF TESTING AGENCY:
05/31/2026
LOS ANGELES FIRE DEPARTMENT
FIRE PROTECTION EQUIPMENT PERFORMANCE REPORT
THIS PAGE BY ITSELF IS NOT A COMPLETE REPORT
Test Report Number
5364932
INITIAL TEST DATE: TEST SITE ADDRESS: (STREET NUMBER AND STREET NAME)
01/30/2024 351 E TEMPLE ST
EQUIPMENT TESTED:
Fire Alarm - Initial Test
12.0 INTEGRATED COMMUNICATOR TRANSMITTER PASS FAIL N/A
Do Not Use This Section For Separate Supervising Station Alarm Control Panels.
12.2 Is Tester certified in supervising station fire alarm.
Yes
12.2 Two (2) means of transmission verified at test site. ☒ ☐ ☐
12.3 Signals sent separately via primary and secondary means of transmission. ☒ ☐ ☐
12.4 Activation and restoration of each type of initiating and supervisory devices verified on-site and at the supervising station within 90 seconds. ☒ ☐ ☐
12.5 Primary communication signal was disconnected and trouble signal indicated on-site and at the supervising station within 200 seconds (4 minutes for DACTS). ☒ ☐ ☐
12.6 Secondary means of communication disconnected and a trouble signal indicated on-site and at the supervising station within 200 seconds (4 minutes for DACTS). ☒ ☐ ☐
12.7 Primary and secondary power loss and restoration indicated a trouble signal within
200 seconds at the test-site. ☒ ☐ ☐
12.8 An open circuit connection to one initiating device and one notification appliance
(when applicable) was opened and indication and restoration was verified on-site and at the supervising station within 200 seconds.
AREAS/DEVICES/APPLIANCES NOT ACCESSIBLE FOR TESTING:
A minimum of 90% of testing is required. If less than 90% testing is conducted, DO NOT SUBMIT THIS REPORT.
Description:
END OF REPORT
ALL FINDINGS INDICATING “FAIL” ARE LISTED IN SECTION III (YELLOW SECTION) AND HAVE BEEN POPULATED WITH THE ITEM
DESCRIPTION, NUMBER AND LOCATION.
I HEREBY CERTIFY THAT THE FIRE PROTECTION EQUIPMENT HAS BEEN FULLY TESTED IN ACCORDANCE WITH THE CHIEF’S REGULATION NO. 4 OF THE LOS ANGELES FIRE CODE AND APPLICABLE SECTIONS OF THE NFPA 72 AND OTHER APPROVED PUBLICATIONS. THE RESULTS ARE ACCURATELY LISTED AND THE EQUIPMENT IS FULLY OPERABLE EXCEPT AS NOTED. YOU ARE A CERTIFIED REGULATION NO. 4 TESTER WITH A VALID CERTIFICATION OR HAVE BEEN AUTHORIZED TO SUBMIT THE INFORMATION
ON BEHALF OF A CERTIFIED CHIEFS REGULATION NO. 4 TESTER.
I ACCEPT
☒Yes
TESTER'S NAME: CERTIFICATE #: EXPIRATION DATE: PHONE NUMBER OF TESTING AGENCY:
05/31/2026
LOS ANGELES FIRE DEPARTMENT
FIRE PROTECTION EQUIPMENT PERFORMANCE REPORT
THIS PAGE BY ITSELF IS NOT A COMPLETE REPORT
Test Report Number
5364932
INITIAL TEST DATE: TEST SITE ADDRESS: (STREET NUMBER AND STREET NAME)
01/30/2024 351 E TEMPLE ST
EQUIPMENT TESTED:
Fire Alarm - Initial Test
File details come from the government source that posted it. Updated .