About this file

This is a specification section for Rough Carpentry work (Section 06 10 00) from a federal construction contract dated October 1, 2017. The section establishes requirements for wood blocking, framing, sheathing, furring, nailers, sub-flooring, rough hardware, and light wood construction on VA Construction sites.

The specification mandates that installers must have a minimum of three years' experience in this type of work. All lumber and plywood must comply with applicable grading standards and bear marks from recognized associations or inspection agencies; unmarked materials require manufacturer's certificates approved by American Lumber Standards agencies. Product delivery requires lumber to be protected from dampness, stacked with air circulation, and stored on well-drained areas at least 152 mm (6 inches) above grade under ventilated sheds with protective roofing. Submittals must include shop drawings showing framing connection details and fasteners, along with manufacturer's literature for lumber, panels, hardware, adhesives, and chemical treatment certifications for wood-preservative and fire-retardant treated materials, including physical property testing by qualified independent agencies.

Material specifications include APA-rated plywood with Exposure 1 or Exterior ratings in specified thicknesses and span ratings depending on application (sheathing, subflooring, or underlayment). Hardware requirements specify ASME B18.6.1 or ASTM C1002 wood-to-wood screws, ASTM C954 or C1002 wood-to-steel screws, and ASTM F1667 nails in various types with galvanized or zinc-coated finishes for weather-exposed applications. Installation execution requires specific spacing, fastening patterns, panel staggering, and clearances; plywood and particle underlayment must be glue-nailed to subfloors, with edge spacing of 3 mm (1/8 inch) and wall clearances of 6 mm (1/4 inch) for combination subflooring-underlayment or 1 mm (1/32 inch) for plywood/hardboard underlayment.

View the file

Other files

File Type Posted
98_209_949 FLOORING SF.xlsx XLSX spreadsheet
36C26127Q0047 Amendment 0003.pdf PDF
Updated SOW ATTACHMENT_Reference Drawings 20261106.pdf PDF
20261117_RFI Responses Replace Flooring MCC.pdf PDF
Updated SOW Replace Flooring in McCellan_20261105_.pdf PDF
36C26127Q0047 Amendment 0002.pdf PDF
36C26127Q0047 Amendment 0001.pdf PDF
Site Visit Sign-in 612A4 27 020 _ 10 23 2026.pdf PDF
36C26127Q0047_Sol.pdf PDF
18. Site Visit Flyer 36C26127Q0047.pdf PDF
2. SOW ATTACHMENT_Reference Drawings.pdf PDF
16._VHA ICRA PROJECT.pdf PDF
13. RB-2_WALL BASE.pdf PDF
9. LVT-2_LUXURY VINYL TILE.pdf PDF
14. RST_RESILIENT STAIR TREADS.pdf PDF
6. CPT-1_CARPET.pdf PDF
1. SOW ATTACHMENT_Specifications_.pdf PDF
8. LVT-1_LUXURY VINYL TILE.pdf PDF
3. SOW ATTACHMENT_Bldg 209 McClellan Lead-Asbestos REP 2017.pdf PDF
12. RB-1_MILLWORK_WALL_FINISHING_SYSTEMS.pdf PDF
19. Price Breakdown Worksheet.docx DOCX document
20. Requests for Information RFI_ Form.docx DOCX document
5. Schluter_vinpro-data-sheet.pdf PDF
11. PCRA 612A4-27-020 Replace Flooring in McCellan.pdf PDF
4. SOW ATTACHMENT_1996 BW Asbestos Survey Bldgs 209.pdf PDF
7. ILSM 612A4-27-020 Replace Flooring in McCellan.pdf PDF
17. WD CA20260007 dtd 9 3 2026.pdf PDF
15. Tarkett Wall Base Made in USA.pdf PDF
10. MANN-0263 Made in the USA Supply Chain PDF v7_Digital.pdf PDF
Show all 29

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

10-01-17

06 10 00 - 1

SECTION 06 10 00

ROUGH CARPENTRY

PART 1 - GENERAL

1.1 DESCRIPTION:

A. This section specifies wood blocking, framing, sheathing, furring, nailers, sub-flooring, rough hardware, and light wood construction.

1.2 RELATED WORK:

NOT USED

1.3 SUBMITTALS:

A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT

DATA, AND SAMPLES.

B. Shop Drawings showing framing connection details, fasteners, connections and dimensions.

C. Manufacturer’s Literature and Data:

1. Submit data for lumber, panels, hardware and adhesives.

2. Submit data for wood-preservative treatment from chemical treatment manufacturer and certification from treating plants that treated materials comply with requirements. Indicate type of preservative used and net amount of preservative retained.

3. Submit data for fire retardant treatment from chemical treatment manufacturer and certification by treating plant that treated materials comply with requirements. Include physical properties of treated materials based on testing by a qualified independent testing agency.

4. For products receiving a waterborne treatment, submit statement that moisture content of treated materials was reduced to levels specified before shipment to project site.

D. Manufacturer’s certificate for unmarked lumber.

1.4 PRODUCT DELIVERY, STORAGE AND HANDLING:

A. Protect lumber and other products from dampness both during and after delivery at site.

B. Pile lumber in stacks in such manner as to provide air circulation around surfaces of each piece.

C. Stack plywood and other board products so as to prevent warping.

D. Locate stacks on well drained areas, supported at least 152 mm

(6 inches) above grade and cover with well-ventilated sheds having

06 10 00 - 2 firmly constructed over hanging roof with sufficient end wall to protect lumber from driving rain.

1.5 QUALITY ASSURANCE:

A. Installer: A firm with a minimum of three (3) years’ experience in the type of work required by this section.

1.6 GRADING AND MARKINGS:

A. Any unmarked lumber or plywood panel for its grade and species will not be allowed on VA Construction sites for lumber and material not normally grade marked, provide manufacturer’s certificates (approved by an American Lumber Standards approved agency) attesting that lumber and material meet the specified the specified requirements.

1.7 APPLICABLE PUBLICATIONS:

A. Publications listed below form a part of this specification to extent referenced. Publications are referenced in the text by basic designation only.

B. American Forest and Paper Association (AFPA):

NDS-15..................National Design Specification for Wood

Construction

WCD1-01.................Details for Conventional Wood Frame

Construction

C. American Institute of Timber Construction (AITC):

A190.1-07...............Structural Glued Laminated Timber

D. American Society of Mechanical Engineers (ASME):

B18.2.1-12(R2013).......Square and Hex Bolts and Screws

B18.2.2-10..............Square and Hex Nuts

B18.6.1-81(R2008).......Wood Screws

E. American Plywood Association (APA):

E30-11..................Engineered Wood Construction Guide

F. ASTM International (ASTM):

A653/A653M-13...........Steel Sheet Zinc-Coated (Galvanized) or Zinc-

Iron Alloy Coated (Galvannealed) by the Hot Dip

Process

C954-11.................Steel Drill Screws for the Application of

Gypsum Board or Metal Plaster Bases to Steel

Studs from 0.033 inch (2.24 mm) to 0.112-inch

(2.84 mm) in thickness

06 10 00 - 3

C1002-14................Steel Self-Piercing Tapping Screws for the

Application of Gypsum Panel Products or Metal

Plaster Bases to Wood Studs or Metal Studs

D198-14.................Test Methods of Static Tests of Lumber in

Structural Sizes

D2344/D2344M-13.........Test Method for Short-Beam Strength of Polymer

Matrix Composite Materials and Their Laminates

D2559-12a...............Adhesives for Structural Laminated Wood

Products for Use Under Exterior (Wet Use)

Exposure Conditions

D3498-03(R2011).........Adhesives for Field-Gluing Plywood to Lumber

Framing for Floor Systems

D6108-13................Test Method for Compressive Properties of

Plastic Lumber and Shapes

D6109-13................Test Methods for Flexural Properties of

Unreinforced and Reinforced Plastic Lumber and

Related Products

D6111-13a...............Test Method for Bulk Density and Specific

Gravity of Plastic Lumber and Shapes by

Displacement

D6112-13................Test Methods for Compressive and Flexural Creep and Creep-Rupture of Plastic Lumber and Shapes

F844-07a(R2013).........Washers, Steel, Plan (Flat) Unhardened for

General Use

F1667-13................Nails, Spikes, and Staples

G. American Wood Protection Association (AWPA):

AWPA Book of Standards

H. Commercial Item Description (CID):

A-A-55615...............Shield, Expansion (Wood Screw and Lag Bolt Self

Threading Anchors)

I. Forest Stewardship Council (FSC):

FSC-STD-01-001(Ver. 4-0)FSC Principles and Criteria for Forest

Stewardship

J. Military Specification (Mil. Spec.):

MIL-L-19140E............Lumber and Plywood, Fire-Retardant Treated

K. Environmental Protection Agency (EPA):

40 CFR 59(2014).........National Volatile Organic Compound Emission

Standards for Consumer and Commercial Products

06 10 00 - 4

L. Truss Plate Institute (TPI):

TPI-85..................Metal Plate Connected Wood Trusses

M. U.S. Department of Commerce Product Standard (PS)

PS 1-95.................Construction and Industrial Plywood

PS 20-10................American Softwood Lumber Standard

N. ICC Evaluation Service (ICC ES):

AC09....................Quality Control of Wood Shakes and Shingles

AC174...................Deck Board Span Ratings and Guardrail Systems

(Guards and Handrails)

PART 2 - PRODUCTS

2.1 PLYWOOD:

A. Comply with PS 1.

B. Bear the mark of a recognized association or independent inspection agency that maintains continuing control over quality of plywood which identifies compliance by veneer grade, group number, span rating where applicable, and glue type.

C. Sheathing:

1. APA rated Exposure 1 or Exterior; panel grade CD or better.

2. Wall sheathing:

a. Minimum 9 mm (11/32 inch) thick with supports 406 mm (16 inches) on center and 12 mm (15/32 inch) thick with supports 610 mm

(24 inches) on center unless specified otherwise.

b. Minimum 1200 mm (48 inches) wide at corners without corner bracing of framing.

3. Roof sheathing:

a. Minimum 9 mm (11/32 inch) thick with span rating 24/0 or 12 mm

(15/32 inch) thick with span rating for supports 406 mm

(16 inches) on center unless specified otherwise.

b. Minimum 15 mm (19/32 inch) thick or span rating of 40/20 or 18 mm

(23/32 inch) thick or span rating of 48/24 for supports 610 mm

(24 inches) on center.

D. Subflooring:

1. Under finish wood flooring or underlayment:

a. APA Rated sheathing, Exposure 1. panel grade CD.

b. Minimum 15 mm (19/32 inch) thick with span rating 32/16 or greater for supports at 406 mm (16 inches) on center and 18.25 mm

(23/32 inch) thick with span rating 48/24 for supports at 610 mm

(24 inches) on center.

06 10 00 - 5

2. Combination subflooring-underlayment under resilient flooring or carpet:

a. APA Rated Stud-I-Floor Exterior or Exposure 1, T and G.

b. Minimum 15 mm (19/32 inch) thick or greater, span rating 16, for supports at 406 mm (16 inches) on center; 18 mm (23/32 inch) thick or greater, span rating 24, for supports at 610 mm

(24 inches) on center.

E. Underlayment:

1. APA rated Exposure 1 or Exterior, panel grade C-C Plugged.

2. Minimum 6 mm (1/4 inch) thick or greater over plywood subflooring and 9 mm (3/8 inch) thick or greater over board subflooring, unless otherwise shown.

2.2 ROUGH HARDWARE AND ADHESIVES:

A. Screws:

1. Wood to Wood: ASME B18.6.1 or ASTM C1002.

2. Wood to Steel: ASTM C954, or ASTM C1002.

B. Nails:

1. Size and type best suited for purpose unless noted otherwise.

Provide aluminum-alloy nails, plated nails, or zinc-coated nails, for nailing wood work exposed to weather and on roof blocking.

2. ASTM F1667:

a. Common: Type I, Style 10.

b. Concrete: Type I, Style 11.

c. Barbed: Type I, Style 26.

d. Underlayment: Type I, Style 25.

e. Masonry: Type I, Style 27.

f. Provide special nails designed for use with ties, strap anchors, framing connectors, joists hangers, and similar items. Nails not less than 32 mm (1-1/4 inches) long, 8d and deformed or annular ring shank.

C. Adhesives:

1. For field-gluing plywood to lumber framing floor or roof systems:

ASTM D3498.

PART 3 - EXECUTION

3.1 INSTALLATION OF FRAMING AND MISCELLANEOUS WOOD MEMBERS:

A. Subflooring:

1. Subflooring may be either boards, structural-use panels, or plywood.

06 10 00 - 6

2. Lay board subflooring diagonally, with close joints. Stagger end joints and make joints over supports. Bear each board on at least three supports.

3. Provide a clearance of approximately 13 mm (1/2 inch) at masonry or concrete at walls.

4. Apply plywood and structural-use panel subflooring with face grain or long dimension at right angles to the supports, with edges 6 mm

(1/4 inch) apart at side joints, and 3 mm (1/8 inch) apart at end joints.

5. Combination subfloor-underlayment:

a. Space edges 3 mm (1/8 inch) apart.

b. Provide a clearance of 6 mm (1/4 inch) at masonry on concrete at walls.

6. Stagger panel end joints and make over support.

B. Underlayment:

1. Where finish flooring of different thickness is used in adjoining areas, provide underlayment of thickness required to bring finish-flooring surfaces into same plane.

2. Apply to dry, level, securely nailed, clean, wood subfloor without any projections.

3. Plywood and particle underlayment are to be glue-nailed to subfloor.

4. Butt underlayment panels to a light contact with a 1 mm (1/32 inch) space between plywood or hardboard underlayment panels and walls, and approximately 9 mm (3/8 inch) between particleboard underlayment panels and walls.

5. Stagger underlayment panel end joints with respect to each other and offset joints with respect to joints in the subfloor at least 50 mm

(2 inches).

6. After installation, avoid traffic on underlayment and damage to the finish surface.

C. Sheathing:

1. Provide plywood or structural-use panels for sheathing.

2. Lay panels with joints staggered, with edge and ends 3 mm (1/8 inch) apart and nailed over bearings as specified.

3. Set nails not less than 9 mm (3/8 inch) from edges.

4. Install 50 mm by 101 mm (2 inch by 4 inch) blocking spiked between joists, rafters and studs to support edge or end joints of panels.

- - - E N D - - -