2020 Temple VA Hydrants.xlsx
XLSX spreadsheet 21 KB Posted
- Attached to
- J042--Fire Alarm and Suppression Systems Monitoring, Maintenance, Repairs and Installations Federal contract opportunity
- Solicitation number
- 36C25722Q0008
About this file
This document contains a fire hydrant flow test report for the VA Medical Center in Temple, Texas and a related solicitation for fire alarm and sprinkler system maintenance services at the same location. The flow test report details results for 39 fire hydrants on the medical center campus, identifying pipe diameters, pressure readings, and gallon flow for each. It notes missing gaskets and an underground flow issue affecting one hydrant. The solicitation seeks offers for fire alarm and sprinkler maintenance services for the Central Texas Veterans Health Care System in Temple under a firm-fixed price contract. The opportunity is set aside for Service-Disabled Veteran Owned Small Businesses and interested vendors must be verified on the Vendor Information Pages database. Technical questions are due by December 6, 2021 and offers must be submitted electronically by the deadline specified in the Standard Form 1449. The base year contract and four option years are available under solicitation number 36C25722Q0008.
View the file
Other files for this federal contract opportunity
Show all 39
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
| REPORT OF ANNUAL FIRE HYDRANT FLOW TEST | |||||
| CUSTOMER: | VA Medical Center | INSPECTOR NAME: | Silvester Harrison | ||
| BUILDING / LOCATION: | Temple | Business | 1st FP Services | ||
| STREET: | 1901 S 1st St | ADDRESS: | 12414 Laws Rd | ||
| CITY / ST / ZIP: | Temple, TX | Buda, Texas 78610 | |||
| ATTN: | Che Buval | PHONE#: | 512-312-9768 | Date: | 8/24/20 |
| PHONE # | 254-319-6866 | LICENSE #: | RME-I-2526918 |
| Hydrant# | Pipe diameter | Pitot Reading | Add Diffuser Correction | Pressure (psi) | Static Pressure | Residual | Coefficient | gpm fireflow | Flow at 20 psi | Time Flowing | Total Gallons |
| 1 | 2.5 | 62 | 0.9 | 62.9 | 89 | 80 | 0.9 | 1325 | 3980 | 1 | 1325 |
| 2 | 2.5 | 55 | 0.9 | 55.9 | 84 | 77 | 0.9 | 1249 | 4126 | 1 | 1249 |
| 3 | 2.5 | 60 | 0.9 | 60.9 | 80 | 76 | 0.9 | 1304 | 5627 | 1 | 1304 |
| 4 | 2.5 | 60 | 0.9 | 60.9 | 85 | 75 | 0.9 | 1304 | 3582 | 1 | 1304 |
| 5 | 2.5 | 56 | 0.9 | 56.9 | 90 | 75 | 0.9 | 1260 | 2895 | 1 | 1260 |
| 6 | 2.5 | 55 | 0.9 | 55.9 | 90 | 75 | 0.9 | 1249 | 2870 | 1 | 1249 |
| 7 | 2.5 | 60 | 0.9 | 60.9 | 85 | 70 | 0.9 | 1304 | 2878 | 1 | 1304 |
| 8 | 2.5 | 64 | 0.9 | 64.9 | 90 | 70 | 0.9 | 1346 | 2647 | 1 | 1346 |
| 9 | 2.5 | 62 | 0.9 | 62.9 | 85 | 68 | 0.9 | 1325 | 2734 | 1 | 1325 |
| 11 | 2.5 | 64 | 0.9 | 64.9 | 85 | 70 | 0.9 | 1346 | 2971 | 1 | 1346 |
| 12 | 2.5 | 55 | 0.9 | 55.9 | 85 | 70 | 0.9 | 1249 | 2757 | 1 | 1249 |
| 13 | 2.5 | 50 | 0.9 | 50.9 | 85 | 70 | 0.9 | 1192 | 2631 | 1 | 1192 |
| 14 | 2.5 | 45 | 0.9 | 45.9 | 85 | 70 | 0.9 | 1132 | 2498 | 1 | 1132 |
| 15 | |||||||||||
| 16 | 2.5 | 50 | 0.9 | 50.9 | 85 | 77 | 0.9 | 1192 | 3694 | 1 | 1192 |
| 17 | 2.5 | 55 | 0.9 | 55.9 | 86 | 76 | 0.9 | 1249 | 3460 | 1 | 1249 |
| 18 | 2.5 | 56 | 0.9 | 56.9 | 85 | 65 | 0.9 | 1260 | 2382 | 1 | 1260 |
| 19 | 2.5 | 52 | 0.9 | 52.9 | 85 | 75 | 0.9 | 1215 | 3339 | 1 | 1215 |
| 20 | 2.5 | 60 | 0.9 | 60.9 | 86 | 84 | 0.9 | 1304 | 8614 | 1 | 1304 |
| 21 | 2.5 | 60 | 0.9 | 60.9 | 80 | 78 | 0.9 | 1304 | 8182 | 1 | 1304 |
| 22 | 2.5 | 64 | 0.9 | 64.9 | 85 | 78 | 0.9 | 1346 | 4484 | 1 | 1346 |
| 23 | 2.5 | 50 | 0.9 | 50.9 | 80 | 73 | 0.9 | 1192 | 3803 | 1 | 1192 |
| 24 | 2.5 | 56 | 0.9 | 56.9 | 80 | 60 | 0.9 | 1260 | 2281 | 1 | 1260 |
| 25 | 2.5 | 50 | 0.9 | 50.9 | 85 | 69 | 0.9 | 1192 | 2541 | 1 | 1192 |
| 26 | 2.5 | 56 | 0.9 | 56.9 | 80 | 65 | 0.9 | 1260 | 2664 | 1 | 1260 |
| 27 | 2.5 | 64 | 0.9 | 64.9 | 80 | 70 | 0.9 | 1346 | 3542 | 1 | 1346 |
| 28 | 2.5 | 52 | 0.9 | 52.9 | 80 | 70 | 0.9 | 1215 | 3197 | 1 | 1215 |
| 29 | 2.5 | 50 | 0.9 | 50.9 | 90 | 67 | 0.9 | 1192 | 2174 | 1 | 1192 |
| 30 | 2.5 | 60 | 0.9 | 60.9 | 82 | 67 | 0.9 | 1304 | 2805 | 1 | 1304 |
| 31 | 2.5 | 50 | 0.9 | 50.9 | 85 | 66 | 0.9 | 1192 | 2316 | 1 | 1192 |
| 32 | 2.5 | 60 | 0.9 | 60.9 | 80 | 69 | 0.9 | 1304 | 3259 | 1 | 1304 |
| 33 | 2.5 | 40 | 0.9 | 40.9 | 84 | 74 | 0.9 | 1068 | 2911 | 1 | 1068 |
| 34 | 2.5 | 50 | 0.9 | 50.9 | 90 | 70 | 0.9 | 1192 | 2344 | 1 | 1192 |
| 35 | 2.5 | 64 | 0.9 | 64.9 | 82 | 68 | 0.9 | 1346 | 3006 | 1 | 1346 |
| 36 | 2.5 | 52 | 0.9 | 52.9 | 85 | 70 | 0.9 | 1215 | 2682 | 1 | 1215 |
| 37 | 2.5 | 58 | 0.9 | 58.9 | 80 | 78 | 0.9 | 1282 | 8046 | 1 | 1282 |
| 38 | 2.5 | 55 | 0.9 | 55.9 | 85 | 80 | 0.9 | 1249 | 4990 | 1 | 1249 |
| 39 | 2.5 | 53 | 0.9 | 60.9 | 85 | 80 | 0.9 | 1304 | 2805 | 1 | 1304 |
| 3208 | 2.5 | 56 | 0.9 | 56.9 | 82 | 75 | 0.9 | 1260 | 4092 | 1 | 1260 |
| 3341 | 2.5 | 66 | 0.9 | 66.9 | 90 | 80 | 0.9 | 1366 | 3908 | 1 | 1366 |
| 3312 | 2.5 | 68 | 0.9 | 68.9 | 80 | 75 | 0.9 | 1387 | 5306 | 1 | 1387 |
| 3211 | 2.5 | 66 | 0.9 | 66.9 | 75 | 70 | 0.9 | 1366 | 4988 | 1 | 1366 |
| Comments | |||||
| Hydrants Missing 1 2 1/2" Gaskets | #13 | #21 | #35 | #38 | 36(2) |
| Hydrants Missing 1 5" Gaskets | #7 | #27 | #3211 | #4 | |
| Hydrant #15- Unable to Flow(Ungerground Flow In Progress | |||||
| #28 Hard to Operate |