VA Sepulveda_16111 Plummer St_Bldg 10_ANN FA_02-06-24_Redacted 30.pdf
PDF 352 KB Posted
- Attached to
- H912--Fire Alarm Inspections - One Year Contract
- Solicitation number
- 36C26225Q0850
About this file
This document is a Fire/Life Safety System Inspection, Testing, and Maintenance Certificate for the VA Sepulveda Building 10 located at 16111 Plummer St in North Hills, CA. The inspection was performed in accordance with multiple NFPA standards, including NFPA 101 (Life Safety Code), NFPA 72 (Fire Alarm Systems), and NFPA 904 (Air Conditioning/Ventilating Systems). The inspection, completed on February 6, 2024, was conducted to ensure compliance with The Joint Commission/VHA Standards and the latest Joint Commission/VHA Clarification Memorandum on Emergency Management and Life Safety Standards.
The accompanying detailed report includes comprehensive testing and inspection results for various fire safety systems and devices across multiple building locations. The inspection covered 277 total devices, including tamper switches, waterflow switches, duct detectors, heat detectors, pull stations, smoke detectors, speaker/strobes, releasing devices, communicators, batteries, control panels, and elevators. The report identifies several discrepancies, such as failed operations of waterflow switches, speaker/strobes, and strobes, as well as expired batteries in certain locations. These findings require corrective actions to ensure full compliance with fire safety regulations and system functionality.
View the file
Other files
Show all 41
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HCI Systems, Inc. 1
Executive Summary Generated by: BuildingReports.com
Building Information Building: VA Sepulveda Bldg 10 Contact: Keith Hayhurst Address: 16111 Plummer St Phone: 310.714.5379 City/State/ZIP Code: North Hills, CA 90012 Mobile:
Country: United States of America Email: Keith.Hayhurst@va.gov
Inspection Performed By Company: HCI Systems, Inc. Inspector: Parris Jackson Address: 1354 S. Parkside Place Phone: 909-628-7773 City/State/ZIP Code: Ontario, CA 91761 Mobile:
Country: United States of America Email: pjackson@hcisystems.net
System Control Unit Manufacturer: Cerberus Inspection Date: 02/05/2024 IDC Style:
Model Number: Pyrotronics - MXL Install Date: 03/09/2020 SLC Style:
Software Version: Version Date: 03/09/2020 NAC Style:
Location: Basement B-B110 Signal Room Current Protection:
Central Station Signal Verification Type: Digital Communicator Mfg.: Detection Systems Model #: DS9471 Test Time/Date: 2/5/24 5:25:22 AM Restore Time: 38 Seconds Note:
Certification Company: HCI Systems, Inc. Building: VA Sepulveda Bldg 10 Inspector: Parris Jackson Contact: Keith Hayhurst
HCI Systems, Inc. 2
Inspection Completion Date: Feb 6, 2024 Building: VA Sepulveda Bldg 10 EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2
(17)(10)(a) & (17)(11)
Devices Tested This
Quarter Pass Fail Tested YTD
(2024) Untested YTD
(2024) Total Quantity Tamper Switch 22 22 0 22 0 22 Waterflow Switch 15 14 1 15 0 15
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Devices Tested This
Quarter Pass Fail Tested YTD
(2024) Untested YTD
(2024) Total Quantity Duct Detector 13 13 0 13 0 13 Heat Detector 4 4 0 4 0 4 Pull Station 26 25 1 26 0 26 Smoke Detector 32 32 0 32 0 32
EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)
Devices Tested This
Quarter Pass Fail Tested YTD
(2024) Untested YTD
(2024) Total Quantity Releasing Device 8 8 0 8 0 8 Speaker/Strobe 88 86 2 88 0 88 Strobe 24 22 2 24 0 24
EC 02.03.05 EP 05 Annual test of fire alarm equipment for notifying off-site fire responders. NFPA 72 (2022) Table 14.4.3.2 (4)
Devices Tested This
Quarter Pass Fail Tested YTD
(2024) Untested YTD
(2024) Total Quantity Communicator 1 1 0 1 0 1
EC 02.03.05 EP 19 Annual test of automatic smoke-detection shutdown devices for air-handling equipment. NFPA 90A (2024) 6.4.1
Devices Tested This
Quarter Pass Fail Tested YTD
(2024) Untested YTD
(2024) Total Quantity Duct Detector 13 13 0 13 0 13 Fan Shutdown 9 9 0 9 0 9
LS 02.01.34 EP 02 Protected master fire alarm control panel
Devices Tested This
Quarter Pass Fail Tested YTD
(2024) Untested YTD
(2024) Total Quantity Control Panel 2 2 0 2 0 2
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
Devices Tested This
Quarter Pass Fail Tested YTD
(2024) Untested YTD
(2024) Total Quantity Annunciator 3 3 0 3 0 3 Battery 14 10 4 14 0 14 Expander Panel 1 1 0 1 0 1 Power Supply 7 7 0 7 0 7
LS 02.01.50 EP 07 Annual - Elevators are fully equipped and protected
Devices Tested This
Quarter Pass Fail Tested YTD
(2024) Untested YTD
(2024) Total Quantity Elevator 8 8 0 8 0 8 Total Device Count: 277
HCI Systems, Inc. 3
Discrepancy Report Generated by: BuildingReports.com
Building: VA Sepulveda Bldg 10 Control Panel: 1 - Cerberus Pyrotronics - MXL The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.
ScanID Location Problem Address Reference
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11)
Waterflow Switch 57079393 1st Bldg 10A Outside East Area Failed Operation 1-01-044 NFPA72 14.2.2.2.2
EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)
Speaker/Strobe 112345648 1st A-A110 Office Failed Operation 1 NFPA72 14.2.2.2.2 57079350 1st Mental Health Clinic Corridor By Women’s
Restroom Failed Operation 1 NFPA72 14.2.2.2.2
Strobe 57079334 1st Men’s Restroom 1-B102 Failed Operation 1 NFPA72 18.5.5.5.2;
18.5.5.6.7 57079455 2nd Elevator Lobby Failed Operation 1 NFPA72 18.5.5.5.2;
18.5.5.6.7
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
Battery 57078900 Basement B-B110 Signal Room Expander
Panel Date Expired 1 NFPA72 Table
14.4.3.2 (9)(5) 57078901 Basement B-B110 Signal Room Expander
Panel Date Expired 1 NFPA72 Table
14.4.3.2 (9)(5) 57079545 2nd Electrical Room B106 By Door B10 BPS 1 Date Expired 1 NFPA72 Table
14.4.3.2 (9)(5) 57079546 2nd Electrical Room B106 By Door B10 BPS 1 Special Note 1 NFPA72 14.2.2.2.2
Code References NFPA72 14.2.2.2.2 System deficiencies shall be corrected.
NFPA72 18.5.5.5.2;
18.5.5.6.7
Rooms: Visual notification appliances shall be installed using one of the following: 1) A single visual notification appliance. 2) Two groups of visual notification appliances, where visual notification appliances of each group are synchronized, in the same room or adjacent space within the field of view. This shall include synchronization of visual appliances operated by separate systems. Corridors:
In corridors where more than two visual notification appliances are in any field of view, they shall flash in synchronization.
NFPA72 Table
14.4.3.2 (9)(5)
Replace the battery or conduct a load test of the battery capacity every 3 years.
HCI Systems, Inc. 4
Building: VA Sepulveda Bldg 10 Control Panel: 2 - Fire-Lite MS - 4424B The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.
ScanID Location Problem Address Reference
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Pull Station 57079522 1st Bldg 10B Rear Exit Door Failed Operation 2-Z002 NFPA72 14.2.2.2.2
Code References NFPA72 14.2.2.2.2 System deficiencies shall be corrected.
HCI Systems, Inc. 5
Notes & Recommendations Generated by: BuildingReports.com
Building: VA Sepulveda Bldg 10 Control Panel: 1 - Cerberus Pyrotronics - MXL
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection.
ScanID Note Device Type Location Comment EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11)
57079406 1 Tamper Switch Basement Fire Pump Room B-C128 Test Header (N/C)
Pass
Normally closed.
57079393 2 Waterflow Switch 1st Bldg 10A Outside East Area Failed Operation
Failed to activate.
EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)
112345648 3 Speaker/Strobe 1st A-A110 Office Failed Operation Failed to activate.
57079350 4 Speaker/Strobe 1st Mental Health Clinic Corridor By Women’s Restroom
Failed Operation
Failed to activate.
57079334 5 Strobe 1st Men’s Restroom 1-B102 Failed Operation
Failed to activate.
57079455 6 Strobe 2nd Elevator Lobby Failed Operation
Failed to activate.
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
57078900 7 Battery Basement B-B110 Signal Room Expander Panel Date Expired Out of date.
57078901 8 Battery Basement B-B110 Signal Room Expander Panel Date Expired Out of date.
57079546 9 Battery 2nd Electrical Room B106 By Door B10 BPS 1 Special Note MFG Dates Different by a year
HCI Systems, Inc. 6
Building: VA Sepulveda Bldg 10 Control Panel: 2 - Fire-Lite MS - 4424B
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection.
ScanID Note Device Type Location Comment EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
57079522 10 Pull Station 1st Bldg 10B Rear Exit Door Failed Operation Failed to activate.
HCI Systems, Inc. 7
Inspection & Testing Generated by: BuildingReports.com
Building: VA Sepulveda Bldg 10 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far-right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.
Passed=P, Failed=F, Replaced=R
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11)
Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(10)(a))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Tamper Switch 22 22 0 22 22 Device Type Location ScanID Address Annual 2024 Tamper Switch Basement Fire Pump Room B-C128 Suction Control
Valve 57079404 1-01-021 Tested – 1 Turn - 02/05 - Pass
Tamper Switch Basement Fire Pump Room B-C128 Pump Bypass #1 57079408 1-01-017 Tested – 2 Turns - 02/05 - Pass Tamper Switch Basement Fire Pump Room B-C128 Pump Bypass #2 57079407 1-01-018 Tested – 1 Turn - 02/05 - Pass Tamper Switch Basement Fire Pump Room B-C128 Discharge
Control Valve 57079405 1-01-020 Tested – 1 Turn - 02/05 - Pass
Tamper Switch Basement Mechanical Room 57079513 1-01-032 Tested – 1 Turn - 02/05 - Pass Tamper Switch Basement Stair 3 57079503 1-01-043 Tested – 1 Turn - 02/05 - Pass Tamper Switch Basement Stair 2 Inside Sub Basement Entrance 57079550 1-01-012 Tested – 1 Turn - 02/05 - Pass Tamper Switch Basement Stair 1 By Passenger Elevator Lobby 57079540 1-01-038 Tested – 2 Turns - 02/05 - Pass Tamper Switch Basement Fire Pump Room B-C128 Test Header
(N/C) 57079406 1-01-019 Switch Tested - Pass
Tamper Switch 1st Bldg 10B Outside Front Entrance 57079395 2-Z004 Tested – 1 Turn - 02/06 - Pass Tamper Switch 1st Dental Clinic Stair 1 By 1-C107 57079371 1-02-020 Tested – 2 Turns - 02/05 - Pass Tamper Switch 1st Bldg 10A Outside East Area 57079392 1-01-045 Tested – 2 Turns - 02/05 - Pass Tamper Switch 1st Mental Health Clinic Stair 3 57079346 1-02-032 Tested – 1 Turn - 02/05 - Pass Tamper Switch 1st OS&Y Outside Main Entrance 57079409 1-01-022 Tested – 1 Turn - 02/05 - Pass Tamper Switch 1st OS&Y Outside Main Entrance 57079410 1-01-022 Tested – 1 Turn - 02/05 - Pass Tamper Switch 1st Stair 2 57079320 1-02-023 Tested – 2 Turns - 02/05 - Pass Tamper Switch 2nd Stair 3 57079501 1-03-029 Tested – 2 Turns - 02/05 - Pass Tamper Switch 2nd Stair 2 At Cubical A30 57079474 1-03-020 Tested – 1 Turn - 02/05 - Pass Tamper Switch 2nd Stair 2 57079317 1-03-023 Tested – 1 Turn - 02/05 - Pass Tamper Switch Roof AC Service Room 1 57079466 1-04-035 Tested – 2 Turns - 02/05 - Pass Tamper Switch Roof AC Service Room 2 57079461 1-04-029 Tested – 2 Turns - 02/05 - Pass Tamper Switch Roof Stair 2 57079303 1-04-006 Tested – 1 Turn - 02/05 - Pass Device Total: 22
HCI Systems, Inc. 8
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11)
Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size installed in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25-20. (NFPA 72-22 Table 14.4.3.2 (17)(11))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Waterflow Switch 15 14 1 15 15 Device Type Location ScanID Address Annual 2024 Waterflow Switch Basement Mechanical Room 57079514 1-01-031 Tested – 32 Seconds - 02/05 - Pass Waterflow Switch Basement Stair 3 57079502 1-01-042 Tested – 40 Seconds - 02/05 - Pass Waterflow Switch Basement Stair 2 Inside Sub Basement Entrance 57079551 1-01-011 Tested – 30 Seconds - 02/05 - Pass Waterflow Switch Basement Stair 1 By Passenger Elevator Lobby 57079539 1-01-037 Tested – 32 Seconds - 02/05 - Pass Waterflow Switch 1st Dental Clinic Stair 1 By 1-C107 57079370 1-02-019 Tested – 40 Seconds - 02/05 - Pass Waterflow Switch 1st Bldg 10B Outside Front Entrance 57079394 2-Z003 Tested – 25 Seconds - 02/05 - Pass Waterflow Switch 1st Mental Health Clinic Stair 3 57079347 1-02-031 Tested – 24 Seconds - 02/05 - Pass Waterflow Switch 1st Stair 2 57079319 1-02-022 Tested – 32 Seconds - 02/05 - Pass Waterflow Switch 1st Bldg 10A Outside East Area 57079393 1-01-044 02/05-F Waterflow Switch 2nd Stair 3 57079500 1-03-028 Tested – 24 Seconds - 02/05 - Pass Waterflow Switch 2nd Stair 2 At Cubical A30 57079475 1-03-019 Tested – 32 Seconds - 02/05 - Pass Waterflow Switch 2nd Stair 2 57079318 1-03-022 Tested – 30 Seconds - 02/05 - Pass Waterflow Switch Roof AC Service Room 1 57079465 1-04-034 Tested – 28 Seconds - 02/05 - Pass Waterflow Switch Roof AC Service Room 2 57079462 1-04-028 Tested – 44 Seconds - 02/05 - Pass Waterflow Switch Roof Stair 2 57079302 1-04-005 Tested – 30 Seconds - 02/05 - Pass Device Total: 15
HCI Systems, Inc. 9
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(7)(e))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Duct Detector 13 13 0 13 13 Device Type Location ScanID Address Annual 2024 Duct Detector Basement Stock Room Prosthetic Services B-C125 57079543 1-01-048 02/05-P Duct Detector Basement Stock Room Prosthetic Services B-C125 57079542 1-01-047 02/05-P Duct Detector Roof BLDG 10A AHU 10 57079515 1-01-059 02/05-P Duct Detector Roof AHU 2 57079459 1-04-024 02/05-P Duct Detector Roof AHU 3 57079311 1-04-021 02/05-P Duct Detector Roof AHU 5 57079310 1-04-018 02/05-P Duct Detector Roof AHU 6 Exhaust Fan Room 57079313 1-04-016 02/05-P Duct Detector Roof AHU 6 Exhaust Fan Room 57079456 1-04-017 02/05-P Duct Detector Roof AHU 6 Exhaust Fan Room 57079315 1-04-015 02/05-P Duct Detector Roof AHU 7 57079463 1-04-023 02/05-P Duct Detector Roof AHU 8 57079305 1-04-033 02/05-P Duct Detector Roof AHU 1 57079457 1-04-026 02/05-P Duct Detector Roof AHU 9 57079306 1-04-030 02/05-P Device Total: 13
HCI Systems, Inc. 10
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions.
Non-Restorable: Do not perform heat test. Test functionality mechanically and electrically. (NFPA 72-22 Table 14.4.3.2 (17)(4)(a))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Heat Detector 4 4 0 4 4 Device Type Location ScanID Address Annual 2024 Heat Detector Roof Elevator Machine Room In Exhaust Fan Room 12345676 1-04-011 02/02-P Heat Detector Roof Elevator Machine Room In Exhaust Fan Room 12345677 1-04-020 02/02-P Heat Detector Roof Elevator Machine Room In Exhaust Fan Room 12345678 1-04-019 02/02-P Heat Detector Roof Elevator Machine Room In Exhaust Fan Room 12345679 1-04-007 02/02-P Device Total: 4
HCI Systems, Inc. 11
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-19 Table 14.4.3.2 (17)(5))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Pull Station 26 25 1 26 26 Device Type Location ScanID Address Annual 2024 Pull Station Basement HPACT SCIC Clinic Exit By B-C120 57079420 1-01-015 02/05-P Pull Station Basement HPACT SCIC Clinic Stair 2 By Men’s Restroom B-C1 57079415 1-01-010 02/05-P Pull Station Basement Corridor Outside B-A128 At Annunciator 57079450 1-01-051 02/05-P Pull Station Basement Stair 3 By Women’s Restroom B-A112 57079444 1-01-041 02/05-P Pull Station Basement Passenger Elevator Lobby By Stair 1 57079428 1-01-030 02/05-P Pull Station Basement Exit By Oxygen Storage B-C129 57079403 1-01-016 02/05-P Pull Station Basement Corridor By B-C101 57079399 1-01-007 02/05-P Pull Station Basement Exit Door By Service Elevator Lobby 57079432 1-01-034 02/05-P Pull Station 1st Bldg 10B Main Entrance 57079520 2-Z002 02/05-P Pull Station 1st Dental Clinic Exit By 1-C130 57079381 1-02-017 02/05-P Pull Station 1st Mental Health Clinic Entrance 57079341 1-02-026 02/05-P Pull Station 1st Mental Health Clinic Exit By 1-A126 57079353 1-02-037 02/05-P Pull Station 1st Mental Health Clinic Corridor By Men’s Staff Res 57079344 1-02-030 02/05-P Pull Station 1st Mental Health Clinic Exit By 1-A137A 57079361 1-02-027 02/05-P Pull Station 1st Dental Clinic Exit By 1-C121 57079376 1-02-021 02/05-P Pull Station 1st Dental Clinic By 1-C107 Outside Stair 1 57079369 1-02-018 02/05-P Pull Station 1st Main Lobby Entrance 57079331 1-02-007 02/05-P Pull Station 1st Passenger Elevator Lobby 57079325 1-02-005 02/05-P Pull Station 1st Bldg 10B Rear Exit Door 57079522 2-Z002 02/05-F Pull Station 2nd Open Office Area At Exit Door 57079509 1-03-034 02/05-P Pull Station 2nd Exit To Stairs By Cubical A6/A12 57079470 1-03-021 02/05-P Pull Station 2nd Stair 3 57079499 1-03-027 02/05-P Pull Station 2nd Exit Door By Cubical A67 57079479 1-03-017 02/05-P Pull Station 2nd Stair 2 At Cubical A30 57079473 1-03-018 02/05-P Pull Station 2nd Exit Door At Door C62 57079506 1-03-026 02/05-P Pull Station 2nd Stair 1 By Passenger Elevator Lobby 57079467 1-03-005 02/05-P Device Total: 26
HCI Systems, Inc. 12
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72-22 Table 14.4.3.2 (17)(7)(a))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Smoke Detector 32 32 0 32 32 Device Type Location ScanID Address Annual 2024 Smoke Detector Basement Electrical Room B-B108 By Signal Room B-B110 57079422 1-01-024 02/05-P Smoke Detector Basement Corridor Outside Signal Room B-B110 57079383 1-01-005 02/05-P Smoke Detector Basement B-B110 Signal Room 57079301 1-01-050 02/05-P Smoke Detector Basement Corridor Outside B-A128 57079453 1-01-053 02/05-P Smoke Detector Basement Corridor Outside B-A128 57079452 1-01-052 02/05-P Smoke Detector Basement Corridor Outside B-C100 57079384 1-01-006 02/05-P Smoke Detector Basement Service Elevator Lobby 57079431 1-01-033 02/05-P Smoke Detector Basement Corridor Outside B-A100 57079439 1-01-040 02/05-P Smoke Detector Basement Corridor Outside B-B106 57079438 1-01-039 02/05-P Smoke Detector Basement Passenger Elevator Lobby 57079426 1-01-029 02/05-P Smoke Detector 1st Bldg 10B Main Entrance Right Side 57079526 2-Z001 02/05-P Smoke Detector 1st Bldg 10B By Rear Exit Door Left Side 57079525 2-Z001 02/05-P Smoke Detector 1st Bldg 10B Main Entrance Left Side 57079527 2-Z001 02/05-P Smoke Detector 1st Bldg 10B By Rear Exit Door Right Side 57079524 2-Z001 02/05-P Smoke Detector 1st Dental Clinic Entrance 57079365 1-02-016 02/05-P Smoke Detector 1st Electrical Closet in Room 1-B106 57079364 1-02-009 02/05-P Smoke Detector 1st Corridor Outside Men’s Restroom 1-B102 57079336 1-02-024 02/05-P Smoke Detector 1st Mental Health Clinic Entrance 57079339 1-02-025 02/05-P Smoke Detector 1st Corridor Outside Dental Clinic By 1-B106 57079328 1-02-015 02/05-P Smoke Detector 1st Service Elevator Lobby 57079324 1-02-008 02/05-P Smoke Detector 1st Passenger Elevator Lobby 57079321 1-02-006 02/05-P Smoke Detector 2nd Room A29B By Stair 2 At Cubical A30 49519224 1-3-035 02/05-P Smoke Detector 2nd TR Storeroom C1A by Kitchen 49519223 1-3-037 02/05-P Smoke Detector 2nd TR Room C-00A 49519222 1-3-036 02/05-P Smoke Detector 2nd Electrical Room B106 By Door B10 57079531 1-03-007 02/05-P Smoke Detector 2nd Corridor At Entrance To North Side 57079486 1-03-015 02/05-P Smoke Detector 2nd Section B Room 107 11224455 1-03-024 02/05-P Smoke Detector 2nd Corridor At Entrance To North Side 57079487 1-03-014 02/05-P Smoke Detector 2nd Corridor Outside Of Kitchen 57079495 1-03-025 02/05-P Smoke Detector 2nd Passenger Elevator Lobby By Stair 1 57079468 1-03-006 02/05-P Smoke Detector 2nd Service Elevator Lobby 57079512 1-03-011 02/02-P Smoke Detector Roof Elevator Machine Room In Exhaust Fan Room 12345675 1-04-010 02/05-P Device Total: 32
HCI Systems, Inc. 13
EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)
Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Releasing Device 8 8 0 8 8 Device Type Location ScanID Address Annual 2024 Releasing Device Basement Corridor Outside B-B106 57079437 1 02/05-P Releasing Device Basement Corridor Outside B-A128 57079454 1 02/05-P Releasing Device Basement Corridor Outside B-B110 57079382 1 02/05-P Releasing Device 1st Mental Health Clinic Entrance 57079338 1 02/05-P Releasing Device 1st Corridor Outside Men’s Restroom 1-B102 57079337 1 02/05-P Releasing Device 1st Corridor Outside Dental Clinic By 1-B106 57079329 1 02/05-P Releasing Device 2nd Corridor At Entrance To North Side 57079485 1 02/05-P Releasing Device 2nd Corridor At Men and Women’s Restroom Middle 57079493 1 02/05-P Device Total: 8
HCI Systems, Inc. 14
EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)
For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Speaker/Strobe 88 86 2 88 88 Device Type Location ScanID Address Annual 2024 Speaker/Strobe Basement Corridor Outside B-C101 57079385 1 02/05-P Speaker/Strobe Basement Corridor By B-B112 57079386 1 02/05-P Speaker/Strobe Basement Corridor By B-C103 57079396 1 02/05-P Speaker/Strobe Basement Corridor By B-C122 57079397 1 02/05-P Speaker/Strobe Basement Corridor By B-C121 57079398 1 02/05-P Speaker/Strobe Basement Corridor By B-C124 57079400 1 02/05-P Speaker/Strobe Basement Corridor By Mechanical Room B-C127 57079402 1 02/05-P Speaker/Strobe Basement HPACT SCIC Clinic Day Room B-C106A 57079411 1 02/05-P Speaker/Strobe Basement HPACT SCIC Clinic Day Room Restroom B-C106A 57079412 1 02/05-P Speaker/Strobe Basement HPACT SCIC Clinic By B-C106B 57079413 1 02/05-P Speaker/Strobe Basement HPACT SCIC Clinic By B-C107 57079414 1 02/05-P Speaker/Strobe Basement HPACT SCIC Clinic By B-C111 57079417 1 02/05-P Speaker/Strobe Basement HPACT SCIC Clinic By B-C115 57079418 1 02/05-P Speaker/Strobe Basement HPACT SCIC Clinic By B-C120 57079419 1 02/05-P Speaker/Strobe Basement Outside Passenger Elevator Lobby 57079427 1 02/05-P Speaker/Strobe Basement Outside Passenger Elevator Lobby 57079429 1 02/05-P Speaker/Strobe Basement Corridor Outside B-B106 57079435 1 02/05-P Speaker/Strobe Basement Office of Recreational Therapy B-B106 57079436 1 02/05-P Speaker/Strobe Basement Corridor Outside B-A101 57079440 1 02/05-P Speaker/Strobe Basement Corridor Outside B-A109 57079441 1 02/05-P Speaker/Strobe Basement Corridor Outside B-A113 57079442 1 02/05-P Speaker/Strobe Basement Exit Door By Men’s Restroom B-A121 57079445 1 02/05-P Speaker/Strobe Basement Stair 3 By Women’s Restroom B-A112 57079443 1 02/05-P Speaker/Strobe Basement Corridor Outside B-A125 57079448 1 02/05-P Speaker/Strobe Basement Corridor Outside B-A127 57079449 1 02/05-P Speaker/Strobe Basement Occupational Therapy Room B-B107 57079538 1 02/05-P Speaker/Strobe Basement Conference Room B-B112 By Electrical Room
B-B108 57079541 1 02/05-P
Speaker/Strobe Basement B-C124 57079549 1 02/05-P Speaker/Strobe 1st Dental Clinic By 1-C114 57079373 1 02/05-P Speaker/Strobe 1st Dental Clinic By 1-C108 57079372 1 02/05-P Speaker/Strobe 1st Dental Clinic By 1-C104 57079368 1 02/05-P Speaker/Strobe 1st Dental Clinic By 1-C102 57079367 1 02/05-P Speaker/Strobe 1st Dental Clinic By 1-C100 57079366 1 02/05-P Speaker/Strobe 1st Corridor Outside Service Elevator Lobby 57079362 1 02/05-P Speaker/Strobe 1st Dental Clinic By 1-C120 57079374 1 02/05-P Speaker/Strobe 1st Dental Clinic By 1-C123 57079377 1 02/05-P Speaker/Strobe 1st Dental Clinic By 1-C127 57079378 1 02/05-P Speaker/Strobe 1st Dental Clinic By 1-C128B 57079380 1 02/05-P Speaker/Strobe 1st Bldg 10A Main Entrance 57079387 1 02/05-P Speaker/Strobe 1st Bldg 10A Corridor By B-D105 57079390 1 02/05-P Speaker/Strobe 1st Bldg 10A Corridor At Restroom 57079388 1 02/05-P Speaker/Strobe 1st Bldg 10B Main Entrance 57079521 2 02/05-P Speaker/Strobe 1st Bldg 10B Rear Exit Door 57079523 2 02/05-P Speaker/Strobe 1st Mental Health Clinic Psychiatrist Office 1-A141 57079360 1 02/05-P Speaker/Strobe 1st Mental Health Clinic Hoteling Office 1-A139 57079359 1 02/05-P Speaker/Strobe 1st Mental Health Clinic Hoteling Office 1-A138 57079358 1 02/05-P Speaker/Strobe 1st Mental Health Clinic Corridor By Conference Room 57079342 1 02/05-P
HCI Systems, Inc. 15
Speaker/Strobe 1st Mental Health Clinic Corridor By 1-A103A 57079340 1 02/05-P Speaker/Strobe 1st Corridor Outside Men’s Restroom 1-B102 57079335 1 02/05-P Speaker/Strobe 1st Main Lobby Entrance 57079330 1 02/05-P Speaker/Strobe 1st Corridor Outside Dental Clinic By 1-B106 57079327 1 02/05-P Speaker/Strobe 1st Corridor Outside 1-B105 57079326 1 02/05-P Speaker/Strobe 1st Mental Health Clinic Outside 1-A138 57079357 1 02/05-P Speaker/Strobe 1st Mental Health Clinic Outside 1-A133 57079356 1 02/05-P Speaker/Strobe 1st Mental Health Clinic By 1-A131 57079355 1 02/05-P Speaker/Strobe 1st Mental Health Clinic By 1-A133 57079354 1 02/05-P Speaker/Strobe 1st Mental Health Clinic By 1-A124 57079352 1 02/05-P Speaker/Strobe 1st Mental Health Clinic By 1-A114A 57079349 1 02/05-P Speaker/Strobe 1st Mental Health Clinic By 1-A112A 57079348 1 02/05-P Speaker/Strobe 1st Mental Health Clinic Corridor By 1-A111 57079345 1 02/05-P Speaker/Strobe 1st Mental Health Clinic Corridor By Women’s Restroom 57079350 1 02/05-F Speaker/Strobe 1st A-A110 Office 112345648 1 02/05-F Speaker/Strobe 2nd Room A29B By Stair 2 At Cubical A30 57079535 1 02/05-P Speaker/Strobe 2nd Corridor Outside Of Kitchen 57079494 1 02/05-P Speaker/Strobe 2nd At Cubical A4 57079471 1 02/05-P Speaker/Strobe 2nd At Cubical A24 57079472 1 02/05-P Speaker/Strobe 2nd At Cubical A41 57079476 1 02/05-P Speaker/Strobe 2nd Corridor By Door A47 By Fountain 57079477 1 02/05-P Speaker/Strobe 2nd Corridor By Door A68 By Fountain 57079478 1 02/05-P Speaker/Strobe 2nd At Cubical A63 57079480 1 02/05-P Speaker/Strobe 2nd Corridor At Men and Women’s Restroom North 57079483 1 02/05-P Speaker/Strobe 2nd At Cubical A86 57079484 1 02/05-P Speaker/Strobe 2nd At Cubical B13 57079488 1 02/05-P Speaker/Strobe 2nd At Cubical B3 57079489 1 02/05-P Speaker/Strobe 2nd Corridor At Men and Women’s Restroom Middle 57079492 1 02/05-P Speaker/Strobe 2nd Open Office Area At Exit Door 57079508 1 02/05-P Speaker/Strobe 2nd Open Office Area At Exit Door Rear 57079510 1 02/05-P Speaker/Strobe 2nd Open Office Area At Pillar 57079507 1 02/05-P Speaker/Strobe 2nd Corridor At Door C6 57079505 1 02/05-P Speaker/Strobe 2nd Corridor At Door C54 By Fountain 57079504 1 02/05-P Speaker/Strobe 2nd At Stair 3 57079498 1 02/05-P Speaker/Strobe 2nd Main Conference Room B6B 57079528 1 02/05-P Speaker/Strobe 2nd Area 2 Room 2-12 B25 57079529 1 02/05-P Speaker/Strobe 2nd Area 2 Room 2-12 B25 57079530 1 02/05-P Speaker/Strobe 2nd Corridor At Main Suite Entrance 57079532 1 02/05-P Speaker/Strobe 2nd C60 Conference Room 57079536 1 02/05-P Speaker/Strobe 2nd Office C12 57079537 1 02/05-P Speaker/Strobe 2nd Data/Computer Room 57079544 1 02/05-P Device Total: 88
HCI Systems, Inc. 16
EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)
For periodic testing, verify that each appliance flashes. (NFPA 72-22 Table 14.4.3.2 (22)(3))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Strobe 24 22 2 24 24 Device Type Location ScanID Address Annual 2024 Strobe Basement Women’s Restroom B-A112 By Exit Door 57079447 1 02/05-P Strobe Basement Men’s Restroom B-A121 By Exit Door 57079446 1 02/05-P Strobe Basement Restroom B-B102 57079434 1 02/05-P Strobe Basement Women’s Restroom B-B109 By Electrical Room
B-B10 57079424 1 02/05-P
Strobe Basement Men’s Restroom B-B111 By Electrical Room B-B108
57079423 1 02/05-P
Strobe Basement HPACT SCIC Clinic Staff Restroom B-C119 By B-C11
57079421 1 02/05-P
Strobe Basement HPACT SCIC Clinic Men’s Restroom B-C108 By Stair
57079416 1 02/05-P
Strobe Basement Women’s Restroom By Mechanical Room B-C127 57079401 1 02/05-P Strobe 1st Bldg 10A Restroom By B-D107 57079391 1 02/05-P Strobe 1st Bldg 10A Restroom B-D103 57079389 1 02/05-P Strobe 1st Dental Clinic Room 1-C129 57079379 1 02/05-P Strobe 1st Dental Clinic By 1-C119 57079375 1 02/05-P Strobe 1st Room 1-B106 57079363 1 02/05-P Strobe 1st Mental Health Clinic Men’s Staff Restroom By Con 57079343 1 02/05-P Strobe 1st Women’s Restroom 1-B103 57079333 1 02/05-P Strobe 1st Mental Health Clinic Women’s Restroom 1-A117 57079351 1 02/05-P Strobe 1st Men’s Restroom 1-B102 57079334 1 02/05-F Strobe 2nd Men’s Restroom South 57079497 1 02/05-P Strobe 2nd Women’s Restroom South 57079496 1 02/05-P Strobe 2nd Men’s Restroom Middle 57079491 1 02/05-P Strobe 2nd Women’s Restroom Middle 57079490 1 02/05-P Strobe 2nd Women’s Restroom North 57079482 1 02/05-P Strobe 2nd Men’s Restroom North 57079481 1 02/05-P Strobe 2nd Elevator Lobby 57079455 1 02/05-F Device Total: 24
HCI Systems, Inc. 17
EC 02.03.05 EP 05 Annual test of fire alarm equipment for notifying off-site fire responders. NFPA 72 (2022) Table 14.4.3.2 (4)
Test all system functions and features in accordance with the equipment manufacturer's published instructions for correct operation in conformance with the applicable sections of Chapter 26. Except for DACT, actuate initiating device and verify receipt of the correct initiating device signal at the supervising station within 90 seconds. Upon completion of the test, restore the system to its functional operating condition. (NFPA 72-22 Table 14.4.3.2 (4))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Communicator 1 1 0 1 1 Device Type Location ScanID Address Annual 2024 Communicator Basement B-B110 Signal Room 57079225 1 02/05-P Device Total: 1
HCI Systems, Inc. 18
EC 02.03.05 EP 19 Annual test of automatic smoke-detection shutdown devices for air-handling equipment. NFPA 90A (2024) 6.4.1
Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(7)(e))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Duct Detector 13 13 0 13 13 Device Type Location ScanID Address Annual 2024 Duct Detector Basement Stock Room Prosthetic Services B-C125 57079543 1-01-048 02/05-P Duct Detector Basement Stock Room Prosthetic Services B-C125 57079542 1-01-047 02/05-P Duct Detector Roof BLDG 10A AHU 10 57079515 1-01-059 02/05-P Duct Detector Roof AHU 2 57079459 1-04-024 02/05-P Duct Detector Roof AHU 3 57079311 1-04-021 02/05-P Duct Detector Roof AHU 5 57079310 1-04-018 02/05-P Duct Detector Roof AHU 6 Exhaust Fan Room 57079313 1-04-016 02/05-P Duct Detector Roof AHU 6 Exhaust Fan Room 57079456 1-04-017 02/05-P Duct Detector Roof AHU 6 Exhaust Fan Room 57079315 1-04-015 02/05-P Duct Detector Roof AHU 7 57079463 1-04-023 02/05-P Duct Detector Roof AHU 8 57079305 1-04-033 02/05-P Duct Detector Roof AHU 1 57079457 1-04-026 02/05-P Duct Detector Roof AHU 9 57079306 1-04-030 02/05-P Device Total: 13
HCI Systems, Inc. 19
EC 02.03.05 EP 19 Annual test of automatic smoke-detection shutdown devices for air-handling equipment. NFPA 90A (2024) 6.4.1
Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Fan Shutdown 9 9 0 9 9 Device Type Location ScanID Address Annual 2024 Fan Shutdown Roof BLDG 10A AHU 10 57079516 1 02/05-P Fan Shutdown Roof AHU 7 57079464 1 02/05-P Fan Shutdown Roof AHU 2 57079460 1 02/05-P Fan Shutdown Roof AHU 3 57079312 1 02/05-P Fan Shutdown Roof AHU 5 57079309 1 02/05-P Fan Shutdown Roof AHU 6 Exhaust Fan Room 57079314 1 02/05-P Fan Shutdown Roof AHU 1 57079458 1 02/05-P Fan Shutdown Roof AHU 8 57079308 1 02/05-P Fan Shutdown Roof AHU 9 57079307 1 02/05-P Device Total: 9
HCI Systems, Inc. 20
LS 02.01.34 EP 02 Protected master fire alarm control panel
Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table 14.4.3.2 (2)(1))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Control Panel 2 2 0 2 2 Device Type Location ScanID Address Annual 2024 Control Panel Basement B-B110 Signal Room 57078905 1 02/05-P Control Panel 1st Bldg 10B Main Entrance FACU 57079517 2 02/05-P Device Total: 2
HCI Systems, Inc. 21
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
Verify the correct operation and identification of annunciators. If provided, verify the correct operation of annunciator under a fault condition. (NFPA 72-22 Table 14.4.3.2 (11))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Annunciator 3 3 0 3 3 Device Type Location ScanID Address Annual 2024 Annunciator Basement Corridor Outside B-A128 57079451 1 02/05-P Annunciator Basement Exit Door By Service Elevator Lobby 57079433 1 02/05-P Annunciator 1st Main Lobby Entrance 57079332 1 02/05-P Device Total: 3
HCI Systems, Inc. 22
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
With the batteries fully charged and connected to the charger, measure the voltage across the batteries with a voltmeter. Then, with the battery charger disconnected, load test the batteries following the manufacturer's recommendations. (NFPA 72-22 Table 14.4.3.2 (9))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Battery 14 10 4 14 14 Device Type Location ScanID Address Annual 2024 Battery Basement B-B110 Signal Room BPS 57078903 1 02/05-P Battery Basement B-B110 Signal Room BPS 57078902 1 02/05-P Battery Basement B-B110 Signal Room Expander Panel 57078901 1 02/05-F Battery Basement B-B110 Signal Room Expander Panel 57078900 1 02/05-F Battery 1st Bldg 10B Main Entrance FACU 57079518 2 02/05-P Battery 1st Bldg 10B Main Entrance FACU 57079519 2 02/05-P Battery 1st Electrical Closet in Room 1-B106 BPS 1 57079553 1 02/05-P Battery 1st Electrical Closet in Room 1-B106 BPS 1 57079554 1 02/05-P Battery 1st Electrical Closet in Room 1-B106 BPS 2 57079556 1 02/05-P Battery 1st Electrical Closet in Room 1-B106 BPS 2 57079557 1 02/05-P Battery 2nd Electrical Room B106 By Door B10 BPS 2 57079547 1 02/05-P Battery 2nd Electrical Room B106 By Door B10 BPS 2 57079548 1 02/05-P Battery 2nd Electrical Room B106 By Door B10 BPS 1 57079545 1 02/05-F Battery 2nd Electrical Room B106 By Door B10 BPS 1 57079546 1 02/05-F Device Total: 14
HCI Systems, Inc. 23
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
At a minimum, control equipment shall be tested to verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table 14.4.3.2 (2)(1))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Expander Panel 1 1 0 1 1 Device Type Location ScanID Address Annual 2024 Expander Panel Basement B-B110 Signal Room 57079300 1 02/05-P Device Total: 1
HCI Systems, Inc. 24
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table 14.4.3.2 (2)(1))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Power Supply 7 7 0 7 7 Device Type Location ScanID Address Annual 2024 Power Supply Basement B-B110 Signal Room 57078904 1 02/05-P Power Supply 1st Electrical Closet in Room 1-B106 BPS #2 66554433 1 02/05-P Power Supply 1st Electrical Closet in Room 1-B106 BPS 1 57079552 1 02/05-P Power Supply 1st Electrical Closet in Room 1-B106 BPS #1 11223344 1 02/05-P Power Supply 1st Electrical Closet in Room 1-B106 BPS 2 57079555 1 02/05-P Power Supply 2nd Electrical Room B106 By Door B10 BPS 2 57079534 1 02/05-P Power Supply 2nd Electrical Room B106 By Door B10 BPS 1 57079533 1 02/05-P Device Total: 7
HCI Systems, Inc. 25
LS 02.01.50 EP 07 Annual - Elevators are fully equipped and protected
Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20))
Devices Annual 2024 Pass Fail Tested YTD (2024) Total Quantity Elevator 8 8 0 8 8 Device Type Location ScanID Address Annual 2024 Elevator Basement Passenger Elevator Lobby 57079425 1 02/05-P Elevator Basement Service Elevator Lobby 57079430 1 02/05-P Elevator 1st Passenger Elevator Lobby 57079322 1 02/05-P Elevator 1st Service Elevator Lobby 57079323 1 02/05-P Elevator 2nd Service Elevator Lobby 57079511 1 02/02-P Elevator 2nd Passenger Elevator Lobby By Stair 1 57079469 1 02/02-P Elevator Roof Elevator Machine Room In Exhaust Fan Room 12345674 1 02/05-P Elevator Roof Elevator Machine Room In Exhaust Fan Room 12345673 1 02/05-P Device Total: 8
HCI Systems, Inc. 26
Inventory Report Generated by: BuildingReports.com
Building: VA Sepulveda Bldg 10 Control Panel: 1 - Cerberus Pyrotronics - MXL The Inventory Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years, or more are grouped together for easy reference.
Device or Type Category % of Inventory Quantity Annunciator Control 1.08% 3
Battery Control 5.05% 14 Communicator Control 0.36% 1 Control Panel Control 0.72% 2 Duct Detector Initiating 4.69% 13
Elevator Auxiliary 2.89% 8 Expander Panel Control 0.36% 1 Fan Shutdown Auxiliary 3.25% 9 Heat Detector Initiating 1.44% 4 Power Supply Control 2.53% 7 Pull Station Initiating 9.39% 26
Releasing Device Auxiliary 2.89% 8 Smoke Detector Initiating 11.55% 32 Speaker/Strobe Indicating 31.77% 88
Strobe Indicating 8.66% 24 Tamper Switch Supervisory 7.94% 22
Waterflow Switch Initiating 5.42% 15