925416-VA Central California Health Care System - Building 28 Facility Notes Report v1 September 2025.xlsx

XLSX spreadsheet 13 KB Posted

Attached to
Z1DZ--FIRE DOOR REPAIRS INSPECTION DEFICIENCIES
Solicitation number
36C26126Q0854
Issued by

About this file

This is a facility inspection report documenting fire door deficiencies at the VA Central California Health Care System's Building 28 (Dogwood building) in Fresno, California, as of September 2025. The report details inspection results for 15 doors across the first floor, identifying their locations, door types, fire ratings, and compliance status. All doors inspected are swinging doors with varying wall ratings (1 Hour, Smoke Barrier) and door/frame ratings (45 Minute or 60 Minute). The inspection, conducted on September 26, 2025, identified seven doors requiring repairs: doors in the clean linens room, storage areas, boiler room, and utility spaces have "Not Repaired" status, while eight doors passed inspection. Notable deficiencies include unrated kick plates on multiple doors and one door with no fire-rated label present. The report serves as a baseline assessment to support the related federal solicitation 36C26126Q0854 for fire door repairs and inspection deficiency corrections at the facility.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Doors

VA Central California Health Care System - Building 28 - Fresno, CA
Door IDAlt IDLocationFloorBuildingDoor TypeInspection DateWall RatingDoor RatingFrame RatingStatusFacility Notes
11528934SP1D11B-28Utility soiled room1Dogwood buildingSwinging Door9/26/20251 Hour45 Minute45 MinutePassKick plate not rated
11528935Clean linens1Dogwood buildingSwinging Door9/26/20251 Hour45 Minute45 MinuteNot RepairedKick plate not rated
11528936Storage1Dogwood buildingSwinging Door9/26/2025Smoke Barrier45 Minute45 MinuteNot Repaired
11528937SP1D1-28Cross corridor near 1d011Dogwood buildingSwinging Door9/26/20251 Hour Fire/Smoke45 Minute45 MinutePass
11528938SP1D1-28Cross corridor near 1d011Dogwood buildingSwinging Door9/26/20251 Hour Fire/Smoke45 Minute45 MinutePass
11528939SP1E18-28Laundry1Dogwood buildingSwinging Door9/26/20251 Hour45 Minute45 MinutePass
11528940SP1E15-28Utility1Dogwood buildingSwinging Door9/26/20251 Hour45 Minute45 MinutePass
11528941SP1E22-28Boiler room1Dogwood buildingSwinging Door9/26/20251 Hour45 Minute45 MinuteNot Repaired
11528942SP1E20-28Storage1Dogwood buildingSwinging Door9/26/20251 Hour45 Minute45 MinuteNot Repaired
11528943SP1E06-28Storage1Dogwood buildingSwinging Door9/26/2025Smoke Barrier45 Minute45 MinutePass
11528944570 EE57585Soiled utility1Dogwood buildingSwinging Door9/26/20251 Hour45 Minute45 MinuteNot RepairedKick plate not rated
11528945570 EE57586Clean linen1Dogwood buildingSwinging Door9/26/20251 Hour45 Minute60 MinuteNot RepairedKick plate not rated
11528946Oxygen storage1Dogwood buildingSwinging Door9/26/2025Smoke BarrierNo label present / not required per wall ratingNo label present / not required per wall ratingNot Repaired

File details come from the government source that posted it. Updated .