SV2401240154 - 16111 Plummer Street Bldg. 10 - ANN FP - 6-12-24_Redacted 6.pdf
PDF 1 MB Posted
- Attached to
- H912--Fire Alarm Inspections - One Year Contract
- Solicitation number
- 36C26225Q0850
About this file
This document is an Annual Fire Pump Inspection and Testing Report for the VA Sepulveda facility located at 16111 Plummer Street in North Hills, California. The report details a comprehensive inspection of the facility's electric fire pump system, conducted on 6/12/24, using a Peerless pump with a Tornatech controller and US MOTORS driver. The pump has a rated capacity of 1000 gpm at 120 psi, with testing performed at 0%, 50%, 100%, and 150% of rated flow using 2.5" nozzle orifices. All inspection items were marked as "Pass", including fire pump start/stop pressures, pump house conditions, control valve inspections, and electrical system checks.
The performance test results demonstrate the fire pump's operational capabilities, with suction pressures ranging from 82 psi at 0% flow to 48 psi at 150% flow, and discharge pressures from 225 psi to 145 psi across the flow ranges. The pump maintained system pressures between 175-142 psi during testing, with RPM slightly decreasing from 3571 to 3545 as flow increased. Both automatic and manual starts were conducted, with 4 starts each deemed satisfactory. The test was performed using flow meters, 45s, diffusers, 50' hoses, and a test kit, and complies with NFPA 25 and California Code of Regulations, Title 19 requirements.
View the file
Other files
Show all 41
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
File details come from the government source that posted it. Updated .