This is an electrical schedules design document for a renovation project at the VA Central California Health Care System's Building 1, First Floor Acute Respiratory Clinic located in Fresno, California. The document includes luminaire schedules, low voltage equipment specifications, electrical load summaries, and branch panel details.
The luminaire schedule specifies LED lighting fixtures including 2x2 LED panels (ranging from 15.6 to 36.3 watts) and 6-inch round downlights (5.14 to 14.95 watts) from manufacturers such as Lithonia Lighting and Gotham Lighting, with specifications for lumen output (500 to 4000 lumens), color temperature (3500K), CRI (80+), and voltage ratings (120-277V multi-volt). The low voltage equipment schedule identifies five equipment types totaling 17 units: four security cameras, three wireless access points, five door security access pads, three room pressure monitors, and two pressure sensors, with installation locations specified in various rooms and spaces. The electrical load summary indicates existing demand loads of 364.30 kVA for MSS-B and 499.22 kVA for MSS-A, with new loads of 3.14 kVA and 10.80 kVA respectively, resulting in total switchboard loading of 31.87% and 44.24%. Branch panel details include normal power loads (estimated demand 4960 VA), life safety loads (2522 VA), and critical branch loads (3318 VA), with panels rated at 100 to 225 amperes at 120/208V, three-phase, four-wire configuration. The document was approved for construction on April 7, 2026, with a revision bulletin issued on May 29, 2026.
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TYPE DESCRIPTION
LUMINAIRE SCHEDULE
MOUNTING VOLTS LAMPS DRIVER WATTAGE MANUFACTURER AND MODEL NO.
A
B
C
2X2 LED PANEL
6" ROUND DOWN LIGHT
RECESSED
RECESSED
LED
LED
15.6
5.14
LITHONIA LIGHTING OR EQUAL CPX 2X2, 2000 LUMENS, 80
CRI, 3500K, SATIN WHITE LENS, 120-277
GOTHAM LIGHTING OR EQUAL IVO6 DOWNLIGHT 500
LUMENS 3500K 80+ CRI MEDIUM BATWING OPEN
PARABOLIC CLEAR ANODIZED MATTE DIFFUSE
MVOLT
MVOLT
EZ1
D
E
X EXIT LIGHT SURFACE LED 0.7
LITHONIA LIGHTING OR EQUAL LQMS W 3 R 120/277 EL N
BAAMVOLT
2X2 LED PANEL RECESSED LED 30.1 LITHONIA LIGHTING OR EQUAL CPX 2X2, 3200 LUMENS, 80
CRI, 3500K, SATIN WHITE LENS, 120-277MVOLT EZ1
2X2 LED PANEL RECESSED LED 36.3 LITHONIA LIGHTING OR EQUAL CPX 2X2, 4000 LUMENS, 80
CRI, 3500K, SATIN WHITE LENS, 120-277MVOLT EZ1
6" ROUND DOWN LIGHT RECESSED LED 14.95
GOTHAM LIGHTING OR EQUAL IVO6 DOWNLIGHT 1500
LUMENS 3500K 80+ CRI MEDIUM BATWING OPEN
PARABOLIC PEWTER ANODIZED MATTE DIFFUSE
MVOLT
LOW VOLTAGE EQUIPMENT SCHEDULE
EQUIPMENT
TAG
COUNT DESCRIPTION
VSCM 4 SECURITY CAMERA, WIRING,
HARDWARE, SOFTWARE
LICENSES
PROCURED BY
CONTRACTOR CONTRACTOR
INSTALLED BYLOCATIONS
1A01A, 1A002, 1A09C
WAP 3 WIRELESS ACCESS POINT,
WIRING, HARDWARE,
SOFTWARE LICENSES
CONTRACTOR CONTRACTOR1A09, 1A09A
SECURITY
ACCESS
PAD
5 DOOR SECURITY ACCESS
PAD, HARDWARE, WIRING,
SOFTWARE
CONTRACTOR CONTRACTOR1A09,1A002, 1A09C
ROOM
PRESSURE
MONITORS
3 HARDWARE, WIRING,
SOFTWARE
MECHANICAL CONTRACTOR MECHANICAL CONTRACTOR1A01A,1A09D, 1A09E
(SEE MH-107)
PRESSURE
SENSOR
2 HARDWARE, WIRING,
SOFTWARE
MECHANICAL CONTRACTOR MECHANICAL CONTRACTOR1A01A
(SEE MH-102)
NOTE:CONTRACTOR TO PROVIDE SUBMITTAL AND APPROVAL PRIOR TO PROCUREMENT IN COORDINATION WITH COR.
LOAD SUMMARY FOR: MSS-B
EXISITNG DEMAND LOAD 364.30 kVA
(30 DAY LOAD READING)
( 04/01/2026 TO 05/01/2026)
NEW LOAD = 3.14 kVA
TOTAL LOAD = 367.44 kVA
AMPS @ 120/208V, 3PH, 4W = 1019.91 AMPS
SWITCHBOARD RATING (A) = 3200.00 AMPS
SWITCHBOARD RATING (KVA) = 1152.85 kVA
SWITCHBOARD (V) = 208.00 V
SWITCHBOARD LOADING = 31.87 %
LOAD SUMMARY FOR: MSS-A
EXISITNG DEMAND LOAD 499.22 kVA
(30 DAY LOAD READING)
( 04/01/2026 TO 05/01/2026)
NEW LOAD = 10.80 kVA
TOTAL LOAD = 510.02 kVA
AMPS @ 120/208V, 3PH, 4W = 1415.67 AMPS
SWITCHBOARD RATING (A) = 3200.00 AMPS
SWITCHBOARD RATING (KVA) = 1152.85 kVA
SWITCHBOARD (V) = 208.00 V
SWITCHBOARD LOADING = 44.24 %
2 3 4 5 6 7 8 9
2 3 4 5 6 7 8 91
A
B
C
D
E
F
A
B
C
D
E
F
ARCHITECT/ENGINEERS DRAWING TITLE:
APPROVED: LOCATION:
PROJECT TITLE:
DATE: CHECKED: DRAWN:
PROJECT NUMBER:
BUILDING NUMBER:
DRAWING NUMBER:
Office of Construction and Facilities Management
VA FORM 08-6231
on e ei gh th in ch o ne fo ot on e qu a rte r i nc h on e fo ot th re e ei gh th s i nc h on e fo ot on e ha lf in ch o ne fo ot th re e q ua rte rs in ch o ne fo ot on e in ch o ne fo ot on e an d o ne h al f i nc he s = o ne fo ot th re e in ch es o ne fo ot
6"
6"
6"
6 "
Department of Veterans Affairs
STAMP
DAV ENERGY SOLUTIONS
2207 GARNET AVE, SUITE I
SAN DIEGO, CA 92109
P: 619.770.8552
WWW.DAVENERGY.COM
CONSULTANTS
1DAV ENERGY SOLUTIONS
2207 GARNET AVE, SUITE I
SAN DIEGO, CA 92109
P: 619.770.8552
WWW.DAVENERGY.COM
DWG. ___ OF ___
05/29/2026
E-701-R
570-23-223
VA Central California Health Care System 2615 E Clinton Ave Fresno, CA 93703
JL RP
ELECTRICAL SCHEDULES DESIGN TO RENOVATE BLDG 1, 1ST FLOOR
ACUTE RESPIRATORY CLINIC
60 62
* ESTIMATED NORMAL BRANCH POWER LOAD.
Notes:
Total Est. Demand Current: 14 A Total Conn. Current: 14 A
Total Est. Demand: 4960 VA Receptacle 3420 VA 100.00% 3420 VA Total Conn. Load: 4960 VA Power 1540 VA 100.00% 1540 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 0 A 31 A 13 A Total Load: 0 VA 3560 VA 1400 VA
41 Space -- 1 -- 0 VA -- -- -- 42
39 -- -- -- 0 VA 0 VA -- -- -- 40
37 NORTH ENTRANCE HEATER 40 A 2 0 VA 0 VA 3 100 A MAIN 38
35 Spare 20 A 1 0 VA 0 VA 1 20 A REC ADMISSION DESK 36 33 (N) VESTIBULE AIR CURTAIN 20 A 1 500 VA 540 VA 1 20 A (N) REC CLEAN SUPPLY 1A02 34
31 ATM MACHINE 20 A 1 0 VA 32
29 (N) REC WAITING AREA 1A01A 20 A 1 360 VA 0 VA -- -- -- 30
27 (N) REC MSA CHECK IN 1A01B 20 A 1 1260... 0 VA -- -- -- 28
25 LIGHTS LOBBY 20 A 1 0 VA 0 VA 3 20 A Spare 26
23 LIGHTS LOBBY 20 A 1 0 VA 500 VA 1 20 A (N) TOILET SENSOR 1A06 24
21 (N) REC TOILET1A06 20 A 1 720 VA 0 VA -- -- -- 22
19 REC RM E103 20 A 1 0 VA 0 VA 2 40 A SPACE HEATER FRONT ENTRANCE 20
17 CORRIDOR REC E103, 1A08 20 A 1 0 VA 0 VA 1 20 A STARBUCKS ROLLUP CAGE 18
15 LIGHTS MAIN ENTRANCE, LIGHTS POLICE... 20 A 1 0 VA 0 VA 1 20 A STARBUCKS ROLLUP CAGE 16
13 LIGHTS MAIN ENTRANCE 20 A 1 0 VA 0 VA 1 20 A EAST AUTO DOORS 14
11 LIGHTS MAIN ENTRANCE 20 A 1 0 VA 0 VA 1 20 A REC CU6, LIGHTS 12
9 (N) VAV SWITCH 20 A 1 180 VA 0 VA 1 20 A LIGHTS, REC RM E103 10
7 ROLLUP GRILLE DOOR 20 A 1 0 VA 0 VA 1 20 A A/C CONTROL POWER 8
5 ROLL UP DOORS-CHECK IN 20 A 1 0 VA 540 VA 1 20 A (N) REC 1A09A, 1A09 6
3 ELEVATOR LOBBY LIGHTS 20 A 1 0 VA 360 VA 1 20 A (N) SINK 1A09B, 1A09A 4
1 REC BY LOBBY ATM, ATM POWER LIGHTS... 20 A 1 0 VA 0 VA 1 20 A LIGHTS CORRIDOR EAST 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 225 A Mounting: RECESSED Wires: 4 Mains Rating: 225 A
Supply From: 1 PNL RISER-D Phases: 3 Mains Type:
Location: Space 70 Volts: 120/208 Wye A.I.C. Rating:
Branch Panel: (E)N-C-1D
* ESTIMATED LIFE SAFETY BRANCH POWER LOAD.
Notes:
Total Est. Demand Current: 7 A Total Conn. Current: 7 A
Total Est. Demand: 2522 VA Power 2500 VA 100.00% 2500 VA Total Conn. Load: 2522 VA Lighting 22 VA 100.00% 22 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 0 A 21 A 0 A Total Load: 0 VA 2500 VA 22 VA
23 (N) EXIT SIGNS 1A01A, 1A09 20 A 1 22 VA 0 VA -- -- -- 24
21 (N) VESTIBULE AUTOMATC DOOR OPENERS 20 A 1 1000... 0 VA -- -- -- 22
19 PACS 20 A 1 0 VA 0 VA 3 100 A MAIN 20
17 PHONE REC 20 A 1 0 VA 0 VA 1 20 A REC VA POLICE 18
15 PHONE REC 20 A 1 0 VA 1500... 1 20 A Power 16
13 PHONE REC 20 A 1 0 VA 0 VA 1 20 A REC VA POLICE 14
11 STAIRWELL LIGHTS 20 A 1 0 VA 0 VA 1 20 A FRONT CANOPY LIGHTS 12
9 STAIRWELL 20 A 1 0 VA 0 VA 1 20 A LIGHTS VA POLICE 10
7 STAIRWELL 20 A 1 0 VA 0 VA 1 20 A AUTO DOOR MAIN ENTRANCE 8
5 STAIRWELL 20 A 1 0 VA 0 VA 1 20 A EXIT LIGHTS SOUTH WEST 6
3 STAIRWELL 20 A 1 0 VA 0 VA 1 20 A AUTO DOOR EAST ENTRANCE 4
1 EXIT LIGHTS 20 A 1 0 VA 0 VA 1 20 A LIGHTS CORRIDOR EAST 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 150 A Mounting: RECESSED Wires: 4 Mains Rating: 150 A
Supply From: 1 PNL EDP2 Phases: 3 Mains Type:
Location: Space 70 Volts: 120/208 Wye A.I.C. Rating:
Branch Panel: LS-E-1E
*ESTIMATED CRITICAL BRANCH POWER LOAD.
Notes:
Total Est. Demand Current: 9 A Receptacle 900 VA 100.00% 900 VA Total Conn. Current: 9 A Power 1166 VA 100.00% 1166 VA Total Est. Demand: 3318 VA Other 0 VA 0.00% 0 VA Total Conn. Load: 3318 VA Lighting 1252 VA 100.00% 1252 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 4 A 18 A 6 A Total Load: 489 VA 2112 VA 717 VA
47 48 45 46 43 44 41 Space -- 1 -- 0 VA -- -- -- 42 39 Space -- 1 -- 0 VA -- -- -- 40 37 Space -- 1 -- 0 VA 3 100 A MAIN 38 35 (N) REC INTERVIEW 1A09A, 1A09B 20 A 1 360 VA -- 1 -- Space 36 33 (N) VESTIBULE LIGHTS 1A002 20 A 1 1121... 75 VA 1 20 A (N) MSA CHECK IN LIGHTS 1A01B 34 31 (N) LIGHTS 1A09A, 1A09B 20 A 1 150 VA 338 VA 1 20 A (N) WAITING AREA LIGHTS 1A01A 32
29 (N) CORRIDOR LIGHTS 1A09 20 A 1 226 VA 131 VA 1 20 A (N) LIGHTS 1A06, 1A02 30
27 (N) REC PORTABLE X-RAY 20 A 1 180 VA 376 VA 1 20 A (N) LIGHTS 1A09C, 1A09D, 1A09E 28 25 CANOPY LIGHTS 20 A 1 0 VA 0 VA 1 20 A Spare 26 23 CORRIDOR LIGHTS 20 A 1 0 VA -- 1 -- Space 24
21 CORRIDOR LIGHTS 20 A 1 0 VA 0 VA 1 20 A OR ADMISSION DESK 22
19 CORRIDOR LIGHTS 20 A 1 0 VA 0 VA 1 20 A OR ADMISSION DESK 20
17 CANOPY LIGHTS 20 A 1 0 VA 0 VA 1 20 A CANOPY LIGHTS 18
15 CANOPY LIGHTS 20 A 1 0 VA 0 VA 1 20 A CANOPY LIGHTS 16
13 CANOPY LIGHTS 20 A 1 0 VA 0 VA 1 20 A CANOPY LIGHTS 14
11 PANEL JB 20 A 1 0 VA 0 VA 1 20 A OR ADMISSION DESK 12
9 (N) REC EXAM 1A09E, 1A09D 20 A 1 360 VA 0 VA 1 20 A OR ADMISSION DESK 10
7 REC ENTRYWAY OUTSIDE LOBBY 20 A 1 0 VA 0 VA 1 20 A PANEL JB 8
5 METASYS ATRIUM 20 A 1 0 VA 0 VA 1 20 A ATRIUM LIGHTS 6
3 MASTER CLOCK CONTROL GA4-B 20 A 1 0 VA 0 VA 1 20 A ATRIUM LIGHTS 4
1 LIGHTS RM E100, REC PATIENT REP 20 A 1 0 VA 0 VA 1 20 A ATRIUM LIGHTS 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 100 A Mounting: Surface Wires: 4 Mains Rating: 100 A
Supply From: 1 PNL EDP1 Phases: 3 Mains Type: MCB Location: Space 70 Volts: 120/208 Wye A.I.C. Rating:
Branch Panel: (E)C-E-1Y
Notes:
Total Est. Demand Current: 15 A Total Conn. Current: 15 A
Total Est. Demand: 12470 VA Total Conn. Load: 12470 VA
Motor 12470 VA 100.00% 12470 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 15 A
Total Conn. Load: 12470 VA
10 (N) ARC EF-01 3 15 A 15 A 6235 VA
9 (N) ARC EF-02 3 15 A 15 A 6235 VA
8 OPC MCP 1-EF-12/13 3 15 A 15 A 0 VA
7 OPC MCP 1-AH-5 3 40 A 40 A 0 VA
6 OPC MCP TEMP COMP 3 20 A 20 A 0 VA
5 OPC CB T-MCC-2E 3 30 A 30 A 0 VA
4 OPC MCP RF-2 3 15 A 15 A 0 VA
3 OPC MCP RF-3 3 80 A 80 A 0 VA
2 OPC MCP EF-2 3 50 A 50 A 0 VA
1 OPC MCP EF-12 3 15 A 15 A 0 VA
CKT Circuit Description # of Poles Frame Size Trip Rating Load Remarks
Notes:
Enclosure: MCB Rating:
Mounting: FREE STANDING Wires: 4 Mains Rating: 600 A
Supply From: OPS ATS A Phases: 3 Mains Type: MLO Location: OPC ROOF PENTHOUSE Volts: 480/277 Wye A.I.C. Rating: 42K
MCC: MCC-2 E
Notes:
Total Est. Demand Current: 9 A Total Conn. Current: 9 A
Receptacle 2520 VA 100.00% 2520 VA Total Est. Demand: 3135 VA Power 615 VA 100.00% 615 VA Total Conn. Load: 3135 VA Other 0 VA 0.00% 0 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 9 A 1 A 19 A Total Load: 900 VA 75 VA 2160 VA
47 48 45 46 43 44
41 REC 1A13C (WEST) 20 A 1 0 VA 0 VA 1 20 A REC 1A14 42
39 REC 1A13B (MID) 20 A 1 0 VA 0 VA 1 20 A REC WAIT AREA 40
37 REC 1A13A (EAST) 20 A 1 0 VA 0 VA 1 20 A REC 1A14 38
35 Space -- 1 -- 180 VA 1 20 A (N) VAV SWITCH 36 33 Space -- 1 -- 0 VA 1 20 A HAND DRYER 1A15A.1 34 31 Spare 20 A 1 0 VA 0 VA 1 20 A REC 1A14 32
29 -- -- -- 0 VA 0 VA 1 20 A 1A15A.3 GLASS 30
27 Spare 30 A 2 0 VA 0 VA -- -- -- 28
25 REC 1A10, E107, 1A13, 1A14 20 A 1 0 VA 0 VA 2 20 A REC 1A15A, 1A15 26
23 REC 1A13, 1A14, 1A16, 1A16B, CORRIDOR 20 A 1 0 VA 0 VA 1 20 A REC EMPLY HEALTH 24 21 REC LOBBY COFFE KIOSK, CLOUD LGT 20 A 1 0 VA 0 VA 1 20 A A/C CONTROLS OVER 1A15C DOOR 22
19 LIGHTS 1A15C 20 A 1 0 VA 0 VA 1 15 A A/C CONTROLS OVER PNL NE1E 20
17 LIGHTS 1A15C 20 A 1 0 VA 0 VA 1 20 A REC 1A15 REC DESK 18
15 REC 1A15C 20 A 1 0 VA 0 VA 1 20 A REC 1A18 HALLWAY 16
13 MAGLOCK 1A15A 20 A 1 0 VA 0 VA 1 20 A LIGHTS 1A15C, REC 1A15A.2, KITCHEN 14
11 Spare 20 A 1 0 VA 0 VA 1 20 A LIGHTS 1A15A.1 12 9 Space -- 1 -- 75 VA 1 20 A (N) 1A11, 1A12 LIGHTS 10 7 Space -- 1 -- 900 VA 1 20 A (N) REC 1A09C,1A09B 8
5 (N) SINKS 1A09E,1A09D 20 A 1 360 VA 1620... 1 20 A (N) REC 1A09E,1A09D,1A11 6
3 LIGHTS 1A13, 1A14, 1A14, BLD OUT 20 A 1 0 VA 0 VA 1 20 A LIGHTS SOUTH PORCH 4
1 LIGHTS 1A13, 1A14, 1A14, BLD OUT 20 A 1 0 VA 0 VA 1 20 A LIGHTS 1A15A, 1AA5A.1, 1A15A.2 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 100 A Mounting: Surface Wires: 4 Mains Rating: 100 A
Supply From: Phases: 3 Mains Type: MCB Location: Space 70 Volts: 120/208 Wye A.I.C. Rating:
Branch Panel: (E) N-E-1E
REVISIONS DATE
100% FOR CONSTRUCTION 04/07/2026
BULLETIN NO.1 05/29/2026