SV2401240151 - 351 E Temple St - ANN FP - 6-12-24_Redacted 8.pdf
PDF 227 KB Posted
- Attached to
- H912--Fire Alarm Inspections - One Year Contract
- Solicitation number
- 36C26225Q0850
About this file
This document is a Los Angeles Fire Department Fire Protection Equipment Performance Report for a fire pump initial test conducted on June 12, 2024, at 351 E Temple St, Los Angeles. The test was performed on a Patterson horizontal split case electric fire pump (Model 6x5 MAC) with a rated capacity of 500 GPM at 75 PSI, located in the P2 level fire pump room. The pump serves the entire building and is part of a combined standpipe and sprinkler system, with water supply from the public main.
The fire pump passed all inspection and operational tests, including six manual and six automatic starts, churn tests, and discharge tests at 50%, 100%, and 150% of rated capacity. The test verified proper pump performance, with suction pressures maintained and no system defects identified. The testing was conducted in accordance with Los Angeles Fire Department Chief's Regulation No. 4, NFPA 25, and other approved publications, with the test performed by a certified tester and completed on June 12, 2024.
View the file
Other files
Show all 41
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TEST SITE INFORMATION
TEST SITE ADDRESS: (STREET) (CITY) (STATE) (ZIP) TEST SITE PHONE:
351 E TEMPLE ST LOS ANGELES CA 90012-3328
OCCUPANCY TYPE: NUMBER OF STORIES: YEAR BUILT: CONSTRUCTION TYPE: SQUARE FOOTAGE:
B - Business 5 1973 Type II 105000
RESPONSIBLE PARTY
NAME: (LAST, FIRST, MI) TITLE: FIRM OR D.B.A.:
HUNT, EDWARD RESPONSIBLE PERSON VA LAACC
MAILING ADDRESS: (STREET) (CITY) (STATE) (ZIP) PHONE:
351 E TEMPLE LOS ANGELES CA 90012 (818) 891-7711
TEST INFORMATION
INITIAL TEST DATE: TESTING AGENCY: PHONE:
06/12/2024
MAILING ADDRESS: (STREET) (CITY) (STATE) (ZIP)
TEST RESULTS
☒ PASS ☐ FAIL
All sections below shall be found in the following pages of this report.
SECTIONS:
I. BUILDING DESCRIPTION
II. SYSTEM DESCRIPTION
III. FINDINGS
IV. TESTING PROCEDURES/WORKSHEETS
I HEREBY CERTIFY THAT THE FIRE PROTECTION EQUIPMENT LISTED ABOVE HAS BEEN FULLY TESTED IN ACCORDANCE WITH THE CHIEF'S REGULATION NO. 4 OF THE LOS ANGELES FIRE CODE AND THAT THE RESULTS ARE ACCURATELY LISTED ABOVE AND THE
EQUIPMENT IS FULLY OPERABLE EXCEPT AS NOTED.
TESTER'S NAME: CERTIFICATE #: EXPIRATION DATE: SIGNATURE:
LILES, JAMES R4565 12/31/2025
REPAIR AND RETEST: IF DEFECTS ARE FOUND IN EQUIPMENT TESTED, CORRECTION OF SUCH DEFECTS SHALL COMMENCE FORTHWITH AND SHALL BE COMPLETED AS SOON AS
POSSIBLE, BUT IN EVERY CASE WITHIN 30 DAYS OF INITIAL TEST. THE F-340RT SHALL BE USED TO DOCUMENT THE RETEST OF DEFECTS FOUND IN SCTION III. A COPY OF
SECTION III OF THIS REPORT SHALL BE ATTACHED TO THE F-340RT PRIOR TO SUBMITTING TO THE FIRE DEPARTMENT.
REPORT SUBMITTAL INFORMATION:
ALL REPORTS ARE REQUIRED TO BE SUBMITTED TO THE LOS ANGELES CITY FIRE DEPARTMENT VIA THE COMPLIANCE ENGINE
WITHIN 7 DAYS OF TEST COMPLETION.
ENTERED BY: ENTERED DATE: ENTERED TIME:
06/14/2024 7:56 AM
LOS ANGELES FIRE DEPARTMENT
FIRE PROTECTION EQUIPMENT PERFORMANCE REPORT
Fire Pump - Initial Test
Test Report Number
5892756
TRN 5892756 Printed Tue Jun 11 19:27:15 CDT 2024
Section I - Building Description:
CHARACTERISTICS
PRIMARY OCCUPANCY TYPE B - Business FIRE CONTROL ROOM: ☐YES ☒NO
SECONDARY OCCUPANCY TYPE I-2 ELEVATOR INFORMATION: CARS BANKS
TYPE OF BUSINESS CONDUCTED PASSENGER 4 1
☐ Apartment/Condo ☐ Museum
☐ Bar/Restaurant ☐ Parking Structure
☐ Church ☒ Office Space
☐ Schools ☐ Repair Garage
☐ Day Care ☐ Retail
☐ Detention Facility ☐ Skilled Nursing
☐ Group Home ☐ Telecommunications
☐ Hospital ☐ Theatre
☐ Hotel/Motel ☐ Warehouse
☒ Medical Office/Clinic ☒ Other: VETERANS
OUTPATIENT CLINIC
FREIGHT
PARKING 2 1
NUMBER OF STAIRWAYS: 5
FIRE PUMP(S): ☒YES ☐NO
LOCATION: P-2
EMERGENCY GENERATOR(S): ☒YES ☐NO
LOCATION: P-1
PARKING STRUCTURE:
☒ UNDERGROUND ☐ DETACHED ☒ ATTACHED
NUMBER OF LEVELS BELOW GROUND: 2
UNIQUE PROPERTY FEATURES: TYPES OF OCCUPANCIES BELOW GROUND:
FULLY SPRINKLERED OUTPATIENT VETERNAS CLINIC
WITH RISER AT SOUTH STAIR #5.
S-2, PARKING
LOS ANGELES FIRE DEPARTMENT
FIRE PROTECTION EQUIPMENT PERFORMANCE REPORT
THIS PAGE BY ITSELF IS NOT A COMPLETE REPORT
Test Report Number
5892756
INITIAL TEST DATE: TEST SITE ADDRESS: (STREET NUMBER AND STREET NAME)
06/12/2024 351 E TEMPLE ST
EQUIPMENT TESTED:
Fire Pump - Initial Test
The owner/owner(s) representative shall ensure that the appropriate permits have been secured prior to any repairs being performed.
A copy of this section shall accompany the F-340RT in all cases.
Section III - Findings: ☐SYSTEM DEFECTS FOUND ☒NO SYSTEM DEFECTS FOUND
GRAY AREAS SHALL BE FILLED OUT BY CERTIFIED TESTER PERFORMING RETEST
DEFECT # ITEM #
(SECTION IV) DESCRIPTION LOCATION RETEST
ONLY
INITIAL TEST PERFORMED BY
SIGNATURE:
STATE: ZIP:
RETEST DATE: RETEST PERFORMED BY
RE-TESTER'S NAME: CERTIFICATE #: EXPIRATION DATE: RE-TESTER'S SIGNATURE: PHONE NUMBER:
LOS ANGELES FIRE DEPARTMENT
FIRE PROTECTION EQUIPMENT PERFORMANCE REPORT
THIS PAGE BY ITSELF IS NOT A COMPLETE REPORT
Test Report Number
5892756
INITIAL TEST DATE: TEST SITE ADDRESS: (STREET NUMBER AND STREET NAME)
06/12/2024 351 E TEMPLE ST
EQUIPMENT TESTED:
Fire Pump - Initial Test
All testing procedures below were performed in accordance with the Los Angeles Fire Department Chief's Regulation No. 4 requirements, applicable sections of NFPA 25 and other approved publications.
ITEM # DESCRIPTION
SECTION II - SYSTEM DESCRIPTION: STATIONARY FIRE PUMP
Type of Fire Pump:
Horizontal Split Case
Pump ID Number:
Pump Manufacturer:
Patterson
Model#:
6x5 MAC
Serial#:
FP-C000224876-01-01
Pump: Rated Capacity (GPM/Flow):
Rated Head (Pressure/PSI):
Rated RPM (Speed):
Pump Configuration:
☐Single
☐Series
☐Parallel
Vertical Zones:
☐Low Zone
☐Mid Zone
☐High Zone
☒No
Type of Driver:
☐Diesel Engine
☒Electric Motor
☐Gasoline Engine
Driver Manufacturer:
WEG
Serial No.:
1078478151
Type of Controller:
TESTER'S NAME: CERTIFICATE #: EXPIRATION DATE: PHONE NUMBER OF TESTING AGENCY:
12/31/2025
LOS ANGELES FIRE DEPARTMENT
FIRE PROTECTION EQUIPMENT PERFORMANCE REPORT
THIS PAGE BY ITSELF IS NOT A COMPLETE REPORT
Test Report Number
5892756
INITIAL TEST DATE: TEST SITE ADDRESS: (STREET NUMBER AND STREET NAME)
06/12/2024 351 E TEMPLE ST
EQUIPMENT TESTED:
Fire Pump - Initial Test
ITEM # DESCRIPTION
☐Diesel
☒Electric
Fire Pump Room/Location
P2 Level
Test Header Location:
N/A
Number of Test Header Hose Valve Outlets:
N/A
Test Header Discharge Location:
☐To Atmosphere
☐To Water Tank
Water Supply:
☒Public Main
☐Water Tank Above Ground
☐Water Tank Below Ground
Refill Valve(s):
☐Automatic
☐Manual
Pump Serves:
☐Sprinkler System Only
☒Combined Standpipe & Sprinkler
☐Class III Combination
Maintenence/Jockey Pump
☒Yes
☐No
Fire department connection (FDC) locations:
Temple St
Fire Pump Serves:
☒Entire building
☐Multiple buildings
☐Partial areas
If the Fire Pump serves multiple buildings, give addresses:
N/A
If the Fire Pump serves partial areas, give areas:
N/A
TESTER'S NAME: CERTIFICATE #: EXPIRATION DATE: PHONE NUMBER OF TESTING AGENCY:
12/31/2025
LOS ANGELES FIRE DEPARTMENT
FIRE PROTECTION EQUIPMENT PERFORMANCE REPORT
THIS PAGE BY ITSELF IS NOT A COMPLETE REPORT
Test Report Number
5892756
INITIAL TEST DATE: TEST SITE ADDRESS: (STREET NUMBER AND STREET NAME)
06/12/2024 351 E TEMPLE ST
EQUIPMENT TESTED:
Fire Pump - Initial Test
All testing procedures below were performed in accordance with the Los Angeles Fire Department Chief's Regulation No. 4 requirements, applicable sections of NFPA 25 and other approved publications.
ITEM # DESCRIPTION
SECTION IV - TESTING PROCUEDURES: STATINOARY FIRE PUMP ASSEMBLY PASS FAIL N/A
1.O SCHEDULING/NOTIFICATION PASS FAIL N/A
1.1 Fire Department dispatch, supervising station & building occupants notified prior to the start of the test.
Yes
2.0 INSPECTION PASS FAIL N/A
2.1 Fire pump piping and valves are free of leaks and excessive corrosion. ☒ ☐ ☐
2.2 Fire pump controller and remote pump status panel (if applicable) indicates proper status. ☒ ☐ ☐
2.3 Fire pump water supply was available. ☒ ☐ ☐
2.4 Small drips of water was observed at the pump packing glands while pump is off. ☒ ☐ ☐
2.5 All gauges are not damaged and legible and in good working order. ☒ ☐ ☐
2.6 Gauges are accurate within 3% of full scale as determined by a calibrated comparison gauge. ☒ ☐ ☐
2.7 Pump rated capacity (Flow), head (pressure), and RPM was obtained from pump name plate. ☒ ☐ ☐
2.8 Batteries are free of physical damage, leaks, loose connections, and corrosion. ☐ ☐ ☒
2.9 Battery water level & voltage readings checked. ☐ ☐ ☒
2.10 Diesel driver oil, water, and fluid levels checked. ☐ ☐ ☒
3.0 OPERATIONAL TESTS PASS FAIL N/A
3.1 Six manual starts were conducted by use of a switch, push button, or manual start handle. ☒ ☐ ☐
3.2 Six automatic starts were conducted by dropping the pressures at the most remote location and the pressure sensing line. ☒ ☐ ☐
3.3 Churn test was conducted (0%) with the fire pump discharge outlets closed (except for minimum flow pump cooling) ☒ ☐ ☐
3.4 Fire pump discharge was tested at 50% of its rated capacity and pressure. ☒ ☐ ☐
3.5 Fire pump discharge was tested at 100% of its rated capacity and pressure. ☒ ☐ ☐
3.6 Fire pump discharge was tested at 150% of its rated capacity and pressure. ☒ ☐ ☐
Note: Where pump is unable to operate at 150% of its rated capacity due to lack of supply from the city main the maximum flow may be allowed with approval the LAFD.
3.7 Pump operated at less than 150% but operated at the maximum capacity allowed by
LAFD. ☒ ☐ ☐
3.8 At 150% of its rated capacity, the pump operated at 65% of its rated pressure/head. ☒ ☐ ☐
3.9 Pump is fed directly from a city main and the suction pressure did not fall below
20 psi at any point during flow testing. ☒ ☐ ☐
3.10 Pump is fed from a suction tank with its base at or above the same level as the pump and the suction pressure did not fall below -3 psi at any point during flow testing.
TESTER'S NAME: CERTIFICATE #: EXPIRATION DATE: PHONE NUMBER OF TESTING AGENCY:
12/31/2025
LOS ANGELES FIRE DEPARTMENT
FIRE PROTECTION EQUIPMENT PERFORMANCE REPORT
THIS PAGE BY ITSELF IS NOT A COMPLETE REPORT
Test Report Number
5892756
INITIAL TEST DATE: TEST SITE ADDRESS: (STREET NUMBER AND STREET NAME)
06/12/2024 351 E TEMPLE ST
EQUIPMENT TESTED:
Fire Pump - Initial Test
ITEM # DESCRIPTION
3.11 Circulation relief valve operated properly. ☒ ☐ ☐
3.12 Pressure relief valve operated properly. ☐ ☐ ☒
3.13 Heat exchanger checked for proper operation. ☐ ☐ ☒
3.14 Pump was checked for unusual noises or vibrations. ☒ ☐ ☐
3.15 Packing box(s) bearings, and pump was checked for overheating. ☒ ☐ ☐
3.16 Diesel driven pump ran for a minimum of 30 minutes ☐ ☐ ☒
3.17 Electric motor driven pump ran for a minimum of 10 minutes. ☒ ☐ ☐
3.18 Pumps arranged to start in series started in intervals of 5 to 10 seconds. ☐ ☐ ☒
3.19 Water tank automatic refill valves were observed for proper operation. ☐ ☐ ☒
Attach - Fire pump worksheet and pump curve sheet.
3.20 LAFD fire pump worksheet and pump curve sheet is attached for the pump listed in Section II of this report.
Yes
AREAS/DEVICES/APPLIANCES NOT ACCESSIBLE FOR TESTING
A minimum of 90% of testing is required. If less than 90% testing is conducted do not submit this report.
Description:
END OF REPORT
ALL FINDINGS INDICATING “FAIL” ARE LISTED IN SECTION III (YELLOW SECTION) AND HAVE BEEN POPULATED WITH THE ITEM
DESCRIPTION, NUMBER AND LOCATION.
THE RESULTS ARE ACCURATELY LISTED AND THE EQUIPMENT IS FULLY OPERABLE EXCEPT AS NOTED. YOU ARE A CERTIFIED REGULATION NO. 4 TESTER WITH A VALID CERTIFICATION OR HAVE BEEN AUTHORIZED TO SUBMIT THE INFORMATION ON BEHALF
OF A CERTIFIED CHIEFS REGULATION NO. 4 TESTER.
I ACCEPT
☒Yes
TESTER'S NAME: CERTIFICATE #: EXPIRATION DATE: PHONE NUMBER OF TESTING AGENCY:
12/31/2025
LOS ANGELES FIRE DEPARTMENT
FIRE PROTECTION EQUIPMENT PERFORMANCE REPORT
THIS PAGE BY ITSELF IS NOT A COMPLETE REPORT
Test Report Number
5892756
INITIAL TEST DATE: TEST SITE ADDRESS: (STREET NUMBER AND STREET NAME)
06/12/2024 351 E TEMPLE ST
EQUIPMENT TESTED:
Fire Pump - Initial Test
LAFD Annual Fire Pump Assembly , F-340R 02-06-2015
LOS ANGELES FIRE DEPARTMENT
ANNUAL FIRE PUMP PERFORMANCE TEST WORK SHEET
THIS PAGE BY ITSELF IS NOT A COMPLETE DOCUMENT AND SHALL BE
ATTACHED TO THE F-340R ANNUAL FIRE PUMP REPORT
PAGE 1 Of TEST SITE ADDRESS: (street) (city) (state) (zip) (Phone
351 E TEMPLE ST LOS ANGELES CA 90012
EQUIPMENT TESTED:
FIRE PUMP
TEST DATE(S) FIRM OR D.B.A.
6-12-2024
FIRE PUMP INFORMATION: PUMP # 1 OF 1
MANUFACTURER
RATED
GPM
HEAD-FT.
RELIEF
VALVE PSI
TANK SIZE AND LOCATION (IF APPLICABLE)
Patterson 500 N/A N/A NA
MODEL
RATED
PSI
RATED
RPM
IMPELLER
SIZE
CITY SUPPLY PRESSURE
(IF SUPPLIED DIRECTLY BY CITY)
5xMAC3 75 3550 6.625 MIN 80 MAX (IF AVAILABLE)
TYPE OF PUMP
RELIEF VALVE SETTING
PUMP LOCATION
Horizontal Split Case N/A Fire Pump Room
DRIVER INFORMATION:
DIESEL
IF DIESEL DRIVEN, HOW MANY GALLONS OF FUEL ARE AVAILABLE (8 HOUR SUPPLY REQUIRED)?
500 GALLONS
ELECTRIC
IF ELECTRICALLY DRIVEN, HOW MANY GALLONS OF FUEL SUPPLY THE EMERGENCY GENERATOR?
CONTROLLER INFORMATION:
MANUFACTURER
AUTO
START
AUTO
STOP
MODEL
OVERRUN
TIME
JOCKEY PUMP (PSI)
Firetrol 135 155 FTA1930-AM30B 10 Mins ON 150 OFF 160
PERFORMANCE TEST:
CAPACITY
REQUIRED
NUMBER OF
OUTLETS
NOZZLE
ORIFICE
SIZE
REQUIRED
PITOT
PRESSURE
OBTAINED
SUCTON
PSI
DISCHARGE
SYSTEM
NET
PUMP SPEED
IN RPM
0% 0 0 0 0 0 80 161 160 81 3576
50% 250 1 6” FM 250 79 156 160 77 3570
100% 500 1 6” FM 500 79 154 160 75 3557
150% 750 1 6” FM 750 79 139 160 60 3551
AUTOMATIC STARTS: 6 MANUAL STARTS: 6
LOCATION(S) OF TEST FLOWS & REMOTE STARTS
STARTS
SATISFACTORY
RESULTS
STARTS
SATISFACTORY
RESULTS
Drain Valve 6
YES NO
YES NO
SYSTEM PRESSURE TAKEN AT:
At 150 percent of rated capacity, the net pump pressure shall be at least 65 percent of the rated pressure
PUMP RATED PRESSURE:75 PUMP NET PRESSURE:60
PUMP NET PRESSURE IS:80 %
Fire Pump Room
PASS FAIL
IS FIRE PUMP STATUS INFORMATION CORRECTLY
INDICATED IN THE FIRE CONTROL ROOM?
IF PREVIOUS RESULTS ARE AVAILABLE, IS THE NET PUMP
PRESSURE
WITHIN 5 % OF THE PREVIOUS RESULTS AT EACH POINT?
YES NO YES NO N/A
TESTER’S NAME & CERTIFICATE # EXPIRATION DATE
12-31-2025
TESTER’S SIGNATURE
FIRE DEPARTMENT WITNESS (SIGNATURE & ASSIGNMENT)
TOTAL HOURS