925415-VA Central California Health Care System - Building 1 Deficiency Report v1 September 2025.xlsx

XLSX spreadsheet 45 KB Posted

Attached to
Z1DZ--FIRE DOOR REPAIRS INSPECTION DEFICIENCIES
Solicitation number
36C26126Q0854
Issued by

About this file

This is a building deficiency inspection report for VA Central California Health Care System Building 1 in Fresno, California, documenting the results of fire door safety compliance evaluations conducted in September 2025. The inspection covered 162 doors across multiple building levels and identified a 59% overall pass rate, with 96 doors passing and 66 failing inspection criteria. The report details deficiencies across several priority categories: 3 doors require replacement, 12 have latching issues, 26 have clearance problems, and 6 items are designated for the client to address. Deficiencies are categorized by wall rating (1 Hour, 2 Hour, Hazardous, and Smoke Barrier) and door type (primarily swinging doors with some chute and rolling doors), with specific material specifications for door and frame construction.

The deficiency analysis identifies common failure modes including excessive clearance gaps (affecting 35 smoke barrier doors), missing or damaged latching hardware, frame misalignment, penetrations with unfilled fastener holes, damaged or missing smoke seals, and missing door labels. The report documents repair status for each deficient door, with most marked "Not Repaired—additional parts required." Several deficiencies are designated as "Client Will Address," indicating VA facility staff responsibility for remediation. The inspection was conducted by two primary inspectors (Frank Herrera and Milton Lemus) and provides location-specific data by floor and building section. Repair recommendations span three phases with specific comments for each, and the report includes a dedicated section listing all doors requiring client-directed corrective actions, suggesting the need for coordinated facility maintenance and compliance effort to achieve full fire door safety certification.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Summary VA Central California Health Care System - Building 1 - Fresno, CA

Initial Inspection Results Current Status

Pass Rate: 59%Pass Rate: 66%
PassFailPassFail
966610755

Priority Items

OpenClosed
Door Replacement30
Latching121
Clearance262
Labeling00
Client Will Address60
An asset may fall in multiple categories if applicable

Wall Rating Door Type

InspectedPassFailInspectedPassFail
1 Hour844Swinging Doors15310053
1 Hour Fire/Smoke1174Chute Doors972
2 Hour433310Rolling Doors000
Hazardous202Sliding Doors000
Smoke Barrier986335WON Doors000
Total16210755Fire Curtains000
Total Doors16210755

Priority Items Door Replacement Latching Clearance Labeling Client Will Address 3 0 0 9 1

Deficiencies

VA Central California Health Care System - Building 1 - Fresno, CA
Door IDAlt IDME IDLocationFloorBuildingInspectorDoor TypeHandedWall RatingDoor MaterialDoor RatingFrame MaterialFrame RatingDeficiencyDeficiency CommentStatusPhase 1 Repair OptionPhase 1 Repair CommentPhase 2 Repair OptionPhase 2 Repair CommentPhase 3 Repair OptionPhase 3 Repair CommentRelabeling Repair Option(s)Relabeling Repair Comment
11015358SPW7SW2-1Stairwell #27MainFrank HerreraSwinging DoorLH2 HourSteel90 MinuteSteel90 MinuteDoor penetrations / unused fastener holesRepaired/PassedDeficiency repaired/passed: filled penetrations
11015361SPE6SW1-1Stairwell #16MainFrank HerreraSwinging DoorRH2 HourSteel90 MinuteSteel90 MinuteExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11015363SP5B04-1Stairwell #25MainFrank HerreraSwinging DoorLH2 HourSteel90 MinuteSteel90 MinuteFrame missing filler plate(s)Not RepairedDeficiency not repaired: additional parts required
11015363SP5B04-1Stairwell #25MainFrank HerreraSwinging DoorLH2 HourSteel90 MinuteSteel90 MinuteHinge(s) or pivot(s) not securely fastened / missing fastenersNot RepairedDeficiency not repaired: additional parts required
11015363SP5B04-1Stairwell #25MainFrank HerreraSwinging DoorLH2 HourSteel90 MinuteSteel90 MinuteExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11015378Cross corridor near radiology room 12MainFrank HerreraSwinging DoorRH1 Hour Fire/SmokeSteel90 MinuteSteel90 MinuteExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11015378Cross corridor near radiology room 12MainFrank HerreraSwinging DoorRH1 Hour Fire/SmokeSteel90 MinuteSteel90 MinuteDoor does not latch - rubbing issueNot RepairedDeficiency not repaired: additional parts required
11015382Cross corridor imaging waiting2OPCFrank HerreraSwinging DoorRH1 Hour Fire/SmokeSteel90 MinuteSteel90 MinuteExcessive undercutNot RepairedDeficiency not repaired: additional parts required
11015386Cross corridor near Starbucks1MainFrank HerreraSwinging DoorRH2 HourSteel90 MinuteSteel90 MinuteDoor does not latchNot RepairedDeficiency not repaired: additional parts required
11015390Stairwell #31MainFrank HerreraSwinging DoorRH2 HourSteel90 MinuteSteel90 MinuteFrame penetrations / unused fastener holesNot RepairedDeficiency not repaired: additional parts required
11015390Stairwell #31MainFrank HerreraSwinging DoorRH2 HourSteel90 MinuteSteel90 MinuteExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11015393SPB1B16-1LaundryBMainMilton LemusSwinging DoorLH1 HourSteel60 MinuteSteelLabel present; no rating specifiedFrame is not alignedNot RepairedDeficiency not repaired: client will addressPer Gary, client will address. Frame and door to be replaced soon
11015393SPB1B16-1LaundryBMainMilton LemusSwinging DoorLH1 HourSteel60 MinuteSteelLabel present; no rating specifiedFrame missing filler plate(s)Not RepairedDeficiency not repaired: client will addressPer Gary, client will address. Frame to be replaced
11015394SPB1A04-1Chemical storageBMainFrank HerreraSwinging DoorRH1 HourWoodDoor Label MissingSteelLabel present; no rating specifiedDoor label is missingNot RepairedDeficiency not repaired: core tested door and door cannot be relabeled, door needs to be replaced
11015396SP1A19-1Stairwell #11MainFrank HerreraSwinging DoorRH2 HourSteel90 MinuteSteel90 MinuteExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11015399SPB1A02-1Chute roomBMainFrank HerreraSwinging DoorLH2 HourWood90 MinuteSteel90 MinuteExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11015400SPB2A06-1Stairwell 2SBMainMilton LemusSwinging DoorRH2 HourSteel90 MinuteSteel90 MinuteExcessive clearanceNot RepairedDeficiency not repaired: additional parts requiredSide and top gaps client
11142788Laboratory2OPCFrank HerreraSwinging DoorLH2 HourSteel3 HourSteel90 MinuteMissing bottom latching hardware or fire pinNot RepairedDeficiency not repaired: additional parts required
11528716Linen room7MainFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingExcessive clearanceRepaired/PassedDeficiency repaired/passed: adjusted clearance
11528717SP7A01B.1-1Storage7MainFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingFrame penetrations / unused fastener holesRepaired/PassedDeficiency repaired/passed: filled penetrations
11528719SPE630-1Laundry room6MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingFrame penetrations / unused fastener holesNot RepairedDeficiency not repaired: additional parts required
11528720SPE626-1Clean supply6MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingDoor penetrations / unused fastener holesRepaired/PassedDeficiency repaired/passed: filled penetrations
11528720SPE626-1Clean supply6MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingFrame penetrations / unused fastener holesRepaired/PassedDeficiency repaired/passed: filled penetrations
11528721Clean utility6MainFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11528722SPE602-1Soiled utility6MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11528724SPE601-1Dumbwaiter room6MainFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11528725SP6A01-1Team D conference area6MainFrank HerreraSwinging DoorRHSmoke BarrierWood20 MinuteSteelLabel present; no rating specifiedDamaged / missing smoke sealNot RepairedDeficiency not repaired: additional parts required
11528726Team D conference area6MainFrank HerreraSwinging DoorLHSmoke BarrierWood20 MinuteSteelLabel present; no rating specifiedDamaged / missing smoke sealNot RepairedDeficiency not repaired: additional parts required
11528727SP6A02-1Restroom6MainFrank HerreraSwinging DoorRHSmoke BarrierWood20 MinuteSteelLabel present; no rating specifiedDamaged / missing smoke sealNot RepairedDeficiency not repaired: additional parts required
11528728SP6B12-1Storage6MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingFrame penetrations / unused fastener holesRepaired/PassedDeficiency repaired/passed: filled penetrations
11528738SP5B32-1Clean linen5MainFrank HerreraSwinging DoorLHSmoke BarrierWood20 MinuteSteelNo label present / not required per wall ratingFrame missing filler plate(s)Not RepairedDeficiency not repaired: additional parts required
11528738SP5B32-1Clean linen5MainFrank HerreraSwinging DoorLHSmoke BarrierWood20 MinuteSteelNo label present / not required per wall ratingFrame penetrations / unused fastener holesNot RepairedDeficiency not repaired: additional parts required
11528741Soiled utility5MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11528742SP5B48-1Soiled utility5MainFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingMajor damage / exposed mineral coreNot RepairedDeficiency not repaired: door needs to be replaced
11528745Storage5MainFrank HerreraSwinging DoorRHSmoke BarrierDoor not installedDoor Not InstalledSteelNo label present / not required per wall ratingDoor not installedNot RepairedDeficiency not repaired: door needs to be replaced
11528746SP5B17-1Clean supply5MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingDoor penetrations / unused fastener holesRepaired/PassedDeficiency repaired/passed: filled penetrations
11528746SP5B17-1Clean supply5MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11528748SP5B42-1Dialysis5MainFrank HerreraSwinging DoorLHSmoke BarrierWood20 MinuteSteel3 HourExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11528749SP5A01-1Waiting area5MainFrank HerreraSwinging DoorLHSmoke BarrierWood20 MinuteSteelNo label present / not required per wall ratingFrame penetrations / unused fastener holesRepaired/PassedDeficiency repaired/passed: filled penetrations
11528752SP5B12-1Comm room5MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingMissing / damaged door closerNot RepairedDeficiency not repaired: additional parts required
11528752SP5B12-1Comm room5MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingIncorrect type of hinge(s) / missing hinge(s) / damaged hinge(s)Not RepairedDeficiency not repaired: additional parts required
11528755SP5B02-15B025MainFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingExcessive undercutNot RepairedDeficiency not repaired: additional parts required
11528758SP5A05-1Dumbwaiter room5MainFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11528761SP5A38-1Soiled utility5MainFrank HerreraSwinging DoorLHSmoke BarrierWood60 MinuteSteelLabel present; no rating specifiedDoor does not latch - rubbing issueRepaired/PassedDeficiency repaired/passed: door swings freely
11528767SP5A21-1Clean supply5MainFrank HerreraSwinging DoorLHSmoke BarrierWood60 MinuteSteelLabel present; no rating specifiedExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11528768Cart sterilization3MainFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingExcessive clearanceRepaired/PassedDeficiency repaired/passed: adjusted clearance
11528775SP4A48-1Restroom4MainFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11528782SP3A02E-1Clean storage3MainFrank HerreraSwinging DoorRHSmoke BarrierSteelNo label present / not required per wall ratingSteelNo label present / not required per wall ratingExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11528790Sterile supplies3MainFrank HerreraSwinging DoorRHSmoke BarrierSteel90 MinuteSteel90 MinuteExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11528793OR suite east entrance3MainFrank HerreraSwinging DoorRH1 Hour Fire/SmokeSteel45 MinuteSteel90 MinuteExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11528798SP2B10A.1-1Radiology room 1 restroom,2MainFrank HerreraSwinging DoorLH1 Hour Fire/SmokeWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingFrame missing filler plate(s)Not RepairedDeficiency not repaired: additional parts required
11528798SP2B10A.1-1Radiology room 1 restroom,2MainFrank HerreraSwinging DoorLH1 Hour Fire/SmokeWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11528799Housekeeping2MainFrank HerreraSwinging DoorLHSmoke BarrierWood90 MinuteSteelNo label present / not required per wall ratingFrame penetrations / unused fastener holesRepaired/PassedDeficiency repaired/passed: filled penetrations
11528800SP2B13-1Anatomic pathology lab2MainFrank HerreraSwinging DoorRHSmoke BarrierWood90 MinuteSteelNo label present / not required per wall ratingDoor penetrations / unused fastener holesRepaired/PassedDeficiency repaired/passed: filled penetrations
11528800SP2B13-1Anatomic pathology lab2MainFrank HerreraSwinging DoorRHSmoke BarrierWood90 MinuteSteelNo label present / not required per wall ratingFrame penetrations / unused fastener holesRepaired/PassedDeficiency repaired/passed: filled penetrations
11528801SP2A02A-1Chapel2MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingDoor does not latchNot RepairedDeficiency not repaired: client will addressPer Taneasha , client will address.
11528801SP2A02A-1Chapel2MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingNon-compliant hold-open device observedNot RepairedDeficiency not repaired: client will addressPer Taneasha , client will address.
11528802SP2B24A-1Microbiology2MainFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11528802SP2B24A-1Microbiology2MainFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingMissing / damaged closer armNot RepairedDeficiency not repaired: additional parts required
11528802SP2B24A-1Microbiology2MainFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingFrame missing filler plate(s)Not RepairedDeficiency not repaired: additional parts required
11528803SP2B24B-1Microbiology lab2MainFrank HerreraSwinging DoorRHSmoke BarrierWood60 MinuteSteelLabel present; no rating specifiedNon-compliant hold-open device observedNot RepairedDeficiency not repaired: additional parts required
11528803SP2B24B-1Microbiology lab2MainFrank HerreraSwinging DoorRHSmoke BarrierWood60 MinuteSteelLabel present; no rating specifiedMissing / damaged latch-set strikeNot RepairedDeficiency not repaired: additional parts required
11528805SP2B24E-1Biohazard waste2MainFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11528806SP2B24B-1Microbiology2MainFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingMissing /damaged latchsetNot RepairedDeficiency not repaired: client will addressPer Taneasha , client will address. Install latch set
11528808SP2A02A-1Chapel2MainFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingNon-compliant hold-open device observedNot RepairedDeficiency not repaired: client will addressPer Taneasha , client will address.
11528808SP2A02A-1Chapel2MainFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingDoor does not latchNot RepairedDeficiency not repaired: client will addressPer Taneasha , client will address.
11528809SP2A02D-1Chaplains office2MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingDoor missing filler plate(s)Not RepairedDeficiency not repaired: additional parts required
11528817SP1A09A.1-1Office1MainFrank HerreraSwinging DoorRHSmoke BarrierWood90 MinuteSteelLabel present; no rating specifiedExcessive undercutNot RepairedDeficiency not repaired: additional parts required
11528818Chapel bottom exit1MainFrank HerreraSwinging DoorLH1 HourAluminumDoor Label MissingSteelFrame Label MissingDoor label is missingNot RepairedDeficiency not repaired: client will addressPer Taneasha , client will address. Door need to be replaced.
11528818Chapel bottom exit1MainFrank HerreraSwinging DoorLH1 HourAluminumDoor Label MissingSteelFrame Label MissingRequired frame label is missingNot RepairedDeficiency not repaired: client will addressPer Taneasha , client will address.
11528819SP1B18-1Coffee storage1MainFrank HerreraSwinging DoorLHSmoke BarrierWood20 MinuteSteelNo label present / not required per wall ratingFrame penetrations / unused fastener holesNot RepairedDeficiency not repaired: additional parts required
11528819SP1B18-1Coffee storage1MainFrank HerreraSwinging DoorLHSmoke BarrierWood20 MinuteSteelNo label present / not required per wall ratingFrame missing filler plate(s)Not RepairedDeficiency not repaired: additional parts required
11528822SP1B16-1Canteen storage1MainFrank HerreraSwinging DoorRHSmoke BarrierWood60 MinuteSteelConstruction Label (Sufficiently Built)Frame penetrations / unused fastener holesNot RepairedDeficiency not repaired: additional parts required
11528823Canteen storage inside door1MainFrank HerreraSwinging DoorLHSmoke BarrierWood60 MinuteSteelNo label present / not required per wall ratingFrame missing filler plate(s)Not RepairedDeficiency not repaired: additional parts required
11528825SPB1B01-1StorageBMainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingDoor penetrations / unused fastener holesNot RepairedDeficiency not repaired: additional parts required
11528826Training areaBMainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingExcessive undercutNot RepairedDeficiency not repaired: additional parts required
11528827Bottom chute doorBMainFrank HerreraChute Door2 HourSteel90 MinuteSteel90 MinuteNon-compliant hold-open device observedNot RepairedDeficiency not repaired: additional parts required
11528828Laundry roomBMainFrank HerreraSwinging DoorRH1 HourSteel90 MinuteSteelLabel present; no rating specifiedFrame missing filler plate(s)Not RepairedDeficiency not repaired: client will addressPer Taneasha , client will address. Reinstall the electric strike that was removed.
11528829Bottom linen chuteBMainFrank HerreraChute Door2 HourSteel90 MinuteSteel90 MinuteNon-compliant hold-open device observedNot RepairedDeficiency not repaired: additional parts required
11528832b1b16bStorageBMainMilton LemusSwinging DoorLHHazardousWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingNon-listed latchsetNot RepairedDeficiency not repaired: additional parts required
11528833b2a03Mechanical roomSBMainMilton LemusSwinging DoorLHHazardousSteelNo label present / not required per wall ratingSteelNo label present / not required per wall ratingMissing / damaged door closerNot RepairedDeficiency not repaired: additional parts required
11528833b2a03Mechanical roomSBMainMilton LemusSwinging DoorLHHazardousSteelNo label present / not required per wall ratingSteelNo label present / not required per wall ratingNon-listed latchsetNot RepairedDeficiency not repaired: additional parts required
11528834SPB2A01-1AHVAC office double doorsSBMainMilton LemusSwinging DoorRHSmoke BarrierSteelNo label present / not required per wall ratingSteelNo label present / not required per wall ratingNon-listed latchsetNot RepairedDeficiency not repaired: additional parts required
11528837SPB2A05-1AEMS storageSBMainMilton LemusSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingNon-listed latchsetNot RepairedDeficiency not repaired: additional parts required
11528840SPB2A08-1bStorageSBMainMilton LemusSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingDoor penetrations / unused fastener holesRepaired/PassedDeficiency repaired/passed: filled penetrations

Client will address

VA Central California Health Care System - Building 1 - Fresno, CA
Door IDAlt IDME IDLocationFloorBuildingInspectorDoor TypeHandedWall RatingDoor MaterialDoor RatingFrame MaterialFrame RatingDeficiencyDeficiency CommentStatusPhase 1 Repair OptionPhase 1 Repair CommentPhase 2 Repair OptionPhase 2 Repair CommentPhase 3 Repair OptionPhase 3 Repair CommentRelabeling Repair Option(s)Relabeling Repair Comment
11015393SPB1B16-1LaundryBMainMilton LemusSwinging DoorLH1 HourSteel60 MinuteSteelLabel present; no rating specifiedFrame is not alignedNot RepairedDeficiency not repaired: client will addressPer Gary, client will address. Frame and door to be replaced soon
11015393SPB1B16-1LaundryBMainMilton LemusSwinging DoorLH1 HourSteel60 MinuteSteelLabel present; no rating specifiedFrame missing filler plate(s)Not RepairedDeficiency not repaired: client will addressPer Gary, client will address. Frame to be replaced
11528801SP2A02A-1Chapel2MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingDoor does not latchNot RepairedDeficiency not repaired: client will addressPer Taneasha , client will address.
11528801SP2A02A-1Chapel2MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingNon-compliant hold-open device observedNot RepairedDeficiency not repaired: client will addressPer Taneasha , client will address.
11528806SP2B24B-1Microbiology2MainFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingMissing /damaged latchsetNot RepairedDeficiency not repaired: client will addressPer Taneasha , client will address. Install latch set
11528808SP2A02A-1Chapel2MainFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingDoor does not latchNot RepairedDeficiency not repaired: client will addressPer Taneasha , client will address.
11528808SP2A02A-1Chapel2MainFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingNon-compliant hold-open device observedNot RepairedDeficiency not repaired: client will addressPer Taneasha , client will address.
11528818Chapel bottom exit1MainFrank HerreraSwinging DoorLH1 HourAluminumDoor Label MissingSteelFrame Label MissingDoor label is missingNot RepairedDeficiency not repaired: client will addressPer Taneasha , client will address. Door need to be replaced.
11528818Chapel bottom exit1MainFrank HerreraSwinging DoorLH1 HourAluminumDoor Label MissingSteelFrame Label MissingRequired frame label is missingNot RepairedDeficiency not repaired: client will addressPer Taneasha , client will address.
11528828Laundry roomBMainFrank HerreraSwinging DoorRH1 HourSteel90 MinuteSteelLabel present; no rating specifiedFrame missing filler plate(s)Not RepairedDeficiency not repaired: client will addressPer Taneasha , client will address. Reinstall the electric strike that was removed.

All doors and deficiencies

VA Central California Health Care System - Building 1 - Fresno, CA
Door IDAlt IDME IDLocationFloorBuildingInspectorDoor TypeHandedWall RatingDoor MaterialDoor RatingFrame MaterialFrame RatingDeficiencyDeficiency CommentStatusPhase 1 Repair OptionPhase 1 Repair CommentPhase 2 Repair OptionPhase 2 Repair CommentPhase 3 Repair OptionPhase 3 Repair CommentRelabeling Repair Option(s)Relabeling Repair Comment
11015356SP7A11-1Stairwell #17MainFrank HerreraSwinging DoorRH2 HourSteel90 MinuteSteel90 MinutePassed
11015358SPW7SW2-1Stairwell #27MainFrank HerreraSwinging DoorLH2 HourSteel90 MinuteSteel90 MinuteDoor penetrations / unused fastener holesRepaired/PassedDeficiency repaired/passed: filled penetrations
11015359SP6B04-1Stairwell #26MainFrank HerreraSwinging DoorLH2 HourSteel90 MinuteSteel90 MinutePassed
11015361SPE6SW1-1Stairwell #16MainFrank HerreraSwinging DoorRH2 HourSteel90 MinuteSteel90 MinuteExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11015362SP5B25-1Stairwell #35MainFrank HerreraSwinging DoorLH2 HourSteel90 MinuteSteel90 MinutePassed
11015363SP5B04-1Stairwell #25MainFrank HerreraSwinging DoorLH2 HourSteel90 MinuteSteel90 MinuteHinge(s) or pivot(s) not securely fastened / missing fastenersNot RepairedDeficiency not repaired: additional parts required
11015363SP5B04-1Stairwell #25MainFrank HerreraSwinging DoorLH2 HourSteel90 MinuteSteel90 MinuteExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11015363SP5B04-1Stairwell #25MainFrank HerreraSwinging DoorLH2 HourSteel90 MinuteSteel90 MinuteFrame missing filler plate(s)Not RepairedDeficiency not repaired: additional parts required
11015365SP5A03-1Linen chute room5MainFrank HerreraSwinging DoorRH2 HourWoodNo label present / not required per wall ratingSteel90 MinutePassed
11015367SP4B47-1Stairwell #34MainFrank HerreraSwinging DoorLH2 HourSteel90 MinuteSteel90 MinutePassed
11015368SP4B03-1Stairwell #24MainFrank HerreraSwinging DoorLH2 HourSteel90 MinuteSteel90 MinutePassed
11015369SP4A58-1Stairwell #14MainFrank HerreraSwinging DoorRH2 HourSteel90 MinuteSteel90 MinutePassed
11015370SP3B02-1Stairwell #23MainFrank HerreraSwinging DoorLH2 HourSteel90 MinuteSteel90 MinutePassed
11015371Operating suite south entrance3MainFrank HerreraSwinging DoorRH2 HourSteel90 MinuteSteel90 MinutePassed
11015372Operating suite south entrance3MainFrank HerreraSwinging DoorRH2 HourSteel90 MinuteSteel90 MinutePassed
11015373Cross corridor entry to out patient3MainFrank HerreraSwinging DoorRH2 HourSteel90 MinuteSteel90 MinutePassed
11015374Cross corridor entry to out patient3MainFrank HerreraSwinging DoorRH2 HourSteel90 MinuteSteel90 MinutePassed
11015375SP3A16-1Stairwell #13MainFrank HerreraSwinging DoorRH2 HourSteel90 MinuteSteel90 MinutePassed
11015376SP2B25-1Stairwell #32MainFrank HerreraSwinging DoorLH2 HourSteel90 MinuteSteel90 MinutePassed
11015377Cross corridor near radiology room 12MainFrank HerreraSwinging DoorRH1 Hour Fire/SmokeSteel90 MinuteSteel90 MinutePassed
11015378Cross corridor near radiology room 12MainFrank HerreraSwinging DoorRH1 Hour Fire/SmokeSteel90 MinuteSteel90 MinuteExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11015378Cross corridor near radiology room 12MainFrank HerreraSwinging DoorRH1 Hour Fire/SmokeSteel90 MinuteSteel90 MinuteDoor does not latch - rubbing issueNot RepairedDeficiency not repaired: additional parts required
11015379Stairwell #22MainFrank HerreraSwinging DoorLH2 HourSteel90 MinuteSteel90 MinutePassed
11015380SP2A01-1Mechanical2OPCFrank HerreraSwinging DoorRH1 Hour Fire/SmokeWood20 MinuteSteel45 MinutePassed
11015381Cross corridors imaging waiting2OPCFrank HerreraSwinging DoorRH1 Hour Fire/SmokeSteel90 MinuteSteel90 MinutePassed
11015382Cross corridor imaging waiting2OPCFrank HerreraSwinging DoorRH1 Hour Fire/SmokeSteel90 MinuteSteel90 MinuteExcessive undercutNot RepairedDeficiency not repaired: additional parts required
11015384SP2A30-1Stairwell #12MainFrank HerreraSwinging DoorLH2 HourSteel90 MinuteSteel90 MinutePassed
11015386Cross corridor near Starbucks1MainFrank HerreraSwinging DoorRH2 HourSteel90 MinuteSteel90 MinuteDoor does not latchNot RepairedDeficiency not repaired: additional parts required
11015387Cross corridor near Starbucks1MainFrank HerreraSwinging DoorRH2 HourSteel90 MinuteSteel90 MinutePassed
11015388Cross corridor entry to out patient1MainFrank HerreraSwinging DoorRH2 HourSteel90 MinuteSteel90 MinutePassed
11015389Cross corridor entry to outpatient1MainFrank HerreraSwinging DoorRH2 HourSteel90 MinuteSteel90 MinutePassed
11015390Stairwell #31MainFrank HerreraSwinging DoorRH2 HourSteel90 MinuteSteel90 MinuteFrame penetrations / unused fastener holesNot RepairedDeficiency not repaired: additional parts required
11015390Stairwell #31MainFrank HerreraSwinging DoorRH2 HourSteel90 MinuteSteel90 MinuteExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11015391Housekeeping1MainFrank HerreraSwinging DoorLH2 HourWoodNo label present / not required per wall ratingSteel90 MinutePassed
11015392SP1B03-1Stairwell #21MainFrank HerreraSwinging DoorLH2 HourSteel90 MinuteSteel90 MinutePassed
11015393SPB1B16-1LaundryBMainMilton LemusSwinging DoorLH1 HourSteel60 MinuteSteelLabel present; no rating specifiedFrame missing filler plate(s)Not RepairedDeficiency not repaired: client will addressPer Gary, client will address. Frame to be replaced
11015393SPB1B16-1LaundryBMainMilton LemusSwinging DoorLH1 HourSteel60 MinuteSteelLabel present; no rating specifiedFrame is not alignedNot RepairedDeficiency not repaired: client will addressPer Gary, client will address. Frame and door to be replaced soon
11015394SPB1A04-1Chemical storageBMainFrank HerreraSwinging DoorRH1 HourWoodDoor Label MissingSteelLabel present; no rating specifiedDoor label is missingNot RepairedDeficiency not repaired: core tested door and door cannot be relabeled, door needs to be replaced
11015396SP1A19-1Stairwell #11MainFrank HerreraSwinging DoorRH2 HourSteel90 MinuteSteel90 MinuteExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11015397SPB1B06-1Electrical roomBMainFrank HerreraSwinging DoorLH1 HourSteel3 HourSteel90 MinutePassed
11015398Old casket liftBMainFrank HerreraSwinging DoorLH1 HourSteel90 MinuteSteel90 MinutePassed
11015399SPB1A02-1Chute roomBMainFrank HerreraSwinging DoorLH2 HourWood90 MinuteSteel90 MinuteExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11015400SPB2A06-1Stairwell 2SBMainMilton LemusSwinging DoorRH2 HourSteel90 MinuteSteel90 MinuteExcessive clearanceNot RepairedDeficiency not repaired: additional parts requiredSide and top gaps client
11015402Stairwell #2BMainFrank HerreraSwinging DoorRH2 HourSteel90 MinuteSteel90 MinutePassed
11142788Laboratory2OPCFrank HerreraSwinging DoorLH2 HourSteel3 HourSteel90 MinuteMissing bottom latching hardware or fire pinNot RepairedDeficiency not repaired: additional parts required
11142789Laboratory2OPCFrank HerreraSwinging DoorRH2 HourSteel3 HourSteel90 MinutePassed
11528715Entry to mental health6MainFrank HerreraSwinging DoorRH1 Hour Fire/SmokeWood20 MinuteSteel45 MinutePassed
115287153SP7A01G-1Soiled utility7MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelLabel present; no rating specifiedPassed
11528716Linen room7MainFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingExcessive clearanceRepaired/PassedDeficiency repaired/passed: adjusted clearance
11528717SP7A01B.1-1Storage7MainFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingFrame penetrations / unused fastener holesRepaired/PassedDeficiency repaired/passed: filled penetrations
11528718SPE632-1Storage room6MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingPassed
11528719SPE630-1Laundry room6MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingFrame penetrations / unused fastener holesNot RepairedDeficiency not repaired: additional parts required
11528720SPE626-1Clean supply6MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingDoor penetrations / unused fastener holesRepaired/PassedDeficiency repaired/passed: filled penetrations
11528720SPE626-1Clean supply6MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingFrame penetrations / unused fastener holesRepaired/PassedDeficiency repaired/passed: filled penetrations
11528721Clean utility6MainFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11528722SPE602-1Soiled utility6MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11528723SPE601-1Dumbwaiter6MainFrank HerreraSwinging DoorRHSmoke BarrierWood60 MinuteSteelLabel present; no rating specifiedPassed
11528724SPE601-1Dumbwaiter room6MainFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11528725SP6A01-1Team D conference area6MainFrank HerreraSwinging DoorRHSmoke BarrierWood20 MinuteSteelLabel present; no rating specifiedDamaged / missing smoke sealNot RepairedDeficiency not repaired: additional parts required
11528726Team D conference area6MainFrank HerreraSwinging DoorLHSmoke BarrierWood20 MinuteSteelLabel present; no rating specifiedDamaged / missing smoke sealNot RepairedDeficiency not repaired: additional parts required
11528727SP6A02-1Restroom6MainFrank HerreraSwinging DoorRHSmoke BarrierWood20 MinuteSteelLabel present; no rating specifiedDamaged / missing smoke sealNot RepairedDeficiency not repaired: additional parts required
11528728SP6B12-1Storage6MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingFrame penetrations / unused fastener holesRepaired/PassedDeficiency repaired/passed: filled penetrations
11528729SP6B11-1Storage6MainFrank HerreraSwinging DoorRHSmoke BarrierWood20 MinuteSteel90 MinutePassed
11528730SP6B13-1Biomedical engineering6MainFrank HerreraSwinging DoorRHSmoke BarrierSteel20 MinuteSteelLabel present; no rating specifiedPassed
11528731SP6B13A-1Medical engineering office6MainFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelLabel present; no rating specifiedPassed
11528732Confined space door6MainFrank HerreraSwinging DoorLHSmoke BarrierSteelNo label present / not required per wall ratingSteelNo label present / not required per wall ratingPassed
11528733Air handler room6MainFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingPassed
11528734SP6B13A.1-1Air handler room6MainFrank HerreraSwinging DoorRHSmoke BarrierSteelNo label present / not required per wall ratingSteelNo label present / not required per wall ratingPassed
11528735SP6B13B.2-1Air handler room6MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingPassed
11528737SP5B31-1Storage5MainFrank HerreraSwinging DoorLHSmoke BarrierWood90 MinuteSteelNo label present / not required per wall ratingPassed
11528738SP5B32-1Clean linen5MainFrank HerreraSwinging DoorLHSmoke BarrierWood20 MinuteSteelNo label present / not required per wall ratingFrame penetrations / unused fastener holesNot RepairedDeficiency not repaired: additional parts required
11528738SP5B32-1Clean linen5MainFrank HerreraSwinging DoorLHSmoke BarrierWood20 MinuteSteelNo label present / not required per wall ratingFrame missing filler plate(s)Not RepairedDeficiency not repaired: additional parts required
11528739Cross corridor near linen room5MainFrank HerreraSwinging DoorLHSmoke BarrierSteel90 MinuteSteelNo label present / not required per wall ratingPassed
11528740Cross corridor near clean linen5MainFrank HerreraSwinging DoorLHSmoke BarrierSteel90 MinuteSteelNo label present / not required per wall ratingPassed
11528741Soiled utility5MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11528742SP5B48-1Soiled utility5MainFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingMajor damage / exposed mineral coreNot RepairedDeficiency not repaired: door needs to be replaced
11528743Cross corridor near soiled utility5MainFrank HerreraSwinging DoorLHSmoke BarrierSteel90 MinuteSteelLabel present; no rating specifiedPassed
11528744Cross corridor near soiled utility5MainFrank HerreraSwinging DoorLHSmoke BarrierSteel90 MinuteSteelNo label present / not required per wall ratingPassed
11528745Storage5MainFrank HerreraSwinging DoorRHSmoke BarrierDoor not installedDoor Not InstalledSteelNo label present / not required per wall ratingDoor not installedNot RepairedDeficiency not repaired: door needs to be replaced
11528746SP5B17-1Clean supply5MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingDoor penetrations / unused fastener holesRepaired/PassedDeficiency repaired/passed: filled penetrations
11528746SP5B17-1Clean supply5MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11528747SP5B39-1Respiratory supplies5MainFrank HerreraSwinging DoorLHSmoke BarrierWood20 MinuteSteelNo label present / not required per wall ratingPassed
11528748SP5B42-1Dialysis5MainFrank HerreraSwinging DoorLHSmoke BarrierWood20 MinuteSteel3 HourExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11528749SP5A01-1Waiting area5MainFrank HerreraSwinging DoorLHSmoke BarrierWood20 MinuteSteelNo label present / not required per wall ratingFrame penetrations / unused fastener holesRepaired/PassedDeficiency repaired/passed: filled penetrations
1152875011528750Cross corridor near elevator s-45MainFrank HerreraSwinging DoorRH1 Hour Fire/SmokeAluminumDoor Label MissingSteelFrame Label MissingPassed
11528751Cross corridor near elevator s-45MainFrank HerreraSwinging DoorRH1 Hour Fire/SmokeAluminumDoor Label MissingSteelFrame Label MissingPassed
11528752SP5B12-1Comm room5MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingMissing / damaged door closerNot RepairedDeficiency not repaired: additional parts required
11528752SP5B12-1Comm room5MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingIncorrect type of hinge(s) / missing hinge(s) / damaged hinge(s)Not RepairedDeficiency not repaired: additional parts required
11528753SP5B01-15B015MainFrank HerreraSwinging DoorLHSmoke BarrierWood20 MinuteSteelLabel present; no rating specifiedPassed
11528754Equipment storage5MainFrank HerreraSwinging DoorRHSmoke BarrierWood20 MinuteSteelLabel present; no rating specifiedPassed
11528755SP5B02-15B025MainFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingExcessive undercutNot RepairedDeficiency not repaired: additional parts required
11528756Linen chute5MainFrank HerreraChute Door2 HourSteel90 MinuteSteel90 MinutePassed
11528758SP5A05-1Dumbwaiter room5MainFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11528759SP5A39-1Soiled utility5MainFrank HerreraSwinging DoorRHSmoke BarrierWood60 MinuteSteelLabel present; no rating specifiedPassed
11528760SP5A38-1Soiled utility5MainFrank HerreraSwinging DoorRHSmoke BarrierWood20 MinuteSteelLabel present; no rating specifiedPassed
11528761SP5A38-1Soiled utility5MainFrank HerreraSwinging DoorLHSmoke BarrierWood60 MinuteSteelLabel present; no rating specifiedDoor does not latch - rubbing issueRepaired/PassedDeficiency repaired/passed: door swings freely
11528762SP5A39-1Soiled utility5MainFrank HerreraSwinging DoorLHSmoke BarrierWood60 MinuteSteelLabel present; no rating specifiedPassed
11528763SP5A27-1Clean supply5MainFrank HerreraSwinging DoorLHSmoke BarrierWood20 MinuteSteelLabel present; no rating specifiedPassed
11528764SP5A46-1Storage5MainFrank HerreraSwinging DoorRHSmoke BarrierWood60 MinuteSteelLabel present; no rating specifiedPassed
11528765SP5A45-1Equipment storage5MainFrank HerreraSwinging DoorLHSmoke BarrierWood20 MinuteSteelLabel present; no rating specifiedPassed
11528766SP5A15-1Stairwell #15MainFrank HerreraSwinging DoorRH2 HourSteel90 MinuteSteel90 MinutePassed
11528767SP5A21-1Clean supply5MainFrank HerreraSwinging DoorLHSmoke BarrierWood60 MinuteSteelLabel present; no rating specifiedExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11528768Cart sterilization3MainFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingExcessive clearanceRepaired/PassedDeficiency repaired/passed: adjusted clearance
11528769SP4B46L-1Soiled utility4MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingPassed
11528770SP4B46M-1Soiled utility4MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelLabel present; no rating specifiedPassed
11528771SP4B39-1Clean supply4MainFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingPassed
11528772SP4B10-1Dumbwaiter storage4MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingPassed
11528773SP4A45-1Clean supply4MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingPassed
11528774SP4A24-1Soiled utility4MainFrank HerreraSwinging DoorRHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingPassed
11528775SP4A48-1Restroom4MainFrank HerreraSwinging DoorLHSmoke BarrierWoodNo label present / not required per wall ratingSteelNo label present / not required per wall ratingExcessive clearanceNot RepairedDeficiency not repaired: additional parts required
11528777Linen chute room7MainFrank HerreraSwinging DoorRHSmoke BarrierAluminumNo label present / not required per wall ratingSteelNo label present / not required per wall ratingPassed
11528778Linen chute7MainFrank HerreraChute Door2 HourSteel90 MinuteSteel90 MinutePassed