This is a Request for Quote (RFQ) from the Department of Veterans Affairs for fire alarm and sprinkler system maintenance services at the Central Texas Veterans Health Care System in Temple, Texas. The base year of services plus four option years are required. The solicitation is set aside for Service-Disabled Veteran Owned Small Businesses. Interested vendors must be verified on the VIP database to be eligible for award. Technical questions are due by December 6th and quotes are due based on the deadline listed on the SF-1449. Masks are required for an optional site visit. The government will award a firm-fixed price contract for maintenance and repairs performed according to the Statement of Work.
View the file
Other files
Show all 39
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate
For
Temple VAMC Bldg. 204 1901 Veterans Memorial Dr
Temple, TX 76504
This inspection was performed in accordance with NFPA 101, EDITION 2021, LIFE SAFETY CODE and NFPA 72, EDITION 2019, FIRE ALARM SYSTEMS. Documentation complies with EC 02.03.05
EP 28.
The inspection/testing frequencies adhered to for this service have been performed in accordance with The Joint Commission/VHA Clarification Memorandum on EC & LS Standards effective January 31, 2021. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Annual Inspection Inspection Completion Date Aug 31, 2020
Building: Temple VAMC Bldg. 204 Company: Convergint Technologies - Central Texas Contact: Che Buval Contact: Troy Hague Title: Safety Officer Title: Service Specialist
Page of 1 69 Executive Summary
Convergint Technologies - Central Texas Download Date: 12/07/2021
Executive Summary Generated by: BuildingReports.com
Building Information Building: Temple VAMC Bldg. 204 Contact: Che Buval
Address: 1901 Veterans Memorial Dr Phone: 254-743-0133
Address: Fax:
City/State/Zip: Temple, TX 76504 Mobile:
Country: United States of America Email: Che.Buval@va.gov
Inspection Performed By Company: Convergint Technologies - Central Texas Inspector: Troy Hague
Address: 10535 Boyer Blvd Phone: 2543132867
Address: Suite 300 Fax:
City/State/Zip: Austin, Texas 78758 Mobile:
Country: United States Email: troy.hague@convergint.com
System Control Unit Manufacturer: SimplexGrinnell Inspection Date: 08/31/2020 IDC Style:
Model Number: 4100 Install Date: 03/10/1998 SLC Style:
Software Version: Version Date: 08/14/2018 NAC Style:
Location: 1st 1G23 Emergency Ops Rm Current Protection:
Central Station Signal Verification Type: Mfg: SimplexGrinnell Model #: 4100
Test Time/Date: 8/31/20 6:21:30 PM Restore Time: Note:
Page of 2 69
Convergint Technologies - Central Texas Download Date: 12/07/2021
Inspection Completion Date: Aug 31, 2020 Building: Temple VAMC Bldg. 204 EC 02.03.05 EP 01 Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; and room temperature supervisory
Devices Tested This
Quarter Pass Fail Tested YTD
(2020) Untested YTD
(2020) Total
Quantity Air Pressure Switch 0 0 0 1 0 1
Water Pressure Switch 0 0 0 1 0 1
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches
Devices Tested This
Quarter Pass Fail Tested YTD
(2020) Untested YTD
(2020) Total
Quantity Tamper Switch 0 0 0 46 0 46
Waterflow Switch 0 0 0 32 0 32
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Devices Tested This
Quarter Pass Fail Tested YTD
(2020) Untested YTD
(2020) Total
Quantity Duct Detector 0 0 0 30 0 30
Heat Detector 0 0 0 16 1 17
Pull Station 0 0 0 8 66 74
Smoke Detector 0 0 0 32 72 104
EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices.
Devices Tested This
Quarter Pass Fail Tested YTD
(2020) Untested YTD
(2020) Total
Quantity Releasing Device 0 0 0 6 24 30
Speaker/Strobe 0 0 0 13 94 107
Strobe 0 0 0 0 6 6
EC 02.03.05 EP 05 Annual test of fire alarm equipment for notifying off-site fire responders
Devices Tested This
Quarter Pass Fail Tested YTD
(2020) Untested YTD
(2020) Total
Quantity Communicator 0 0 0 1 0 1
EC 02.03.05 EP 19 Annual test of automatic smoke-detection shutdown devices for air-handling equipment per NFPA 90A-2021
Devices Tested This
Quarter Pass Fail Tested YTD
(2020) Untested YTD
(2020) Total
Quantity Duct Detector 0 0 0 30 0 30
Fan Shutdown 0 0 0 23 0 23
LS 02.01.34 EP 02 Protected master fire alarm control panel
Devices Tested This
Quarter Pass Fail Tested YTD
(2020) Untested YTD
(2020) Total
Quantity
Page of 3 69
Convergint Technologies - Central Texas Download Date: 12/07/2021
LS 02.01.34 EP 02 Protected master fire alarm control panel Control Panel 1 0 1 2 0 2
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2021 18/19.3.4
Devices Tested This
Quarter Pass Fail Tested YTD
(2020) Untested YTD
(2020) Total
Quantity Annunciator 0 0 0 1 10 11
Battery 2 0 2 4 2 6
Phone Jack 0 0 0 5 14 19
Power Supply 0 0 0 0 1 1
Programmable Relay 0 0 0 0 3 3
Smoke Alarm 0 0 0 0 1 1
Total Device Count: 515
Page of 4 69
Convergint Technologies - Central Texas Download Date: 12/07/2021
Certification Company: Convergint Technologies - Central Texas Building: Temple VAMC Bldg. 204 Inspector: Troy Hague Contact: Che Buval
Signed: Aug 29, 2020
Troy Hague Certifications Certification Type Number EST3 Series Certification
Page of 5 69 Discrepancy Report
Convergint Technologies - Central Texas Download Date: 12/07/2021
Discrepancy Report Generated by: BuildingReports.com
Building: Temple VAMC Bldg. 204 Control Panel: 1 - SimplexGrinnell 4100 The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty Items listed for Recall or Replacement/Upgrade
No items found during this inspection.
ScanID Location Problem Address Reference
LS 02.01.34 EP 02 Protected master fire alarm control panel
Control Panel 41135000 1st 1G23 Emergency Ops Rm Requires
Maintenance
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2021 18/19.3.4
Battery 58263832 1st FACP 1G18 Left Battery Failed Test 1 NFPA72 Table
14.4.3.2 (9a)(1)
62947646 1st FACP 1G18 Right Battery Failed Test 1 NFPA72 Table
14.4.3.2 (9a)(1)
Building: Temple VAMC Bldg. 204 Control Panel: 2 - SimplexGrinnell 4100U
The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty Items listed for Recall or Replacement/Upgrade
No items found during this inspection.
ScanID Location Problem Address Reference
LS 02.01.34 EP 02 Protected master fire alarm control panel
Control Panel 58263833 1st Security 1G18 Requires
Maintenance javascript:openEditDevice('load-edit-f2-device','771928','2605316','41135000');
javascript:openEditDevice('load-edit-f2-device','771928','2605316','58263832');
javascript:openEditDevice('load-edit-f2-device','771928','2605316','62947646');
javascript:openEditDevice('load-edit-f2-device','771928','2605316','58263833');
Page of 6 69 Proposed Solutions Report
Convergint Technologies - Central Texas Download Date: 12/07/2021
Proposed Solutions Report Generated by: BuildingReports.com
Building: Temple VAMC Bldg. 204 Control Panel: 1 - SimplexGrinnell 4100 The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.
ScanID Location Solution Model # Cost Fix
LS 02.01.34 EP 02 Protected master fire alarm control panel
Control Panel 41135000 1st 1G23 Emergency Ops Rm 4100 T/M
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2021 18/19.3.4
Battery 58263832 1st FACP 1G18 Left Battery Replace LFP1250 T/M 62947646 1st FACP 1G18 Right Battery Replace LFP1250 T/M
Building: Temple VAMC Bldg. 204 Control Panel: 2 - SimplexGrinnell 4100U The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.
ScanID Location Solution Model # Cost Fix
LS 02.01.34 EP 02 Protected master fire alarm control panel
Control Panel 58263833 1st Security 1G18 Service 4100U T/M
PO #: (none) T/M
Page of 7 69 Notes & Recommendations
Convergint Technologies - Central Texas Download Date: 12/07/2021
Notes & Recommendations Generated by: BuildingReports.com
Building: Temple VAMC Bldg. 204 The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
General Note 8/28/20 - Semi-Annual Fire Alarm Inspection Complete.
***System is Red Tagged for multiple (17) active Trouble signals on panel.*** (See panel for actual troubles.
Devices not required to be tested at this time) **Deficiencies noted this inspection:
1. Campus monitor panel in Security 1G118 failed due to dead batteries.
2. Batteries in FACP 1G118 failed load test.
3. Main FACP failed due to 17 active trouble signals.
a. LCD Cards 20 through 29 missing/failed
b. Card 2 Power Supply/Charger negative earth ground
c. Card 16 Power Supply/Charger (Audio) negative earth ground
d. BRB Basement pump room test open circuit
e. Building 205 fire alarm monitor missing
f. BRB basement Mechanical room b35 Smoke detector excessively dirty
g. BRB 2nd floor 2K12 mechanical Room AHU2J Duct detector excessively dirty
h. NAC circuit basement pump Room - open circuit Note 1 **Panel previously red tagged for multiple troubles on panel including the following noted deficiencies:
1. 4 Batteries failed load test.
2. 10 annunciators were offline and not functional.
Called monitoring station and verified signals and restorals received.
(See Device notes and comments of deficient devices for amplifying information.)
Building: Temple VAMC Bldg. 204 Control Panel: 1 - SimplexGrinnell 4100 Note Device Type Location Comment ScanID
LS 02.01.34 EP 02 Protected master fire alarm control panel 2 Control Panel 1st 1G23 Emergency Ops Rm Requires
Maintenance 41135000
Panel has numerous red tag faults from previous inspections.
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2021 18/19.3.4 3 Battery 1st 1G23 FACP LEFT BATTERY Passed 41135001
8/27/20 - Load Test = 100%.
4 Battery 1st 1G23 FACP RIGHT BATTERY Passed 62947638
8/27/20 - Load Test = 100%.
5 Battery 1st FACP 1G18 Left Battery Failed Test 58263832
Failed Load Test 5/29/20.
6 Battery 1st FACP 1G18 Right Battery Failed Test 62947646
Failed Load Test 5/29/20.
Building: Temple VAMC Bldg. 204 Control Panel: 2 - SimplexGrinnell 4100U
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the javascript:openEditDevice('load-edit-f2-device','771928','2605316','41135000');
javascript:openEditDevice('load-edit-f2-device','771928','2605316','41135001');
javascript:openEditDevice('load-edit-f2-device','771928','2605316','62947638');
javascript:openEditDevice('load-edit-f2-device','771928','2605316','58263832');
javascript:openEditDevice('load-edit-f2-device','771928','2605316','62947646');
Page of 8 69 Notes & Recommendations
Convergint Technologies - Central Texas Download Date: 12/07/2021 building inspection. Notes are grouped by Category.
Note Device Type Location Comment ScanID
LS 02.01.34 EP 02 Protected master fire alarm control panel 7 Control Panel 1st Security 1G18 Requires
Maintenance 58263833 replace batteries javascript:openEditDevice('load-edit-f2-device','771928','2605316','58263833');
Page of 9 69 Inspection & Testing
Convergint Technologies - Central Texas Download Date: 12/07/2021
Inspection & Testing Generated by: BuildingReports.com
Building: Temple VAMC Bldg. 204 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.
Passed=P, Failed=F, Replaced=R
EC 02.03.05 EP 01
Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; and room temperature supervisory
Operate switch and verify receipt of signal is obtained where the required pressure is increased or decreased a maximum 10 psi from the required pressure level. (NFPA 72-19 Table 14.4.3.2 (17)(9b)) Devices Tested Q3/20 Pass Q3/20 Fail Q3/20 Tested YTD (2020) Total Quantity Air Pressure Switch 0 0 0 1 1
Device Type Location ScanID Address Q3/19 Q4/19 Q1/20 Q2/20 Q3/20 Q4/20 Q1/21 Air Pressure Switch
Penthouse Elevator Mech Room Pre Action
40444656 1 08/07-P 03/13-P
Device Total: 1 Return to Executive Summary
Page of 10 69
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 01
Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; and room temperature supervisory
Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-19 Table
14.4.3.2 (2)(1)) Devices Tested Q3/20 Pass Q3/20 Fail Q3/20 Tested YTD (2020) Total Quantity Water Pressure Switch 0 0 0 1 1
Device Type Location ScanID Address Q3/19 Q4/19 Q1/20 Q2/20 Q3/20 Q4/20 Q1/21 Water Pressure Switch
Penthouse Elevator Mech Room Pre Action
40444715 1 08/07-P 03/13-P
Page of 11 69
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches
Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-19 Table 14.4.3.2 (17)(10)(a)) Devices Tested Q3/20 Pass Q3/20 Fail Q3/20 Tested YTD (2020) Total Quantity Tamper Switch 0 0 0 46 46
Device Type Location ScanID Address Q3/19 Q4/19 Q1/20 Q2/20 Q3/20 Q4/20 Q1/21 Tamper Switch
Basement Fire pump room
40444735 1 08/06-P 03/13-P
Tamper Switch
Basement Fire pump room
40444736 1 08/06-F 03/13-F
Tamper Switch
Basement Fire pump room
40444739 1 08/06-F 03/13-F
Tamper Switch
Basement Fire pump room
40444740 1 08/06-P 03/13-P
Tamper Switch
Basement Fire pump room
40444741 1 08/06-P 03/13-P
Tamper Switch
Basement Fire pump room
58263070 1 03/13-P
Tamper Switch
Basement Fire pump room bf shutoff 1
40444733 1 08/06-P 03/13-P
Tamper Switch
Basement Fire pump room bf shutoff 2
40444734 1 08/06-P 03/13-P
Tamper Switch
Basement Fire pump room bypass
40444737 1 08/06-P 03/13-P
Tamper Switch
Basement Fire pump room bypass
40444738 1 08/06-P 03/13-P
Tamper Switch
Basement Fire pump room jockey
40444722 1 08/06-P 03/13-P
Tamper Switch
Basement Fire pump room jockey
40444724 1 08/06-P 03/13-P
Tamper Switch
Basement Stair 11
40444779 1 08/06-P 03/13-P
Tamper Switch
Basement Stair 8
40444661 1 08/06-P 03/13-P
Tamper Switch
Basement Stair 8
40444663 1 08/06-P 03/13-P
Tamper Switch
Basement Stair 9
40444687 1 08/06-P 03/13-P
Tamper Switch
Basement Stair 9
40444688 1 08/06-P 03/13-P
Page of 12 69
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q3/19 Q4/19 Q1/20 Q2/20 Q3/20 Q4/20 Q1/21 Tamper Switch
1st Floor 1G52 Dry System
40444783 1 08/07-P 03/13-P
Tamper Switch
1st Floor Corr 1K61 above ceilin
40444788 1 08/07-P 03/13-P
Tamper Switch
1st Floor Stair
40444761 1 08/07-P 03/13-P
Tamper Switch
1st Floor Stair
40444775 1 08/07-P 03/13-P
Tamper Switch
1st Floor Stair
40444776 1 08/07-P 03/13-P
Tamper Switch
1st Floor Stair
40444697 1 08/07-P 03/13-P
Tamper Switch
1st Floor Stair
40444684 1 08/07-P 03/13-P
Tamper Switch
1st Floor Stair
40444694 1 08/07-P 03/13-P
Tamper Switch
2nd 40444962 1 08/07-P 03/13-F
Tamper Switch
2nd Floor Stair
40444770 1 08/07-P 03/13-P
Tamper Switch
2nd Floor Stair
40444771 1 08/07-P 03/13-P
Tamper Switch
2nd Floor Stair
40444701 1 08/07-P 03/13-P
Tamper Switch
2nd Floor Stair
40444682 1 08/07-P 03/13-P
Tamper Switch
3rd Floor Stair
40444755 1 08/07-P 03/13-P
Tamper Switch
3rd Floor Stair
40444758 1 08/07-P 03/13-P
Tamper Switch
3rd Floor Stair
40444704 1 08/07-P 03/13-P
Tamper Switch
3rd Floor Stair
40444679 1 08/07-P 03/13-P
Tamper Switch
4th Floor Stair
40444658 1 08/07-P 03/13-P
Tamper Switch
4th Floor Stair
40444676 1 08/07-P 03/13-P
Tamper Switch
5th Floor Stair
40444708 1 08/07-P 03/13-P
Tamper Switch
5th Floor Stairwell 9
40444673 1 08/07-P 03/13-P
Tamper Switch
6th Floor Stairwell 10
40444752 1 08/07-P 03/13-P
Tamper 6th Stariwell 10 40444749 1 08/07-P 03/13-P
Page of 13 69
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q3/19 Q4/19 Q1/20 Q2/20 Q3/20 Q4/20 Q1/21 Switch Tamper Switch
6th Stariwell 8 40444711 1 08/07-P 03/13-P
Tamper Switch
6th Stariwell 9 40444670 1 08/07-P 03/13-P
Tamper Switch
Penthouse Elevator Mech Room Pre Action
40444716 1 08/07-P 03/13-P
Tamper Switch
Penthouse Stair 10
40444746 1 08/07-P 03/13-P
Tamper Switch
Penthouse Stair 8
40444713 1 08/07-P 03/13-P
Tamper Switch
Penthouse Stair 9
40444667 1 08/07-P 03/13-P
Device Total: 46 Return to Executive Summary
Page of 14 69
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches
Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size installed in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25-20. (NFPA 72-19 Table
14.4.3.2 (17)(11)) Devices Tested Q3/20 Pass Q3/20 Fail Q3/20 Tested YTD (2020) Total Quantity Waterflow Switch 0 0 0 32 32
Device Type Location ScanID Address Q3/19 Q4/19 Q1/20 Q2/20 Q3/20 Q4/20 Q1/21 Waterflow Switch
Basement Stair 11
40444780 1 08/06-P 03/13-P
Waterflow Switch
Basement Stair 8 Basement Level Flow
40444662 1 08/06-P 03/13-P
Waterflow Switch
Basement Stair 8 Basement Level Under Stairs Flow
49876639 1 08/07-P 03/13-P
Waterflow Switch
Basement Stair 9
40444689 1 08/06-P 03/13-P
Waterflow Switch
Basement Fire pump room bf shutoff 1
40444742 1 08/06-P 03/13-P
Waterflow Switch
Basement Stair 11
40444787 1 08/06-P 03/13-P
Waterflow Switch
1st 1G52 valet dry system
40444781 1 08/07-P 03/13-P
Waterflow Switch
1st 1G52 valet dry system
40444782 1 08/07-P 03/13-P
Waterflow Switch
1st Floor Stair
40444762 1 08/07-P 03/13-P
Waterflow Switch
1st Floor Stair
40444777 1 08/07-P 03/13-P
Waterflow Switch
1st Floor Stair
40444683 1 08/07-P 03/13-P
Waterflow Switch
1st Floor Stair
40444698 1 08/07-P 03/13-P
Waterflow Switch
2nd Floor Stair
40444772 1 08/07-P 03/13-P
Waterflow Switch
2nd Floor Stair
40444773 1 08/07-P 03/13-P
Waterflow Switch
2nd Floor Stair
40444700 1 08/07-P 03/13-P
Waterflow Switch
2nd Floor Stair
40444681 1 08/07-P 03/13-P
Waterflow 3rd Floor Stair 40444759 1 08/07-P 03/13-P
Page of 15 69
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q3/19 Q4/19 Q1/20 Q2/20 Q3/20 Q4/20 Q1/21 Switch 10 Waterflow Switch
3rd Floor Stair
40444703 1 08/07-P 03/13-P
Waterflow Switch
3rd Floor Stair
40444678 1 08/07-P 03/13-P
Waterflow Switch
4th Floor Stair
40444756 1 08/07-P 03/13-P
Waterflow Switch
4th Floor Stair
40444675 1 08/07-P 03/13-P
Waterflow Switch
4th Stair 8 40444696 1 08/07-P 03/13-P
Waterflow Switch
5th Floor Stair
40444753 1 08/07-P 03/13-P
Waterflow Switch
5th Floor Stair
40444707 1 08/07-P 03/13-P
Waterflow Switch
5th Floor Stairwell 10
40444672 1 08/07-P 03/13-P
Waterflow Switch
6th Floor Stairwell 10
40444750 1 08/07-P 03/13-P
Waterflow Switch
6th Floor Stairwell 8
40444710 1 08/07-P 03/13-P
Waterflow Switch
6th Floor Stairwell 9
40444669 1 08/07-P 03/13-P
Waterflow Switch
Penthouse Stairwell 10
400444777 1 08/07-P 03/13-P
Waterflow Switch
Penthouse Stairwell 10
40444747 1 08/07-P 03/13-P
Waterflow Switch
Penthouse Stairwell 8
40444714 1 08/07-P 03/13-P
Waterflow Switch
Penthouse Stairwell 9
40444666 1 08/07-P 03/13-P
Device Total: 32 Return to Executive Summary
Page of 16 69
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72- 19 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q3/20 Pass Q3/20 Fail Q3/20 Tested YTD (2020) Total Quantity Duct Detector 0 0 0 30 30
Device Type Location ScanID Address Q3/19 Q4/19 Q1/20 Q2/20 Q3/20 Q4/20 Q1/21 Duct Detector
Basement Mechanical Rm BG05
AHU-1G2
supply
41135281 1-M1 20 02/05-P
Duct Detector
Basement Mechanical Rm BG05
AHU-1G2
supply
41135286 1-M1 20 02/05-P
Duct Detector
Basement Mechanical Rm BG05 AHU-1g2 supply
41135282 1-M1 20 02/05-P
Duct Detector
Basement Mechanical Rm BG05 AHU-1k2 supply
41135283 1-M1 21 02/05-P
Duct Detector
Basement Mechanical Rm BG05 AHU-1k2 supply
41135284 1-M1 21 02/05-P
Duct Detector
Basement Mechanical Rm BG05 AHU-1k2 supply
41135285 1-M1 21 02/05-P
Duct Detector
Basement Mechanical Rm BG35
AHU-1G3
41135279 1-M1 39 03/11-P
Duct Detector
1st Mech Rm
1K07 AHU-
1J1 Supply
41135241 1-M1 58 03/12-P
Duct Detector
1st Mech Rm
1K07 AHU-
1K1 Return
41135239 1-M1 60 03/12-P
Page of 17 69
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q3/19 Q4/19 Q1/20 Q2/20 Q3/20 Q4/20 Q1/21 Duct Detector
1st Mech Rm
1K07 AHU-
1K1 Supply
41135237 1-M1 59 03/12-P
Duct Detector
2nd Mech Rm
2G09 AHU-2G
Return
41135198 1-M1 97 02/10-F
Duct Detector
2nd Mech Rm
2G09 AHU-2G
Supply
41135200 1-M1 96 02/10-F
Duct Detector
2nd Mech Rm
2G09 AHU-2G
Supply
58263825 1-M1 96 03/10-P
Duct Detector
2nd Mech Rm
2K12 AHU-2J
Supply
41135174 1-M1
03/10-F
Duct Detector
2nd Mech Rm
2K12 AHU-2K
Supply
41135173 1-M1
03/10-P
Duct Detector
3rd Mech Rm
3G09 AHU-4G
Supply
41135132 1-M2 12 02/10-P
Duct Detector
3rd Mech Rm
3K12 AHU-3J
Supply
41135154 1-M2 11 03/12-P
Duct Detector
3rd Mech Rm
3K12 AHU-3K
Supply
41135155 1-M3 10 03/12-P
Duct Detector
4th Mech Rm
4G09 AHU-4G
Supply
41135102 1-M3 12 03/11-P
Duct Detector
4th Mech Rm
4K12 AHU-4J
Supply
41135125 1-M3 23 03/11-P
Duct Detector
4th Mech Rm
4K12 AHU-4K
Supply
41135126 1-M3 22 03/11-P
Duct Detector
5th Mech Rm
5G09 AHU 5G
Supply
41135066 1 03/11-P
Duct Detector
5th Mech Rm
5G09 AHU 5G
Supply
41135209 1 03/11-P
Duct Detector
5th Mech Rm
5K12 AHU-5J
Supply
41135095 1-M3 35 03/11-P
Duct Detector
5th Mech Rm
5K12 AHU-5K
41135096 1-M3 36 03/11-P
Page of 18 69
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q3/19 Q4/19 Q1/20 Q2/20 Q3/20 Q4/20 Q1/21
Supply Duct Detector
6th Mech Rm
6G09 AHU-6G
supply
41135062 1-m2 92 03/11-P
Duct Detector
6th Mech Rm
6K12 AHU 6K
Return
41135059 1 03/11-P
Duct Detector
6th Mech Rm
6K12 AHU-6J
Return
41135058 1-m3 57 03/11-P
Duct Detector
6th Mech Rm
6K12 AHU-6J
Supply
41135057 1-m3 59 03/11-P
Duct Detector
6th Mech Rm
6K1212 AHU
6K Supply
41135060 1-m3 58 03/11-P
Device Total: 30 Return to Executive Summary
Page of 19 69
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions. Non-Restorable: Do not perform heat test. Test functionality mechanically and electrically.
(NFPA 72-19 Table 14.4.3.2 (17)(4)(a)) Devices Tested Q3/20 Pass Q3/20 Fail Q3/20 Tested YTD (2020) Total Quantity Heat Detector 0 0 0 16 17
Device Type Location ScanID Address Q3/19 Q4/19 Q1/20 Q2/20 Q3/20 Q4/20 Q1/21 Heat Detector
Penthouse Elevator Mech Room Pre Action
EE46808
Heat Detector
Penthouse Penthouse elevator equipment rm Penthouse
411335020 1-m3 97 03/13-F
Heat Detector
Penthouse east exit above dry system AHU 6K Supply
41135006 1-m3 67 02/07-P
Heat Detector
Penthouse elevator equipment rm
41135007 1-m3 89 03/11-P
Heat Detector
Penthouse elevator equipment rm
41135008 1-m3 89 03/11-P
Heat Detector
Penthouse elevator equipment rm
41135009 1-m3 88 03/11-P
Heat Detector
Penthouse elevator equipment rm
41135010 1-m3 90 03/11-P
Heat Detector
Penthouse elevator equipment rm
41135011 1-m3 91 03/11-P
Heat Detector
Penthouse elevator equipment rm
41135012 1-m3 91 03/11-P
Heat Detector
Penthouse elevator equipment rm
41135017 1-m3 93 03/11-P
Heat Detector
Penthouse elevator equipment rm
41135018 1-m3 98 03/11-P
Heat Detector
Penthouse elevator
41135019 1-m3 99 03/11-P
Page of 20 69
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q3/19 Q4/19 Q1/20 Q2/20 Q3/20 Q4/20 Q1/21 equipment rm Heat Detector
Penthouse elevator equipment rm
41135021 1-m3 95 03/11-P
Heat Detector
Penthouse elevator equipment rm
41135022 1-m3 93 03/11-P
Heat Detector
Penthouse elevator equipment rm
41135023 1-m3 94 03/11-P
Heat Detector
Penthouse elevator equipment rm
41135024 1-m3 70 03/11-P
Heat Detector
Penthouse elevator equipment rm
41135020 1-m3 99 03/11-P
Device Total: 17 Return to Executive Summary
Page of 21 69
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-19 Table 14.4.3.2 (17)(5)) Devices Tested Q3/20 Pass Q3/20 Fail Q3/20 Tested YTD (2020) Total Quantity Pull Station 0 0 0 8 74
Device Type Location ScanID Address Q3/19 Q4/19 Q1/20 Q2/20 Q3/20 Q4/20 Q1/21 Pull Station
Basement BG01 in fire pump rm above NAC
41135289 1-m1 33 03/03-P 03/11-P
Pull Station
Basement cor by stair 8
41135278 1-m1 12 02/05-P 03/09-P
Pull Station
Basement corr by BG01
41135258 1-m1 9 02/05-P 03/09-P
Pull Station
Basement inpatient rehab at stair
41135262 1-m1
02/05-P 03/01-P
Pull Station
1st exit by 1G23
41135004 1-m1 28 11/05-P 02/03-P 08/31-P 11/06-P 03/01-P
Pull Station
1st exit by 1G18
41135226 1-m1 24 02/04-P 08/29-P 03/01-P
Pull Station
1st 1st cor behind stagf elev lobby
41135220 1-m1 37 02/04-P 03/01-P
Pull Station
1st Staff Elevator Lobby at exit.
41135218 1-m1 12 02/04-P 03/01-P
Pull Station
1st audiology waiting
41135243 1-m1 61 02/04-P 03/01-P
Pull Station
1st cor by 1G05 trash rm dock exit
41135252 1-m1 73 02/04-P 03/01-P
Pull Station
1st cor by 1G18
41135225 1-m1 24 02/06-P 03/01-P
Pull Station
1st library cor exit
41135245 1-m1 71 02/04-P 03/01-P
Pull Station
1st valet entry 41135228 1-m1 41??
02/04-P 03/01-P
Pull Station
1st welcome center waiting
41135232 1-m1 41??
02/04-P 03/01-P
Pull Station
2nd cor by 2G14e or lounge in bldg
41135217 1-m1 74 02/06-P
Pull 2nd cor by 41135161 1-m1 88 02/06-P 03/11-P
Page of 22 69
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q3/19 Q4/19 Q1/20 Q2/20 Q3/20 Q4/20 Q1/21 Station 2G22 Pull Station
2nd cor by 2K02
41135180 1-m1
03/12-P 03/01-P
Pull Station
2nd cor by 2K11
41135172 1-m1
03/12-P 03/01-P
Pull Station
2nd cor by 2K12
41135170 1-m1
03/12-P 03/01-P
Pull Station
2nd cor by
2K39 HAC
41135195 1-m1
02/06-P 03/01-P
Pull Station
2nd cor by mech rm 2G09
41135194 1-m1 77 02/06-P 03/01-P
Pull Station
2nd cor by stair 11
41135167 1-m1
02/06-P 03/11-P
Pull Station
2nd cor by stair 8
41135193 1-m1 76 02/06-P 03/01-P
Pull Station
2nd cor by stair 9
41135179 1-m1
02/06-P 03/01-P
Pull Station
2nd cor by women's restroom
41135181 1-m1 83 02/06-P 03/01-P
Pull Station
2nd icu nurses station
41135168 1-m1
02/06-P
Pull Station
2nd nurses station 2k00
41135177 1-m1
03/12-P 03/01-P
Pull Station
3rd by 3G03 41135140 1-m2 6 02/07-P 03/01-P
Pull Station
3rd by 3K02 41135139 1-m2 8 02/07-P 03/01-P
Pull Station
3rd by 3K12 41135152 1-m2 8 02/07-P 03/01-P
Pull Station
3rd by 3K13 41135151 1-m2 18 02/07-P 03/01-P
Pull Station
3rd by mech rm 3G09
41135131 1-m2 7 02/07-P 03/01-P
Pull Station
3rd by nurses station 3j00
41135148 1-m3 5 02/07-P 03/01-P
Pull Station
3rd by rm 3K39 41135134 1-m2 10 03/12-P 03/01-P
Pull Station
3rd by stair 10 41135150 1-m3 4 03/12-P 03/01-P
Pull Station
3rd by stair 8 41135130 1-m2 5 02/07-P 03/01-P
Pull Station
3rd by stair 9 41135138 1-m2 19 02/07-P 03/01-P
Pull Station
3rd nurses station 3K00
41135137 1-m2 17 02/07-P 03/01-P
Page of 23 69
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q3/19 Q4/19 Q1/20 Q2/20 Q3/20 Q4/20 Q1/21 Pull Station
4th by cor by 4K13
41135122 1-m3 24 02/07-P 03/01-P
Pull Station
4th by mech rm 4K12
41135120 1-m3 21 02/07-P 03/01-P
Pull Station
4th by stair 8 41135100 1-m2 42 02/07-P 03/01-P
Pull Station
4th cor by 4K12
41135121 1-m3 20 03/10-P 03/01-P
Pull Station
4th cor by 4K12
4113W 1-m3 20 02/07-P 03/10-P
Pull Station
4th cor by 4K39
41135104 1-m2 36 02/07-P 03/01-P
Pull Station
4th cor by 4K39
41135107 1-m2 45 02/07-P 03/01-P
Pull Station
4th cor by 4K39
41135108 1-m2 26 03/10-P 03/01-P
Pull Station
4th cor by 4g09
41135101 1-m2 36 02/07-P 03/01-P
Pull Station
4th cor by women's RR 4G03
41135110 1-m2 38 02/07-P 03/01-P
Pull Station
4th nurse manager 4K02
41135109 1-m2 46 02/07-P 03/01-P
Pull Station
4th nurses station 4J00
41135118 1-m3 17 02/07-P 03/01-P
Pull Station
5th Hall by 5G09
41135065 1 02/07-P 03/01-P
Pull Station
5th Hall by 5K39
41135069 1-m2 53 02/07-P 03/01-P
Pull Station
5th Hall by stair 8 fire exit
41135064 1-m2 50 02/07-P 03/01-P
Pull Station
5th Nurse Station 5K00
41135071 1-m2 63 02/07-P 03/01-P
Pull Station
5th Nurses Station 5J00
41135085 1-m3 31 02/07-P 03/01-P
Pull Station
5th Stair 9 Fire Exit
41135072 1-m2 65 03/10-P 03/01-P
Pull Station
5th by trash collection rm 5G05
51135065 1 02/07-P 03/10-P
Pull Station
5th cor by 5G03 women's RR
41135075 1-m2 60 02/07-P 03/01-P
Pull Station
5th cor by 5K02
41135074 1-m2 61 02/07-P 03/01-P
Pull 5th cor by 5k13 41135093 1-m2 64 02/07-P 03/01-P
Page of 24 69
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q3/19 Q4/19 Q1/20 Q2/20 Q3/20 Q4/20 Q1/21 Station Pull Station
5th cor by mech rm 5K12
41135094 1-m3 49 02/07-P 03/01-P
Pull Station
5th stair 10 41135090 1-m3 28 02/07-P 03/01-P
Pull Station
6th 6J00 41135046 1-m3 40 02/07-P
Pull Station
6th Hall by 6G03
41135039 1-m2 94 02/07-P 03/11-P
Pull Station
6th Hall by 6G09
41135027 1-m2 93 02/07-P 03/11-P
Pull Station
6th Hall by 6K13
41135061 1-m2 84 02/07-P
Pull Station
6th Hall by 6K43
41135038 1-m2 80 02/07-P 03/11-P
Pull Station
6th Hall by 6k12
41135056 1-m3 55 02/07-P
Pull Station
6th Hall by elevator lobby
41135026 1-m2 72 02/07-P
Pull Station
6th Hall by stair 10
41135053 1-m3 48 02/07-P
Pull Station
6th Nursing station @6K00
41135035 1-m2 82 02/07-P 03/11-P
Pull Station
6th by 6K39 41135029 1-m2 78 02/07-P 03/11-P
Pull Station
6th hall by 6k27
41135036 1 03/10-P
Pull Station
Penthouse by dry system penthouse
41135005 1-m3 64 02/07-P 03/10-P
Device Total: 74 Return to Executive Summary
Page of 25 69
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72- 19 Table 14.4.3.2 (17)(7)(a)) Devices Tested Q3/20 Pass Q3/20 Fail Q3/20 Tested YTD (2020) Total Quantity Smoke Detector 0 0 0 32 104
Device Type Location ScanID Address Q3/19 Q4/19 Q1/20 Q2/20 Q3/20 Q4/20 Q1/21 Smoke Detector
Basement Public Elevator Lobby
41135276 1-m1 10 02/05-P 03/01-P
Smoke Detector
Basement Staff elev, lobby
41135287 1-m1 11 02/05-P 03/01-P
Smoke Detector
Basement cor by BG01
41135256 1-m1 8 03/12-P 03/09-P
Smoke Detector
1st 1G25 reception area
41135227 1-m2 29 03/12-P 03/01-P
Smoke Detector
1st Above
FACP
41135003 1-m2 28 02/07-P
Smoke Detector
1st Audiology Waiting
41135244 1-m1 62 02/04-P 03/01-P
Smoke Detector
1st By Valet reception in waiting area
41135229 1-m2 42 02/04-P 03/01-P
Smoke Detector
1st cor behind staff elevator Lobby
41135221 1-m2 35 02/04-P 03/01-P
Smoke Detector
1st cor by 1G05
41135253 1-m1 53 02/04-P 03/01-P
Smoke Detector
1st cor by 1G18
41135222 1-m2 25 02/04-P 03/01-P
Smoke Detector
1st cor by
1G18 VA
Police
41135223 1-m2 27 02/04-P 03/01-P
Smoke Detector
1st cor by 1G20
41135251 1-m1 44 02/04-P 03/01-P
Smoke Detector
1st cor by 1K48
41135246 1-m1 72 02/04-P 03/01-P
Smoke Detector
1st cor by 1K60
41135249 1-m1 52 02/10-P 03/01-P
Smoke Detector
1st cor by Valet at fire doors
41135231 1-m2 54 02/04-P 03/01-P
Smoke Detector
1st cor by mech rm 1K07
41135235 1-m2 57 02/04-P 03/01-P
Smoke Detector
1st in office 1G26
41135255 1-m1 30 03/12-P 03/10-P
Page of 26 69
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q3/19 Q4/19 Q1/20 Q2/20 Q3/20 Q4/20 Q1/21 Smoke Detector
1st public elev lobby
41135250 1-m1 45 02/04-P 03/01-P
Smoke Detector
1st staff elevator Lobby
41135219 1-m2 23 03/12-P 03/01-P
Smoke Detector
1st waiting Area by Piano M
41135230 1-m2 43 02/07-P 03/01-P
Smoke Detector
1st welcome center waiting
41135233 1-m2 58 02/07-P 03/01-P
Smoke Detector
2nd 2G14 overnight Rm
41135216 1-m1 85 02/07-P
Smoke Detector
2nd by 2G22 at fire doors
41135163 1-m1 98 02/06-P 03/01-P
Smoke Detector
2nd by 2G24 41135164 1-m1 87 03/12-P 03/01-P
Smoke Detector
2nd by 2G26 41135165 1-m1 93 02/06-P 03/11-P
Smoke Detector
2nd by 2G36 41135166 1-m1 95 02/06-P 03/01-P
Smoke Detector
2nd by 2k02 41135183 1-m1
02/06-P
Smoke Detector
2nd by 2k12 41135171 1-m1
03/12-P 03/01-P
Smoke Detector
2nd by visitors lounge 2G01
41135184 1-m1 84 03/12-P 03/01-P
Smoke Detector
2nd cor by 2G05
41135196 1-m1
02/06-P 03/01-P
Smoke Detector
2nd cor by 2G45
41135192 1-m1 90 02/06-P 03/01-P
Smoke Detector
2nd cor by S courtyard
41135190 1-m1 89 02/06-P 03/01-P
Smoke Detector
2nd cor by desk 2G
41135187 1-m1 86 03/12-P 03/01-P
Smoke Detector
2nd cor by desk 2G
41135189 1-m1 80 02/06-P 03/01-P
Smoke Detector
2nd public elevator lobby
41135185 1-m1 78 02/06-P 03/01-P
Smoke Detector
2nd public elevator lobby
41135186 1-m1 82 02/06-P 03/01-P
Smoke Detector
2nd staff elevator lobby.
41135160 1-m1 75 02/06-P 03/01-P
Smoke Detector
3rd by 3G02 41135143 1-m2 2 02/07-P 03/01-P
Smoke Detector
3rd by 3k02 41135142 1-m2 9 02/07-P 03/01-P
Smoke 3rd by 3k39 41135135 1-m2 11 02/07-P 03/01-P
Page of 27 69
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q3/19 Q4/19 Q1/20 Q2/20 Q3/20 Q4/20 Q1/21 Detector Smoke Detector
3rd cor by 3G31
41135146 1-m2 7 02/07-P 03/01-P
Smoke Detector
3rd cor by 3G34
41135145 1-m2 1 03/12-P 03/01-P
Smoke Detector
3rd cor by 3J35
41135157 1-m3 9 02/07-P 03/01-P
Smoke Detector
3rd cor by 3K12
41135153 1-m3 9 02/07-P 03/01-P
Smoke Detector
3rd public elevator Lobby
41135144 1-m2 3 02/07-P 03/01-P
Smoke Detector
3rd staff elevator lobby
41135129 1-m2 4 02/07-P 03/01-P
Smoke Detector
4th Public Elevator Lobby
41135114 1-m2 41 02/07-P 03/01-P
Smoke Detector
4th Staff Elevator Lobby
41135099 1-m2 43 02/07-P 03/01-P
Smoke Detector
4th cor by 4G02
41135113 1-m2 40 02/07-P 03/01-P
Smoke Detector
4th cor by 4G40
41135115 1-m2 44 03/10-P 03/01-P
Smoke Detector
4th cor by 4J30 41135116 1-m3 19 03/10-P 03/01-P
Smoke Detector
4th cor by 4J33 41135128 1-m3 18 02/07-P 03/01-P
Smoke Detector
4th cor by 4K02
41135112 1-m2 25 02/07-P 03/01-P
Smoke Detector
4th cor by 4K12
41135124 1-m3 20 02/07-P 03/01-P
Smoke Detector
4th cor by 4K39
41135105 1-m2 39 02/07-P 03/01-P
Smoke Detector
5th Public Elevator Lobby
41135079 1-m2 48 02/07-P 03/01-P
Smoke Detector
5th Staff Elevator Lobby
41135063 1-m2 51 02/07-P 03/01-P
Smoke Detector
5th cor 5G02 41135078 1-m2 49 02/07-P 03/01-P
Smoke Detector
5th cor 5K02 door holder
41135077 1-m2 62 02/07-P 03/01-P
Smoke Detector
5th cor by 5G37
41135081 1-m2 47 03/10-P 03/01-P
Smoke Detector
5th cor by 5J00A
41135084 1-m3 37 03/10-P 03/01-P
Smoke Detector
5th cor by 5J01 41135089 1-m3 29 03/10-P 03/01-P
Page of 28 69
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q3/19 Q4/19 Q1/20 Q2/20 Q3/20 Q4/20 Q1/21 Smoke Detector
5th cor by 5J16 41135091 1-m3 34 02/07-P 03/01-P
Smoke Detector
5th cor by 5J28 41135083 1-m3 33 03/10-P 03/01-P
Smoke Detector
5th cor by 5J33 41135098 1-m3 32 02/07-P 03/01-P
Smoke Detector
5th cor by mechanical 5k12
41135092 1-m3 38 02/07-P 03/01-P
Smoke Detector
5th waiting 5K01A
41135073 1-m2 58 02/07-P 03/01-P
Smoke Detector
5th waiting area 5J11
41135087 1-m3 30 03/10-P 03/01-P
Smoke Detector
5th waiting area 5J11 by tv
41135088 1-m3 39 03/10-P 03/01-P
Smoke Detector
5th waiting area by 5G01
41135080 1-m2 56 02/07-P 03/01-P
Smoke Detector
6th Hall by 6G03
41135045 1-m2 94 02/07-P
Smoke Detector
6th Hall by 6J11
41135051 1-m3 45 02/07-P
Smoke Detector
6th Hall by 6J26
41135054 1-m3 43 02/07-P
Smoke Detector
6th Hall by 6K12
41135055 1-m3 54 02/07-P
Smoke Detector
6th Hall by Lobby 6G01
41135041 1-m2 73 03/10-P 03/11-P
Smoke Detector
6th Hall cor by 6K31 womens clinic
41135037 1-m2 86 03/10-P
Smoke Detector
6th Lobby Area by 6J02
41135048 1 02/07-P
Smoke Detector
6th Lobby Area by 6J06
41135052 1-m3 47 02/07-P
Smoke Detector
6th Lobby Area by 6J14
41135049 1-m3 53 02/07-P
Smoke Detector
6th Public elevator lobby
41135042 1-m2 70 02/07-P
Smoke Detector
6th Service Elevator Lobby
41135025 1-m2 71 02/07-P
Smoke Detector
6th by nurse station 6K01 in Atrium up High
41135034 1-m2 85 03/10-P 03/11-P
Smoke Detector
6th by nurses station day
41135033 1-m2 83 03/10-P 03/11-P
Page of 29 69
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q3/19 Q4/19 Q1/20 Q2/20 Q3/20 Q4/20 Q1/21 room 6K01 Smoke Detector
6th cor by 6G04
41135028 1-m2 79 03/10-P 03/11-P
Smoke Detector
6th cor by 6J04 41135050 1-m3 44 02/07-P
Smoke Detector
6th cor by 6J31 411335045 1-m3 43 02/07-P
Smoke Detector
6th cor by 6K42
41135040 1-m2 81 02/07-P 03/11-P
Smoke Detector
6th nurses station 6J00
41335048 1-m3 41 02/10-P
Smoke Detector
6th top of shaft public elevators
41137343 1-m3 71 03/10-P
Smoke Detector
6th top of shaft public elevators
41137340 1-m3 74 03/10-P
Smoke Detector
6th top of shaft public elevators
41137341 1-m3 73 03/10-P
Smoke Detector
6th top of shaft public elevators
41137342 1-m3 72 03/10-P
Smoke Detector
6th top of shaft service elevators
41137344 1-m3 76 03/10-P
Smoke Detector
6th top of shaft service elevators
41137345 1-m3 75 03/10-P
Smoke Detector
6th top of shaft service elevators
41137346 1-m3 78 03/10-P
Smoke Detector
6th top of shaft service elevators
41137347 1-m3 77 03/10-P
Smoke Detector
Penthouse Elevator Mech Room Pre Action
EE46424
1 02/10-P
Smoke Detector
Penthouse elevator equip rm
41135013 1-m3 65 03/11-P
Smoke Detector
Penthouse elevator equip rm
41135014 1-m3 66 03/11-P
Smoke Detector
Penthouse elevator equip
41135015 1-m3 69 03/11-P
Page of 30 69
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q3/19 Q4/19 Q1/20 Q2/20 Q3/20 Q4/20 Q1/21 rm Smoke Detector
Penthouse elevator equip rm
41135016 1-m3 68 03/11-P
Smoke Detector top of shaft public elevators
411337340 1-m3 74 02/10-P
Smoke Detector top of shaft public elevators
411337341 1-m3 73 02/10-P
Smoke Detector top of shaft public elevators
411337342 1-m3 72 02/10-P
Device Total: 104 Return to Executive Summary
Page of 31 69
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices.
Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-19 Table 14.4.3.2 (20)) Devices Tested Q3/20 Pass Q3/20 Fail Q3/20 Tested YTD (2020) Total Quantity Releasing Device 0 0 0 6 30
Device Type Location ScanID Address Q3/19 Q4/19 Q1/20 Q2/20 Q3/20 Q4/20 Q1/21 Releasing Device
Basement Corr by BG01
41135257 1 02/07-P
Releasing Device
1st cor by honors
52282203 1 08/31 Removed
02/26-P
Releasing Device
1st 1 st corr by 1K62 X 2
41135254 1 02/04-P 02/26-P
Releasing Device
1st 1 st corr by rm 1K60 X 2
4113524 1 02/07-P
Releasing Device
1st 1 st in corr by 1G32
41135370 1 02/07-P 02/26-P
Releasing Device
1st cor by 1G18x2
41135224 1 02/03-P
Releasing Device
1st cor by rm 1K48x2
41135247 1 02/04-P 02/26-P
Releasing Device
1st cor by rm 1K60x2
41135248 1 02/07-P 02/26-P
Releasing Device
1st cor by vallet reception x2
41135234 1 02/04-P 02/26-P
Releasing Device
1st cor by vallet reception x2
41135236 1 02/04-P
Releasing Device
1st smoke doors by 1G18 Corridor
41135933 1-m1 28 02/04-P 02/26-P
Releasing Device
2nd Stair 9 by 4K28
52282164 1 08/31 Removed
02/26-P
Releasing Device
2nd corr by 2K02
52282162 1 08/31 Removed
02/26-P
Releasing Device
2nd WON door corr by 2G01 waiting
41135191 1 02/07-P 02/26-P
Releasing Device
2nd corr by 2G05
41135197 1 02/06-P 02/26-P
Releasing Device
2nd corr by 2G22 X 2
41135162 1 02/07-P 02/26-P
Releasing Device
2nd corr by 2K02
41135182 1 02/06-P
Releasing 3rd Stair 9 by 52282161 1 08/31 02/26-P
Page of 32 69
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q3/19 Q4/19 Q1/20 Q2/20 Q3/20 Q4/20 Q1/21 Device 4K28 Removed Releasing Device
3rd corridor by 3K13 X 2
52282160 1 08/31 Removed
02/26-P
Releasing Device
3rd Stair 10 by 4J07
52282159 1 08/31 Removed
02/26-P
Releasing Device
3rd corridor by 3K13 X 2
52282163 1 08/31 Removed
02/26-F
Releasing Device
3rd corridor by 3G31 X 2
41135147 1 02/07-P 02/26-P
Releasing Device
3rd corridor by 3G35 X 2
41135156 1 02/07-P 02/26-P
Releasing Device
3rd corridor by 3K02 X 2
41135141 1 02/07-P 02/26-P
Releasing Device
3rd corridor by 3K39 X 2
41135133 1 02/07-P 02/26-P
Releasing Device
4th Stair 9 by 4K28
52282158 1 08/31 Removed
02/26-P
Releasing Device
4th Stair 10 by 4J07
52282157 1 08/31 Removed
02/26-P
Releasing Device
4th corridor by 4J30 X 2
41135117 1 02/07-P 02/26-P
Releasing Device
4th corridor by 4J35 X 2
41135127 1 02/07-P 02/26-P
Releasing Device
4th corridor by 4K02 X 2
41135111 1 02/07-P 02/26-P
Releasing Device
4th corridor by 4K13 X 2
41135123 1 02/07-P 02/26-P
Releasing Device
4th corridor by 4K40 X 2
41135103 1 02/07-P 02/26-P
Releasing Device
5th outside Stair 9 by 5K28
52282156 1 08/31 Removed
02/26-P
Releasing Device
5th stair by 5J07
52282155 1 08/31 Removed
02/26-P
Releasing Device
5th corridor by 5G03 X 2
41135076 1 02/07-P 02/26-P
Releasing Device
5th corridor by 5G05
41135067 1 02/07-P 02/26-P
Releasing Device
5th corridor by 5G35 X 2
41135082 1 02/07-P 02/26-P
Releasing Device
5th corridor by 5J35 X 2
41135097 1 02/07-P 02/26-P
Releasing Device
6th corridor by 6J31 X 2
41135043 1 02/07-P
Releasing Device
6th corridor by 6K39
41135030 1 02/07-P 03/11-P
Page of 33 69
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q3/19 Q4/19 Q1/20 Q2/20 Q3/20 Q4/20 Q1/21 Releasing Device
6th corridor by 6K42
41135044 1 02/07-P 03/11-P
Page of 34 69
Convergint Technologies - Central Texas Download Date: 12/07/2021
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices.
For periodic testing, verify the operation of the notification appliances. (NFPA 72-19 Table 14.4.3.2 (22)(2)) Devices Tested Q3/20 Pass Q3/20 Fail Q3/20 Tested YTD (2020) Total Quantity Speaker/Strobe 0 0 0 13 107
Device Type Location ScanID Address Q3/19 Q4/19 Q1/20 Q2/20 Q3/20 Q4/20 Q1/21 Speaker /Strobe
Basement BG35 mech m
41135274 1 02/07-P 03/10-P
Speaker /Strobe
Basement SPS storage by BG06A
41135288 1 02/05-P 03/10-P
Speaker /Strobe
Basement corr by BG01
41135261 1 02/05-P 03/09-P
Speaker /Strobe
Basement corr by BG23
41135271 1 02/05-P 03/09-P
Speaker /Strobe
Basement inpatient rehab corr by
BG38
41135263 1 02/05-P 03/10-P
Speaker /Strobe
Basement inpatient rehab open area
41135265 1 02/05-P 03/09-P
Speaker /Strobe
Basement inpatient rehab open area
41135266 1 02/05-P 03/10-P
Speaker /Strobe
Basement inpatient rehab open area
41135269 1 02/05-P 03/09-P
Speaker /Strobe
Basement inpatient rehab whirlpools
BG24
41135267 1 02/05-P 03/10-P
Speaker /Strobe
Basement mech em
BG05
41135280 1 02/05-P 03/11-P
Speaker /Strobe
Basement public elev lobby
41135277 1 02/05-P 03/09-P
Speaker /Strobe
1st hall of honors by army
52282178 1 08/31 Removed
02/26-P
Speaker /Strobe
1st 1J11 welcome center corr by
41135374 1 02/04-P 02/26-P
Page of 35 69
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q3/19 Q4/19 Q1/20 Q2/20 Q3/20 Q4/20 Q1/21
1J07 Speaker /Strobe
1st 1K00 library
41135380 1 02/07-P 02/26-P
Speaker /Strobe
1st 1K00 library
41135381 1 02/07-P 02/26-P
Speaker /Strobe
1st at information center
41135372 1 02/07-P 02/26-P
Speaker /Strobe
1st at piano by public elevator lobby
41135371 1 02/04-P 02/26-P
Speaker /Strobe
1st audiology corr by 1K13
41135377 1 02/04-P 02/26-P
Speaker /Strobe
1st audiology corr by 1K26
41135376 1 02/04-P 02/26-P
Speaker /Strobe
1st audiology waiting rm
41135375 1 02/04-P 02/26-P
Speaker /Strobe
1st by staff elevator lobby
41135384 1 02/04-P 02/26-P
Speaker /Strobe
1st corr 2G25 by 1G26
41135369 1 02/07-P 02/26-P
Speaker /Strobe
1st corr 2G25 by 1G40
41135368 1 02/07-P 02/26-P
Speaker /Strobe
1st corr by 1G10
41135383 1 02/04-P 02/26-P
Speaker /Strobe
1st corr by 1G10
41135838 1 02/07-P
Speaker /Strobe
1st corr by 1G25
41135367 1 02/07-P 02/26-P
Speaker /Strobe
1st corr by 1J14 rest rm
41135373 1 02/04-P 02/26-P
Speaker /Strobe
1st corr by 1K00
41135379 1 02/04-P 02/26-P
Speaker /Strobe
1st corr by 1K49
41135378 1 02/04-P
Speaker /Strobe
1st corr by restrooms
41135382 1 02/04-P 02/26-P
Speaker /Strobe
1st hall of honors by army
41137335 1 02/04-P
Speaker /Strobe
2nd Corr by 2G09
41135350 1 02/06-P 02/26-P
Speaker /Strobe
2nd Corr by 2K26
4113535 1 02/07-P
Speaker /Strobe
2nd Corr by 2K26
41135353 1 02/07-P 02/26-P
Page of 36 69
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q3/19 Q4/19 Q1/20 Q2/20 Q3/20 Q4/20 Q1/21 Speaker /Strobe
2nd Corr by 2K36
41135351 1 02/06-P 02/26-P
Speaker /Strobe
2nd Corr by 2K36
4113551 1 02/07-P
Speaker /Strobe
2nd bldg 163 lounge 2G14E
41135366 1 02/07-P
Speaker /Strobe
2nd corr by 2G01 waiting
41135359 1 02/07-P 02/26-P
Speaker /Strobe
2nd corr by 2G03 women’ s rest rm
41135358 1 02/06-P 02/26-P
Speaker /Strobe
2nd corr by 2G13
41135361 1 02/06-P 03/11-P
Speaker /Strobe
2nd corr by 2G18
41135360 1 02/06-P 03/11-P
Speaker /Strobe
2nd corr by 2G29
41135365 1 02/06-P 03/11-P
Speaker /Strobe
2nd corr by 2G29
41135782 1 02/06-P 03/11-P
Speaker /Strobe
2nd corr by 2G37
41135364 1 02/07-P 02/26-P
Speaker /Strobe
2nd corr by 2J18
41135357 1 02/07-P 02/26-P
Speaker /Strobe
2nd corr by 2J35
41135362 1 02/06-P 02/26-P
Speaker /Strobe
2nd corr by 2K03
41135354 1 02/07-P 02/26-P
Speaker /Strobe
2nd corr by 2K12
41135356 1 02/07-P 02/26-P
Speaker /Strobe
2nd corr by 2K14
41135355 1 02/07-P 02/26-P
Speaker /Strobe
2nd icu nurse station
41135363 1 02/06-P 02/26-P
Speaker /Strobe
2nd nurse station 2K00
41135352 1 02/07-P 02/26-P
Speaker /Strobe
3rd corr by 3G08
41135337 1 02/07-P 02/26-P
Speaker /Strobe
3rd corr by 3K36
41135338 1 02/07-P 02/26-P
Speaker /Strobe
3rd corr by staff elev lobby
41135336 1 02/07-P 02/26-P
Speaker /Strobe
3rd floor corr by 3G03
41135344 1 02/07-P 02/26-P
Speaker /Strobe
3rd floor corr by 3G19
41135349 1 02/07-P 02/26-P
Speaker 3rd floor corr 41135342 1 02/07-P 02/26-P
Page of 37 69
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q3/19 Q4/19 Q1/20 Q2/20 Q3/20 Q4/20 Q1/21 /Strobe by 3G21 Speaker /Strobe
3rd floor corr by 3G26
41135348 1 02/07-P 02/26-P
Speaker /Strobe
3rd floor corr by 3G32
41135343 1 02/07-P 02/26-P
Speaker /Strobe
3rd floor corr by 3J00
41135346 1 02/07-P 02/26-P
Speaker /Strobe
3rd floor corr by 3J07
41135347 1 02/07-P 02/26-P
Speaker /Strobe
3rd floor corr by 3K03
41135345 1 02/07-P 02/26-P
Speaker /Strobe
3rd floor corr by 3K11
41135341 1 02/07-P 02/26-P
Speaker /Strobe
3rd floor corr by 3K26
41135340 1 02/07-P 02/26-P
Speaker /Strobe
3rd floor nurse station 3K00
41135339 1 02/07-P 02/26-P
Speaker /Strobe
4th cor by 4K39 4th floor by 4K-38
41135324 1-m2 45 02/07-P 02/26-P
Speaker /Strobe
4th floor 4G03 women’s rest room
41135329 1 02/07-P 02/26-P
Speaker /Strobe
4th floor 4J00 41135331 1 02/07-P 02/26-P
Speaker /Strobe
4th floor by staff elevator lobby
41135322 1 02/07-P 02/26-P
Speaker /Strobe
4th floor corr by 4G09
41135323 1 02/07-P 02/26-P
Speaker /Strobe
4th floor corr by 4G17
41135335 1 02/07-P 02/26-P
Speaker /Strobe
4th floor corr by 4G30
41135334 1 02/17-F 02/26-P
Speaker /Strobe
4th floor corr by 4G38
41135330 1 02/07-P 02/26-P
Speaker /Strobe
4th floor corr by 4J08
41135332 1 02/07-P 02/26-P
Speaker /Strobe
4th floor corr by 4J21
41135333 1 02/07-P 02/26-P
Speaker /Strobe
4th floor corr by 4K14
41135327 1 02/07-P 02/26-P
Speaker /Strobe
4th floor corr by 4K27
41135326 1 02/07-P 02/26-P
Speaker /Strobe
4th floor nurse station 4K00
41135325 1 02/07-P 02/26-P
Page of 38 69
Convergint Technologies - Central Texas Download Date: 12/07/2021
Device Type Location ScanID Address Q3/19 Q4/19 Q1/20 Q2/20 Q3/20 Q4/20 Q1/21 Speaker /Strobe
4th floor nurse station 4K01
41135328 1 02/17-F 02/26-P
Speaker /Strobe
5th Corr by Staff Elevator Lobby
41135306 1 02/07-P 02/26-P
Speaker /Strobe
5th Hall by 5G09
41135307 1 02/07-P 02/26-P
Speaker /Strobe
5th Hall by 5K01
41135308 1 02/07-P 02/26-P
Speaker /Strobe
5th Hall by 5K26
41135310 1 02/07-P 02/26-P
Speaker /Strobe
5th Nurse Station 5K00
41135309 1 02/07-P 02/26-P
Speaker /Strobe
5th floor corr by 5G03 women’s rr
41135320 1 02/07-P 02/26-P
Speaker /Strobe
5th floor corr by 5G24
41135319 1 02/07-P 02/26-P
Speaker /Strobe
5th floor corr by 5G32
41135318 1 02/07-P 02/26-P
Speaker /Strobe
5th floor corr by 5G36
41135315 1 02/07-P 02/26-P
Speaker /Strobe
5th floor corr by 5J08
41135316 1 02/07-P 02/26-P
Speaker /Strobe
5th floor corr by 5J28
41135314 1 02/07-P 02/26-P
Speaker…