CLIN 03 Bldg 35- Quarterly Sprinkler 12-22-25 FAIL.pdf
PDF 75 KB Posted
- Solicitation number
- 36C25926Q0408
About this file
This is a Semi-Annual Inspection Report for the fire protection systems at VA Grand Junction Building 35, completed on December 16, 2025, by James Trudeau of Platinum Fire Protection (PO Box 607, Mead, CO 80542). The inspection was conducted in accordance with NFPA 25 2011 – Standard for the Inspection, Testing, and Maintenance of Water Based Fire Protection Systems and was performed as a Joint Commission inspection.
The report identifies three deficiencies. Deficiency #1 concerns control valves (including backflow preventer isolation valves) that should be supervised with seals in correct open or closed positions per section 13.3.2.2; however, the notes indicate there are no control valves present at the facility. Deficiency #2 relates to flow observation for a wet sprinkler system per section 13.2.5; the inspector noted no gauge is available to read flow. Deficiency #3 addresses the inspector's test connection located at the east door of the building, which fails to terminate in a smooth orifice and lacks required signage. The notes explain the system consists of a single head fed from the domestic water system with an inspector's test using a washing machine hose, no control valve, and only a flow switch connected to a single sidewall head. The inspector certified that all information is correct and that equipment tested was left in operational condition upon completion, signing the report on December 16, 2025.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Semi Annual Inspection Report
Completed on: 12-16-2025 for
VA Grand Junction Building 35 2121 North Ave
Grand Junction, CO
Conducted By:
James Trudeau
Platinum Fire Protection PO Box 607
Mead, CO 80542
This Joint Commission inspection was performed in accordance with the following codes and regulations:
• NFPA 25 2011 - Standard for the Inspection, Testing, and Maintenance of Water Based Fire Protection Systems
Deficiencies - General Questions
Deficiency #1
Are the control valves (including backflow preventer isolation valves) supervised with seals in correct (open or closed) position? - 13.3.2.2: No
Notes: There are no control valves.
Deficiency #1 - Photo #1
Date Taken: July 10, 2025
Deficiencies - General Wet System Questions
None
Deficiencies - Wet
Deficiency #2
Sprinkler Type: Wet Is flow observed? - 13.2.5: No
Notes: No gauge to read.
Deficiencies - Inspectors Test Connection
Report of Inspection / Test Semi-Annual NFPA 25
12-16-2025 Property VA Grand Junction Building 35 2121 North Ave Grand Junction CO
Print Date: 12-22-2025
Conducted by: James Trudeau
Platinum Fire Protection PO Box 607 Mead CO 80542 3036880177 rachel@platfire.com
Copyright 2025 Inspect Point
Deficiency #3
Location: East door on bldg Description: Inspectors test Terminates in Smooth Orifice?: No Signs: No
Notes: This system consists of a single head fed from domestic system. The inspectors test is a washing machine hose with no sign. No control valve.
Just a flow switch to a single sidewall head.
Report of Inspection / Test Semi-Annual NFPA 25
12-16-2025 Property VA Grand Junction Building 35 2121 North Ave Grand Junction CO
Print Date: 12-22-2025
Conducted by: James Trudeau
Platinum Fire Protection PO Box 607 Mead CO 80542 3036880177 rachel@platfire.com
Inspector Signature
I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.
Inspector Name Signature Date Completed
James Trudeau 2025-12-16
Report of Inspection / Test Semi-Annual NFPA 25
12-16-2025 Property VA Grand Junction Building 35 2121 North Ave Grand Junction CO
Print Date: 12-22-2025
Conducted by: James Trudeau
Platinum Fire Protection PO Box 607 Mead CO 80542 3036880177 rachel@platfire.com
File details come from the government source that posted it. Updated .