CLIN 03 Bldg 7- Quarterly Sprinkler 12-22-25 FAIL.pdf
PDF 81 KB Posted
- Solicitation number
- 36C25926Q0408
About this file
This document is a Semi-Annual Inspection Report for the water-based fire protection system at VA Grand Junction Building 7, completed on December 16, 2025. The inspection was conducted by James Trudeau of Platinum Fire Protection (PO Box 607, Mead, CO 80542) in accordance with NFPA 25 2011 - Standard for the Inspection, Testing, and Maintenance of Water Based Fire Protection Systems.
The inspection identified one deficiency: two pressure gauges on the system require replacement due to being past their serviceable condition per standard 5.2.4.1. A photograph of the gauges was taken on August 19, 2025, documenting their condition. All other inspection categories returned no deficiencies, including general wet system questions, inspector test connection, and valves. The inspector certified that all equipment tested was left in operational condition upon completion of the inspection, with the exception of items noted in the report. The report was printed on December 22, 2025.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Semi Annual Inspection Report
Completed on: 12-16-2025 for
VA Grand Junction Building 7 2121 North Ave
Grand Junction, CO
Conducted By:
James Trudeau
Platinum Fire Protection PO Box 607
Mead, CO 80542
This Joint Commission inspection was performed in accordance with the following codes and regulations:
• NFPA 25 2011 - Standard for the Inspection, Testing, and Maintenance of Water Based Fire Protection Systems
Deficiencies - General Questions
Deficiency #1
Are the gauges on system in good condition and showing normal water supply pressure? - 5.2.4.1: No
Notes: 2 gauges due for replacement
Deficiency #1 - Photo #1
Date Taken: August 19, 2025
Deficiencies - General Wet System Questions
None
Deficiencies - Wet
None
Deficiencies - Inspectors Test Connection
None
Deficiencies - Valves
None
Report of Inspection / Test Semi-Annual NFPA 25
12-16-2025 Property VA Grand Junction Building 7 2121 North Ave Grand Junction CO
Print Date: 12-22-2025
Conducted by: James Trudeau
Platinum Fire Protection PO Box 607 Mead CO 80542 3036880177 rachel@platfire.com
Copyright 2025 Inspect Point
Inspector Signature
I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.
Inspector Name Signature Date Completed
James Trudeau 2025-12-16
Report of Inspection / Test Semi-Annual NFPA 25
12-16-2025 Property VA Grand Junction Building 7 2121 North Ave Grand Junction CO
Print Date: 12-22-2025
Conducted by: James Trudeau
Platinum Fire Protection PO Box 607 Mead CO 80542 3036880177 rachel@platfire.com
Copyright 2025 Inspect Point
File details come from the government source that posted it. Updated .