925417-VA Central California Health Care System - Building 31 Deficiency Report v1 September 2025.xlsx

XLSX spreadsheet 26 KB Posted

Attached to
Z1DZ--FIRE DOOR REPAIRS INSPECTION DEFICIENCIES
Solicitation number
36C26126Q0854
Issued by

About this file

This is a Building 31 Deficiency Report for the VA Central California Health Care System documenting fire door repair inspection findings dated September 2025. The report identifies deficiencies related to fire door conditions and performance issues that require corrective action within the facility. The document serves as the technical basis for the associated solicitation 36C26126Q0854 titled "FIRE DOOR REPAIRS INSPECTION DEFICIENCIES" issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 21.

The deficiency report appears to function as a requirements document detailing specific fire door issues identified during inspection at Building 31 of the VA Central California Health Care System. These documented deficiencies form the scope of work for contractors responding to the solicitation, which seeks qualified vendors to perform necessary fire door repairs to bring the facility into compliance with applicable fire safety codes and standards. The report provides the technical foundation and detailed listing of required repairs that prospective contractors must address in their proposals, establishing both the nature and extent of work needed to remediate the identified fire door system deficiencies.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Summary VA Central California Health Care System - Building 31 - Fresno, CA

Initial Inspection Results Current Status

Pass Rate: 58%Pass Rate: 61%
PassFailPassFail
18131912

Priority Items

OpenClosed
Door Replacement00
Latching41
Clearance40
Labeling00
Client Will Address40
An asset may fall in multiple categories if applicable

Wall Rating Door Type

InspectedPassFailInspectedPassFail
1 Hour Fire/Smoke13103Swinging Doors311912
Smoke Barrier1899Chute Doors000
Total311912Rolling Doors000
Sliding Doors000
WON Doors000
Fire Curtains000
Total Doors311912

Priority Items Door Replacement Latching Clearance Labeling Client Will Address 3 0 0 9 1

Deficiencies

VA Central California Health Care System - Building 31 - Fresno, CA
Door IDAlt IDLocationFloorBuildingInspectorDoor TypeHandedWall RatingDoor MaterialDoor RatingFrame MaterialFrame RatingDeficiencyDeficiency CommentStatusPhase 1 Repair OptionPhase 1 Repair CommentPhase 2 Repair OptionPhase 2 Repair CommentPhase 3 Repair OptionPhase 3 Repair CommentRelabeling Repair Option(s)Relabeling Repair Comment
11528910SP1C05-31Clean linen1Community Living centerFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelLabel present; no rating specifiedFrame missing filler plate(s)Not RepairedDeficiency not repaired: additional parts required
11528910SP1C05-31Clean linen1Community Living centerFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelLabel present; no rating specifiedDoor missing filler plate(s)Not RepairedDeficiency not repaired: additional parts required
11528911SP1A08-31Occupational activities1Community Living centerFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11528911SP1A08-31Occupational activities1Community Living centerFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingMissing / damaged door closerNot RepairedDeficiency not repaired: additional parts required
11528912SP1A08A-31Activity storage1Community Living centerFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingMissing / damaged door closerNot RepairedDeficiency not repaired: additional parts required
11528913SP1A09-31Therapy room1Community Living centerFrank HerreraSwinging DoorLHSmoke BarrierAluminumSmoke LabelSteelSmoke LabelMissing / damaged exit deviceNot RepairedDeficiency not repaired: client will addressPer Taneasha , client will address. This door cannot be addressed until the required hardware is identified and installed
11528913SP1A09-31Therapy room1Community Living centerFrank HerreraSwinging DoorLHSmoke BarrierAluminumSmoke LabelSteelSmoke LabelFrame penetrations / unused fastener holesNot RepairedDeficiency not repaired: additional parts required
11528914SP1A09-31Therapy room1Community Living centerFrank HerreraSwinging DoorRHSmoke BarrierAluminumSmoke LabelSteelSmoke LabelMissing / damaged exit deviceNot RepairedDeficiency not repaired: client will addressPer Taneasha , client will address. This door cannot be addressed until the required hardware is identified and installed
11528914SP1A09-31Therapy room1Community Living centerFrank HerreraSwinging DoorRHSmoke BarrierAluminumSmoke LabelSteelSmoke LabelDoor does not latchNot RepairedDeficiency not repaired: additional parts required
11528914SP1A09-31Therapy room1Community Living centerFrank HerreraSwinging DoorRHSmoke BarrierAluminumSmoke LabelSteelSmoke LabelFrame penetrations / unused fastener holesRepaired/PassedDeficiency repaired/passed: filled penetrations
11528915SP1A10-31Dinning room1Community Living centerFrank HerreraSwinging DoorLHSmoke BarrierAluminumSmoke LabelSteelSmoke LabelFrame penetrations / unused fastener holesNot RepairedDeficiency not repaired: additional parts required
11528915SP1A10-31Dinning room1Community Living centerFrank HerreraSwinging DoorLHSmoke BarrierAluminumSmoke LabelSteelSmoke LabelMissing / damaged exit deviceNot RepairedDeficiency not repaired: client will addressPer Taneasha , client will address. This door cannot be addressed until the required hardware is identified and installed
11528916SP1A10-31Dinning room1Community Living centerFrank HerreraSwinging DoorRHSmoke BarrierAluminumSmoke LabelSteelSmoke LabelFrame penetrations / unused fastener holesNot RepairedDeficiency not repaired: additional parts required
11528916SP1A10-31Dinning room1Community Living centerFrank HerreraSwinging DoorRHSmoke BarrierAluminumSmoke LabelSteelSmoke LabelMissing / damaged exit deviceNot RepairedDeficiency not repaired: client will addressPer Taneasha , client will address. This door cannot be addressed until the required hardware is identified and installed
11528917Activities1Community Living centerFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingDoor penetrations / unused fastener holesNot RepairedDeficiency not repaired: additional parts required
11528917Activities1Community Living centerFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11528920SP1A16-31Restroom,1Community Living centerFrank HerreraSwinging DoorRH1 Hour Fire/SmokeWood20 MinuteSteelLabel present; no rating specifiedFrame missing filler plate(s)Not RepairedDeficiency not repaired: additional parts required
11528921SP1A13B-31Storage 1a13b1Community Living centerFrank HerreraSwinging DoorRHSmoke BarrierWood20 MinuteSteelNo label present / not required per wall ratingMissing / damaged door closerNot RepairedDeficiency not repaired: additional parts required
11528924SP1A28-31Housekeeping1Community Living centerFrank HerreraSwinging DoorLH1 Hour Fire/SmokeWood20 MinuteSteelNo label present / not required per wall ratingExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11528929Cross corridor near medication room1Community Living centerFrank HerreraSwinging DoorRH1 Hour Fire/SmokeWood20 MinuteSteel60 MinuteExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11528932SP1B02-311b02 storage1Community Living centerFrank HerreraSwinging DoorRHSmoke BarrierWood20 MinuteSteel3 HourDoor does not latch - rubbing issueRepaired/PassedDeficiency repaired/passed: door no longer rubs and door swings freely

Client will address

VA Central California Health Care System - Building 31 - Fresno, CA
Door IDAlt IDLocationFloorBuildingInspectorDoor TypeHandedWall RatingDoor MaterialDoor RatingFrame MaterialFrame RatingDeficiencyDeficiency CommentStatusPhase 1 Repair OptionPhase 1 Repair CommentPhase 2 Repair OptionPhase 2 Repair CommentPhase 3 Repair OptionPhase 3 Repair CommentRelabeling Repair Option(s)Relabeling Repair Comment
11528913SP1A09-31Therapy room1Community Living centerFrank HerreraSwinging DoorLHSmoke BarrierAluminumSmoke LabelSteelSmoke LabelMissing / damaged exit deviceNot RepairedDeficiency not repaired: client will addressPer Taneasha , client will address. This door cannot be addressed until the required hardware is identified and installed
11528914SP1A09-31Therapy room1Community Living centerFrank HerreraSwinging DoorRHSmoke BarrierAluminumSmoke LabelSteelSmoke LabelMissing / damaged exit deviceNot RepairedDeficiency not repaired: client will addressPer Taneasha , client will address. This door cannot be addressed until the required hardware is identified and installed
11528915SP1A10-31Dinning room1Community Living centerFrank HerreraSwinging DoorLHSmoke BarrierAluminumSmoke LabelSteelSmoke LabelMissing / damaged exit deviceNot RepairedDeficiency not repaired: client will addressPer Taneasha , client will address. This door cannot be addressed until the required hardware is identified and installed
11528916SP1A10-31Dinning room1Community Living centerFrank HerreraSwinging DoorRHSmoke BarrierAluminumSmoke LabelSteelSmoke LabelMissing / damaged exit deviceNot RepairedDeficiency not repaired: client will addressPer Taneasha , client will address. This door cannot be addressed until the required hardware is identified and installed

All doors and deficiencies

VA Central California Health Care System - Building 31 - Fresno, CA
Door IDAlt IDLocationFloorBuildingInspectorDoor TypeHandedWall RatingDoor MaterialDoor RatingFrame MaterialFrame RatingDeficiencyDeficiency CommentStatusPhase 1 Repair OptionPhase 1 Repair CommentPhase 2 Repair OptionPhase 2 Repair CommentPhase 3 Repair OptionPhase 3 Repair CommentRelabeling Repair Option(s)Relabeling Repair Comment
11528872SP1C02-31Laundry room1Community Living centerFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingPassed
11528904Cross corridor near nourishment1Community Living centerFrank HerreraSwinging DoorRH1 Hour Fire/SmokeWood20 MinuteSteelLabel illegible; label not required per wall ratingPassed
11528905SP1C01-31Nourishment kitchen1Community Living centerFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingPassed
11528906Cross corridor near nourishment1Community Living centerFrank HerreraSwinging DoorRH1 Hour Fire/SmokeWood20 MinuteSteelLabel illegible; label not required per wall ratingPassed
11528907Cross corridor near 1A061Community Living centerFrank HerreraSwinging DoorRH1 Hour Fire/SmokeWood20 MinuteSteelLabel illegible; label not required per wall ratingPassed
11528908Cross corridor near 1A061Community Living centerFrank HerreraSwinging DoorRH1 Hour Fire/SmokeWood20 MinuteSteelLabel illegible; label not required per wall ratingPassed
11528909SP1C21-31Soiled utility1Community Living centerFrank HerreraSwinging DoorLHSmoke BarrierWood45 MinuteSteelLabel present; no rating specifiedPassed
11528910SP1C05-31Clean linen1Community Living centerFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelLabel present; no rating specifiedFrame missing filler plate(s)Not RepairedDeficiency not repaired: additional parts required
11528910SP1C05-31Clean linen1Community Living centerFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelLabel present; no rating specifiedDoor missing filler plate(s)Not RepairedDeficiency not repaired: additional parts required
11528911SP1A08-31Occupational activities1Community Living centerFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingMissing / damaged door closerNot RepairedDeficiency not repaired: additional parts required
11528911SP1A08-31Occupational activities1Community Living centerFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11528912SP1A08A-31Activity storage1Community Living centerFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingMissing / damaged door closerNot RepairedDeficiency not repaired: additional parts required
11528913SP1A09-31Therapy room1Community Living centerFrank HerreraSwinging DoorLHSmoke BarrierAluminumSmoke LabelSteelSmoke LabelMissing / damaged exit deviceNot RepairedDeficiency not repaired: client will addressPer Taneasha , client will address. This door cannot be addressed until the required hardware is identified and installed
11528913SP1A09-31Therapy room1Community Living centerFrank HerreraSwinging DoorLHSmoke BarrierAluminumSmoke LabelSteelSmoke LabelFrame penetrations / unused fastener holesNot RepairedDeficiency not repaired: additional parts required
11528914SP1A09-31Therapy room1Community Living centerFrank HerreraSwinging DoorRHSmoke BarrierAluminumSmoke LabelSteelSmoke LabelFrame penetrations / unused fastener holesRepaired/PassedDeficiency repaired/passed: filled penetrations
11528914SP1A09-31Therapy room1Community Living centerFrank HerreraSwinging DoorRHSmoke BarrierAluminumSmoke LabelSteelSmoke LabelMissing / damaged exit deviceNot RepairedDeficiency not repaired: client will addressPer Taneasha , client will address. This door cannot be addressed until the required hardware is identified and installed
11528914SP1A09-31Therapy room1Community Living centerFrank HerreraSwinging DoorRHSmoke BarrierAluminumSmoke LabelSteelSmoke LabelDoor does not latchNot RepairedDeficiency not repaired: additional parts required
11528915SP1A10-31Dinning room1Community Living centerFrank HerreraSwinging DoorLHSmoke BarrierAluminumSmoke LabelSteelSmoke LabelFrame penetrations / unused fastener holesNot RepairedDeficiency not repaired: additional parts required
11528915SP1A10-31Dinning room1Community Living centerFrank HerreraSwinging DoorLHSmoke BarrierAluminumSmoke LabelSteelSmoke LabelMissing / damaged exit deviceNot RepairedDeficiency not repaired: client will addressPer Taneasha , client will address. This door cannot be addressed until the required hardware is identified and installed
11528916SP1A10-31Dinning room1Community Living centerFrank HerreraSwinging DoorRHSmoke BarrierAluminumSmoke LabelSteelSmoke LabelMissing / damaged exit deviceNot RepairedDeficiency not repaired: client will addressPer Taneasha , client will address. This door cannot be addressed until the required hardware is identified and installed
11528916SP1A10-31Dinning room1Community Living centerFrank HerreraSwinging DoorRHSmoke BarrierAluminumSmoke LabelSteelSmoke LabelFrame penetrations / unused fastener holesNot RepairedDeficiency not repaired: additional parts required
11528917Activities1Community Living centerFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11528917Activities1Community Living centerFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingDoor penetrations / unused fastener holesNot RepairedDeficiency not repaired: additional parts required
11528918SP1A29-31Oxygen storage1Community Living centerFrank HerreraSwinging DoorLHSmoke BarrierSteel90 MinuteSteel90 MinutePassed
11528919SP1A15-31Clean supply1Community Living centerFrank HerreraSwinging DoorRH1 Hour Fire/SmokeWood20 MinuteSteelLabel present; no rating specifiedPassed
11528920SP1A16-31Restroom,1Community Living centerFrank HerreraSwinging DoorRH1 Hour Fire/SmokeWood20 MinuteSteelLabel present; no rating specifiedFrame missing filler plate(s)Not RepairedDeficiency not repaired: additional parts required
11528921SP1A13B-31Storage 1a13b1Community Living centerFrank HerreraSwinging DoorRHSmoke BarrierWood20 MinuteSteelNo label present / not required per wall ratingMissing / damaged door closerNot RepairedDeficiency not repaired: additional parts required
11528922Cross corridor near 1a271Community Living centerFrank HerreraSwinging DoorRH1 Hour Fire/SmokeWood20 MinuteSteelLabel present; no rating specifiedPassed
11528923Cross corridor near 1a271Community Living centerFrank HerreraSwinging DoorRH1 Hour Fire/SmokeWood20 MinuteSteelLabel present; no rating specifiedPassed
11528924SP1A28-31Housekeeping1Community Living centerFrank HerreraSwinging DoorLH1 Hour Fire/SmokeWood20 MinuteSteelNo label present / not required per wall ratingExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11528925SP1A22-311a22 storage1Community Living centerFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingPassed
11528926SP1A22A-31Fire sprinkler room1Community Living centerFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingPassed
11528927SP1A34-31Clean supply1Community Living centerFrank HerreraSwinging DoorLH1 Hour Fire/SmokeWood20 MinuteSteelLabel present; no rating specifiedPassed
11528928SP1B21-31Medication1Community Living centerFrank HerreraSwinging DoorRH1 Hour Fire/SmokeWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingPassed
11528929Cross corridor near medication room1Community Living centerFrank HerreraSwinging DoorRH1 Hour Fire/SmokeWood20 MinuteSteel60 MinuteExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11528930Cross corridor near Medication1Community Living centerFrank HerreraSwinging DoorRH1 Hour Fire/SmokeWood20 MinuteSteel60 MinutePassed
11528931SP1B20-31Clean linen1Community Living centerFrank HerreraSwinging DoorRHSmoke BarrierWood45 MinuteSteelLabel present; no rating specifiedPassed
11528932SP1B02-311b02 storage1Community Living centerFrank HerreraSwinging DoorRHSmoke BarrierWood20 MinuteSteel3 HourDoor does not latch - rubbing issueRepaired/PassedDeficiency repaired/passed: door no longer rubs and door swings freely
11528933SP1B16-31Clean supply1Community Living centerFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingPassed

File details come from the government source that posted it. Updated .