This solicitation requests quotes for fire alarm and sprinkler system maintenance services. The Department of Veterans Affairs Network Contracting Office 17 is seeking to award a firm-fixed price contract for maintenance of fire alarm and sprinkler systems at the Central Texas Veterans Health Care System facilities in Temple, Texas. The base period of performance is one year with four optional one-year extensions. This requirement is set aside for Service-Disabled Veteran Owned Small Businesses. Interested vendors must be verified on the Vendor Information Pages database. Questions are due by December 6th and quotes must be submitted via email by the date and time specified in block 8 of the SF1449. The scope of work involves maintenance of fire alarm and sprinkler systems in accordance with the statement of work.
View the file
Other files
Show all 39
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate
For
Waco VAMC Bldg. 7 4800 Memorial Dr Waco, TX 76711
This inspection was performed in accordance with NFPA 101, EDITION 2021, LIFE SAFETY CODE and NFPA 72, EDITION 2019, FIRE ALARM SYSTEMS. Documentation complies with EC 02.03.05
EP 28.
The inspection/testing frequencies adhered to for this service have been performed in accordance with The Joint Commission/VHA Clarification Memorandum on EC & LS Standards effective January 31, 2021. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Annual Inspection Inspection Completion Date Nov 10, 2021
Building: Waco VAMC Bldg. 7 Company: Convergint Technologies - Central Texas Contact: Che Buval Contact: Jessy Martin Title: Safety Officer Title: Service Specialist
Page of 1 45 Executive Summary
Convergint Technologies - Central Texas Download Date: 12/07/2021
Executive Summary Generated by: BuildingReports.com
Building Information Building: Waco VAMC Bldg. 7 Contact: Che Buval
Address: 4800 Memorial Dr Phone: 254-743-0133
Address: Fax:
City/State/Zip: Waco, TX 76711 Mobile:
Country: United States of America Email: Che.Buval@va.gov
Inspection Performed By Company: Convergint Technologies - Central Texas Inspector: Jessy Martin
Address: 10535 Boyer Blvd Phone: 5034626730
Address: Suite 300 Fax:
City/State/Zip: Austin, Texas 78758 Mobile: 5034626730
Country: United States Email: jessy.martin@convergint.com
System Control Unit Manufacturer: SimplexGrinnell Inspection Date: 11/08/2021 IDC Style:
Model Number: 4020 Install Date: 09/11/2001 SLC Style:
Software Version: Version Date: 09/30/2021 NAC Style:
Location: Basement BC-102 Simplex FACP 4020 Current Protection:
Central Station Signal Verification Type: Mfg: SimplexGrinnell Model #: 4020
Test Time/Date: 11/10/21 2:11:17 PM Restore Time: Note: 11/10/21 JC verified signals reached central monitoring station. Panel is acceptable BLUE only for Simplex 4020 FACP (DACT)
Page of 2 45
Convergint Technologies - Central Texas Download Date: 12/07/2021
Inspection Completion Date: Nov 10, 2021 Building: Waco VAMC Bldg. 7 EC 02.03.05 EP 01 Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; and room temperature supervisory
Devices Tested This
Quarter Pass Fail Tested YTD
(2021) Untested YTD
(2021) Total
Quantity Air Pressure Switch 0 0 0 0 1 1
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches
Devices Tested This
Quarter Pass Fail Tested YTD
(2021) Untested YTD
(2021) Total
Quantity Tamper Switch 0 0 0 0 14 14
Waterflow Switch 0 0 0 0 13 13
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Devices Tested This
Quarter Pass Fail Tested YTD
(2021) Untested YTD
(2021) Total
Quantity Duct Detector 24 24 0 24 0 24
Heat Detector 7 7 0 7 0 7
Pull Station 24 24 0 24 0 24
Smoke Detector 25 24 1 26 0 26
EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices.
Devices Tested This
Quarter Pass Fail Tested YTD
(2021) Untested YTD
(2021) Total
Quantity Bell 2 2 0 2 0 2
Bell/Strobe 51 47 4 51 0 51
Releasing Device 35 35 0 35 0 35
Speaker/Strobe 1 1 0 1 0 1
Strobe 5 5 0 5 0 5
EC 02.03.05 EP 05 Annual test of fire alarm equipment for notifying off-site fire responders
Devices Tested This
Quarter Pass Fail Tested YTD
(2021) Untested YTD
(2021) Total
Quantity Communicator 1 1 0 1 0 1
EC 02.03.05 EP 19 Annual test of automatic smoke-detection shutdown devices for air-handling equipment per NFPA 90A-2021
Devices Tested This
Quarter Pass Fail Tested YTD
(2021) Untested YTD
(2021) Total
Quantity Duct Detector 24 24 0 24 0 24
Fan Shutdown 5 1 4 5 0 5
LS 02.01.34 EP 02 Protected master fire alarm control panel Tested This Tested YTD Untested YTD Total
Page of 3 45
Convergint Technologies - Central Texas Download Date: 12/07/2021
LS 02.01.34 EP 02 Protected master fire alarm control panel Devices Quarter Pass Fail (2021) (2021) Quantity Control Panel 2 2 0 2 0 2
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2021 18/19.3.4
Devices Tested This
Quarter Pass Fail Tested YTD
(2021) Untested YTD
(2021) Total
Quantity Annunciator 2 2 0 2 0 2
Battery 8 8 0 8 0 8
Locking Device 4 4 0 4 0 4
Power Supply 2 1 1 2 0 2
Remote Indicator 18 18 0 19 0 19
Total Device Count: 246
Page of 4 45
Convergint Technologies - Central Texas Download Date: 12/07/2021
Certification Company: Convergint Technologies - Central Texas Building: Waco VAMC Bldg. 7 Inspector: Jessy Martin Contact: Che Buval
Signed: Nov 10, 2021 Signed: Nov 10, 2021
Jessy Martin Certifications Certification Type Number NICET Fire Alarm Systems Level II 152267
Texas State Certification - Fire Alarm Systems 2688841
Page of 5 45 Discrepancy Report
Convergint Technologies - Central Texas Download Date: 12/07/2021
Discrepancy Report Generated by: BuildingReports.com
Building: Waco VAMC Bldg. 7 Control Panel: 1 - SimplexGrinnell 4020 The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty Items listed for Recall or Replacement/Upgrade
No items found during this inspection.
ScanID Location Problem Address Reference
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Smoke Detector 52281986 Basement Public Elevator Lobby Damaged/Worn 1 NFPA72 14.2.2.2.2
EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices.
Bell/Strobe 46937627 Sub-Basement Failed Operation 1
46937628 Sub-Basement Failed Operation 1
46937587 1st Corridor 1B106 Failed Operation 1
46937589 1st Corridor By Room 1B112 Failed Operation 1
EC 02.03.05 EP 19 Annual test of automatic smoke-detection shutdown devices for air-handling equipment per NFPA 90A-2021
Fan Shutdown 52281975 Basement 1C105A Failed Operation 1 NFPA72 21.7.3
52281977 Basement 1C105A Failed Operation 1 NFPA72 21.7.3
52281973 Basement AHU 2 Return Failed Operation 1 NFPA72 21.7.3
52281971 Basement AHU 2 Supply Failed Operation 1 NFPA72 21.7.3
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2021 18/19.3.4
Power Supply 46937958 Basement BC-112 Failed to Report 1 NFPA72 14.2.2.2.2 javascript:openEditDevice('load-edit-f2-device','771914','2807820','52281986');
javascript:openEditDevice('load-edit-f2-device','771914','2807820','46937627');
javascript:openEditDevice('load-edit-f2-device','771914','2807820','46937628');
javascript:openEditDevice('load-edit-f2-device','771914','2807820','46937587');
javascript:openEditDevice('load-edit-f2-device','771914','2807820','46937589');
javascript:openEditDevice('load-edit-f2-device','771914','2807820','52281975');
javascript:openEditDevice('load-edit-f2-device','771914','2807820','52281977');
javascript:openEditDevice('load-edit-f2-device','771914','2807820','52281973');
javascript:openEditDevice('load-edit-f2-device','771914','2807820','52281971');
javascript:openEditDevice('load-edit-f2-device','771914','2807820','46937958');
Page of 6 45 Proposed Solutions Report
Convergint Technologies - Central Texas Download Date: 12/07/2021
Proposed Solutions Report Generated by: BuildingReports.com
Building: Waco VAMC Bldg. 7 Control Panel: 1 - SimplexGrinnell 4020 The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.
ScanID Location Solution Model # Cost Fix
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Smoke Detector 52281986 Basement Public Elevator Lobby Replace T/M
EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices.
Bell/Strobe 46937627 Sub-Basement Replace T/M 46937628 Sub-Basement Replace T/M 46937587 1st Corridor 1B106 Replace T/M 46937589 1st Corridor By Room 1B112 Replace T/M
EC 02.03.05 EP 19 Annual test of automatic smoke-detection shutdown devices for air-handling equipment per
NFPA 90A-2021
Fan Shutdown 52281975 Basement 1C105A Service T/M 52281977 Basement 1C105A Service T/M 52281973 Basement AHU 2 Return Service T/M 52281971 Basement AHU 2 Supply Service T/M
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2021 18/19.3.4
Power Supply 46937958 Basement BC-112 Service FCPS-24 T/M
PO #: (none) T/M
Page of 7 45 Notes & Recommendations
Convergint Technologies - Central Texas Download Date: 12/07/2021
Notes & Recommendations Generated by: BuildingReports.com
Building: Waco VAMC Bldg. 7 The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
General Note 11/11/21 JC/JCM Annual Inspection complete. Panel is previously Red tagged. Panel is still red tagged.
-Fan shutdowns failed:
Basement 1C105A Supply and Return Basement AHU 2 supply and return.
-All AV's need to be brought up to proper specs. Db level is so faint that it cannot be heard in all areas. Suggest upgrade to correct issue.
-Smoke detector in Basement Public Elevator Lobby has paint in smoke chamber and requires replacement.
-Remote indicators need to be barcode added/inventoried for floor 1
-All second floor pull stations are without lockboxes. Recommend replacing just the cover box to make these inaccessible for public in the future.
-Unable to test elevator hoistway fire alarm devices, no access at time of testing.
- Pull station by 1C108 cover box needs to be loosened. It is really tough to open in case of an actual event with key.
**Panel is Red Tagged from previous inspection 7/20/20 for:
1. NAC Panel 2 failed to report trouble to FACP when batteries were disconnected. Not Repaired.
Simplex 4020 Panel ** Panel was Blue Tagged - No deficiencies noted.
Note 1
1. All sprinkler devices tested by 1st FP on Sprinkler Scan Report. (not on site during our annual inspection)
*Customer needs to contact Monitoring Entity (Johnson Controls) and verify if Trouble signals are being monitored.
If they are notify David Matthews with Hurtvet to schedule Service to troubleshoot issue.
(Customer must perform this action because account is password protected and has designated contacts who can discuss account settings and we are not on that list)
Building: Waco VAMC Bldg. 7 Control Panel: 1 - SimplexGrinnell 4020 Note Device Type Location Comment ScanID
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
2 Smoke Detector Basement Public Elevator Lobby Damaged/Worn 52281986 head had paint splattered all over it. needs to be replaced
3 Smoke Detector 2nd Floor service Elevator Shaft 52282039 No access javascript:openEditDevice('load-edit-f2-device','771914','2807820','52281986');
javascript:openEditDevice('load-edit-f2-device','771914','2807820','52282039');
Page of 8 45 Notes & Recommendations
Convergint Technologies - Central Texas Download Date: 12/07/2021
Note Device Type Location Comment ScanID
EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices.
4 Bell/Strobe Sub-Basement Failed Operation 46937627 strobe failed 5 Bell/Strobe Sub-Basement Failed Operation 46937628 failed strobe 6 Bell/Strobe 1st Corridor 1B106 Failed Operation 46937587
Bell failed test 7 Bell/Strobe 1st Corridor By Room 1B112 Failed Operation 46937589
Bell failed test
EC 02.03.05 EP 05 Annual test of fire alarm equipment for notifying off-site fire responders 8 Communicator Basement BC-102 Passed 46937943
11/10/21 JC verified signals reached central monitoring station. Panel is acceptable BLUE only for Simplex 4020
FACP (DACT)
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2021 18/19.3.4 9 Power Supply Basement BC-112 Failed to Report 46937958 disconnected battery failed to report to FACP 10 Remote Indicator 2nd Floor service Elevator Shaft 52282038
No access javascript:openEditDevice('load-edit-f2-device','771914','2807820','46937627');
javascript:openEditDevice('load-edit-f2-device','771914','2807820','46937628');
javascript:openEditDevice('load-edit-f2-device','771914','2807820','46937587');
javascript:openEditDevice('load-edit-f2-device','771914','2807820','46937589');
javascript:openEditDevice('load-edit-f2-device','771914','2807820','46937943');
javascript:openEditDevice('load-edit-f2-device','771914','2807820','46937958');
javascript:openEditDevice('load-edit-f2-device','771914','2807820','52282038');
Page of 9 45 Inspection & Testing
Convergint Technologies - Central Texas Download Date: 12/07/2021
Inspection & Testing Generated by: BuildingReports.com
Building: Waco VAMC Bldg. 7 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.
Passed=P, Failed=F, Replaced=R
EC 02.03.05 EP 01
Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; and room temperature supervisory
Operate switch and verify receipt of signal is obtained where the required pressure is increased or decreased a maximum 10 psi from the required pressure level. (NFPA 72-19 Table 14.4.3.2 (17)(9b)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Air Pressure Switch 0 0 0 0 1
Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Air Pressure Switch
Basement mech room bc105
33964559 1
Device Total: 1 Return to Executive Summary
Page of 10 45
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches
Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-19 Table 14.4.3.2 (17)(10)(a)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Tamper Switch 0 0 0 0 14
Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Tamper Switch Basement mech room bc105 41143870 1
Tamper Switch Basement mech room bc105
41143871 1
Tamper Switch Basement mech room bc105
41143872 1
Tamper Switch Basement mech room bc105
41143873 1
Tamper Switch Basement mech room bc105
41143874 1
Tamper Switch Basement mech room bc105
41143875 1
Tamper Switch Basement stairwell 1 33964621 1 Tamper Switch Basement stairwell 2 33964608 1 Tamper Switch 1st stair 2 33964606 1 Tamper Switch 1st stair 3 33964592 1 Tamper Switch 2nd floor stair 1 33964612 1 Tamper Switch 2nd floor stair 2 33964595 1 Tamper Switch 2nd floor stair 3 33964585 1 Tamper Switch outside 41143876 1
Device Total: 14 Return to Executive Summary
Page of 11 45
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches
Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size installed in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25-20. (NFPA 72-19 Table
14.4.3.2 (17)(11)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Waterflow Switch 0 0 0 0 13
Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Waterflow Switch Basement Mech room
BC-105
33964275 1
Waterflow Switch Basement Mech room
BC-105
33964558 1
Waterflow Switch Basement Mech room
BC-105
33964561 1
Waterflow Switch Basement Mech room
BC-105
33964576 1
Waterflow Switch Basement stairwell 1 33964620 1 Waterflow Switch Basement stairwell 2 33964607 1 Waterflow Switch Basement stairwell to sub basement 33964582 1
Waterflow Switch 1st floor stair 1 above ceiling
33964622 1
Waterflow Switch 1st stair 2 33964601 1 Waterflow Switch 1st stair 3 33964593 1 Waterflow Switch 2nd floor stair 1 above ceiling 33964611 1
Waterflow Switch 2nd floor stair 2 33964598 1 Waterflow Switch 2nd floor stair 3 33964586 1
Device Total: 13 Return to Executive Summary
Page of 12 45
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72- 19 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Duct Detector 24 24 0 24 24
Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Duct Detector Sub-Basement AHU 4
Supply 46937571 1 02/05-P 11/08-P
Duct Detector Sub-Basement AHU 4 Return
46937570 1 02/05-P 11/08-P
Duct Detector Sub-Basement AHU 5 Return
46937574 1 02/05-P 11/08-P
Duct Detector Sub-Basement AHU 5 Supply
46937573 1 02/05-P 11/08-P
Duct Detector Sub-Basement AHU 3 46937569 1 02/05-P 11/08-P Duct Detector Sub-Basement AHU 3 46937568 1 02/10-P 11/08-P Duct Detector Basement Corridor @
BA104
52281988 1 02/10-P 11/10-P
The above device replaced ScanID 46937566:
Duct Detector Basement Corridor @
BA104
46937566 1 02/10-R
Duct Detector Basement Corridor @
BA108
52281992 1 02/10-P 11/10-P
The above device replaced ScanID 46937567:
Duct Detector Basement Corridor @
BA108
46937567 1 02/10-R
Duct Detector Basement AHU 1 Return
46937563 1 02/03-P 11/08-P
Duct Detector Basement AHU 1 Supply
46937562 1 02/03-P 11/08-P
Duct Detector Basement AHU 2 Return
46937564 1 02/03-P 11/08-P
Duct Detector Basement AHU 2 Supply
46937565 1 02/03-P 11/08-P
Duct Detector 1st Floor Corridor by 1C111
52282016 1 02/08-P 11/10-P
The above device replaced ScanID 46937552:
Duct Detector 1st Floor Corridor by 1C111
46937552 1 02/08-R
Duct Detector 1st Floor Corridor by 1C111
52282017 1 02/08-P 11/10-P
The above device replaced ScanID 46937551:
Duct Detector 1st Floor Corridor by 1C111
46937551 1 02/08-R
Page of 13 45
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Duct Detector 1st Floor Corridor by
1B106A 46937554 1 02/08-P 11/10-P
Duct Detector 1st Floor Corridor by 1A109
46937550 1 02/08-P 11/10-P
Duct Detector 1st Floor Corridor by 1B106
46937553 1 02/08-P 11/10-P
Duct Detector 1st Floor 1B106A 46937555 1 02/08-P 11/10-P Duct Detector 2nd Floor Corridor @
2C112 52282035 1 02/09-P 11/10-P
Duct Detector 2nd Floor Corridor @ 2C112
52282034 1 02/09-P 11/10-P
The above device replaced ScanID 46937558:
Duct Detector 2nd Floor Corridor @ 2C112
46937558 1 02/09-R
Duct Detector 2nd Floor 2B112 46937561 1 02/09-P 11/10-P Duct Detector 2nd Floor Corridor @
2B107 46937559 1 02/09-P 11/10-P
Duct Detector 2nd Floor 2A106 46937560 1 02/10-P 11/10-P Duct Detector 2nd Floor Corridor @
2A110 52282043 1 02/09-P 11/10-P
The above device replaced ScanID 46937556:
Duct Detector 2nd Floor Corridor @ 2A110
46937556 1 02/09-R
Duct Detector 2nd Floor Corridor @ 2A110
46937557 1 02/10 Removed
Device Total: 24 Return to Executive Summary
Page of 14 45
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions. Non-Restorable: Do not perform heat test. Test functionality mechanically and electrically.
(NFPA 72-19 Table 14.4.3.2 (17)(4)(a)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Heat Detector 7 7 0 7 7
Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Heat Detector Basement BC-102 46937581 1 02/10-P 11/10-P Heat Detector Basement BC-102 46937580 1 02/10-P 11/10-P Heat Detector Attic Elevator
Equipment Room 46937578 1 02/05-P 11/10-P
Heat Detector Attic Elevator Equipment Room
46937579 1 02/05-P 11/10-P
Heat Detector Attic Elevator Equipment Room
46937575 1 02/05-P 11/10-P
Heat Detector Attic Elevator Equipment Room
46937576 1 02/05-P 11/10-P
Heat Detector Attic Elevator Equipment Room
46937577 1 02/05-P 11/10-P
Device Total: 7 Return to Executive Summary
Page of 15 45
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-19 Table 14.4.3.2 (17)(5)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Pull Station 24 24 0 24 24
Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Pull Station Sub-Basement Pipe
Basement 52281990 1 02/05-P 11/08-P
The above device replaced ScanID 46937522:
Pull Station Sub-Basement Pipe Basement
46937522 1 02/05-R
Pull Station Sub-Basement Pipe Basement
46937521 1 02/05-P 11/08-P
Pull Station Basement By Stair 2 46937519 1 02/05-P 11/08-P Pull Station Basement By Room
BA101
52281994 1 02/10-P 11/08-P
Pull Station Basement Nurses Station
46937520 1 02/05-P 11/08-P
Pull Station Basement By Room
BB100
46937515 1 02/05-P 11/08-P
Pull Station Basement In Stair 2 46937516 1 02/05-P 11/08-P Pull Station Basement Service
Elevator Lobby 46937512 1 10/13-P 02/05-P 04/20-P 07/06-P 11/08-P
Pull Station Basement By Room
BC110
46937518 1 02/05-P 11/08-P
Pull Station Basement By Room
BC104
46937513 1 02/10
Pull Station Basement By Room
BA101
46937542 1 02/10
Pull Station Basement By Room
BB107
46937543 1 02/10
Pull Station 1st Floor By Room 1C119
46937507 1 02/08-P 11/10-P
Pull Station 1st Floor By Room 1C108
52282018 1 02/08-P 11/10-P
The above device replaced ScanID 46937505:
Pull Station 1st Floor By Room 1C108
46937505 1 02/08-R
Pull Station 1st Corridor By Room 1C101
52282014 1 02/08-P 11/10-P
Pull Station 1st Floor by Stair 2 46937523 1 02/08-P 11/10-P Pull Station 1st Floor by Room
1A103 46937502 1 02/08-P 11/10-P
Pull Station 1st Floor Stair 2 46937506 1 02/08-P 11/10-P Pull Station 1st Floor By Room 46937504 1 02/08-P 11/10-P
Page of 16 45
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 1B119
Pull Station 1st Floor by Room 1B100
46937503 1 02/08-P 11/10-P
Pull Station 1st Floor Elevator Lobby
46937501 1 02/10
Pull Station 2nd floor Nurses Station
52282033 1 02/09-P 11/10-P
The above device replaced ScanID 46937524:
Pull Station 2nd floor Nurses Station
46937524 1 02/09-R
Pull Station 2nd floor By Stair 3 46937514 1 02/09-P 11/10-P Pull Station 2nd floor By Room
2C101 46937509 1 02/09-P 11/10-P
Pull Station 2nd floor By Stair 2 46937511 1 02/09-P 11/10-P Pull Station 2nd floor By Stair 1 46937510 1 02/09-P 11/10-P Pull Station 2nd floor By 2A103 46937508 1 02/09-P 11/10-P Pull Station Attic 46937931 1 02/05-P 11/10-P
Page of 17 45
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72- 19 Table 14.4.3.2 (17)(7)(a)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Smoke Detector 25 24 1 26 26
Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Smoke Detector Basement Service
Elevator Lobby 52281999 1 02/05-P 11/10-P
The above device replaced ScanID 46937547:
Smoke Detector Basement Service Elevator Lobby
46937547 1 02/05-R
Smoke Detector Basement Elevator Machine Room
46937545 1 11/10-P
The above device replaced ScanID 46937945:
Smoke Detector Basement Elevator Machine Room
46937945 1 10/13-R 02/05-P
Smoke Detector Basement Switch Gear Room
52282048 1 02/10-P 11/08-P
The above device replaced ScanID 36937548:
Smoke Detector Basement Switch Gear Room
36937548 1 02/10-R
Smoke Detector Basement Switchgear Room in BC105 Mech Rm
46937548 1 02/05-P 11/08-P
Smoke Detector Basement By Room
BB107
52281987 1 02/10-P 11/08-P
The above device replaced ScanID 4693753:
Smoke Detector Basement By Room
BB107
4693753 1 02/10-R
Smoke Detector Basement Floor by Room BA-121
52281995 1 02/05-P 11/08-P
Smoke Detector Basement By Room
BC114
52282002 1 02/05-P 11/08-P
The above device replaced ScanID 46937544:
Smoke Detector Basement By Room
BC114
46937544 1 02/05-R
Smoke Detector Basement Public Elevator Lobby
52281986 1 02/05-F 11/10-F
The above device replaced ScanID 46937546:
Smoke Detector Basement Public Elevator Lobby
46937546 1 02/05-R
Smoke Detector 1st Floor Service Elevator Lobby
46937532 1 02/08-P 11/10-P
Smoke Detector 1st Floor Public Elevator Lobby
46937531 1 02/05-P 11/10-P
Page of 18 45
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Smoke Detector 1st Floor by Room
1C113 46937530 1 02/08-P 11/10-P
Smoke Detector 1st Floor by Room 1C100
46937938 1 02/08-P 11/10-P
Smoke Detector 1st Floor by Room 1A111
46937525 1 02/08-P 11/10-P
Smoke Detector 1st Floor by Room 1B107
46937527 1 02/10-P 11/10-P
Smoke Detector 1st Floor by Room 1B105
46937526 1 02/08-P 11/10-P
Smoke Detector 1st Floor by Room 1B121
46937528 1 02/10-P 11/10-P
Smoke Detector 2nd Floor public Elevator Lobby
46937540 1 02/09-P 11/10-P
Smoke Detector 2nd Floor public Elevator Lobby
46937539 1 02/09-P 11/10-P
Smoke Detector 2nd Floor service Elevator Lobby
46937537 1 02/09-P 11/10-P
Smoke Detector 2nd Floor by Room 2C100
46937935 1 02/09-P 11/10-P
Smoke Detector 2nd Floor by Room 2B107
46937535 1 02/09-P 11/10-P
Smoke Detector 2nd floor B106 46937934 1 02/09-P 11/10-P Smoke Detector 2nd Floor by Room
2A112 46937533 1 02/09-P 11/10-P
Smoke Detector 2nd Floor by Room 2B121
46937549 1 02/09-P 11/10-P
Smoke Detector 2nd Floor service Elevator Shaft
52282039 1 02/09-P
The above device replaced ScanID 46937538:
Smoke Detector 2nd Floor service Elevator Shaft
46937538 1 02/09-R
Smoke Detector Attic Elevator Equipment Room
46937541 1 02/05-P 11/10-P
Device Total: 26 Return to Executive Summary
Page of 19 45
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices.
For periodic testing, verify the operation of the notification appliances. (NFPA 72-19 Table 14.4.3.2 (22)(1)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Bell 2 2 0 2 2
Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Bell Basement Summons
Bell BA119 46937631 1 02/10
Bell 1st Outside Exit to courtyard By Room 1B120 Outside
52282062 1 02/10-P 11/10-P
Bell 1st Exit by 1B100 Outside
52282061 1 02/10-P 11/10-P
Device Total: 2 Return to Executive Summary
Page of 20 45
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices.
For periodic testing, verify the operation of the notification appliances. (NFPA 72-19 Table 14.4.3.2 (22)(1)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Bell/Strobe 51 47 4 51 51
Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Bell/Strobe Sub-Basement 46937627 1 02/10-F 11/10-F Bell/Strobe Sub-Basement 46937628 1 02/10-F 11/10-F Bell/Strobe Basement Corridor By
Room BC110
674EE44646 1 02/05-P 11/10-P
Bell/Strobe Basement by BB106 674EE44645 1 02/05-P 11/10-P Bell/Strobe Basement Corridor By
Public Elevator
674EE44616 1 02/05-P 11/10-P
Bell/Strobe Basement By Room
BB107
52282093 1 02/10-P 11/10-P
The above device replaced ScanID 46937954:
Bell/Strobe Basement By Room
BB107
46937954 1 02/10-R
Bell/Strobe Basement Corridor By Room BA103
52282078 1 02/10-P 11/10-P
Bell/Strobe Basement Corridor By Room BA121
52282047 1 02/10-P 11/10-P
The above device replaced ScanID 46937615:
Bell/Strobe Basement Corridor By Room BA101
46937615 1 02/10-R
Bell/Strobe Basement Corridor By Stair 2
52282046 1 02/10-P 11/10-P
The above device replaced ScanID 46937620:
Bell/Strobe Basement Corridor By Stair 2
46937620 1 02/10-R
Bell/Strobe Basement Room BB105 Training Kitchen
52282005 1 02/05-P 11/10-P
Bell/Strobe Basement Corridor By Room BA104
52281993 1 02/05-P 11/10-P
The above device replaced ScanID 46937617:
Bell/Strobe Basement Corridor By Room BA104
46937617 1 02/05-R
Bell/Strobe Basement 1C105A 46937953 1 02/05-P 11/10-P Bell/Strobe Basement Room
BC105
46937942 1 02/03-P 11/10-P
Bell/Strobe Basement Room
BC111
46937626 1 02/10-P 11/10-P
Bell/Strobe Basement Room
BB115
46937625 1 02/05-P 11/10-P
Bell/Strobe Basement Room
BC105
46937624 1 02/05-P 11/10-P
Page of 21 45
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Bell/Strobe Basement Exit By
Room BB100 46937623 1 02/05-P 11/10-P
Bell/Strobe Basement Corridor By Room BC102
46937621 1 02/05-P 11/10-P
Bell/Strobe Basement Corridor By Room BA113
46937619 1 02/05-P 11/10-P
Bell/Strobe Basement Corridor By Room BA103
46937616 1 02/05-P 11/10-P
Bell/Strobe Basement Dock Exit 46937613 1 02/05-P 11/10-P Bell/Strobe Basement At Nurses
Station BA109 46937612 1 02/05-P 11/10-P
Bell/Strobe 1st By Room 1C108 52282019 1 02/08-P 11/10-P The above device replaced ScanID 46937592:
Bell/Strobe 1st By Room 1C108 46937592 1 02/08-R Bell/Strobe 1st Floor By Room
1C101 52282013 1 02/10-P 11/10-P
The above device replaced ScanID 46937591:
Speaker/Strobe 1st Floor By Room 1C11
46937591 1 02/10-R
Bell/Strobe 1st By Room 1C114 46937941 1 02/08-P 11/10-P Bell/Strobe 1st By Service Elevator 46937937 1 02/08-P 11/10-P Bell/Strobe 1st By Room 1A111 46937936 1 02/08-P 11/10-P Bell/Strobe 1st Corridor By Room
1B107 46937588 1 02/08-P 11/10-P
Bell/Strobe 1st Corridor 1A110 46937586 1 02/08-P 11/10-P Bell/Strobe 1st Corridor 1A106 46937584 1 02/08-P 11/10-P Bell/Strobe 1st Corridor By Room
1A102 46937583 1 02/08-P 11/10-P
Bell/Strobe 1st Floor by Stair 2 46937582 1 02/08-P 11/10-P Bell/Strobe 1st Corridor By Room
1B112 46937589 1 02/08-P 11/10-F
Bell/Strobe 1st Corridor 1B106 46937587 1 02/08-P 11/10-F Bell/Strobe 2nd Floor Elevator
Lobby 2B100 46937933 1 02/09-P 11/10-P
Bell/Strobe 2nd Floor Corridor by Room 2A112
46937932 1 02/09-P 11/10-P
Bell/Strobe 2nd Floor by Stair 2 46937608 1 02/09-P 11/10-P Bell/Strobe 2nd Floor Corridor by
Room 2C101 46937604 1 02/09-P 11/10-P
Bell/Strobe 2nd Floor Corridor by Room 2B113
46937603 1 02/09-P 11/10-P
Bell/Strobe 2nd Floor Corridor by Room 2B108
46937602 1 02/09-P 11/10-P
Bell/Strobe 2nd Floor Corridor by Room 2B107
46937601 1 02/09-P 11/10-P
Page of 22 45
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Bell/Strobe 2nd Floor Corridor by
Room 2A111 46937599 1 02/09-P 11/10-P
Bell/Strobe 2nd Floor Corridor by Room 2A106
46937598 1 02/09-P 11/10-P
Bell/Strobe 2nd Floor Corridor by Room 2A101
46937597 1 02/09-P 11/10-P
Bell/Strobe 2nd Floor Corridor by Room 2C116
46937606 1 02/09-P 11/10-P
Bell/Strobe 2nd Floor Corridor by Room 2C112
46937605 1 02/09-P 11/10-P
Bell/Strobe 2nd Floor Corridor by Stair 3
46937595 1 02/09-P 11/10-P
Bell/Strobe Attic 46937611 1 02/05-P 11/10-P Bell/Strobe Attic C Wing 46937955 1 02/09-P 11/10-P Bell/Strobe Attic 46937610 1 02/05-P 11/10-P Bell/Strobe Attic 46937609 1 02/05-P 11/10-P
Device Total: 51 Return to Executive Summary
Page of 23 45
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices.
Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-19 Table 14.4.3.2 (20)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Releasing Device 35 35 0 35 35
Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Releasing Device
Basement BC-102 Elevator Hat Relay
52281998 1 02/05-P 11/10-P
Releasing Device
Basement BC-102 Elevator Primary Recall
52281984 1 02/10-P 11/10-P
Releasing Device
Basement BC-102 Elevator Alternate Recall
52281985 1 02/10-P 11/10-P
Releasing Device
Basement Corridor By Room BB124
46937665 1 02/05-P 11/10-P
Releasing Device
Basement Corridor By Room BC100
52282001 1 02/05-P 11/08-P
The above device replaced ScanID 46937668:
Releasing Device
Basement Corridor By Room BC100
46937668 1 02/05-R
Releasing Device
Basement Corridor By Room BB100
52282000 1 02/05-P 11/08-P
The above device replaced ScanID 46937669:
Releasing Device
Basement Corridor By Room BB100
46937669 1 02/05-R
Releasing Device
Basement Corridor By Room BB108
52281996 1 02/10-P 11/08-P
The above device replaced ScanID 46937666:
Releasing Device
Basement Corridor By Room BB108
46937666 1 02/10-R
Releasing Device
Basement Corridor By Room BB124
46937664 1 02/05-P 11/08-P
Releasing Device
Basement Corridor By Room BB112
46937663 1 02/05-P 11/08-P
Releasing Device
Basement Corridor By Room BB112
46937662 1 02/05-P 11/08-P
Releasing Device
Basement Corridor By Room BB108
52281997 1 02/10-P 11/08-P
The above device replaced ScanID 46937667:
Releasing Device
Basement Corridor By Room BB108
46937667 1 02/10-R
Releasing Device
1st Floor By Room 1C109
52282012 1 02/08-P 11/10-P
Releasing Device
1st Floor Corridor By Room 1A100
52282008 1 02/10-P 11/10-P
Page of 24 45
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 The above device replaced ScanID 46937643:
Releasing Device
1st Floor Corridor By Room 1A100
46937643 1 02/10-R
Releasing Device
1st Corridor By Room 1B120
46937652 1 02/10-P 11/10-P
Releasing Device
1st Corridor By Room 1B120
46937651 1 02/10-P 11/10-P
Releasing Device
1st Corridor By Room 1B106
46937648 1 02/08-P 11/10-P
Releasing Device
1st Corridor By Room 1B106
46937647 1 02/08-P 11/10-P
Releasing Device
1st Floor Stair 2 Door Strike
46937639 1 02/08-P 11/10-P
Releasing Device
1st Corridor By Room 1C100
52282010 1 02/08-P 11/10-P
The above device replaced ScanID 46937650:
Releasing Device
1st Corridor By Room 1C100
46937650 1 02/08-R
Releasing Device
1st Corridor By Room 1C100
52282011 1 02/08-P 11/10-P
The above device replaced ScanID 46937649:
Releasing Device
1st Corridor By Room 1C100
46937649 1 02/08-R
Releasing Device
1st Corridor By Room 1B105
46937646 1 02/08-P 11/10-P
Releasing Device
1st Corridor By Room 1A111
46937644 1 02/08-P 11/10-P
Releasing Device
1st Corridor By Room 1A111
46937645 1 02/08-P 11/10-P
Releasing Device
1st By Room 1C113 46937939 1 02/10
Releasing Device
1st By Room 1C113 46937940 1 02/10
1st Floor By Room 1C108
46937529 1 02/10
1st Floor Stair 1 Door Strike
46937637 1 02/10
1st Floor Stair 1 Door Strike
46937638 1 02/10
2nd Floor Stair 1 Door Strike
46937640 1 02/09-P 11/10-P
Releasing Device
2nd Floor Stair 3 Door Strike
52282020 1 02/10-P 11/10-P
The above device replaced ScanID 46937642:
Releasing Device
2nd Floor Stair 3 Door Strike
46937642 1 02/10-R
Page of 25 45
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Releasing Device
2nd Floor Corridor By Room 2C100
52282021 1 02/09-P 11/10-P
The above device replaced ScanID 46937660:
Releasing Device
2nd Floor Corridor By Room 2C100
46937660 1 02/09-R
Releasing Device
2nd Floor Corridor By Room 2C100
52282022 1 02/09-P 11/10-P
The above device replaced ScanID 46937661:
Releasing Device
2nd Floor Corridor By Room 2C100
46937661 1 02/09-R
Releasing Device
2nd Floor Corridor By Room 2B107
46937658 1 02/09-P 11/10-P
Releasing Device
2nd Floor Corridor By Room 2B107
46937659 1 02/09-P 11/10-P
Releasing Device
2nd Floor Stair 2 Door Strike
46937641 1 02/09-P 11/10-P
Releasing Device
2nd Floor Corridor By Room 2B106
46937657 1 02/09-P 11/10-P
Releasing Device
2nd Floor Corridor By Room 2A112
46937656 1 02/09-P 11/10-P
Releasing Device
2nd Floor Corridor By Room 2A112
46937655 1 02/09-P 11/10-P
Releasing Device
2nd Floor Corridor By 2A100
46937653 1 02/09-P 11/10-P
Releasing Device
2nd Floor Corridor By 2A100
46937654 1 02/09-P 11/10-P
Device Total: 35 Return to Executive Summary
Page of 26 45
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices.
For periodic testing, verify the operation of the notification appliances. (NFPA 72-19 Table 14.4.3.2 (22)(2)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Speaker/Strobe 1 1 0 1 1
Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Speaker/Strobe Basement Corridor By
Room BC110 46937622 1 02/10-P 11/10-P
Page of 27 45
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices.
For periodic testing, verify that each appliance flashes. (NFPA 72-19 Table 14.4.3.2 (22)(3)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Strobe 5 5 0 5 5
Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Strobe Basement Room
BA101
46937634 1 02/05-P 11/10-P
Strobe 1st Floor Dining Room 1C117
52282009 1 02/08-P 11/10-P
Strobe 1st Floor Corridor By Room 1C101
46937585 1 02/10
Strobe 1st Floor Corridor By Room 1C101
46937590 1 02/10
Strobe 2nd Floor Room 2A111A
52282042 1 02/09-P 11/10-P
The above device replaced ScanID 46937635:
Strobe 2nd Floor Room 2A111A
46937635 1 02/09-R
Strobe 2nd Floor Dining Room By 2C118
46937633 1 02/10-P 11/10-P
Strobe Attic C wing 46937956 1 02/09-P 11/10-P
Device Total: 5 Return to Executive Summary
Page of 28 45
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 05 Annual test of fire alarm equipment for notifying off-site fire responders
Test all system functions and features in accordance with the equipment manufacturer's published instructions for correct operation in conformance with the applicable sections of Chapter 26. Except for DACT, actuate initiating device and verify receipt of the correct initiating device signal at the supervising station within 90 seconds. Upon completion of the test, restore the system to its functional operating condition. (NFPA 72-19 Table 14.4.3.2 (4)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Communicator 1 1 0 1 1
Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Communicator Basement BC-102 46937943 1 10/13-P 01/13-P 04/20-P 09/30-F 11/10-P
Page of 29 45
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 19
Annual test of automatic smoke-detection shutdown devices for air-handling equipment per NFPA 90A-2021
Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72- 19 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Duct Detector 24 24 0 24 24
Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Duct Detector Sub-Basement AHU 4
Supply 46937571 1 02/05-P 11/08-P
Duct Detector Sub-Basement AHU 4 Return
46937570 1 02/05-P 11/08-P
Duct Detector Sub-Basement AHU 5 Return
46937574 1 02/05-P 11/08-P
Duct Detector Sub-Basement AHU 5 Supply
46937573 1 02/05-P 11/08-P
Duct Detector Sub-Basement AHU 3 46937569 1 02/05-P 11/08-P Duct Detector Sub-Basement AHU 3 46937568 1 02/10-P 11/08-P Duct Detector Basement Corridor @
BA104
52281988 1 02/10-P 11/10-P
The above device replaced ScanID 46937566:
Duct Detector Basement Corridor @
BA104
46937566 1 02/10-R
Duct Detector Basement Corridor @
BA108
52281992 1 02/10-P 11/10-P
The above device replaced ScanID 46937567:
Duct Detector Basement Corridor @
BA108
46937567 1 02/10-R
Duct Detector Basement AHU 1 Return
46937563 1 02/03-P 11/08-P
Duct Detector Basement AHU 1 Supply
46937562 1 02/03-P 11/08-P
Duct Detector Basement AHU 2 Return
46937564 1 02/03-P 11/08-P
Duct Detector Basement AHU 2 Supply
46937565 1 02/03-P 11/08-P
Duct Detector 1st Floor Corridor by 1C111
52282016 1 02/08-P 11/10-P
The above device replaced ScanID 46937552:
Duct Detector 1st Floor Corridor by 1C111
46937552 1 02/08-R
Duct Detector 1st Floor Corridor by 1C111
52282017 1 02/08-P 11/10-P
The above device replaced ScanID 46937551:
Duct Detector 1st Floor Corridor by 1C111
46937551 1 02/08-R
Page of 30 45
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Duct Detector 1st Floor Corridor by
1B106A 46937554 1 02/08-P 11/10-P
Duct Detector 1st Floor Corridor by 1A109
46937550 1 02/08-P 11/10-P
Duct Detector 1st Floor Corridor by 1B106
46937553 1 02/08-P 11/10-P
Duct Detector 1st Floor 1B106A 46937555 1 02/08-P 11/10-P Duct Detector 2nd Floor Corridor @
2C112 52282035 1 02/09-P 11/10-P
Duct Detector 2nd Floor Corridor @ 2C112
52282034 1 02/09-P 11/10-P
The above device replaced ScanID 46937558:
Duct Detector 2nd Floor Corridor @ 2C112
46937558 1 02/09-R
Duct Detector 2nd Floor 2B112 46937561 1 02/09-P 11/10-P Duct Detector 2nd Floor Corridor @
2B107 46937559 1 02/09-P 11/10-P
Duct Detector 2nd Floor 2A106 46937560 1 02/10-P 11/10-P Duct Detector 2nd Floor Corridor @
2A110 52282043 1 02/09-P 11/10-P
The above device replaced ScanID 46937556:
Duct Detector 2nd Floor Corridor @ 2A110
46937556 1 02/09-R
Duct Detector 2nd Floor Corridor @ 2A110
46937557 1 02/10
Page of 31 45
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 19
Annual test of automatic smoke-detection shutdown devices for air-handling equipment per NFPA 90A-2021
Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-19 Table 14.4.3.2 (20)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Fan Shutdown 5 1 4 5 5
Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Fan Shutdown Sub-Basement AHU 5 52282028 1 02/05-P 11/08-P Fan Shutdown Basement 1C105A 52281977 1 02/03-F 11/10-F Fan Shutdown Basement AHU 2
Supply 52281971 1 02/03-F 11/10-F
Fan Shutdown Basement 1C105A 52281975 1 02/03-F 11/10-F Fan Shutdown Basement AHU 2
Return 52281973 1 02/03-F 11/10-F
Device Total: 5 Return to Executive Summary
Page of 32 45
Convergint Technologies - Central Texas Download Date: 12/07/2021
LS 02.01.34 EP 02 Protected master fire alarm control panel
Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-19 Table
14.4.3.2 (2)(1)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Control Panel 2 2 0 2 2
Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Control Panel Basement BC-102
Simplex FACP 4020
674EE41909 1 09/30-P 11/08-P
Control Panel Basement BC-112 46937946 2 10/13-F 02/03-P 04/20-P 09/30-P 11/08-P
Page of 33 45
Convergint Technologies - Central Texas Download Date: 12/07/2021
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2021 18/19.3.4
Verify the correct operation and identification of annunciators. If provided, verify the correct operation of annunciator under a fault condition. (NFPA 72-19 Table 14.4.3.2 (11)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Annunciator 2 2 0 2 2
Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Annunciator Basement Exit BB100 46937630 1 10/13-P 01/13-P 04/20-P 07/08-P 11/08-P Annunciator 1st Floor by 1B100 46937517 1 10/13-P 02/08-P 04/20-P 07/08-P 11/10-P
Page of 34 45
Convergint Technologies - Central Texas Download Date: 12/07/2021
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2021 18/19.3.4
With the batteries fully charged and connected to the charger, measure the voltage across the batteries with a voltmeter. Then, with the battery charger disconnected, load test the batteries following the manufacturer's recommendations. (NFPA 72-19 Table 14.4.3.2 (9)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Battery 8 8 0 8 8
Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Battery Basement BC-102
Simplex Right Battery 62947707 1 10/13-P 01/13-P 04/20-P 09/30-P 11/08-P
Battery Basement BC-102 Simplex Left Battery
46937944 1 10/13-P 01/13-P 04/20-P 09/30-P 11/08-P
Battery Basement BC-112 Main battery cabinet right
46937948 1 10/13-P 02/03-P 04/20-P 09/30-P 11/08-P
Battery Basement BC-112 Main battery cabinet left
46937947 2 10/13-P 02/03-P 04/20-P 09/30-P 11/08-P
Battery Basement BC-112 Nac 2 Left Battery
46937951 1 02/03-P 11/08-P
Battery Basement BC-112 Nac 2 Right Battery
46937952 1 02/03-P 11/08-P
Battery Basement BC-112 Nac 1 Right Battery
46937950 1 10/13-F 02/03-P 11/08-P
Battery Basement BC-112 Nac 1 Left Battery
46937949 1 10/13-F 02/03-P 11/08-P
Device Total: 8 Return to Executive Summary
Page of 35 45
Convergint Technologies - Central Texas Download Date: 12/07/2021
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2021 18/19.3.4
Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-19 Table 14.4.3.2 (20)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Locking Device 4 4 0 4 4
Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Locking Device Basement Exit by
Service Elevator Lobby 52282004 1 02/05-P 11/10-P
Locking Device Basement South Exit by BC110
52282003 1 02/10-P 11/10-P
Locking Device 1st Exit by 1B100 52282007 1 02/08-P 11/10-P Locking Device 1st Floor exit by 1B100 52282006 1 02/10-P 11/10-P
Device Total: 4 Return to Executive Summary
Page of 36 45
Convergint Technologies - Central Texas Download Date: 12/07/2021
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2021 18/19.3.4
Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-19 Table
14.4.3.2 (2)(1)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Power Supply 2 1 1 2 2
Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Power Supply Basement BC-112 46937957 1 10/13-F 02/03-P 11/08-P Power Supply Basement BC-112 46937958 1 10/13-F 02/03-F 11/10-F
Page of 37 45
Convergint Technologies - Central Texas Download Date: 12/07/2021
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2021 18/19.3.4
Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-19 Table 14.4.3.2 (20)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Remote Indicator 18 18 0 19 19
Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Remote Indicator Sub-Basement AHU 4
Supply 52282024 1 02/05-P 11/08-P
Remote Indicator Sub-Basement AHU 4 Return
52282023 1 02/05-P 11/08-P
Remote Indicator Sub-Basement AHU 5 Return
52282026 1 02/05-P 11/08-P
Remote Indicator Sub-Basement AHU 5 Supply
52282025 1 02/05-P 11/08-P
Remote Indicator Sub-Basement AHU 3 Return
52282031 1 02/05-P 11/08-P
Remote Indicator Sub-Basement AHU 3 Supply
52282032 1 02/05-P 11/08-P
Remote Indicator Basement AHU 2 Supply
52281972 1 02/03-P 11/10-P
Remote Indicator Basement by BA-104 52281989 1 02/10-P 11/10-P Remote Indicator Basement by BA-105 52281991 1 02/10-P 11/10-P Remote Indicator Basement 1C105A 52281978 1 02/03-P 11/08-P Remote Indicator Basement 1C105A 52281976 1 02/03-P 11/08-P Remote Indicator Basement AHU 2
Return 52281974 1 02/03-P 11/08-P
Remote Indicator 2nd Floor Corridor @ 2C112
52282037 1 02/09-P 11/10-P
Remote Indicator 2nd Floor Corridor @ 2C112
52282036 1 02/09-P 11/10-P
Remote Indicator 2nd Floor AHU 3 2B112 52282040 1 02/09-P 11/10-P Remote Indicator 2nd Floor AHU 3 by
2B114 52282041 1 02/09-P 11/10-P
Remote Indicator 2nd Floor Corridor @ 2A106
52282045 1 02/09-P 11/10-P
Remote Indicator 2nd Floor Corridor @ 2A110
52282044 1 02/09-P 11/10-P
Remote Indicator 2nd Floor service Elevator Shaft
52282038 1 02/09-P
Device Total: 19 Return to Executive Summary
Page of 38 45 Service Summary
Convergint Technologies - Central Texas Download Date: 12/07/2021
Service Summary Generated by: BuildingReports.com
Building: Waco VAMC Bldg.