This document is an Inspection, Testing, and Maintenance Cover Sheet for a fire sprinkler system at the VA Sepulveda facility located at 16611 Plummer St (Bldg. 47) in North Hills, California. The one-story building, constructed in 1953, underwent an annual fire sprinkler inspection on 02-19-2024, with no defects noted during the inspection. The report covers a comprehensive quarterly and annual review of the wet pipe fire sprinkler system, including riser information, system details, and compliance with California Code of Regulations, Title 19.
Key inspection details include a single riser in the service room with a 2-1/2" riser diameter and 1-1/4" main drain diameter. The main drain test showed an initial static pressure of 85 PSI, which dropped to 55 PSI during the residual pressure test, with a final static pressure of 85 PSI. The inspection covered various system components such as control valves, waterflow alarm devices, supervisory devices, and fire department connections, with most items receiving a "Pass" status. The report is part of the facility's ongoing fire protection system maintenance and meets requirements from NFPA, Joint Commission, and local regulatory standards.