This is a Semi-Annual Inspection Report for water-based fire protection systems at VA Grand Junction Building 13, 2121 North Ave, Grand Junction, CO, completed on December 16, 2025. The inspection was conducted by James Trudeau of Platinum Fire Protection (PO Box 607, Mead, CO 80542) in accordance with NFPA 25 2011 standards for the inspection, testing, and maintenance of water-based fire protection systems.

The report documents 11 deficiencies across multiple categories. Control valve supervision deficiencies include unsecured and unsupervised lint trap backflow valves (Deficiency #1), lack of proper valve identification signage (Deficiencies #2 and #3), and specific valve issues at the break room location where two ball valves (1-1/4" lint trap backflows #1 and #2) and one 1" butterball valve lack seals, supervision, or signage (Deficiencies #9, #10, and #11). System condition deficiencies include two gauges requiring replacement (Deficiency #4). Testing deficiencies involve missing inspector's test valves on the riser's flow switch (Deficiency #7) and lint trap system flow (Deficiency #8), preventing proper waterflow alarm testing for both mechanical and electrical devices (Deficiencies #5 and #6). All alarm testing was performed manually without observed flow due to the absence of inspector's test connections. The inspector certified that all equipment was left in operational condition except as noted in the deficiencies.

View the file

Other files

File Type Posted
CLIN 03 Bldg 22 Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 1- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 01 VA- NFS-Kitchen Hood 2121- N Ave-FAIL.pdf PDF
CLIN 01 VA -Grnd Junc CLC Kitchen Hood 2121 N Ave FAIL.pdf PDF
CLIN 02 VA B37 Audible Deficiencies.pdf PDF
36C25926Q0408 0002.docx DOCX document
CLIN 03 Bldg 12- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 7- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 36- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 35- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 02 VA Hosp - Grand Junction Battery List 2025.pdf PDF
CLIN 03 Bldg 34- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 6- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 20- Quarterly Sprinkler 12-22-25 Fail.pdf PDF
CLIN 03 Bldg 8- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 33- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 5- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 37- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 45- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
Questions and Answers.docx DOCX document
36C25926Q0408 0001.docx DOCX document
36C25926Q0408.docx DOCX document
Attachment 2 - Price Schedule.docx DOCX document
Attachment 3 - VA Notice of Limitations on Subcontracting.docx DOCX document
Attachment 1 - SOW.docx DOCX document
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Semi Annual Inspection Report

Completed on: 12-16-2025 for

VA Grand Junction Building 13 2121 North Ave

Grand Junction, CO

Conducted By:

James Trudeau

Platinum Fire Protection PO Box 607

Mead, CO 80542

This Joint Commission inspection was performed in accordance with the following codes and regulations:

• NFPA 25 2011 - Standard for the Inspection, Testing, and Maintenance of Water Based Fire Protection Systems

Deficiencies - General Questions

Deficiency #1

Are the control valves (including backflow preventer isolation valves) supervised with seals locked or is supervision in place? - 13.3.2.2: No

Notes: Lint trap backflow valves not secured or supervised

Deficiency #1 - Photo #1

Date Taken: August 19, 2025

Deficiency #2

Are the control valves (including backflow preventer isolation valves) supervised with seals properly identified? - 13.3.2.2: No

Notes: No valves are labeled with signs

Deficiency #3

Are the control valves (including valves on backflow preventers) with locks or electrical supervision properly identified? - 13.3.2.2: No

Notes: No valve signs

Report of Inspection / Test Semi-Annual NFPA 25

12-16-2025 Property VA Grand Junction Building 13 2121 North Ave Grand Junction CO

Print Date: 12-22-2025

Conducted by: James Trudeau

Platinum Fire Protection PO Box 607 Mead CO 80542 3036880177 rachel@platfire.com

Copyright 2025 Inspect Point

Deficiency #4

Are the gauges on system in good condition and showing normal water supply pressure? - 5.2.4.1: No

Notes: 2 gauges due for replacement

Deficiency #5

Have the mechanical waterflow alarm devices passed tests by opening inspector's test connection/bypass connection with alarms actuating and flow observed? - 5.3.3.3: No

Notes: No inspectors test valves found

Deficiency #6

The electrical waterflow alarm devices passed test by opening inspector's test connection/bypass connection with alarms actuating and flow observed? - 5.3.3.3:

No

Notes: Flow is not observed since there is no inspectors test valve found. Alarms tested manually

Deficiencies - General Wet System Questions

None

Deficiencies - Wet

None

Deficiencies - Inspectors Test Connection

Deficiency #7

Location: Riser Description: Flow switch Terminates in Smooth Orifice?: No Easily Accessible?: No Signs: No

Notes: No inspectors test found. Manual test only

Deficiency #8

Location: Lint trap Description: Lint trap system flow Terminates in Smooth Orifice?: No Signs: No

Notes: No inspectors test on this system. Manual trip only

Deficiencies - Valves

Report of Inspection / Test Semi-Annual NFPA 25

12-16-2025 Property VA Grand Junction Building 13 2121 North Ave Grand Junction CO

Print Date: 12-22-2025

Conducted by: James Trudeau

Platinum Fire Protection PO Box 607 Mead CO 80542 3036880177 rachel@platfire.com

Deficiency #9

Location: Outside break room Valve Type: Ball Size: 1-1/4 Description: Lint trap backflow #1 Signs: No

Notes: No seal or supervision

Deficiency #10

Location: Outside break room Valve Type: Butterball Size: 1 Description: Lint trap butterball Signs: No

Notes: No sign

Deficiency #11

Location: Outside break room Valve Type: Ball Size: 1-1/4 Description: Lint trap backflow #2 Signs: No

Notes: No seal or supervision

Report of Inspection / Test Semi-Annual NFPA 25

12-16-2025 Property VA Grand Junction Building 13 2121 North Ave Grand Junction CO

Print Date: 12-22-2025

Conducted by: James Trudeau

Platinum Fire Protection PO Box 607 Mead CO 80542 3036880177 rachel@platfire.com

Inspector Signature

I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.

Inspector Name Signature Date Completed

James Trudeau 2025-12-16

Report of Inspection / Test Semi-Annual NFPA 25

12-16-2025 Property VA Grand Junction Building 13 2121 North Ave Grand Junction CO

Print Date: 12-22-2025

Conducted by: James Trudeau

Platinum Fire Protection PO Box 607 Mead CO 80542 3036880177 rachel@platfire.com