Updated Specifications 28 31 00 Page 3-VAJB-FireAlarm Updated 1-13-2021 172.pdf

PDF 10 KB Posted

Attached to
Z2DA--Replace Obsolete Fire Alarm Devices, 537-16-101
Solicitation number
36C25221B0003
Issued by

About this file

This document includes a federal contract opportunity for replacing obsolete fire alarm devices at the Jesse Brown VA Medical Center in Chicago, Illinois. The contract is set aside for Service-Disabled Veteran-Owned Small Businesses and has an estimated value between $2-5 million. Interested contractors must be registered in the System for Award Management and listed as verified in the Vendor Information Pages database. A pre-bid site visit will be held and details will be included in the solicitation package to be posted on November 25, 2020, with bids due on January 14, 2021. The work must be completed within 581 calendar days of receiving a notice to proceed and includes providing all tools, materials, components, labor and supervision for construction and remodeling of a fully functional fire alarm system and exit signs in accordance with design documents.

View the file

Other files

File Type Posted
VHA Directive 1192.01 Seasonal Influenza Prevention Program for VHA Health Care Personnel.pdf PDF
Updated Specifications Section 28 31 00 1.2 Scope.docx DOCX document
36C25221B0003 0009.docx DOCX document
36C25221B0003 0008.docx DOCX document
Clarifications.docx DOCX document
Information Regarding Bidding Material Bid Guarantee and Bonds.docx DOCX document
36C25221B0003 0007.docx DOCX document
Final Responses to Consolidated RFI Sheet 3_36C25221B0003_2-1-2021.xlsx XLSX spreadsheet
537.16.101_G-004_updated 1-29-2021.pdf PDF
537.16.101_G-007.pdf PDF
FinalSpecifications-VAJB-FireAlarm Updated 2-03-2021-1.pdf PDF
537.16.101_G-008.pdf PDF
537.16.101_G-001.pdf PDF
36C25221B0003 0006.docx DOCX document
537.16.101_G-009.pdf PDF
36C25221B0003 0005.docx DOCX document
RFI SHEET_36C25221B0003.xlsx XLSX spreadsheet
Consolidated RFI Sheet 2_36C25221B0003_1-19-21.xlsx XLSX spreadsheet
36C25221B0003 0004.docx DOCX document
S15 RFI List with VA Responses_36C25221B0003_1-13-2021.xlsx XLSX spreadsheet
Updated Specifications Table of Contents Updated January 13 2021.pdf PDF
36C25221B0003 0003.docx DOCX document
Specifications Cover Sheet dated January 13 2021.pdf PDF
Updated Drawing Number G-002_updated 1-13-2021.pdf PDF
VAAR 852-219-10 NOV 2020.docx DOCX document
Updated Specifications 28 31 00 Page 4-VAJB-FireAlarm Updated 1-13-2021 173.pdf PDF
FinalSpecifications-Re-issue 2-VAJB-FireAlarm Part 1 of 1 Updated 12-29-2020.pdf PDF
Wage Determination IL20210009 Dated 1-1-2021.pdf PDF
36C25221B0003 0002.docx DOCX document
36C25221B0003 0001.docx DOCX document
36C25221B0003 0001 Attachments.zip ZIP file
36C25221B0003_1.docx DOCX document
36C25221B0003 Attachments.zip ZIP file
Show all 33

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

28 31 00 - 3

D. Existing waterflow/pressure switches, and valve tamper switches reused by the Contractor shall be equipped with an address able interface device compatible with the new equipment being inst alled.

E. Existing reused equipment shall be covered as ne w equipment under the

Warranty specified herein.

F. Basic Performance:

1. Alarm and trouble signals from each building fir e alarm control panel shall be digitally encoded by UL listed elect ronic devices onto a multiplexed communication system.

2. Response time between alarm initiation (contact closure) and recording at the main fire alarm control unit (appe arance on alphanumeric read out) shall not exceed 5 seconds.

3. The signaling line circuits (SLC) between buildi ng fire alarm control units shall be wired Class X in accordance with NFPA 72.

Isolation shall be provided so that no more than on e building can be lost due to a short circuit fault.

4. Initiating device circuits (IDC) shall be wired Class B in accordance with NFPA 72.

5. Signaling line circuits (SLC) within buildings s hall be wired Class

B in accordance with NFPA 72. Individual signaling line circuits shall be limited to covering 22,500 square feet (2, 090 square meters) of floor space or 3 floors whichever is les s.

6. Notification appliance circuits (NAC) shall be w ired Class B in accordance with NFPA 72.

1.3 RELATED WORK

A. Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, A ND SAMPLES.

Requirements for procedures for submittals.

B. Section 07 84 00 - FIRESTOPPING. Requirements fo r fire proofing wall penetrations.

1.4 SUBMITTALS

A. General: Submit 5 copies in accordance with Sect ion 01 33 23, SHOP

DRAWINGS, PRODUCT DATA, AND SAMPLES, and Section 26 05 11, REQUIREMENTS

FOR ELECTRICAL INSTALLATIONS.

B. Drawings:

1. Prepare drawings using latest AutoCAD Release so ftware and include all contractors information. Layering shall be by V A criteria as provided by the Contracting Officer’s Representativ e (COR). Bid drawing files will be provided to the Contractor at the pre-