This document contains a fire hydrant flow test report for the VA Medical Center in Temple, Texas and a related solicitation for fire alarm and sprinkler system maintenance services at the same location. The flow test report details results for 39 fire hydrants on the medical center campus, identifying pipe diameters, pressure readings, and gallon flow for each. It notes missing gaskets and an underground flow issue affecting one hydrant. The solicitation seeks offers for fire alarm and sprinkler maintenance services for the Central Texas Veterans Health Care System in Temple under a firm-fixed price contract. The opportunity is set aside for Service-Disabled Veteran Owned Small Businesses and interested vendors must be verified on the Vendor Information Pages database. Technical questions are due by December 6, 2021 and offers must be submitted electronically by the deadline specified in the Standard Form 1449. The base year contract and four option years are available under solicitation number 36C25722Q0008.

View the file

Other files for this federal contract opportunity

Other files attached to J042--Fire Alarm and Suppression Systems Monitoring, Maintenance, Repairs and Installations, newest first.
File Type Posted
SF30 - 36C25722Q0008 0003.pdf PDF
36C25722Q0008 0003.docx DOCX document
REVISED SOW - FIRE Maint Mon SOW - 2021.pdf PDF
SF30 - 36C25722Q0008 0002.pdf PDF
36C25722Q0008 0002.docx DOCX document
2021-10-19_Temple-VAMC-Bldg--147_SprinklerScan.pdf PDF
2021-10-26_Temple-VAMC-Bldg--147_FireScan.pdf PDF
2021-04-05_Temple-VAMC-Bldg--221_FireScan.pdf PDF
2021-11-30_Temple-VAMC-Bldg--163_SprinklerScan.pdf PDF
Inspection Schedule - Temple_Waco.xlsx XLSX spreadsheet
2021-01-14_Waco-VAMC-Bldg--94_SprinklerScan.pdf PDF
2021-01-13_Waco-VAMC-Bldg--11_SprinklerScan.pdf PDF
2021-11-19_Waco-VAMC-Bldg--202_SprinklerScan.pdf PDF
36C25722Q0008 0001.docx DOCX document
2020-08-31_Temple-VAMC-Bldg--204_FireScan.pdf PDF
2021-02-24_Temple-VAMC-Bldg--204_SprinklerScan.pdf PDF
2021-02-05_Temple-VAMC-Bldg--221_SprinklerScan.pdf PDF
2021-10-19_Temple-VAMC-Bldg--146_SprinklerScan.pdf PDF
2021-03-04_Waco-VAMC-Bldg--94_FireScan.pdf PDF
2021-05-26_Waco-VAMC-Bldg--91_FireScan.pdf PDF
2021-11-18_Waco-VAMC-Bldg--7_SprinklerScan.pdf PDF
2021-02-01_Waco-VAMC-Bldg--11_FireScan.pdf PDF
2020 VA Waco Hydrant Report.xlsx XLSX spreadsheet
WACO - sign in sheet - VHACTXBuvalC_120321_100124.pdf PDF
2021-09-02_Temple-VAMC-Bldg--202_FireScan.pdf PDF
2021-10-19_Waco-VAMC-Bldg--4_SprinklerScan.pdf PDF
2021-05-19_Waco-VAMC-Bldg--91_SprinklerScan.pdf PDF
2021-11-10_Waco-VAMC-Bldg--7_FireScan.pdf PDF
TEMPLE - sign in sheet - VHACTXBuvalC_120321_100216.pdf PDF
QUESTION and ANSWERS.pdf PDF
SF30 - 36C25722Q0008 0001.pdf PDF
2021-10-26_Temple-VAMC-Bldg--146_FireScan.pdf PDF
2021-11-18_Temple-VAMC-Bldg--163_FireScan.pdf PDF
2021-09-30_Waco-VAMC-Bldg--4_FireScan.pdf PDF
Wage Determination Temple TX.pdf PDF
Limitations on Subcontracting Acknowledgment and Certification.pdf PDF
Wage Determination Waco TX.pdf PDF
36C25722Q0008_2.docx DOCX document
36C25722Q0008.pdf PDF
Show all 39

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

REPORT OF ANNUAL FIRE HYDRANT FLOW TEST
CUSTOMER:VA Medical CenterINSPECTOR NAME:Silvester Harrison
BUILDING / LOCATION:TempleBusiness1st FP Services
STREET:1901 S 1st StADDRESS:12414 Laws Rd
CITY / ST / ZIP:Temple, TXBuda, Texas 78610
ATTN:Che BuvalPHONE#:512-312-9768Date:8/24/20
PHONE #254-319-6866LICENSE #:RME-I-2526918
Hydrant#Pipe diameterPitot ReadingAdd Diffuser CorrectionPressure (psi)Static PressureResidualCoefficientgpm fireflowFlow at 20 psiTime FlowingTotal Gallons
12.5620.962.989800.91325398011325
22.5550.955.984770.91249412611249
32.5600.960.980760.91304562711304
42.5600.960.985750.91304358211304
52.5560.956.990750.91260289511260
62.5550.955.990750.91249287011249
72.5600.960.985700.91304287811304
82.5640.964.990700.91346264711346
92.5620.962.985680.91325273411325
112.5640.964.985700.91346297111346
122.5550.955.985700.91249275711249
132.5500.950.985700.91192263111192
142.5450.945.985700.91132249811132
15
162.5500.950.985770.91192369411192
172.5550.955.986760.91249346011249
182.5560.956.985650.91260238211260
192.5520.952.985750.91215333911215
202.5600.960.986840.91304861411304
212.5600.960.980780.91304818211304
222.5640.964.985780.91346448411346
232.5500.950.980730.91192380311192
242.5560.956.980600.91260228111260
252.5500.950.985690.91192254111192
262.5560.956.980650.91260266411260
272.5640.964.980700.91346354211346
282.5520.952.980700.91215319711215
292.5500.950.990670.91192217411192
302.5600.960.982670.91304280511304
312.5500.950.985660.91192231611192
322.5600.960.980690.91304325911304
332.5400.940.984740.91068291111068
342.5500.950.990700.91192234411192
352.5640.964.982680.91346300611346
362.5520.952.985700.91215268211215
372.5580.958.980780.91282804611282
382.5550.955.985800.91249499011249
392.5530.960.985800.91304280511304
32082.5560.956.982750.91260409211260
33412.5660.966.990800.91366390811366
33122.5680.968.980750.91387530611387
32112.5660.966.975700.91366498811366
Comments
Hydrants Missing 1 2 1/2" Gaskets#13#21#35#3836(2)
Hydrants Missing 1 5" Gaskets#7#27#3211#4
Hydrant #15- Unable to Flow(Ungerground Flow In Progress
#28 Hard to Operate