VA Sepulveda_16111 Plummer St_Bldg 201_ANN SP_02-19-24_Redacted 10.pdf
PDF 632 KB Posted
- Attached to
- H912--Fire Alarm Inspections - One Year Contract
- Solicitation number
- 36C26225Q0850
About this file
This document is an annual fire sprinkler system inspection report for the VA Sepulveda facility located at 16611 Plummer St. in North Hills, California. The inspection was conducted on 02-19-2024 and covers a wet pipe fire sprinkler system in a building constructed in 1997. The report indicates no defects were noted during the inspection, with passing grades for quarterly and annual inspections across various system components including control valves, water flow alarm devices, supervisory devices, and sprinklers. The inspection covers three system risers located at the rear of the building, with riser diameters of 2-1/2" and main drain diameters of 1-1/4", and documents pressure tests showing consistent static pressures between 75-95 PSI.