2021-10-19_Temple-VAMC-Bldg--147_SprinklerScan.pdf

PDF 96 KB Posted

Attached to
J042--Fire Alarm and Suppression Systems Monitoring, Maintenance, Repairs and Installations
Solicitation number
36C25722Q0008
Issued by

About this file

This document includes a fire sprinkler inspection report and related federal contract opportunity. The inspection report details the results of an annual inspection of the fire sprinkler and alarm system at the Temple VA Medical Center Building 147 located in Temple, Texas. The inspection was performed in accordance with applicable NFPA standards and identified no deficiencies.

The related federal contract opportunity is a request for quote to provide fire alarm and sprinkler system maintenance, repairs, and installations for the Central Texas Veterans Health Care System facilities. The solicitation is set aside for Service-Disabled Veteran Owned Small Businesses and interested vendors must be verified on the VIP database. The contract will be a firm-fixed price award with an initial base year and four option years. Questions regarding the solicitation are due by December 6th and quotes must be submitted electronically by the date and time specified in block 8 of the SF-1449.

View the file

Other files

File Type Posted
36C25722Q0008 0003.docx DOCX document
SF30 - 36C25722Q0008 0003.pdf PDF
SF30 - 36C25722Q0008 0002.pdf PDF
36C25722Q0008 0002.docx DOCX document
REVISED SOW - FIRE Maint Mon SOW - 2021.pdf PDF
36C25722Q0008 0001.docx DOCX document
2021-11-19_Waco-VAMC-Bldg--202_SprinklerScan.pdf PDF
2021-02-24_Temple-VAMC-Bldg--204_SprinklerScan.pdf PDF
2020-08-31_Temple-VAMC-Bldg--204_FireScan.pdf PDF
2021-10-19_Temple-VAMC-Bldg--146_SprinklerScan.pdf PDF
WACO - sign in sheet - VHACTXBuvalC_120321_100124.pdf PDF
Inspection Schedule - Temple_Waco.xlsx XLSX spreadsheet
2021-10-26_Temple-VAMC-Bldg--146_FireScan.pdf PDF
2021-02-01_Waco-VAMC-Bldg--11_FireScan.pdf PDF
2021-05-26_Waco-VAMC-Bldg--91_FireScan.pdf PDF
2021-11-18_Waco-VAMC-Bldg--7_SprinklerScan.pdf PDF
2021-01-14_Waco-VAMC-Bldg--94_SprinklerScan.pdf PDF
2021-10-26_Temple-VAMC-Bldg--147_FireScan.pdf PDF
2021-01-13_Waco-VAMC-Bldg--11_SprinklerScan.pdf PDF
2021-04-05_Temple-VAMC-Bldg--221_FireScan.pdf PDF
2021-02-05_Temple-VAMC-Bldg--221_SprinklerScan.pdf PDF
2021-03-04_Waco-VAMC-Bldg--94_FireScan.pdf PDF
2021-11-30_Temple-VAMC-Bldg--163_SprinklerScan.pdf PDF
2021-11-18_Temple-VAMC-Bldg--163_FireScan.pdf PDF
2021-09-30_Waco-VAMC-Bldg--4_FireScan.pdf PDF
2020 VA Waco Hydrant Report.xlsx XLSX spreadsheet
2020 Temple VA Hydrants.xlsx XLSX spreadsheet
SF30 - 36C25722Q0008 0001.pdf PDF
2021-09-02_Temple-VAMC-Bldg--202_FireScan.pdf PDF
2021-05-19_Waco-VAMC-Bldg--91_SprinklerScan.pdf PDF
2021-11-10_Waco-VAMC-Bldg--7_FireScan.pdf PDF
2021-10-19_Waco-VAMC-Bldg--4_SprinklerScan.pdf PDF
QUESTION and ANSWERS.pdf PDF
TEMPLE - sign in sheet - VHACTXBuvalC_120321_100216.pdf PDF
Wage Determination Waco TX.pdf PDF
36C25722Q0008.pdf PDF
Limitations on Subcontracting Acknowledgment and Certification.pdf PDF
Wage Determination Temple TX.pdf PDF
36C25722Q0008_2.docx DOCX document
Show all 39

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sprinkler Inspection, Testing and/or Maintenance Certificate

For

Temple VAMC Bldg. 147 1901 Veterans Memorial Dr

Temple, TX 76504

This inspection was performed in accordance with NFPA 101, EDITION 2012, LIFE

SAFETY CODE, NFPA 72, EDITION 2010, FIRE ALARM SYSTEMS, NFPA 25,

EDITION 2011,WATER-BASED FIRE PROTECTION SYSTEMS and other regulatory standards applicable to this inspection.

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Annual Inspection Inspection Completion Date Oct 19, 2021

Building: Temple VAMC Bldg. 147 Company: Convergint Technologies - Central Texas Contact: Che Buval Contact: Adrian Mendez Title: Safety Officer Title: Inspector

Page of 1 20Convergint Technologies - Central Texas Download Date: 12/07/2021

Executive Summary Generated by: BuildingReports.com

Building Information Building: Temple VAMC Bldg. 147 Contact: Che Buval

Address: 1901 Veterans Memorial Dr Phone: 254-743-0133

Address: Fax:

City/State/Zip: Temple, TX 76504 Mobile:

Country: United States of America Email: Che.Buval@va.gov

Inspection Performed By Company: Convergint Technologies - Central Texas Inspector: Adrian Mendez

Address: 10535 Boyer Blvd Phone: 5124661490

Address: Suite 300 Fax:

City/State/Zip: Austin, Texas 78758 Mobile: 5124661490

Country: United States Email: Adrian.mendez@1stfpservices.com

Page of 2 20Convergint Technologies - Central Texas Download Date: 12/07/2021

Inspection Completion Date: Oct 19, 2021 Building: Temple VAMC Bldg. 147 EC 02.03.05 EP 02 Six-month testing of tamper switches and vane-type and pressure-type water-flow devices. Quarterly testing of mechanical water-flow devices. NFPA 72-2010 Table 14.4.5; NFPA 25-2011 Table 5.1.1.2.

Devices Tested This Quarter Pass Fail Tested YTD (2021) Total Quantity Tamper Switch 2 2 0 2 2

Waterflow Switch 1 1 0 1 1

Watermotor Gong 1 1 0 1 1

EC 02.03.05 EP 09 Annual test of main drains at system low point or at all system risers. NFPA 25-2011:

13.2.5; 13.3.3.4; Table 13.1.1.2; Table 13.8.1

Devices Tested This Quarter Pass Fail Tested YTD (2021) Total Quantity Drain 1 1 0 1 1

EC 02.03.05 EP 10 Quarterly inspection of all fire department water supply connections. NFPA 25-2011:

13.7; Table 13.1.1.2

Devices Tested This Quarter Pass Fail Tested YTD (2021) Total Quantity Fire Dep't Connection 1 1 0 1 1

LS 02.01.35 EP 07 At least six spare sprinkler heads of each type and temperature rating installed in the facility, with associated wrenches, are kept in a cabinet that will not exceed 100 degrees

F. NFPA 25-2011: 5.4.1

Devices Tested This Quarter Pass Fail Tested YTD (2021) Total Quantity Sprinkler Box 1 1 0 1 1

LS 02.01.35 EP 14 All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2012 18/19.3.5

Devices Tested This Quarter Pass Fail Tested YTD (2021) Total Quantity Alarm Valve 1 1 0 1 1

Backflow Prevention 1 1 0 1 1

Check Valve 1 1 0 1 1

Control Valve 2 2 0 2 2

Gauge 2 2 0 2 2

Inspector's Test 2 2 0 2 2

Total Device Count: 16

Page of 3 20Convergint Technologies - Central Texas Download Date: 12/07/2021

Certification Company: Convergint Technologies - Central Texas Building: Temple VAMC Bldg. 147 Inspector: Adrian Mendez Contact: Che Buval

Signed: Oct 4, 2021

Adrian Mendez Certifications Certification Type Number Texas State Certification - Fire Sprinkler Systems

Page of 4 20Convergint Technologies - Central Texas Download Date: 12/07/2021

Inspection & Testing Generated by: BuildingReports.com

Building: Temple VAMC Bldg. 147 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.

Passed=P, Failed=F, Replaced=R

EC 02.03.05 EP 02

Six-month testing of tamper switches and vane-type and pressure-type water-flow devices. Quarterly testing of mechanical water-flow devices. NFPA 72-2010 Table 14.4.5; NFPA 25-2011 Table 5.1.1.2.

Valve shall be operated and signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (2010 ed.) (NFPA 72 Table

14.4.2.2 (14i.1)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Tamper Switch 2 2 0 2 2

Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Tamper Switch 1st west stairwell by

212 bottom of BF 41136893 1 11/04-P 02/02-P 05/03-P 08/05-P 10/19-P

Tamper Switch 1st west stairwell by W212 Top of BF

41136894 1 11/04-P 02/02-P 05/03-P 08/05-P 10/19-P

Device Total: 2 Return to Executive Summary

Page of 5 20Convergint Technologies - Central Texas Download Date: 12/07/2021

EC 02.03.05 EP 02

Six-month testing of tamper switches and vane-type and pressure-type water-flow devices. Quarterly testing of mechanical water-flow devices. NFPA 72-2010 Table 14.4.5; NFPA 25-2011 Table 5.1.1.2.

Vane-type and pressure switch-type waterflow alarm devices shall be tested semiannually. Per NFPA 25, Section 5.3.3.1, mechanical waterflow alarm devices shall be tested quarterly. Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size installed in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems.

(2010 ed.) (NFPA 72 Table 14.4.2.2 (14j)) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Waterflow Switch 1 1 0 1 1

Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Waterflow Switch 2nd west stairwell by

W212 41136902 1 11/04-P 02/02-P 05/03-P 08/05-P 10/19-P

Device Total: 1 Return to Executive Summary

Page of 6 20Convergint Technologies - Central Texas Download Date: 12/07/2021

EC 02.03.05 EP 02

Six-month testing of tamper switches and vane-type and pressure-type water-flow devices. Quarterly testing of mechanical water-flow devices. NFPA 72-2010 Table 14.4.5; NFPA 25-2011 Table 5.1.1.2.

Waterflow alarm devices including, but not limited to, water motor gongs, shall be tested quarterly. (2011 ed.)

(NFPA 25 5.3.3.1)

Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Watermotor Gong 1 1 0 1 1

Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Watermotor Gong

1st west stairwell by W212

41136897 0 11/04-P 02/02-P 05/03-P 08/05-P 10/19-P

Page of 7 20Convergint Technologies - Central Texas Download Date: 12/07/2021

EC 02.03.05 EP 09

Annual test of main drains at system low point or at all system risers. NFPA 25-2011:

13.2.5; 13.3.3.4; Table 13.1.1.2; Table 13.8.1

A main drain test shall be conducted annually at each water-based fire protection system riser to determine whether there has been a change in the condition of the water supply piping and control valves. Auxiliary and low-point drains in preaction or deluge systems shall be operated after each system operation and before the onset of freezing conditions (and thereafter as needed). (2011 ed.) (NFPA 25 13.2.5; 13.4.4.3.2) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Drain 1 1 0 1 1

Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Drain 1st west stairwell by

W212 41136896 0 11/04-P 02/02-P 05/03-P 08/05-P 10/19-P

Page of 8 20Convergint Technologies - Central Texas Download Date: 12/07/2021

EC 02.03.05 EP 10

Quarterly inspection of all fire department water supply connections. NFPA 25-2011:

13.7; Table 13.1.1.2

Fire department connections shall be inspected quarterly to verify the following: Connections are visible and accessible, couplings or swivels are not damaged and rotate smoothly, plugs or caps are in place and undamaged, gaskets are in place and in good condition, identification signs are in place, the check valve is not leaking, the automatic drain valve is in place and operating properly and the clapper is in place and operating properly. (2011 ed.) (NFPA 25 13.7.1) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Fire Dep't Connection 1 1 0 1 1

Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Fire Dep't Connection

1st west stairwell by W212

49876581 0 11/04-P 02/02-P 05/03-P 08/05-P 10/18-P

Page of 9 20Convergint Technologies - Central Texas Download Date: 12/07/2021

LS 02.01.35 EP 07

At least six spare sprinkler heads of each type and temperature rating installed in the facility, with associated wrenches, are kept in a cabinet that will not exceed 100 degrees

F. NFPA 25-2011: 5.4.1

A supply of spare sprinklers (never fewer than six) shall be maintained on the premises so that any sprinklers that have operated or been damaged in any way can be promptly replaced. (2011 ed.) (NFPA 25 5.4.1.4) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Sprinkler Box 1 1 0 1 1

Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Sprinkler Box 1st west stairwell by

W212 41136899 0 11/04-P 02/02-P 05/03-P 08/05-P 10/04-P

Page of 10 20Convergint Technologies - Central Texas Download Date: 12/07/2021

LS 02.01.35 EP 14

All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2012 18/19.3.5

Monthly: Alarm valves and system riser check valves shall be externally inspected monthly. Periodically: Internal components shall be cleaned/repaired as necessary in accordance with the manufacturer's instructions. (2011 ed.)

(NFPA 25 13.4.1.1; 13.4.1.3.1)

Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Alarm Valve 1 1 0 1 1

Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Alarm Valve 1st west stairwell by

W212 41136895 0 11/04-P 02/02-P 05/03-P 08/05-P 10/04-P

Page of 11 20Convergint Technologies - Central Texas Download Date: 12/07/2021

All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2012 18/19.3.5

All backflow preventers installed in fire protection system piping shall be tested annually by conducting a forward flow test of the system at the designed flow rate, including hose stream demand, where hydrants or inside hose stations are located downstream of the backflow preventer. (2011 ed.) (NFPA 25 13.6.2.1) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Backflow Prevention 1 1 0 1 1

Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Backflow Prevention

1st west stairwell by W212

49876582 0 11/04-P 02/02-P 05/03-P 08/05-P 10/19-P

Page of 12 20Convergint Technologies - Central Texas Download Date: 12/07/2021

All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2012 18/19.3.5

Monthly: Alarm valves and system riser check valves shall be externally inspected monthly. Periodically: Internal components shall be cleaned/repaired as necessary in accordance with the manufacturer's instructions. (2011 ed.)

(NFPA 25 13.4.1.1)

Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Check Valve 1 1 0 1 1

Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Check Valve 1st west stairwell by

W212 41136900 1 11/04-P 02/02-P 05/03-P 08/05-P 10/04-P

Page of 13 20Convergint Technologies - Central Texas Download Date: 12/07/2021

All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2012 18/19.3.5

Monthly: Valves secured with locks or supervised in accordance with applicable NFPA standards shall be permitted to be inspected monthly. Periodically: Each control valve shall be operated annually through its full range and returned to its normal position. (2011 ed.) (NFPA 25 13.3.2.1.1; 13.3.3.1) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Control Valve 2 2 0 2 2

Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Control Valve 1st west stairwell by

W212 bottom of BF 49876579 1 11/04-P 02/02-P 05/03-P 08/05-P 10/19-P

Control Valve 1st west stairwell by W212 top of BF

49876580 1 11/04-P 02/02-P 05/03-P 08/05-P 10/19-P

Page of 14 20Convergint Technologies - Central Texas Download Date: 12/07/2021

All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2012 18/19.3.5

Gauges are in good condition and normal pressure is being maintained. [Inspection frequency will depend on type of system gauge]; Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge. (2011 ed.) (NFPA 25 13.2.7.1; 5.3.2.1) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Gauge 2 2 0 2 2

Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Gauge 1st west stairwell by

W212 41136898 0 11/04-P 02/02-P 05/03-P 08/05-P 10/04-P

Gauge 1st west stairwell by W212

49876578 0 11/04-P 02/02-P 05/03-P 08/05-P 10/04-P

Page of 15 20Convergint Technologies - Central Texas Download Date: 12/07/2021

All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2012 18/19.3.5

Testing the waterflow alarms on wet pipe systems shall be accomplished by opening the inspector's test connection. (2011 ed.) (NFPA 25 5.3.3.3) Devices Tested Q4/21 Pass Q4/21 Fail Q4/21 Tested YTD (2021) Total Quantity Inspector's Test 2 2 0 2 2

Device Type Location ScanID Address Q4/20 Q1/21 Q2/21 Q3/21 Q4/21 Inspector's Test 1st E-137 41136901 0 11/04-P 02/02-P 05/03-P 08/05-P 10/19-P Inspector's Test 2nd attic 41136910 0 11/04-P 02/02-P 05/03-P 08/05-P 10/19-P

Page of 16 20Convergint Technologies - Central Texas Download Date: 12/07/2021

Service Summary Generated by: BuildingReports.com

Building: Temple VAMC Bldg. 147 The Service Summary section provides an overview of the services performed in this report.

Device Type Service Quantity

Passed Alarm Valve Inspected 1 Backflow Prevention Inspected 1 Check Valve Inspected 1 Control Valve Tested 2 Drain Tested 1 Fire Dep't Connection Inspected 1 Gauge Tested 2 Inspector's Test Tested 2 Sprinkler Box Annual 1 Tamper Switch Tested 2 Waterflow Switch Tested 1 Watermotor Gong Tested 1

Total 16 Grand Total 16

Page of 17 20Convergint Technologies - Central Texas Download Date: 12/07/2021

Wet Pipe Fire Sprinkler Systems Generated by: BuildingReports.com

Building: Temple VAMC Bldg. 147 This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Tamper Switch

Type Description Location Number of Turns

Zone /Address

OK ScanID

OS&Y Supervisory 1st west stairwell by W212 Top of

BF

2 1 41136894

OS&Y Supervisory 1st west stairwell by 212 bottom of BF

2 1 41136893

Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter Electric VSR-4 18.10000 4 1 41136902

Components Alarm Valve

Type Manufacturer Model # Position Status Size OK ScanID Flanged Star 6-175-D 6" 41136895

Internal Date 08/21/2018

Backflow Prevention Manufacturer Model # Size Type Service Type Install Date Ames 2000ss 6" Double Check Fire Line 08/21/2018

ScanID Water Purveyor Location Meter Account # Serial Number 49876582 1st west stairwell by W212 166994

Initial Test Check Valve 1 Check Valve 2 Relief Valve Pressure Vacuum Breaker

Held At Repairs or Notes

Final Test Check Valve 1 Check Valve 2 Relief Valve Pressure Vacuum Breaker

Held At Condition of Control Valve 1 Condition of Control Valve 2

Check Valve Type Location Internal Date Size OK ScanID javascript:openEditDevice('load-edit-p2-device','771924','2300479','41136894');

javascript:openEditDevice('load-edit-p2-device','771924','2300479','41136893');

javascript:openEditDevice('load-edit-p2-device','771924','2300479','41136902');

javascript:openEditDevice('load-edit-p2-device','771924','2300479','41136895');

javascript:openEditDevice('load-edit-p2-device','771924','2300479','49876582');

Page of 18 20Convergint Technologies - Central Texas Download Date: 12/07/2021

Grooved 1st west stairwell by W212 08/21/2018 4" 41136900

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

OS&Y Kennedy KS-FW

1st west stairwell by W212 bottom of BF

6" Open Locked & Supervised

49876579

Description Main Control

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

OS&Y Kennedy KS-FW 1st west stairwell by W212 top of BF

6" Open Locked & Supervised

49876580

Description Main Control

Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID Randalman Globe 41136901

Location 1st E-137

Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID

AGF 1011 18.10 41136910

Location 2nd attic

Devices Drain

Current Inspection

Type Location Size Supply psi Restored psi

Residual psi Sec OK ScanID

Main 1st west stairwell by W212 2" 105 75 70 61.65000 41136896

Previous Inspections

August 5, 2021

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st west stairwell by W212 2" 68 50 30 41136896

May 3, 2021

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st west stairwell by W212 2" 68 50 120 41136896

Fire Dep't Connection Location Type BallDrip Rotating Swivels Size OK ScanID

1st west stairwell by W212 Wall No Yes 4" 49876581 javascript:openEditDevice('load-edit-p2-device','771924','2300479','41136900');

javascript:openEditDevice('load-edit-p2-device','771924','2300479','49876579');

javascript:openEditDevice('load-edit-p2-device','771924','2300479','49876580');

javascript:openEditDevice('load-edit-p2-device','771924','2300479','41136901');

javascript:openEditDevice('load-edit-p2-device','771924','2300479','41136910');

javascript:openEditDevice('load-edit-p2-device','771924','2300479','41136896');

javascript:openEditDevice('load-edit-p2-device','0','2228555','41136896');

javascript:openEditDevice('load-edit-p2-device','0','2140162','41136896');

javascript:openEditDevice('load-edit-p2-device','771924','2300479','49876581');

Page of 19 20Convergint Technologies - Central Texas Download Date: 12/07/2021

Gauge Location Service Date 1st west stairwell by W212 03/19/2025

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Wika 75 Air/Water 1/4 41136898

Gauge Location Service Date 1st west stairwell by W212 03/19/2025

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure Wika 75 Air/Water 1/4 49876578

Sprinkler Box

Qty Tool Available?

SIN List? Size Manufacturer Location OK ScanID

10 Yes No 6 unit 1st west stairwell by W212

41136899

Watermotor Gong Location Manufacturer Model # Size OK ScanID 1st west stairwell by W212 Tyco WMA-1 41136897 javascript:openEditDevice('load-edit-p2-device','771924','2300479','41136898');

javascript:openEditDevice('load-edit-p2-device','771924','2300479','49876578');

javascript:openEditDevice('load-edit-p2-device','771924','2300479','41136899');

javascript:openEditDevice('load-edit-p2-device','771924','2300479','41136897');

Page of 20 20Convergint Technologies - Central Texas Download Date: 12/07/2021

Inventory & Warranty Report Generated by: BuildingReports.com

Building: Temple VAMC Bldg. 147 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity Alarm Valve Valve 6.25% 1

Backflow Prevention Valve 6.25% 1

Check Valve Valve 6.25% 1

Control Valve Valve 12.50% 2

Drain Device 6.25% 1

Fire Dep't Connection Hose 6.25% 1

Gauge Device 12.50% 2

Inspector's Test Valve 12.50% 2

Sprinkler Box Sprinkler 6.25% 1

Tamper Switch Alarm 12.50% 2

Waterflow Switch Alarm 6.25% 1

Watermotor Gong Device 6.25% 1

Device Type Qty Model # Type Description Install Date

In Service - 1 Year to 2 Years Wet Pipe

Gauge 1 Supply Pressure 03/19/2020 Gauge 1 System Pressure 03/19/2020

In Service - 3 Years to 5 Years Wet Pipe

Sprinkler Box 1 08/21/2018 Inspector's Test 1 1011 08/21/2018 Backflow Prevention 1 2000ss Double Check 08/21/2018 Control Valve 2 KS-FW OS&Y Main Control 08/21/2018 Waterflow Switch 1 VSR-4 Vane Alarm 08/21/2018 Inspector's Test 1 Globe 08/21/2018 Drain 1 Angle Main 08/21/2018 Alarm Valve 1 6-175-D Flanged 08/21/2018 Tamper Switch 2 OSY2 OS&Y Supervisory 08/21/2018 Check Valve 1 CV-1F Grooved 08/21/2018 Watermotor Gong 1 WMA-1 08/21/2018

In Service - 15 Years to 25 Years Wet Pipe

Fire Dep't Connection 1 6-175-D Wall 08/21/2002

Sprinkler Inspection, Testing and/or Maintenance Certificate