This document is a battery and panel inspection report prepared by ALARM Specialists, Inc. for the VA Hospital in Grand Junction, Colorado, dated August 22, 2025.
The report contains detailed battery and backup power system (BPS) inventory lists across five facility locations: Parking Garage, Building 5, Building 6, Building 33, and Building 37. Each battery group is assessed for operational status (OK or FAIL) with voltage measurements, ampere-hour (AH) ratings, and physical sizes documented. The Parking Garage location contains two battery groups with 55.0Ah and 9.0Ah capacity batteries, with four batteries marked as failed due to 0 AH ratings. Building 5's Basement Panel and BPS systems include 55.0Ah batteries (OK status) and 12.0Ah batteries (FAIL status with 2.7 AH ratings). Building 6 similarly reports 55.0Ah batteries (OK) and 12.0Ah batteries (FAIL) with 0 AH ratings. Building 33 contains two battery groups with 50 AH and 12 AH rated systems, with mixed OK and FAIL statuses. Building 37 houses a single BPS unit in Room 122 with two 12 AH batteries, both marked as failed with 1.9 AH ratings. Panel voltages across all locations range from 118.7 to 121.0 VAC, with charging voltages between 26.1 and 27.8 VDC. Inspection dates range from February 25 to March 23, 2025, with one December 22 reading documented.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Prepared by
ALARMSpecialists, Inc
Battery
Group Location
Panel
Voltage
Charging
Voltage Voltage
AH
Rating OK FAIL Size Comments
13.6 VDC 17 AH X 55.0Ah
13.6 VDC 17 AH X 55.0Ah
12.6 VDC 0 AH X 9.0Ah
12.6 VDC 0 AH X 9.0Ah
VA Hospital - Grand Junction - Parking Garage - Battery and Panel List - August 22, 2025
1 Electrical Room 104 Panel 119.0 VAC 27.7 VDC 23-Mar
2 Electrical Room 104 BPS 1 119.0 VAC 26.1 VDC 23-Mar
6786 S Revere Pkwy Ste 100 Centennial, CO 80112
Battery
Group Location
Panel
Voltage
Charging
Voltage Voltage
AH
Rating OK FAIL Size Comments
13.5 VDC 39 AH X 55.0Ah
13.6 VDC 40 AH X 55.0Ah
12.8 VDC 2.7 AH X 12.0Ah
12.7 VDC 2.7 AH X 12.0Ah
VA Hospital - Grand Junction - Bldg 5 - Battery and Panel List - August 22, 2025
1 Basement Panel 118.7 VAC 27.7 VDC 25-Feb
2 Basement BPS (ACPS) - Lower CAB of FACP 118.7 VAC 27.8 VDC
Battery
Group Location
Panel
Voltage
Charging
Voltage Voltage
AH
Rating OK FAIL Size Comments
13.5 VDC 38 AH X 55.0Ah
13.1 VDC 32 AH X 55.0Ah
12.6 VDC 0 AH X 12.0Ah
12.7 VDC 0 AH X 12.0Ah
VA Hospital - Grand Junction - Bldg 6 - Battery and Panel List - August 22, 2025
1 Basement Panel 121.0 VAC 27.7 VDC 25-Feb
2 Basement BPS (bottom of FACP cabinet) 121.0 VAC 27.4 VDC
\ Location Panel
Voltage
Charging
Voltage Voltage
AH
Rating OK FAIL Size Comments
13.5 VAC 5 AH X 50 AH
13.5 VAC 7.5 AH X 50 AH
13.1 VDC 7.8 AH X 12 AH
13.0 VDC 7.6 AH X 12 AH
VA Hospital - Grand Junction - Bldg 33 - Battery and Panel List - August 22, 2025
1 Panel 119.0 VAC 27.7 VDC 23-Mar
2 BPS 119.1 VAC 27.8 VDC
22-Dec
Battery
Group Location
Panel
Voltage
Charging
Voltage Voltage AH Rating OK FAIL Size Comments
13.0 VDC 1.9 AH X 12 AH
12.8 VDC 1.9 AH X 12 AH
VA Hospital - Grand Junction - Bldg 37 - Battery and Panel List - August 22, 2025
1 Room 122 BPS 119.5 VAC 27.6 VDC 23-Jan