2021-10-26_Temple-VAMC-Bldg--147_FireScan.pdf

PDF 105 KB Posted

Attached to
J042--Fire Alarm and Suppression Systems Monitoring, Maintenance, Repairs and Installations
Solicitation number
36C25722Q0008
Issued by

About this file

This solicitation requests quotes for fire alarm and suppression systems monitoring, maintenance, repairs, and installations at the Central Texas Veterans Health Care System in Temple, Texas. The Department of Veterans Affairs seeks to award a firm-fixed price contract to a verified Service-Disabled Veteran Owned Small Business for a base year plus four option years. Technical questions must be submitted by December 6, 2021 and quotes are due by the date and time specified in block 8 of the SF-1449. Interested vendors must be registered in the System for Award Management and listed as verified on the Vendor Information Pages database to be eligible for award under the Veterans First Contracting Program.

View the file

Other files

File Type Posted
36C25722Q0008 0003.docx DOCX document
SF30 - 36C25722Q0008 0003.pdf PDF
SF30 - 36C25722Q0008 0002.pdf PDF
36C25722Q0008 0002.docx DOCX document
REVISED SOW - FIRE Maint Mon SOW - 2021.pdf PDF
36C25722Q0008 0001.docx DOCX document
2021-11-19_Waco-VAMC-Bldg--202_SprinklerScan.pdf PDF
2021-02-24_Temple-VAMC-Bldg--204_SprinklerScan.pdf PDF
2020-08-31_Temple-VAMC-Bldg--204_FireScan.pdf PDF
2021-10-19_Temple-VAMC-Bldg--146_SprinklerScan.pdf PDF
WACO - sign in sheet - VHACTXBuvalC_120321_100124.pdf PDF
Inspection Schedule - Temple_Waco.xlsx XLSX spreadsheet
2021-10-26_Temple-VAMC-Bldg--146_FireScan.pdf PDF
2021-02-01_Waco-VAMC-Bldg--11_FireScan.pdf PDF
2021-05-26_Waco-VAMC-Bldg--91_FireScan.pdf PDF
2021-11-18_Waco-VAMC-Bldg--7_SprinklerScan.pdf PDF
2021-01-14_Waco-VAMC-Bldg--94_SprinklerScan.pdf PDF
2021-10-19_Temple-VAMC-Bldg--147_SprinklerScan.pdf PDF
2021-01-13_Waco-VAMC-Bldg--11_SprinklerScan.pdf PDF
2021-04-05_Temple-VAMC-Bldg--221_FireScan.pdf PDF
2021-02-05_Temple-VAMC-Bldg--221_SprinklerScan.pdf PDF
2021-03-04_Waco-VAMC-Bldg--94_FireScan.pdf PDF
2021-11-30_Temple-VAMC-Bldg--163_SprinklerScan.pdf PDF
2021-11-18_Temple-VAMC-Bldg--163_FireScan.pdf PDF
2021-09-30_Waco-VAMC-Bldg--4_FireScan.pdf PDF
2020 VA Waco Hydrant Report.xlsx XLSX spreadsheet
2020 Temple VA Hydrants.xlsx XLSX spreadsheet
SF30 - 36C25722Q0008 0001.pdf PDF
2021-09-02_Temple-VAMC-Bldg--202_FireScan.pdf PDF
2021-05-19_Waco-VAMC-Bldg--91_SprinklerScan.pdf PDF
2021-11-10_Waco-VAMC-Bldg--7_FireScan.pdf PDF
2021-10-19_Waco-VAMC-Bldg--4_SprinklerScan.pdf PDF
QUESTION and ANSWERS.pdf PDF
TEMPLE - sign in sheet - VHACTXBuvalC_120321_100216.pdf PDF
Wage Determination Waco TX.pdf PDF
36C25722Q0008.pdf PDF
Limitations on Subcontracting Acknowledgment and Certification.pdf PDF
Wage Determination Temple TX.pdf PDF
36C25722Q0008_2.docx DOCX document
Show all 39

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate

For

Temple VAMC Bldg. 147 1901 Veterans Memorial Dr

Temple, TX 76504

This inspection was performed in accordance with NFPA 101, EDITION 2021, LIFE SAFETY CODE and NFPA 72, EDITION 2019, FIRE ALARM SYSTEMS. Documentation complies with EC 02.03.05

EP 28.

The inspection/testing frequencies adhered to for this service have been performed in accordance with The Joint Commission/VHA Clarification Memorandum on EC & LS Standards effective January 31, 2021. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Annual Inspection Inspection Completion Date Oct 26, 2021

Building: Temple VAMC Bldg. 147 Company: Convergint Technologies - Central Texas Contact: Che Buval Contact: Jessy Martin Title: Safety Officer Title: Service Specialist

Page of 1 22 Executive Summary

Convergint Technologies - Central Texas Download Date: 12/07/2021

Executive Summary Generated by: BuildingReports.com

Building Information Building: Temple VAMC Bldg. 147 Contact: Che Buval

Address: 1901 Veterans Memorial Dr Phone: 254-743-0133

Address: Fax:

City/State/Zip: Temple, TX 76504 Mobile:

Country: United States of America Email: Che.Buval@va.gov

Inspection Performed By Company: Convergint Technologies - Central Texas Inspector: Jessy Martin

Address: 10535 Boyer Blvd Phone: 5034626730

Address: Suite 300 Fax:

City/State/Zip: Austin, Texas 78758 Mobile: 5034626730

Country: United States Email: jessy.martin@convergint.com

System Control Unit Manufacturer: SimplexGrinnell Inspection Date: 10/26/2021 IDC Style:

Model Number: 4100es Install Date: 08/22/2018 SLC Style:

Software Version: Version Date: 08/22/2018 NAC Style:

Location: 1st Electrical Rm E133 Current Protection:

Central Station Signal Verification Type: Mfg: Model #:

Test Time/Date: 10/26/21 11:17:34 AM Restore Time: Note:

Page of 2 22

Convergint Technologies - Central Texas Download Date: 12/07/2021

Inspection Completion Date: Oct 26, 2021 Building: Temple VAMC Bldg. 147 EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches

Devices Tested This

Quarter Pass Fail Tested YTD

(2021) Untested YTD

(2021) Total

Quantity Tamper Switch 0 0 0 0 2 2

Waterflow Switch 0 0 0 0 1 1

EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors

Devices Tested This

Quarter Pass Fail Tested YTD

(2021) Untested YTD

(2021) Total

Quantity Duct Detector 2 2 0 2 0 2

Pull Station 6 6 0 6 0 6

Smoke Detector 5 5 0 5 0 5

EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices.

Devices Tested This

Quarter Pass Fail Tested YTD

(2021) Untested YTD

(2021) Total

Quantity Horn/Strobe 18 18 0 18 0 18

Strobe 20 20 0 20 0 20

EC 02.03.05 EP 05 Annual test of fire alarm equipment for notifying off-site fire responders

Devices Tested This

Quarter Pass Fail Tested YTD

(2021) Untested YTD

(2021) Total

Quantity Communicator 1 1 0 1 0 1

EC 02.03.05 EP 19 Annual test of automatic smoke-detection shutdown devices for air-handling equipment per NFPA 90A-2021

Devices Tested This

Quarter Pass Fail Tested YTD

(2021) Untested YTD

(2021) Total

Quantity Duct Detector 2 2 0 2 0 2

Fan Shutdown 2 2 0 2 0 2

LS 02.01.34 EP 02 Protected master fire alarm control panel

Devices Tested This

Quarter Pass Fail Tested YTD

(2021) Untested YTD

(2021) Total

Quantity Control Panel 1 1 0 1 0 1

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2021 18/19.3.4

Devices Tested This

Quarter Pass Fail Tested YTD

(2021) Untested YTD

(2021) Total

Quantity Annunciator 1 1 0 1 0 1

Battery 2 2 0 2 0 2

Total Device Count: 61

Page of 3 22

Convergint Technologies - Central Texas Download Date: 12/07/2021

Certification Company: Convergint Technologies - Central Texas Building: Temple VAMC Bldg. 147 Inspector: Jessy Martin Contact: Che Buval

Signed: Oct 26, 2021 Signed: Oct 26, 2021

Jessy Martin Certifications Certification Type Number NICET Fire Alarm Systems Level II 152267

Texas State Certification - Fire Alarm Systems 2688841

Page of 4 22 Notes & Recommendations

Convergint Technologies - Central Texas Download Date: 12/07/2021

Notes & Recommendations Generated by: BuildingReports.com

Building: Temple VAMC Bldg. 147 The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.

General Note 10/26/2021 - JCM- Annual Fire Alarm Inspection & Testing Complete - No new deficiencies to report. Systems is

NORMAL before & after testing.

Panel is Red Tagged & Yellow Tagged from previous inspections for deficiencies noted below:

**1. Changed Yellow Tag to Red Tag from 5-2018 for defective display LCD on FACP & Annunciator. FACP Display & Annunciator have deteriorated and are no longer legible to the user.

2. A/V's not synced. Need to add a sync module to NAC circuit that is out of sync.

Page of 5 22 Inspection & Testing

Convergint Technologies - Central Texas Download Date: 12/07/2021

Inspection & Testing Generated by: BuildingReports.com

Building: Temple VAMC Bldg. 147 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.

Passed=P, Failed=F, Replaced=R

EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches

Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-19 Table 14.4.3.2 (17)(10)(a)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Tamper Switch 0 0 0 0 2

Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Tamper Switch bottom tamper riser stair well 41136893 1

Tamper Switch top tamper riser stairwell

41136894 1-w214

Device Total: 2 Return to Executive Summary

Page of 6 22

Convergint Technologies - Central Texas Download Date: 12/07/2021

EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches

Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size installed in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25-20. (NFPA 72-19 Table

14.4.3.2 (17)(11)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Waterflow Switch 0 0 0 0 1

Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Waterflow Switch Mezzanine Stairwell

Riser 41136902 1

Device Total: 1 Return to Executive Summary

Page of 7 22

Convergint Technologies - Central Texas Download Date: 12/07/2021

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors

Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72- 19 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Duct Detector 2 2 0 2 2

Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Duct Detector Attic East end AHU 1 41136911 1-m1 13 03/17-P 10/26-P Duct Detector Attic East end AHU 1 41136910 1-m1 12 03/17-P 10/26-P

Page of 8 22

Convergint Technologies - Central Texas Download Date: 12/07/2021

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors

Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-19 Table 14.4.3.2 (17)(5)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Pull Station 6 6 0 6 6

Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Pull Station 1st 1st copy rm E117 41136949 1-m1 6 03/17-P 09/01-P 10/26-P Pull Station 1st exit in rm w228 41136921 1-m1 10 03/17-P 10/26-P Pull Station 1st exit stairs by riser 41136914 1-m1 11 03/17-P 10/26-P Pull Station 1st entrance by w102 41136945 1-m1 9 03/17-P 10/26-P Pull Station 1st entrance by w102 41136933 1-m1 08 03/17-P 10/26-P Pull Station 1st exit corridor by e123 41136990 1-m1 7 11/05-P 03/17-P 05/04-P 10/26-P

Device Total: 6 Return to Executive Summary

Page of 9 22

Convergint Technologies - Central Texas Download Date: 12/07/2021

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors

Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72- 19 Table 14.4.3.2 (17)(7)(a)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Smoke Detector 5 5 0 5 5

Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Smoke Detector 1st Comms Rm E134 41136995 1-m1 2 03/17-P 10/26-P Smoke Detector 1st Comms Rm W225 41136994 1-m1 5 03/17-P 10/26-P Smoke Detector 1st electrical Rm w226 41136924 1-m1 4 03/17-P 10/26-P Smoke Detector 1st Mech Rm E106 41136993 1-m1 3 03/17-P 10/26-P Smoke Detector 1st electrical Rm e133 above FACP 41136980 1-m1 1 03/17-P 09/01-P 10/26-P

Device Total: 5 Return to Executive Summary

Page of 10 22

Convergint Technologies - Central Texas Download Date: 12/07/2021

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices.

For periodic testing, verify the operation of the notification appliances. (NFPA 72-19 Table 14.4.3.2 (22)(1)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Horn/Strobe 18 18 0 18 18

Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Horn/Strobe 1st Corr by W236 41136927 1 03/17-P 10/26-P Horn/Strobe 1st Corr by reception 41136937 1 03/17-P 10/26-P Horn/Strobe 1st Corr by W211 52282230 1 03/17-P 10/26-P The above device replaced ScanID 41136918:

Horn/Strobe 1st Corr by W211 41136918 1 03/17-R Horn/Strobe 1st Conference Rm

E135 41136943 1 03/17-P 10/26-P

Horn/Strobe 1st Corr by W202 41136930 1 03/17-P 10/26-P Horn/Strobe 1st lounge w237 41136928 1 03/17-P 10/26-P Horn/Strobe 1st Corr by W229 41136925 1 03/17-P 10/26-P Horn/Strobe 1st Corr by W207 41136923 1 03/17-P 10/26-P Horn/Strobe 1st Corr by W227 41136919 1 03/17-P 10/26-P Horn/Strobe 1st Corr by W215 41136915 1 03/17-P 10/26-P Horn/Strobe 1st Corr by bathroom 41136941 1 03/17-P 10/26-P Horn/Strobe 1st Corr by by e112 41136942 1 03/17-P 10/26-P Horn/Strobe 1st Lounge E137 41136948 1 03/17-P 10/26-P Horn/Strobe 1st W Corr by restroom 41136946 1 03/17-P 10/26-P Horn/Strobe 1st Corr by e116 41136944 1 03/17-P 10/26-P Horn/Strobe 1st Corr by E132 41136985 1 03/17-P 10/26-P Horn/Strobe 1st Corr by E121 41136986 1 03/17-P 10/26-P Horn/Strobe 1st Corr by E123 41136989 1 03/17-P 10/26-P

Device Total: 18 Return to Executive Summary

Page of 11 22

Convergint Technologies - Central Texas Download Date: 12/07/2021

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices.

For periodic testing, verify that each appliance flashes. (NFPA 72-19 Table 14.4.3.2 (22)(3)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Strobe 20 20 0 20 20

Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Strobe 1st Bathroom W239 41136929 1 03/17-P 10/26-P Strobe 1st waiting area 41136934 1 03/17-P 10/26-P Strobe 1st Office Reception

E140 52282231 1 03/17-P 10/26-P

The above device replaced ScanID 41136931:

Strobe 1st Office Reception Closet

41136931 1 03/17-R

Strobe 1st Rm E102 House keeping

41136996 1 03/17-P 10/26-P

Strobe 1st Rm E121 41136992 1 03/17-P 10/26-P Strobe 1st waiting area 41136935 1 03/17-P 10/26-P Strobe 1st Office Reception 41136932 1 03/17-P 10/26-P Strobe 1st Rm W234 41136926 1 03/17-P 10/26-P Strobe 1st W223 41136922 1 03/17-P 10/26-P Strobe 1st Group Room W220 41136917 1 03/17-P 10/26-P Strobe 1st W228 41136920 1 03/17-P 10/26-P Strobe 1st Restroom W212 41136916 1 03/17-P 10/26-P Strobe 1st mens room E109 41136939 1 03/17-P 10/26-P Strobe 1st womens room E110 41136940 1 03/17-P 10/26-P Strobe 1st waiting area 41136936 1 03/17-P 10/26-P Strobe 1st Rm E138 41136947 1 03/17-P 10/26-P Strobe 1st break room e118 41136984 1 03/17-P 10/26-P Strobe 1st Bathroom E120 41136991 1 03/17-P 10/26-P Strobe 1st Rm 126 41136987 1 03/17-P 10/26-P Strobe 1st Rm E123 41136988 1 03/17-P 10/26-P Strobe 1st restroom e138 411336947 1 03/17

Removed

Device Total: 20 Return to Executive Summary

Page of 12 22

Convergint Technologies - Central Texas Download Date: 12/07/2021

EC 02.03.05 EP 05 Annual test of fire alarm equipment for notifying off-site fire responders

Test all system functions and features in accordance with the equipment manufacturer's published instructions for correct operation in conformance with the applicable sections of Chapter 26. Except for DACT, actuate initiating device and verify receipt of the correct initiating device signal at the supervising station within 90 seconds. Upon completion of the test, restore the system to its functional operating condition. (NFPA 72-19 Table 14.4.3.2 (4)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Communicator 1 1 0 1 1

Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Communicator 1st Electrical Rm E133 41136982 1-m1 3 11/05-P 03/17-P 05/04-P 09/01-P 10/26-P

Page of 13 22

Convergint Technologies - Central Texas Download Date: 12/07/2021

EC 02.03.05 EP 19

Annual test of automatic smoke-detection shutdown devices for air-handling equipment per NFPA 90A-2021

Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72- 19 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Duct Detector 2 2 0 2 2

Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Duct Detector Attic East end AHU 1 41136911 1-m1 13 03/17-P 10/26-P Duct Detector Attic East end AHU 1 41136910 1-m1 12 03/17-P 10/26-P

Page of 14 22

Convergint Technologies - Central Texas Download Date: 12/07/2021

EC 02.03.05 EP 19

Annual test of automatic smoke-detection shutdown devices for air-handling equipment per NFPA 90A-2021

Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-19 Table 14.4.3.2 (20)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Fan Shutdown 2 2 0 2 2

Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Fan Shutdown Attic East end AHU 1 41136913 1 03/17-P 10/26-P Fan Shutdown Attic East end AHU 1 41136912 1 03/17-P 10/26-P

Page of 15 22

Convergint Technologies - Central Texas Download Date: 12/07/2021

LS 02.01.34 EP 02 Protected master fire alarm control panel

Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-19 Table

14.4.3.2 (2)(1)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Control Panel 1 1 0 1 1

Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Control Panel 1st Electrical Rm E133 41136981 1 11/05-F 03/17-F 05/04-P 09/01-P 10/26-P

Page of 16 22

Convergint Technologies - Central Texas Download Date: 12/07/2021

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2021 18/19.3.4

Verify the correct operation and identification of annunciators. If provided, verify the correct operation of annunciator under a fault condition. (NFPA 72-19 Table 14.4.3.2 (11)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Annunciator 1 1 0 1 1

Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Annunciator 1st Corr by Reception 41136938 1 03/17-P 05/04-P 10/26-P

Page of 17 22

Convergint Technologies - Central Texas Download Date: 12/07/2021

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2021 18/19.3.4

With the batteries fully charged and connected to the charger, measure the voltage across the batteries with a voltmeter. Then, with the battery charger disconnected, load test the batteries following the manufacturer's recommendations. (NFPA 72-19 Table 14.4.3.2 (9)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Battery 2 2 0 2 2

Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Battery 1st Electrical Rm E133

Right Battery 62947708 1 11/05-P 03/17-P 05/04-P 09/01-P 10/26-P

Battery 1st Electrical Rm E133 Left Battery

41136983 1 11/05-P 03/17-P 05/04-P 09/01-P 10/26-P

Page of 18 22 Service Summary

Convergint Technologies - Central Texas Download Date: 12/07/2021

Service Summary Generated by: BuildingReports.com

Building: Temple VAMC Bldg. 147 The Service Summary section provides an overview of the services performed in this report.

Device Type Service Quantity

Passed Annunciator Tested 1 Battery Tested 2 Communicator Tested 1 Control Panel Tested 1 Duct Detector Tested 2 Fan Shutdown Tested 2 Horn/Strobe Tested 18 Pull Station Tested 6 Smoke Detector Tested 5 Strobe Tested 20

Total 58

Untested Tamper Switch 2 Waterflow Switch 1

Total 3 Grand Total 61

Page of 19 22 Auxiliary Functions Testing

Convergint Technologies - Central Texas Download Date: 12/07/2021

Auxiliary Functions Testing Generated by: BuildingReports.com

Building: Temple VAMC Bldg. 147 Control Panel: 1 - SimplexGrinnell 4100es The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.

Type Location Comment ScanID Simulated

Passed Fan Shutdown

AHU Shutdown Attic East end AHU 1 Passed 41136912 AHU Shutdown Attic East end AHU 1 Passed 41136913

Duct Detector AHU Shutdown Attic East end AHU 1 Passed 41136910 AHU Shutdown Attic East end AHU 1 Passed 41136911 javascript:openEditDevice('load-edit-f2-device','771924','2790899','41136912');

javascript:openEditDevice('load-edit-f2-device','771924','2790899','41136913');

javascript:openEditDevice('load-edit-f2-device','771924','2790899','41136910');

javascript:openEditDevice('load-edit-f2-device','771924','2790899','41136911');

Page of 20 22 Battery & Power Supply Testing

Convergint Technologies - Central Texas Download Date: 12/07/2021

Battery & Power Supply Testing Generated by: BuildingReports.com

Building: Temple VAMC Bldg. 147 Control Panel: 1 - SimplexGrinnell 4100es

The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.

Type Location Rated Ah

Rated Volts Pre Test

Post Test Min Ah Tested Ah

Battery

Passed Sealed Lead Acid 1st Electrical Rm E133 Left

Battery 35ah 12v 13.7 13.5 90%

Sealed Lead Acid 1st Electrical Rm E133 Right Battery

35ah 12v 13.7 13.4 90%

Page of 21 22 Inventory & Warranty Report

Convergint Technologies - Central Texas Download Date: 12/07/2021

Inventory & Warranty Report Generated by: BuildingReports.com

Building: Temple VAMC Bldg. 147 Control Panel: 1 - SimplexGrinnell 4100es The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity Annunciator Control 1.64% 1

Battery Control 3.28% 2

Communicator Control 1.64% 1

Control Panel Control 1.64% 1

Duct Detector Initiating 3.28% 2

Fan Shutdown Auxiliary 3.28% 2

Horn/Strobe Indicating 29.51% 18

Pull Station Initiating 9.84% 6

Smoke Detector Initiating 8.20% 5

Strobe Indicating 32.79% 20

Tamper Switch Supervisory 3.28% 2

Waterflow Switch Initiating 1.64% 1

Type Qty Model # Description Install Date

In Service - 3 Years to 5 Years Tamper Switch 1 08/23/2018 Waterflow Switch 1 08/23/2018

System sensor Tamper Switch 1 OSY2 08/23/2018

Communicator 1 08/22/2018 Duct Detector 2 Photoelectric 08/22/2018 Fan Shutdown 2 AHU Shutdown 08/22/2018 Horn/Strobe 18 08/22/2018 Pull Station 5 08/22/2018 Smoke Detector 5 08/22/2018 Strobe 20 08/22/2018

Duracell Ultra Battery 2 Sealed Lead Acid 08/22/2018

Simplex Pull Station 1 Dual Action 08/22/2018

SimplexGrinnell Annunciator 1 08/22/2018 Control Panel 1 4100es 08/22/2018

Page of 22 22 Zone Address Report

Convergint Technologies - Central Texas Download Date: 12/07/2021

Zone Address Report Generated by: BuildingReports.com

Building: Temple VAMC Bldg. 147 Control Panel: 1 - SimplexGrinnell 4100es

The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.

Address Device Type Location Type ScanID

Zone/Circuit: m1 1 Smoke Detector 1st electrical Rm e133 above FACP 41136980 2 Smoke Detector 1st Comms Rm E134 41136995 3 Communicator 1st Electrical Rm E133 41136982 3 Smoke Detector 1st Mech Rm E106 41136993 4 Smoke Detector 1st electrical Rm w226 41136924 5 Smoke Detector 1st Comms Rm W225 41136994 6 Pull Station 1st 1st copy rm E117 41136949 7 Pull Station 1st exit corridor by e123 Dual Action 41136990

08 Pull Station 1st entrance by w102 41136933 9 Pull Station 1st entrance by w102 41136945

10 Pull Station 1st exit in rm w228 41136921 11 Pull Station 1st exit stairs by riser 41136914 12 Duct Detector Attic East end AHU 1 Photoelectric 41136910 13 Duct Detector Attic East end AHU 1 Photoelectric 41136911

Zone/Circuit: w214 Tamper Switch top tamper riser stairwell 41136894 javascript:openEditDevice('load-edit-f2-device','771924','2790899','41136980');

javascript:openEditDevice('load-edit-f2-device','771924','2790899','41136995');

javascript:openEditDevice('load-edit-f2-device','771924','2790899','41136982');

javascript:openEditDevice('load-edit-f2-device','771924','2790899','41136993');

javascript:openEditDevice('load-edit-f2-device','771924','2790899','41136924');

javascript:openEditDevice('load-edit-f2-device','771924','2790899','41136994');

javascript:openEditDevice('load-edit-f2-device','771924','2790899','41136949');

javascript:openEditDevice('load-edit-f2-device','771924','2790899','41136990');

javascript:openEditDevice('load-edit-f2-device','771924','2790899','41136933');

javascript:openEditDevice('load-edit-f2-device','771924','2790899','41136945');

javascript:openEditDevice('load-edit-f2-device','771924','2790899','41136921');

javascript:openEditDevice('load-edit-f2-device','771924','2790899','41136914');

javascript:openEditDevice('load-edit-f2-device','771924','2790899','41136910');

javascript:openEditDevice('load-edit-f2-device','771924','2790899','41136911');

javascript:openEditDevice('load-edit-f2-device','771924','2790899','41136894');

Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate