This document is a request for quote from the Department of Veterans Affairs for fire alarm and sprinkler system maintenance services at the Central Texas Veterans Health Care System located in Temple, Texas. The solicitation is set aside for Service-Disabled Veteran Owned Small Businesses and interested vendors must be verified on the VIP vendor database. The contract will be awarded on a firm-fixed price basis for a one year base period plus four option years. Technical questions are due by December 6th and quotes are due as specified in block 8 of the SF-1449. The site visit date is also provided. The scope of work involves maintenance and repair of fire alarm and sprinkler systems at the facility in accordance with the statement of work.
View the file
Other files
Show all 39
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate
For
Temple VAMC Bldg. 221 1901 Veterans Memorial Dr
Temple, TX 76504
This inspection was performed in accordance with NFPA 101, EDITION 2021, LIFE SAFETY CODE and NFPA 72, EDITION 2019, FIRE ALARM SYSTEMS. Documentation complies with EC 02.03.05
EP 28.
The inspection/testing frequencies adhered to for this service have been performed in accordance with The Joint Commission/VHA Clarification Memorandum on EC & LS Standards effective January 31, 2021. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Annual Inspection Inspection Completion Date Apr 5, 2021
Building: Temple VAMC Bldg. 221 Company: Convergint Technologies - Central Texas Contact: Che Buval Contact: Troy Hague Title: Safety Officer Title: Service Specialist
Page of 1 50 Executive Summary
Convergint Technologies - Central Texas Download Date: 12/07/2021
Executive Summary Generated by: BuildingReports.com
Building Information Building: Temple VAMC Bldg. 221 Contact: Che Buval
Address: 1901 Veterans Memorial Dr Phone: 254-743-0133
Address: Fax:
City/State/Zip: Temple, TX 76504 Mobile:
Country: United States of America Email: Che.Buval@va.gov
Inspection Performed By Company: Convergint Technologies - Central Texas Inspector: Troy Hague
Address: 10535 Boyer Blvd Phone: 2543132867
Address: Suite 300 Fax:
City/State/Zip: Austin, Texas 78758 Mobile:
Country: United States Email: troy.hague@convergint.com
System Control Unit Manufacturer: Inspection Date: 03/30/2021 IDC Style:
Model Number: Install Date: 08/22/2018 SLC Style:
Software Version: Version Date: 12/31/1969 NAC Style:
Location: 1st main entry building A Current Protection:
Central Station Signal Verification Type: Mfg: Model #:
Test Time/Date: 3/30/21 8:57:12 AM Restore Time: Note:
Page of 2 50
Convergint Technologies - Central Texas Download Date: 12/07/2021
Inspection Completion Date: Apr 5, 2021 Building: Temple VAMC Bldg. 221 EC 02.03.05 EP 01 Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; and room temperature supervisory
Devices Tested This
Quarter Pass Fail Tested YTD
(2021) Untested YTD
(2021) Total
Quantity Air Pressure Switch 0 0 0 0 4 4
Power Loss 0 0 0 6 0 6
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches
Devices Tested This
Quarter Pass Fail Tested YTD
(2021) Untested YTD
(2021) Total
Quantity Tamper Switch 0 0 0 0 28 28
Waterflow Switch 0 0 0 0 20 20
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Devices Tested This
Quarter Pass Fail Tested YTD
(2021) Untested YTD
(2021) Total
Quantity Duct Detector 0 0 0 1 0 1
Heat Detector 0 0 0 6 0 6
Pull Station 0 0 0 23 0 23
Smoke Detector 0 0 0 77 0 77
EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices.
Devices Tested This
Quarter Pass Fail Tested YTD
(2021) Untested YTD
(2021) Total
Quantity Horn/Strobe 0 0 0 36 1 37
Releasing Device 0 0 0 4 0 4
Speaker/Strobe 0 0 0 70 0 70
Strobe 0 0 0 30 0 30
EC 02.03.05 EP 05 Annual test of fire alarm equipment for notifying off-site fire responders
Devices Tested This
Quarter Pass Fail Tested YTD
(2021) Untested YTD
(2021) Total
Quantity Communicator 0 0 0 2 0 2
EC 02.03.05 EP 19 Annual test of automatic smoke-detection shutdown devices for air-handling equipment per NFPA 90A-2021
Devices Tested This
Quarter Pass Fail Tested YTD
(2021) Untested YTD
(2021) Total
Quantity Duct Detector 0 0 0 1 0 1
Fan Shutdown 1 0 1 2 0 2
LS 02.01.34 EP 02 Protected master fire alarm control panel Tested This Tested YTD Untested YTD Total
Page of 3 50
Convergint Technologies - Central Texas Download Date: 12/07/2021
LS 02.01.34 EP 02 Protected master fire alarm control panel Devices Quarter Pass Fail (2021) (2021) Quantity Control Panel 0 0 0 2 0 2
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2021 18/19.3.4
Devices Tested This
Quarter Pass Fail Tested YTD
(2021) Untested YTD
(2021) Total
Quantity Annunciator 0 0 0 2 0 2
Battery 0 0 0 4 0 4
Remote Test Switch 0 0 0 1 0 1
Special Control 0 0 0 2 0 2
LS 02.01.50 EP 07 Annual - Elevators are fully equipped and protected
Devices Tested This
Quarter Pass Fail Tested YTD
(2021) Untested YTD
(2021) Total
Quantity Elevator 0 0 0 24 0 24
Total Device Count: 345
Page of 4 50
Convergint Technologies - Central Texas Download Date: 12/07/2021
Certification Company: Convergint Technologies - Central Texas Building: Temple VAMC Bldg. 221 Inspector: Troy Hague Contact: Che Buval
Signed: Mar 31, 2021
Troy Hague Certifications Certification Type Number EST3 Series Certification
Page of 5 50 Discrepancy Report
Convergint Technologies - Central Texas Download Date: 12/07/2021
Discrepancy Report Generated by: BuildingReports.com
Building: Temple VAMC Bldg. 221 Control Panel: 1 - The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty Items listed for Recall or Replacement/Upgrade
No items found during this inspection.
ScanID Location Problem Address Reference
EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices.
Releasing Device 49875355 1st building B outside of room 1B108 Failed Test 1 NFPA72 14.2.2.2.2
49875337 2nd 2 FL door holder relay by 2B108 Failed Test 1 NFPA72 14.2.2.2.2
49875382 2nd building A outside 2A108 multiuse Failed Test 1 NFPA72 14.2.2.2.2
EC 02.03.05 EP 19 Annual test of automatic smoke-detection shutdown devices for air-handling equipment per NFPA 90A-2021
Fan Shutdown 49875350 2nd 2 FL Mezzanine shutdown relay Failed Test 1 NFPA72 14.2.2.2.2
LS 02.01.50 EP 07 Annual - Elevators are fully equipped and protected
Elevator 52282297 1st Elevator AB Shunt Trip 1
Building: Temple VAMC Bldg. 221 Control Panel: 2 - The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty Items listed for Recall or Replacement/Upgrade
No items found during this inspection.
ScanID Location Problem Address Reference
EC 02.03.05 EP 19 Annual test of automatic smoke-detection shutdown devices for air-handling equipment per NFPA 90A-2021
Fan Shutdown 49875252 2nd Floor mezzanine HP-32/16 Failed Test 2 NFPA72 14.2.2.2.2
LS 02.01.34 EP 02 Protected master fire alarm control panel
Control Panel 41143106 1st building C main entry Active trouble signals javascript:openEditDevice('load-edit-f2-device','771929','2586150','49875355');
javascript:openEditDevice('load-edit-f2-device','771929','2586150','49875337');
javascript:openEditDevice('load-edit-f2-device','771929','2586150','49875382');
javascript:openEditDevice('load-edit-f2-device','771929','2586150','49875350');
javascript:openEditDevice('load-edit-f2-device','771929','2586150','52282297');
javascript:openEditDevice('load-edit-f2-device','771929','2586150','49875252');
javascript:openEditDevice('load-edit-f2-device','771929','2586150','41143106');
Page of 6 50 Discrepancy Report
Convergint Technologies - Central Texas Download Date: 12/07/2021
ScanID Location Problem Address Reference
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2021 18/19.3.4
Battery 41143108 1st Left Battery building C main entry Failed Test 2 NFPA72 Table
14.4.3.2 (9)
Remote Test Switch 49875251 Penthouse building C entry from stair Failed Test 2
Building: Temple VAMC Bldg. 221 Control Panel: 3 The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty Items listed for Recall or Replacement/Upgrade
No items found during this inspection.
ScanID Location Problem Address Reference
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2021 18/19.3.4
Battery 62947702 1st Right Battery building C main entry Failed Test 3 NFPA72 Table
14.4.3.2 (9) javascript:openEditDevice('load-edit-f2-device','771929','2586150','41143108');
javascript:openEditDevice('load-edit-f2-device','771929','2586150','49875251');
javascript:openEditDevice('load-edit-f2-device','771929','2586150','62947702');
Page of 7 50 Proposed Solutions Report
Convergint Technologies - Central Texas Download Date: 12/07/2021
Proposed Solutions Report Generated by: BuildingReports.com
Building: Temple VAMC Bldg. 221 Control Panel: 1 - The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.
ScanID Location Solution Model # Cost Fix
EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices.
Releasing Device 49875355 1st building B outside of room 1B108 Adjust T/M 49875337 2nd 2 FL door holder relay by 2B108 Adjust T/M 49875382 2nd building A outside 2A108 multiuse Adjust T/M
EC 02.03.05 EP 19 Annual test of automatic smoke-detection shutdown devices for air-handling equipment per
NFPA 90A-2021
Fan Shutdown 49875350 2nd 2 FL Mezzanine shutdown relay Troubleshoot T/M
LS 02.01.50 EP 07 Annual - Elevators are fully equipped and protected
Elevator 52282297 1st Elevator AB Shunt Trip T/M
Building: Temple VAMC Bldg. 221 Control Panel: 2 - The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.
ScanID Location Solution Model # Cost Fix
EC 02.03.05 EP 19 Annual test of automatic smoke-detection shutdown devices for air-handling equipment per
NFPA 90A-2021
Fan Shutdown 49875252 2nd Floor mezzanine HP-32/16 Relocate T/M
LS 02.01.34 EP 02 Protected master fire alarm control panel
Control Panel 41143106 1st building C main entry Repair noted deficiencies T/M
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2021 18/19.3.4
Battery 41143108 1st Left Battery building C main entry Replace DURDC 12-35j T/M
Remote Test Switch 49875251 Penthouse building C entry from stair Investigate T/M
Page of 8 50 Proposed Solutions Report
Convergint Technologies - Central Texas Download Date: 12/07/2021
Building: Temple VAMC Bldg. 221 Control Panel: 3 The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.
ScanID Location Solution Model # Cost Fix
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2021 18/19.3.4
Battery 62947702 1st Right Battery building C main entry Replace DURDC12-35J T/M
PO #: (none) T/M
Page of 9 50 Notes & Recommendations
Convergint Technologies - Central Texas Download Date: 12/07/2021
Notes & Recommendations Generated by: BuildingReports.com
Building: Temple VAMC Bldg. 221 The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
General Note 3/30/21 - Annual Fire Alarm Inspection complete.
*Panel 221 A/B is Red Tagged for the following noted deficiencies:
1. A/B Service Elevator failed to shunt trip when heat detector was activated.
2. Fire Doors by 2A108, 1B108 & 2B108 all failed to latch upon release. 3 sets of doors total.
3. Remote Rest Switch failed to operate duct detector Building A mezzanine.
4. Fan shut down did not function when existing duct detector was initiated.
*Panel 221 C/D is Red Tagged for the following noted deficiencies:
1. FACP Batteries failed load test.
2. Active Trouble signal Card 5, Expansion Power Supply A/C Failure.
3. Failed to report when batteries were disconnected.
4. Remote Rest Switch failed to operate duct detector Building C mezzanine.
5. Fan shut down did not function when existing duct detector was initiated.
**Both Panels were yellow tagged for the following noted deficiencies:
1. (18) OAHP Units having a CFM delivery of over 2,000 do not have duct smoke detectors installed on the supply side after the filters as required by NFPA 90A, 6.4.2.1 (1). The following is a list of the units referred to.
OAHP-22/16, OAHP-22/1415 1ST fl, OAHP-21/1415, OAHP 1/13, OAHP 12/1415, OAHP-11/1415, OAHP-12/16, OAHP 11/16, OAHP 21/16, OAHP-41/16, OAHP-42/16, OAHP-41/1415, OAHP-31/1415, OAHP-3/13, OAHP-32
/1415, OAHP-31/1415, OAHP-32/16, OAHP-31/16
RECOMMENDATIONS
**During the inspection I observed only 2 duct smoke detectors installed throughout Buildings A/B & C/D combined.
Further investigation revealed the 2 duct detectors were installed on Heat Pumps and none of the (18) OAHP units installed in the facility. We reviewed the volume of air exchanged by these units and found they deliver 4,000 CFM each which is well beyond the requirement for installation of duct smoke detectors on supply side of all units which deliver over 2,000 CFM as stated in NFPA 90A, 6.4.2.1(1), 2012-2018 versions. We recommend having duct detectors installed on all units listed to bring system in compliance with code.
NOTE:
Announcement issued in C/D was for location of devices activated in Building A/B. Location of device activated in C /D never announced. investjgate.
***Also, Red & Yellow Tagged for deficiencies from previous Inspections.
Building: Temple VAMC Bldg. 221 Control Panel: 1 - Note Device Type Location Comment ScanID
EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices.
2 Releasing Device 1st building B outside of room 1B108 Failed Test 49875355
Doors failed to latch when released. Contact entity responsible for Fire Door maintenance.
3 Releasing Device 2nd 2 FL door holder relay by 2B108 Failed Test 49875337
Doors failed to latch when released. Contact entity responsible for Fire Door maintenance.
4 Releasing Device 2nd building A outside 2A108 multiuse Failed Test 49875382
Doors failed to latch when released. Contact entity responsible for Fire Door maintenance.
LS 02.01.50 EP 07 Annual - Elevators are fully equipped and protected javascript:openEditDevice('load-edit-f2-device','771929','2586150','49875355');
javascript:openEditDevice('load-edit-f2-device','771929','2586150','49875337');
javascript:openEditDevice('load-edit-f2-device','771929','2586150','49875382');
Page of 10 50 Notes & Recommendations
Convergint Technologies - Central Texas Download Date: 12/07/2021
Note Device Type Location Comment ScanID 5 Elevator 1st Elevator AB Shunt Trip 52282297
3/30/21 JP-Shunt trip did not activate upon heat detector alarm in elevator machine room.
Building: Temple VAMC Bldg. 221 Control Panel: 2 - The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
Note Device Type Location Comment ScanID
LS 02.01.34 EP 02 Protected master fire alarm control panel 6 Control Panel 1st building C main entry Active trouble signals 41143106
Batteries failed load test, existing Red Tag from. previous inspection for AC Power failure Card 5 Expansion Power Supply.
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2021 18/19.3.4 7 Battery 1st Left Battery building C main entry Failed Test 41143108
Failed load test 3/30/21.
Building: Temple VAMC Bldg. 221 Control Panel: 3 The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
Note Device Type Location Comment ScanID
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2021 18/19.3.4 8 Battery 1st Right Battery building C main entry Failed Test 62947702
Failed load Test 3/30/21.
javascript:openEditDevice('load-edit-f2-device','771929','2586150','52282297');
javascript:openEditDevice('load-edit-f2-device','771929','2586150','41143106');
javascript:openEditDevice('load-edit-f2-device','771929','2586150','41143108');
javascript:openEditDevice('load-edit-f2-device','771929','2586150','62947702');
Page of 11 50 Inspection & Testing
Convergint Technologies - Central Texas Download Date: 12/07/2021
Inspection & Testing Generated by: BuildingReports.com
Building: Temple VAMC Bldg. 221 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.
Passed=P, Failed=F, Replaced=R
EC 02.03.05 EP 01
Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; and room temperature supervisory
Operate switch and verify receipt of signal is obtained where the required pressure is increased or decreased a maximum 10 psi from the required pressure level. (NFPA 72-19 Table 14.4.3.2 (17)(9b)) Devices Tested Q2/21 Pass Q2/21 Fail Q2/21 Tested YTD (2021) Total Quantity Air Pressure Switch 0 0 0 0 4
Device Type Location ScanID Address Q2/20 Q3/20 Q4/20 Q1/21 Q2/21 Air Pressure Switch
1st floor riser room bldg A attic system
49875124 1
Air Pressure Switch
1st floor riser room bldg B attic system
49875088 1
Air Pressure Switch
1st floor riser room bldg C attic system
49875019 1
Air Pressure Switch
1st floor riser room bldg D attic system
49875051 1
Device Total: 4 Return to Executive Summary
Page of 12 50
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 01
Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; and room temperature supervisory
Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-19 Table
14.4.3.2 (2)(1)) Devices Tested Q2/21 Pass Q2/21 Fail Q2/21 Tested YTD (2021) Total Quantity Power Loss 0 0 0 6 6
Device Type Location ScanID Address Q2/20 Q3/20 Q4/20 Q1/21 Q2/21 Power Loss 1st Elevator CD Power
Monitor 52282291 2 03/30-P
Power Loss 1st Elevator AB Power Monitor
52282296 1 03/30-P
Power Loss 2nd 2D116 Elevator D Power Monitor
52282308 2 03/30-P
Power Loss 2nd 2C116 Elevator C Power Monitor
52282313 1 03/30-P
Power Loss 2nd 2B116 Elevator B Power Monitor
52282298 1 03/30-P
Power Loss 2nd 2A116 Elev A Power Monitor
52282303 1 03/30-P
Device Total: 6 Return to Executive Summary
Page of 13 50
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches
Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-19 Table 14.4.3.2 (17)(10)(a)) Devices Tested Q2/21 Pass Q2/21 Fail Q2/21 Tested YTD (2021) Total Quantity Tamper Switch 0 0 0 0 28
Device Type Location ScanID Address Q2/20 Q3/20 Q4/20 Q1/21 Q2/21 Tamper Switch 1st floor riser room bldg A 2nd flr system 1 49875118 1
Tamper Switch 1st floor riser room bldg A 2nd flr system 2
49875117 1
Tamper Switch 1st floor riser room bldg A attic system
49875130 1
Tamper Switch 1st floor riser room bldg A bottom of backflow
49875142 1
Tamper Switch 1st floor riser room bldg A system 1
49875116 1
Tamper Switch 1st floor riser room bldg A system 2
49875115 1
Tamper Switch 1st floor riser room bldg A top of backflow
49875143 1
Tamper Switch 1st floor riser room bldg B first floor system east
49875079 1
Tamper Switch 1st floor riser room bldg B first floor system west
49875080 1
Tamper Switch 1st floor riser room bldg B second floor system eas
49875081 1
Tamper Switch 1st floor riser room bldg B second floor system wes
49875082 1
Tamper Switch 1st floor riser room bldg B attic system
49875094 1
Tamper Switch 1st floor riser room bldg B bottom of back flow
49875106 1
Tamper Switch 1st floor riser room bldg B top of back flow
49875107 1
Tamper Switch 1st floor riser room bldg C attic system
49875014 1
Tamper Switch 1st floor riser room bldg C bottom of backflow
49875033 1
Tamper Switch 1st floor riser room bldg C first floor
49875007 1
Page of 14 50
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q2/20 Q3/20 Q4/20 Q1/21 Q2/21 system 1 Wes
Tamper Switch 1st floor riser room bldg C first floor system 2 Eas
49875006 1
Tamper Switch 1st floor riser room bldg C second floor system 1 We
49875009 1
Tamper Switch 1st floor riser room bldg C second floor system 2 ea
49875008 1
Tamper Switch 1st floor riser room bldg C top of backflow
49875034 1
Tamper Switch 1st floor riser room bldg D attic system
49875057 1
Tamper Switch 1st floor riser room bldg D bottom of backflow
49875070 1
Tamper Switch 1st floor riser room bldg D first floor system 1 wes
49875043 1
Tamper Switch 1st floor riser room bldg D first floor system 2 eas
49875042 1
Tamper Switch 1st floor riser room bldg D second floor system 1 we
49875045 1
Tamper Switch 1st floor riser room bldg D second floor system 2 ea
49875044 1
Tamper Switch 1st floor riser room bldg D top of backflow
49875071 1
Device Total: 28 Return to Executive Summary
Page of 15 50
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches
Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size installed in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25-20. (NFPA 72-19 Table
14.4.3.2 (17)(11)) Devices Tested Q2/21 Pass Q2/21 Fail Q2/21 Tested YTD (2021) Total Quantity Waterflow Switch 0 0 0 0 20
Device Type Location ScanID Address Q2/20 Q3/20 Q4/20 Q1/21 Q2/21 Waterflow Switch 1st floor riser room bldg A attic system 49875125 1
Waterflow Switch 1st floor riser room bldg A first floor system 1
49875112 1
Waterflow Switch 1st floor riser room bldg A first floor system 2
49875111 1
Waterflow Switch 1st floor riser room bldg A second floor system 1
49875114 1
Waterflow Switch 1st floor riser room bldg A second floor system 2
49875113 1
Waterflow Switch 1st floor riser room bldg B attic system
49875089 1
Waterflow Switch 1st floor riser room bldg B first floor system east
49875075 1
Waterflow Switch 1st floor riser room bldg B first floor system west
49875076 1
Waterflow Switch 1st floor riser room bldg B second floor system east
49875077 1
Waterflow Switch 1st floor riser room bldg B second floor system west
49875078 1
Waterflow Switch 1st floor riser room bldg C attic system
49875020 1
Waterflow Switch 1st floor riser room bldg C first floor system 1 wes
49875003 1
Waterflow Switch 1st floor riser room bldg C first floor system 2 eas
49875002 1
Waterflow Switch 1st floor riser room bldg C second floor system 1 we
49875005 1
Waterflow Switch 1st floor riser room 49875004 1
Page of 16 50
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q2/20 Q3/20 Q4/20 Q1/21 Q2/21 bldg C second floor system 2 ea
Waterflow Switch 1st floor riser room bldg D attic system
49875052 1
Waterflow Switch 1st floor riser room bldg D first floor system 2 ea
49875038 1
Waterflow Switch 1st floor riser room bldg D first floor system 1 wes
49875039 1
Waterflow Switch 1st floor riser room bldg D second floor system 1 we
49875041 1
Waterflow Switch 1st floor riser room bldg D second floor system 2 ea
49875040 1
Device Total: 20 Return to Executive Summary
Page of 17 50
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72- 19 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q2/21 Pass Q2/21 Fail Q2/21 Tested YTD (2021) Total Quantity Duct Detector 0 0 0 1 1
Device Type Location ScanID Address Q2/20 Q3/20 Q4/20 Q1/21 Q2/21 Duct Detector 2nd Floor mezzanine 49875253 2 03/31-P
Device Total: 1 Return to Executive Summary
Page of 18 50
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions. Non-Restorable: Do not perform heat test. Test functionality mechanically and electrically.
(NFPA 72-19 Table 14.4.3.2 (17)(4)(a)) Devices Tested Q2/21 Pass Q2/21 Fail Q2/21 Tested YTD (2021) Total Quantity Heat Detector 0 0 0 6 6
Device Type Location ScanID Address Q2/20 Q3/20 Q4/20 Q1/21 Q2/21 Heat Detector 1st Elevator CD
Machine Room (from outside)
49875277 2 03/30-P
Heat Detector 1st Elevator AB Machine Room (from outside)
49875354 1 03/30-P
Heat Detector 2nd 2D116 Elevator D Machine Room
49875206 2 03/30-P
Heat Detector 2nd 2C116 Elevator C Machine Room
49875265 1 03/30-P
Heat Detector 2nd 2B116 Elevator B Machine Room
49875335 1 03/30-P
Heat Detector 2nd 2A116 Elev A Machine Room
49875373 1 03/30-P
Device Total: 6 Return to Executive Summary
Page of 19 50
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-19 Table 14.4.3.2 (17)(5)) Devices Tested Q2/21 Pass Q2/21 Fail Q2/21 Tested YTD (2021) Total Quantity Pull Station 0 0 0 23 23
Device Type Location ScanID Address Q2/20 Q3/20 Q4/20 Q1/21 Q2/21 Pull Station 1st building A across from 1A116 49875290 1 03/29-P
Pull Station 1st building A inside 1A122
49875293 1 03/29-P
Pull Station 1st Stairwell building A exit between A and B section
49875413 1 03/29-P
Pull Station 1st building C main entry
49875000 2 06/10-P 08/11-P 03/29-P
Pull Station 1st building A left of 1A135
49875410 1 03/29-P
Pull Station 1st building D by rm 1D114 Tele Health Clinic
49875192 2 03/29-P
Pull Station 1st building B outside 1B129
49875294 1 03/29-P
Pull Station 1st building D First Floor elev lobby
49875180 2 03/29-P
Pull Station 1st building D dining Pantry 1D126
49875173 2 03/29-P
Pull Station 1st building C stairwell exit between C-D
49875165 2 03/29-P
Pull Station 1st building D by 1D128 Pantry
49875170 2 03/29-P
Pull Station 1st building C across from room 1C135
49875164 2 03/29-P
Pull Station 1st building C outside room 1C116
49875151 2 03/29-P
Pull Station 1st building C room 1C122
49875267 2 03/29-P
Pull Station 1st building B main entry
49875307 1 03/29-P
Pull Station 1st main entry building A
49875281 1 05/18-P 08/12-P 11/06-P 03/29-P
Pull Station 1st building B outside room 1B116
49875315 1 03/26-P
Pull Station 1st building A inside 1A126
49875298 1 04/05 Removed
Pull Station 2nd building A across from 2A114
49875375 1 03/29-P
Page of 20 50
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q2/20 Q3/20 Q4/20 Q1/21 Q2/21 Pull Station 2nd building C outside room 2C114 49875254 2 03/29-P
Pull Station 2nd 2nd Floor building C stairwell across from 2C135
49875220 2 03/29-P
Pull Station 2nd 2nd Floor building D by 2D114
49875193 2 03/29-P
Pull Station 2nd building B across room 2B114
49875343 1 03/26-P
Pull Station 2nd building A outside stairway between A-B
49875401 1 03/26-P
Device Total: 23 Return to Executive Summary
Page of 21 50
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72- 19 Table 14.4.3.2 (17)(7)(a)) Devices Tested Q2/21 Pass Q2/21 Fail Q2/21 Tested YTD (2021) Total Quantity Smoke Detector 0 0 0 77 77
Device Type Location ScanID Address Q2/20 Q3/20 Q4/20 Q1/21 Q2/21 Smoke Detector 1st 1D101 Bldg D
Elevator Lobby 49875181 2 03/30-P
Smoke Detector 1st Elevator CD Machine Room (from outside)
49875276 2 03/30-P
Smoke Detector 1st building C main entry elevator lobby
41143109 2 03/30-P
Smoke Detector 1st 1B101 Bldg B Elevator Lobby
49875308 1 03/30-P
Smoke Detector 1st Elevator AB Machine Room (from outside)
49875353 1 03/30-P
Smoke Detector 1st Elevator Lobby by 1A131
49875405 1 03/30-P
Smoke Detector 1st 1A101 Bldg A Elevator Lobby
49875282 1 03/30-P
Smoke Detector 1st building B outside room 1B114
49875316 1 03/29-P
Smoke Detector 1st building A 1A125 49875418 1 03/29-P Smoke Detector 1st building A across from 1A128 49875414 1 03/29-P
Smoke Detector 1st building A outside of 1A116
49875289 1 03/29-P
Smoke Detector 1st building A right side of 1A110
49875428 1 03/29-P
Smoke Detector 1st By 1A107 49875423 1 03/29-P Smoke Detector 1st building A across from 1A119 49875420 1 03/29-P
Smoke Detector 1st building C outside room 1C110
49875153 2 03/29-P
Smoke Detector 1st building D by rm 1D110 PhysicalTherapy
49875189 2 03/29-P
Smoke Detector 1st building D dining Pantry 1D126
49875171 2 03/29-P
Smoke Detector 1st building C room 1C122
49875268 2 03/29-P
Smoke Detector 1st building C outside room 1C125
49875157 2 03/29-P
Smoke Detector 1st building A 1A122 Dining
49875417 1 03/29-P
Page of 22 50
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q2/20 Q3/20 Q4/20 Q1/21 Q2/21 Smoke Detector 1st building C outside room 1C116 49875152 2 03/29-P
Smoke Detector 1st building B outside 1B128
49875296 1 03/29-P
Smoke Detector 1st building D by rm 1D114 Tele Health Clinic
49875190 2 03/29-P
Smoke Detector 1st building D by rm 1D108
49875185 2 03/29-P
Smoke Detector 1st building D by rm 1D108
49875187 2 03/29-P
Smoke Detector 1st building D Nurses Station 1D119
49875177 2 03/29-P
Smoke Detector 1st building A outside 1B123
49875301 1 03/29-P
Smoke Detector 1st building D by 1D126 Pantry
49875176 2 03/29-P
Smoke Detector 1st building D by 1D128 Pantry
49875168 2 03/29-P
Smoke Detector 1st building C outside room 1C131
49875162 2 03/29-P
Smoke Detector 1st building C outside room 1C128
49875160 2 03/29-P
Smoke Detector 1st 1B122 Dining Room 49875300 1 03/29-P Smoke Detector 1st building C lobby
1C104 49875155 2 03/29-P
Smoke Detector 1st building B room 1B104
49875303 1 03/29-P
Smoke Detector 1st building C outside room 1C108
49875154 2 03/29-P
Smoke Detector 1st building C outside room 1C108
49875148 2 03/29-P
Smoke Detector 1st building B outside of room 1B107
49875309 1 03/29-P
Smoke Detector 1st building B outside room 1B110
49875317 1 03/26-P
Smoke Detector 2nd building B outside 2B107
52282280 1 03/31-P
The above device replaced ScanID 49875336:
Smoke Detector 2nd building B outside 2B108
49875336 1 03/31-R
Smoke Detector 2nd Bldg D Elevator Lobby 2D101
49875208 2 03/30-P
Smoke Detector 2nd 2D116 Elevator D Machine Room
49875205 2 03/30-P
Smoke Detector 2nd Elevator Lobby by 49875226 2 03/30-P
Page of 23 50
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q2/20 Q3/20 Q4/20 Q1/21 Q2/21 2c131
Smoke Detector 2nd FL Elevator C Lobby
49875239 2 03/30-P
Smoke Detector 2nd 2C116 Elevator C Machine Room
49875264 1 03/30-P
Smoke Detector 2nd Bldg B Elevator Lobby 2B101
49875333 1 03/30-P
Smoke Detector 2nd 2B116 Elevator B Machine Room
49875334 1 03/30-P
Smoke Detector 2nd 2A116 Elev A Machine Room
49875372 1 03/30-P
Smoke Detector 2nd 2A101 Elevator Lobby
49875371 1 03/30-P
Smoke Detector 2nd building C outside room 2C108
49875260 2 03/29-P
Smoke Detector 2nd 2nd Floor building C outside room 2C119
49875235 2 03/29-P
Smoke Detector 2nd 2nd Floor building C room 2C122
49875231 2 03/29-P
Smoke Detector 2nd 2nd Floor building C outside room 2C125
49875232 2 03/29-P
Smoke Detector 2nd 2nd Floor building D 2D122 dining
49875213 2 03/29-P
Smoke Detector 2nd 2A122 Dining Room
49875392 1 03/29-P
Smoke Detector 2nd building A across 2A125
49875391 1 03/29-P
Smoke Detector 2nd building C outside room 2C114
49875255 2 03/29-P
Smoke Detector 2nd building C outside room 2C108
49875259 2 03/29-P
Smoke Detector 2nd 2nd Floor building C doors by 2C108
49875263 1 03/29-P
Smoke Detector 2nd 2nd Floor building C outside of 2C128
49875229 2 03/29-P
Smoke Detector 2nd 2nd Floor building D near 2D128 Pantry
49875219 2 03/29-P
Smoke Detector 2nd 2nd Floor building D near 2D125
49875215 2 03/29-P
Smoke Detector 2nd 2nd Floor building D 2D119 Workstation
49875211 1 03/29-P
Smoke Detector 2nd 2nd Floor building D by 2D108
49875202 2 03/29-P
Smoke Detector 2nd 2nd Floor building D by 2D108
49875203 2 03/29-P
Smoke Detector 2nd 2nd Floor building 49875197 2 03/29-P
Page of 24 50
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q2/20 Q3/20 Q4/20 Q1/21 Q2/21 D by 2D108
Smoke Detector 2nd 2nd Floor building D by 2D114
49875194 2 03/29-P
Smoke Detector 2nd building B outside room 2B114
49875341 1 03/26-P
Smoke Detector 2nd building B outside 2B109
52282281 1 03/26-P
The above device replaced ScanID 49875340:
Smoke Detector 2nd building B outside room 2B108
49875340 1 03/26-R
Smoke Detector 2nd building B outside 2B119
49875329 1 03/26-P
Smoke Detector 2nd building B outside room 2B125
49875327 1 03/26-P
Smoke Detector 2nd building B room 2B126
52282279 1 03/26-P
The above device replaced ScanID 49875325:
Smoke Detector 2nd building B room 2B126
49875325 1 03/26-R
Smoke Detector 2nd building B outside room 2B128
49875322 1 03/26-P
Smoke Detector 2nd building A in front of 2A128
49875396 1 03/26-P
Smoke Detector 2nd building A outside 2A114
49875374 1 03/26-P
Smoke Detector 2nd building A outside 2A108 multiuse
49875377 1 03/26-P
Smoke Detector 2nd building A outside 2A108 multiuse
49875385 1 03/26-P
Smoke Detector 2nd building A outside 2A117
49875388 1 03/26-P
Smoke Detector 2nd building A across from 2A131 and elevator
49875404 1 04/05 Removed
Device Total: 77 Return to Executive Summary
Page of 25 50
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices.
For periodic testing, verify the operation of the notification appliances. (NFPA 72-19 Table 14.4.3.2 (22)(1)) Devices Tested Q2/21 Pass Q2/21 Fail Q2/21 Tested YTD (2021) Total Quantity Horn/Strobe 0 0 0 36 37
Device Type Location ScanID Address Q2/20 Q3/20 Q4/20 Q1/21 Q2/21 Horn/Strobe 1st building A inside room 1A110 49875286 1 03/31-P
Horn/Strobe 1st building C outside room 1C133A
49875247 2 03/31-P
Horn/Strobe 1st building B room 1B110
49875318 1 03/29-P
Horn/Strobe 1st building C room 1C122
49875266 2 03/29-P
Horn/Strobe 1st building B inside 1B128
49875348 1 03/29-P
Horn/Strobe 1st building C room 1C110
49875240 2 03/29-P
Horn/Strobe 1st building C room 1C110
49875270 2 03/29-P
Horn/Strobe 1st building C room 1C108
49875243 2 03/29-P
Horn/Strobe 1st building C lobby 1C104
49875146 2 03/29-P
Horn/Strobe 1st building C main entry
49875001 2 03/29-P
Horn/Strobe 1st building A outside room 1A133
49875412 1 03/29-P
Horn/Strobe 1st building C outside room 1C125
49875158 2 03/29-P
Horn/Strobe 1st building C across from room 1C135
49875163 2 03/29-P
Horn/Strobe 1st building C outside room 1C128
49875159 2 03/29-P
Horn/Strobe 1st building C outside room 1C116
49875150 2 03/29-P
Horn/Strobe 1st building C outside room 1C110
49875149 2 03/29-P
Horn/Strobe 1st building C room 1C122
49875269 2 03/29-P
Horn/Strobe 1st building C outside room 1C108
49875147 2 03/29-P
Horn/Strobe 1st building B room 1B108
49875320 1 03/26-P
Horn/Strobe 1st building A inside 2A133
49875399 1 03/26-P
Horn/Strobe 2nd building C room 49875246 2 03/31-P
Page of 26 50
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q2/20 Q3/20 Q4/20 Q1/21 Q2/21 2C108
Horn/Strobe 2nd building C room 2C108
49875245 2 03/31-P
Horn/Strobe 2nd building C room 2C133
49875223 2 03/31-P
Horn/Strobe 2nd building C room 2C128
49875228 2 03/29-P
Horn/Strobe 2nd building C room 2C110
49875258 2 03/29-P
Horn/Strobe 2nd building A in 2A128 49875352 1 03/29-P Horn/Strobe 2nd building B room
2B128 49875323 1 03/29-P
Horn/Strobe 2nd 2nd floor building C room 2C101
49875238 2 03/29-P
Horn/Strobe 2nd 2nd Floor-building C left of room 2C101
49875237 2 03/29-P
Horn/Strobe 2nd building B outside room 2B108
49875339 1 03/26-P
Horn/Strobe 2nd building B room 2B110
49875345 1 03/26-P
Horn/Strobe 2nd building B room 2B108
49875346 1 03/26-P
Horn/Strobe 2nd building B room 2B108
49875347 1 03/26-P
Horn/Strobe 2nd building A right of 2A128
49875395 1 03/26-P
Horn/Strobe 2nd building A room 2A110
49875383 1 03/26-P
Horn/Strobe 2nd building A outside 2A103
49875386 1 03/26-P
Horn/Strobe 2nd building C room 2C112
49875257 2
Device Total: 37 Return to Executive Summary
Page of 27 50
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices.
Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-19 Table 14.4.3.2 (20)) Devices Tested Q2/21 Pass Q2/21 Fail Q2/21 Tested YTD (2021) Total Quantity Releasing Device 0 0 0 4 4
Device Type Location ScanID Address Q2/20 Q3/20 Q4/20 Q1/21 Q2/21 Releasing Device
1st By 1A108 49875427 1 03/29-P
Releasing Device
1st building B outside of room 1B108
49875355 1 03/31-F
Releasing Device
2nd building A outside 2A108 multiuse
49875382 1 03/31-F
Releasing Device
2nd 2 FL door holder relay by 2B108
49875337 1 03/31-F
Page of 28 50
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices.
For periodic testing, verify the operation of the notification appliances. (NFPA 72-19 Table 14.4.3.2 (22)(2)) Devices Tested Q2/21 Pass Q2/21 Fail Q2/21 Tested YTD (2021) Total Quantity Speaker/Strobe 0 0 0 70 70
Device Type Location ScanID Address Q2/20 Q3/20 Q4/20 Q1/21 Q2/21 Speaker/Strobe 1st building A across from 1A125 49875419 1 03/29-P
Speaker/Strobe 1st building A right side of 1A116
49875288 1 03/29-P
Speaker/Strobe 1st building A right side of 1A110
49875429 1 03/29-P
Speaker/Strobe 1st building A outside room 1A108
49875424 1 03/29-P
Speaker/Strobe 1st building A inside room 1A108
49875426 1 03/29-P
Speaker/Strobe 1st building A in 1A120 49875425 1 03/29-P Speaker/Strobe 1st 1st Floor building D
1D128 Pantry 49875275 2 03/29-P
Speaker/Strobe 1st 1st Floor building C 1C128 Pantry
52282284 2 03/29-P
Speaker/Strobe 1st building D Living Room 1D120
49875174 2 03/29-P
Speaker/Strobe 1st building D dining Pantry 1D126
49875172 2 03/29-P
Speaker/Strobe 1st building D by 1D108 Shower Room
49875186 2 03/29-P
Speaker/Strobe 1st 1A128 Pantry 52282283 1 03/29-P Speaker/Strobe 1st building A outside
1A126 49875416 1 03/29-P
Speaker/Strobe 1st building A right from 1A128
49875415 1 03/29-P
Speaker/Strobe 1st building A left of 1A135
49875409 1 03/29-P
Speaker/Strobe 1st building B outside 1B129
49875295 1 03/29-P
Speaker/Strobe 1st building D by rm 1D114 Tele Health Clinic
49875191 2 03/29-P
Speaker/Strobe 1st building D by rm 1D110 PhysicalTherapy
49875188 2 03/29-P
Speaker/Strobe 1st building D by rm 1D108
49875184 2 03/29-P
Speaker/Strobe 1st building D First Floor elev lobby
49875182 2 03/29-P
Speaker/Strobe 1st building D by rm 1D103
49875178 2 03/29-P
Page of 29 50
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q2/20 Q3/20 Q4/20 Q1/21 Q2/21 Speaker/Strobe 1st building A outside
1B125 49875302 1 03/29-P
Speaker/Strobe 1st 1B120 Ceiling living room
52282282 1 03/29-P
The above device replaced ScanID 49875299:
Smoke Detector 1st building A inside 1B122
49875299 1 03/29-R
Speaker/Strobe 1st building D by 1D128 Pantry
49875169 2 03/29-P
Speaker/Strobe 1st building B main entry
49875306 1 03/29-P
Speaker/Strobe 1st building B outside of room 1B103
49875305 1 03/29-P
Speaker/Strobe 1st building B outside of room 1B108
49875310 1 03/29-P
Speaker/Strobe 1st building A outside 1A103
49875422 1 03/26-P
Speaker/Strobe 1st 1B126 Kitchen 49875297 1 03/26-P Speaker/Strobe 1st building B outside room 1B114 49875312 1 03/26-P
Speaker/Strobe 1st building B outside room 1B110
49875311 1 03/26-P
Speaker/Strobe 1st building A outside 2A135
49875397 1 03/26-P
Speaker/Strobe 1st main entry building A
49875283 1 03/26-P
Speaker/Strobe 2nd 2nd Floor Conference Room 2D108
49875201 2 03/29-P
Speaker/Strobe 2nd 2nd Floor building D Elev Lobby-near 2D101
49875207 2 03/29-P
Speaker/Strobe 2nd 2nd Floor building D 2D128 Pantry
49875217 2 03/29-P
Speaker/Strobe 2nd building A inside 2A120
49875393 1 03/29-P
Speaker/Strobe 2nd building A in 2A125 49875390 1 03/29-P Speaker/Strobe 2nd 2nd Floor building
C rom 2C120 49875234 2 03/29-P
Speaker/Strobe 2nd 2nd Floor building C room 2C122
49875230 2 03/29-P
Speaker/Strobe 2nd 2nd Floor building C outside room 2C125
49875233 2 03/29-P
Speaker/Strobe 2nd 2nd Floor building C left of 2C128
49875227 2 03/29-P
Speaker/Strobe 2nd 2nd Floor building 49875218 2 03/29-P
Page of 30 50
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q2/20 Q3/20 Q4/20 Q1/21 Q2/21 D near 2D128 Pantry
Speaker/Strobe 2nd 2nd Floor building D 2D126 Kitchen
49875214 2 03/29-P
Speaker/Strobe 2nd building C room 2C114
49875256 2 03/29-P
Speaker/Strobe 2nd building C outside room 2C108
49875261 2 03/29-P
Speaker/Strobe 2nd building C outside room 2C108
49875262 2 03/29-P
Speaker/Strobe 2nd 2nd Floor building C outside room 2C135
49875221 2 03/29-P
Speaker/Strobe 2nd 2nd Floor building D near 2D125
49875216 2 03/29-P
Speaker/Strobe 2nd 2nd Floor building D 2D120 Living Room
49875212 2 03/29-P
Speaker/Strobe 2nd 2nd Floor building D Elev Lobby-near 2D101
49875209 2 03/29-P
Speaker/Strobe 2nd 2nd Floor building D by 2D108
49875204 2 03/29-P
Speaker/Strobe 2nd 2nd Floor building D by 2D108
49875198 2 03/29-P
Speaker/Strobe 2nd 2nd Floor building D by 2D114
49875195 2 03/29-P
Speaker/Strobe 2nd building B outside room 2B114
49875342 1 03/26-P
Speaker/Strobe 2nd building B outside 2B108
49875338 1 03/26-P
Speaker/Strobe 2nd building B sitting room 2B101
49875331 1 03/26-P
Speaker/Strobe 2nd building B right of 2B103
49875332 1 03/26-P
Speaker/Strobe 2nd building B outside room 2B125
49875328 1 03/26-P
Speaker/Strobe 2nd building B room 2B122
49875326 1 03/26-P
Speaker/Strobe 2nd building B room 2B126
52282278 1 03/26-P
The above device replaced ScanID 49875324:
Speaker/Strobe 2nd building B room 2B126
49875324 1 03/26-R
Speaker/Strobe 2nd building B left of 2B128
49875321 1 03/26-P
Speaker/Strobe 2nd building A outside 2A126
49875394 1 03/26-P
Speaker/Strobe 2nd building A room 49875381 1 03/26-P
Page of 31 50
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q2/20 Q3/20 Q4/20 Q1/21 Q2/21 2A112
Speaker/Strobe 2nd building A outside room 2A108
49875378 1 03/26-P
Speaker/Strobe 2nd building A outside 2A108 multiuse
49875384 1 03/26-P
Speaker/Strobe 2nd building A outside 2A114
49875376 1 03/26-P
Speaker/Strobe 2nd building A room 2A108
49875379 1 03/26-P
Speaker/Strobe 2nd building A room 2A108
49875380 1 03/26-P
Speaker/Strobe 2nd building A inside 2A101 lobby
49875387 1 03/26-P
Device Total: 70 Return to Executive Summary
Page of 32 50
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices.
For periodic testing, verify that each appliance flashes. (NFPA 72-19 Table 14.4.3.2 (22)(3)) Devices Tested Q2/21 Pass Q2/21 Fail Q2/21 Tested YTD (2021) Total Quantity Strobe 0 0 0 30 30
Device Type Location ScanID Address Q2/20 Q3/20 Q4/20 Q1/21 Q2/21 Strobe 1st building B room
1B114 49875313 1 03/31-P
Strobe 1st building B room 1B112
49875314 1 03/29-P
Strobe 1st building B room 1B110
49875319 1 03/29-P
Strobe 1st building A room 1A131
49875406 1 03/29-P
Strobe 1st building A inside restroom 1A117
49875421 1 03/29-P
Strobe 1st building C restroom 1C133C
49875248 2 03/29-P
Strobe 1st building C room 1C114
49875241 2 03/29-P
Strobe 1st building C room 1C112
49875242 2 03/29-P
Strobe 1st building C room 1C131
49875167 2 03/29-P
Strobe 1st building C room 1C117
49875156 2 03/29-P
Strobe 1st building D restroom by Front Lobby
49875179 2 03/29-P
Strobe 1st building A across from 1A131
49875407 1 03/29-P
Strobe 1st building A outside room 1A133C
49875411 1 03/29-P
Strobe 1st building D by 1D126 Pantry
49875175 2 03/29-P
Strobe 1st building C room 1C135
49875166 2 03/29-P
Strobe 1st building C across from 1C131
49875161 2 03/29-P
Strobe 1st building B 1B117 49875304 1 03/29-P Strobe 1st building A room
1A135 49875408 1 03/26-P
Strobe 1st building A inside 2A135
49875400 1 03/26-P
Strobe 2nd building A room 2A131
49875398 1 03/31-P
Strobe 2nd building C room 2C133C
49875224 2 03/31-P
Page of 33 50
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q2/20 Q3/20 Q4/20 Q1/21 Q2/21 Strobe 2nd 2nd Floor building
D Restroom -near 2D101
49875210 2 03/29-P
Strobe 2nd building C Restroom 2C117
49875236 2 03/29-P
Strobe 2nd building C room 2c131
49875244 2 03/29-P
Strobe 2nd building A across from 2A131
49875403 1 03/29-P
Strobe 2nd 2nd Floor building C across from room 2c131
49875225 2 03/29-P
Strobe 2nd building C room 2C135
49875222 2 03/29-P
Strobe 2nd building B restroom 2B117
49875330 1 03/26-P
Strobe 2nd building A inside 2A133C
49875402 1 03/26-P
Strobe 2nd building A inside 2A117
49875389 1 03/26-P
Device Total: 30 Return to Executive Summary
Page of 34 50
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 05 Annual test of fire alarm equipment for notifying off-site fire responders
Test all system functions and features in accordance with the equipment manufacturer's published instructions for correct operation in conformance with the applicable sections of Chapter 26. Except for DACT, actuate initiating device and verify receipt of the correct initiating device signal at the supervising station within 90 seconds. Upon completion of the test, restore the system to its functional operating condition. (NFPA 72-19 Table 14.4.3.2 (4)) Devices Tested Q2/21 Pass Q2/21 Fail Q2/21 Tested YTD (2021) Total Quantity Communicator 0 0 0 2 2
Device Type Location ScanID Address Q2/20 Q3/20 Q4/20 Q1/21 Q2/21 Communicator 1st building C main entry 41143107 2 06/10-P 08/11-P 11/06-P 03/30-P
Communicator 1st main entry building A
49875279 1 05/18-P 08/11-P 11/06-P 03/30-P
Device Total: 2 Return to Executive Summary
Page of 35 50
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 19
Annual test of automatic smoke-detection shutdown devices for air-handling equipment per NFPA 90A-2021
Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72- 19 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q2/21 Pass Q2/21 Fail Q2/21 Tested YTD (2021) Total Quantity Duct Detector 0 0 0 1 1
Device Type Location ScanID Address Q2/20 Q3/20 Q4/20 Q1/21 Q2/21 Duct Detector 2nd Floor mezzanine 49875253 2 03/31-P
Page of 36 50
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 19
Annual test of automatic smoke-detection shutdown devices for air-handling equipment per NFPA 90A-2021
Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-19 Table 14.4.3.2 (20)) Devices Tested Q2/21 Pass Q2/21 Fail Q2/21 Tested YTD (2021) Total Quantity Fan Shutdown 1 0 1 2 2
Device Type Location ScanID Address Q2/20 Q3/20 Q4/20 Q1/21 Q2/21 Fan Shutdown 2nd 2 FL Mezzanine shutdown relay 49875350 1 04/05-F
Fan Shutdown 2nd Floor mezzanine
HP-32/16
49875252 2 03/31-F
Pa…