This is a Semi-Annual Inspection Report for water-based fire protection systems at VA Grand Junction Building 13, 2121 North Ave, Grand Junction, CO, completed on December 16, 2025. The inspection was conducted by James Trudeau of Platinum Fire Protection (PO Box 607, Mead, CO 80542) in accordance with NFPA 25 2011 standards for the inspection, testing, and maintenance of water-based fire protection systems.
The report documents 11 deficiencies across multiple categories. Control valve supervision deficiencies include unsecured and unsupervised lint trap backflow valves (Deficiency #1), lack of proper valve identification signage (Deficiencies #2 and #3), and specific valve issues at the break room location where two ball valves (1-1/4" lint trap backflows #1 and #2) and one 1" butterball valve lack seals, supervision, or signage (Deficiencies #9, #10, and #11). System condition deficiencies include two gauges requiring replacement (Deficiency #4). Testing deficiencies involve missing inspector's test valves on the riser's flow switch (Deficiency #7) and lint trap system flow (Deficiency #8), preventing proper waterflow alarm testing for both mechanical and electrical devices (Deficiencies #5 and #6). All alarm testing was performed manually without observed flow due to the absence of inspector's test connections. The inspector certified that all equipment was left in operational condition except as noted in the deficiencies.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Semi Annual Inspection Report
Completed on: 12-16-2025 for
VA Grand Junction Building 13 2121 North Ave
Grand Junction, CO
Conducted By:
James Trudeau
Platinum Fire Protection PO Box 607
Mead, CO 80542
This Joint Commission inspection was performed in accordance with the following codes and regulations:
• NFPA 25 2011 - Standard for the Inspection, Testing, and Maintenance of Water Based Fire Protection Systems
Deficiencies - General Questions
Deficiency #1
Are the control valves (including backflow preventer isolation valves) supervised with seals locked or is supervision in place? - 13.3.2.2: No
Notes: Lint trap backflow valves not secured or supervised
Deficiency #1 - Photo #1
Date Taken: August 19, 2025
Deficiency #2
Are the control valves (including backflow preventer isolation valves) supervised with seals properly identified? - 13.3.2.2: No
Notes: No valves are labeled with signs
Deficiency #3
Are the control valves (including valves on backflow preventers) with locks or electrical supervision properly identified? - 13.3.2.2: No
Notes: No valve signs
Report of Inspection / Test Semi-Annual NFPA 25
12-16-2025 Property VA Grand Junction Building 13 2121 North Ave Grand Junction CO
Print Date: 12-22-2025
Conducted by: James Trudeau
Platinum Fire Protection PO Box 607 Mead CO 80542 3036880177 rachel@platfire.com
Copyright 2025 Inspect Point
Deficiency #4
Are the gauges on system in good condition and showing normal water supply pressure? - 5.2.4.1: No
Notes: 2 gauges due for replacement
Deficiency #5
Have the mechanical waterflow alarm devices passed tests by opening inspector's test connection/bypass connection with alarms actuating and flow observed? - 5.3.3.3: No
Notes: No inspectors test valves found
Deficiency #6
The electrical waterflow alarm devices passed test by opening inspector's test connection/bypass connection with alarms actuating and flow observed? - 5.3.3.3:
No
Notes: Flow is not observed since there is no inspectors test valve found. Alarms tested manually
Deficiencies - General Wet System Questions
None
Deficiencies - Wet
None
Deficiencies - Inspectors Test Connection
Deficiency #7
Location: Riser Description: Flow switch Terminates in Smooth Orifice?: No Easily Accessible?: No Signs: No
Notes: No inspectors test found. Manual test only
Deficiency #8
Location: Lint trap Description: Lint trap system flow Terminates in Smooth Orifice?: No Signs: No
Notes: No inspectors test on this system. Manual trip only
Deficiencies - Valves
Report of Inspection / Test Semi-Annual NFPA 25
12-16-2025 Property VA Grand Junction Building 13 2121 North Ave Grand Junction CO
Print Date: 12-22-2025
Conducted by: James Trudeau
Platinum Fire Protection PO Box 607 Mead CO 80542 3036880177 rachel@platfire.com
Deficiency #9
Location: Outside break room Valve Type: Ball Size: 1-1/4 Description: Lint trap backflow #1 Signs: No
Notes: No seal or supervision
Deficiency #10
Location: Outside break room Valve Type: Butterball Size: 1 Description: Lint trap butterball Signs: No
Notes: No sign
Deficiency #11
Location: Outside break room Valve Type: Ball Size: 1-1/4 Description: Lint trap backflow #2 Signs: No
Notes: No seal or supervision
Report of Inspection / Test Semi-Annual NFPA 25
12-16-2025 Property VA Grand Junction Building 13 2121 North Ave Grand Junction CO
Print Date: 12-22-2025
Conducted by: James Trudeau
Platinum Fire Protection PO Box 607 Mead CO 80542 3036880177 rachel@platfire.com
Inspector Signature
I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.
Inspector Name Signature Date Completed
James Trudeau 2025-12-16
Report of Inspection / Test Semi-Annual NFPA 25
12-16-2025 Property VA Grand Junction Building 13 2121 North Ave Grand Junction CO
Print Date: 12-22-2025
Conducted by: James Trudeau
Platinum Fire Protection PO Box 607 Mead CO 80542 3036880177 rachel@platfire.com