VA Sepulveda_16111 Plummer St_Bldg 22_ANN FA_02-07-24_Redacted 26.pdf
PDF 527 KB Posted
- Attached to
- H912--Fire Alarm Inspections - One Year Contract
- Solicitation number
- 36C26225Q0850
About this file
This document is an Annual Fire Alarm Report for the VA Sepulveda Building 22, located at 1611 Plummer St, North Hills, CA 90012. The report, conducted on February 7th, 2024 by technician Parris Jackson, details a comprehensive inspection of fire alarm system components across multiple floors and locations, including duct detectors, heat detectors, manual pull stations, smoke detectors, water flow switches, audible visual devices, elevator recall functions, magnetic door holders, air handler unit shutdowns, and control panels/power supplies.
The inspection revealed two key discrepancies: a primary elevator recall failure in the elevator machine room (due to programming issues) and a water flow switch failure above the ceiling corridor by Women's Restroom 115 (system sensor issue). The report also notes a site observation that a pre-action system is disconnected. The testing was performed using a Cerberus Pyrotronics - MXL panel, with contact information for Keith Hayhurst (310-714-5379, keith.hayhurst@va.gov) and monitoring by Valley Alarm Co. The batteries for the fire alarm control units were tested and found to be at 79% capacity, manufactured in 2020.
View the file
Other files
Show all 41