This document is an Annual Fire Pump Inspection and Testing Report for the VA Sepulveda facility located at 16111 Plummer Street, Building 200 in North Hills, California. The report details a comprehensive inspection of an electric fire pump manufactured by Peerless (Model 4AEF10G, Serial Number 50020538) with a Tornatech controller, performed on 6/12/24. The inspection covers multiple aspects including pump start/stop pressures, pump house conditions, control valves, suction and discharge pressures, and electrical system status, with all items marked as passing the required tests.
Key technical details include the pump's rated specifications of 70 PSI, 500 GPM, and 3525 RPM, with a maximum suction pressure of 34 PSI and a max shutoff pressure of 141 PSI. The performance test was conducted at 0%, 50%, 100%, and 150% rated flow, with flow meters and other testing equipment used. The pump was tested with 2.5" nozzle orifices, achieving flows of 0, 250, 500, and 750 GPM at various pressures, with all automatic and manual starts deemed satisfactory. The report was prepared by James Liles and certified that all fire protection equipment was fully inspected, tested, and maintained in accordance with NFPA 25 and California Code of Regulations, Title 19.
View the file
Other files
Show all 41
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
File details come from the government source that posted it. Updated .