Consolidated RFI Sheet 2_36C25221B0003_1-19-21.xlsx

XLSX spreadsheet 22 KB Posted

Attached to
Z2DA--Replace Obsolete Fire Alarm Devices, 537-16-101
Solicitation number
36C25221B0003
Issued by

About this file

This document contains a consolidated request for information sheet and related federal contract opportunity notice for replacing obsolete fire alarm devices. The federal contract opportunity is seeking proposals for project number 537-16-101 to replace fire alarm systems and exit signs at the Jesse Brown VA Medical Center in Chicago, Illinois. The work includes providing all labor, materials, and components for a fully functional fire alarm system in compliance with applicable codes and regulations. The project value is estimated between $2-5 million. Proposals are due by January 14, 2021 for the solicitation to be issued on November 25, 2020. The NAICS code is 238210 and the size standard is $16.5 million. The set-aside is for Service-Disabled Veteran-Owned Small Businesses. The contract award is through the Department of Veterans Affairs Veterans Health Administration VISN 12.

View the file

Other files

File Type Posted
VHA Directive 1192.01 Seasonal Influenza Prevention Program for VHA Health Care Personnel.pdf PDF
Updated Specifications Section 28 31 00 1.2 Scope.docx DOCX document
36C25221B0003 0009.docx DOCX document
36C25221B0003 0008.docx DOCX document
Clarifications.docx DOCX document
Information Regarding Bidding Material Bid Guarantee and Bonds.docx DOCX document
36C25221B0003 0007.docx DOCX document
Final Responses to Consolidated RFI Sheet 3_36C25221B0003_2-1-2021.xlsx XLSX spreadsheet
537.16.101_G-004_updated 1-29-2021.pdf PDF
537.16.101_G-007.pdf PDF
FinalSpecifications-VAJB-FireAlarm Updated 2-03-2021-1.pdf PDF
537.16.101_G-008.pdf PDF
537.16.101_G-001.pdf PDF
36C25221B0003 0006.docx DOCX document
537.16.101_G-009.pdf PDF
36C25221B0003 0005.docx DOCX document
RFI SHEET_36C25221B0003.xlsx XLSX spreadsheet
36C25221B0003 0004.docx DOCX document
S15 RFI List with VA Responses_36C25221B0003_1-13-2021.xlsx XLSX spreadsheet
Updated Specifications Table of Contents Updated January 13 2021.pdf PDF
36C25221B0003 0003.docx DOCX document
Specifications Cover Sheet dated January 13 2021.pdf PDF
Updated Specifications 28 31 00 Page 3-VAJB-FireAlarm Updated 1-13-2021 172.pdf PDF
Updated Drawing Number G-002_updated 1-13-2021.pdf PDF
VAAR 852-219-10 NOV 2020.docx DOCX document
Updated Specifications 28 31 00 Page 4-VAJB-FireAlarm Updated 1-13-2021 173.pdf PDF
FinalSpecifications-Re-issue 2-VAJB-FireAlarm Part 1 of 1 Updated 12-29-2020.pdf PDF
Wage Determination IL20210009 Dated 1-1-2021.pdf PDF
36C25221B0003 0002.docx DOCX document
36C25221B0003 0001.docx DOCX document
36C25221B0003 0001 Attachments.zip ZIP file
36C25221B0003_1.docx DOCX document
36C25221B0003 Attachments.zip ZIP file
Show all 33

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

CONSOLIDATED RFI LIST 2 - JANUARY 16, 2021

SOLICITATION #: 36C25221B0003

PROJECT TITLE: Replace Obsolete Fire Alarm Devices

PROJECT #: 537-16-101

FACILITY:Jesse Brown VA Medical Center
Chicago, IL
RFI #RFIVA RESPONSEREFERENCE
148Scope of Work states that: “All locations with a security system card reader shall have automatic unlock of the associated electric lock upon fire alarm activation.” Please clarify this requirement in relation to type of existing electric locks and provide up-to-date list of all doors with card readers, including information about existing electric lock at each door. Most of these doors have fail-secure type electric door strikes, i.e., when power is disconnected from electric door strike by means of fire alarm system activation, the electric strike becomes not operational, door remains closed, latched, and locked; egress is permitted from secure side of door only, in the direction of path of egress indicated by EXIT sign. To comply with the automatic unlock requirement, fail-secure electric door strikes would have to be replaced with fail-safe devices. Doors located in non-rated walls or barriers can have fail-secure electric door strikes replaced with fail-safe type, but doors located in fire or smoke barrier walls must have electric door strikes replaced with fail-safe electric locks or exit devices so that such doors stay closed and latched after automatic unlock by fire alarm system.No replacement of electric strikes is contemplated in this work- even at locations where fail-secure electric strikes are disconnected from power upon fire alarm activation. As noted, egress is still available in the direction of egress.
149The effective date is missing from Amendment #2The effective date was omitted due to technical difficulties publishing the amendment. The "effective date" would be the date Amendment 2 was published which was January 5, 2021.
150The RFI deadline on Amendment #1 has December 30th, 2021, I believe this is a typo and should read 2020.RFI suspense was incorrectly entered as "December 30, 2021". It should have read December 30, 2020. Amendment 1 also extended the Bid opening to January 27, 2021, therefore, it would be impossible to entertain RFI's until December 30, 2021 as the solicitation would be closed by that date.
151Will three separate field personnel ‐ QC, SSHO, and Superintendent be required?Three separate individuals are required: QC, Site Safety & Health Officer (SSHO), and Superintendent; QC cannot perform the SSHO or Superintendent duty at the same time; Same action applies to both SSHO & superintendent.
152Will it be acceptable to VA if the contractor provide required certifications for PM and Superintendent prior to commencing the work?Qualifications per SOW to be reviewed at kick-off meeting for awarded contractor.
153Scope of Work states that: "All locations with a security system card reader shall have automatic unlock of the associated electric lock upon fire alarm activation.” Please clarify this requirement in relation to type of existing electric locks and provide up‐to‐date list of all doors with card readers, including information about existing electric lock at each door. There are almost 300 doors at Jesse Brown VA Medical Center that have card readers. Most of these doors have fail‐secure type electric door strikes, i.e., when power is disconnected from electric door strike by means of fire alarm system activation, the electric strike becomes not operational, door remains closed, latched, and locked; egress is permitted from secure side of door only, in the direction of path of egress indicated by EXIT sign. To comply with the automatic unlock requirement, fail‐secure electric door strikes would have to be replaced with fail‐safe devices. Doors located in non‐rated walls or barriers can have fail‐secure electric door strikes replaced with fail‐safe type, but doors located in fire or smoke barrier walls must have electric door strikes replaced with fail‐safe electric locks or exit devices so that such doors stay closed and latched after automatic unlock by fire alarm system.No replacement of electric strikes is contemplated in this work- even at locations where fail-secure electric strikes are disconnected from power upon fire alarm activation. As noted, egress is still available in the direction of egress.
154In addendum #1 on drawing G-004 a detail #16 was added. The note says to field verify locations and quantities of doors equipped with a card reader and to assume 1,850 locations when only about 70 are shown on the floor plans. This a very high quantity of card readers for a VA so I would like to verify the assumed quantity is accurate as this is going to be a substantial cost in the bid. The estimated cost for each card reader interface will be over $ 1,000 and with 1,850 readers this one detail could total well over 2.0 Million dollars so a clear scope of work is desired. The card reader relays shown on the drawings are shown as being replaced. Can the conduit, cabling and relays be re-used? Will there be any coordination required with the security vendor? Who is the security vendor? Since a parallel system is required will the doors need to be connected to both the old and new system at the same time?Contractor is to include 1850 locations as stated in the detail. Contractor is responsible to field verify exact locations and quantities as stated in the detail.Drawing sheet G-004 detail 16
155We presume the existing Fire Alarm Panel is Simplex. Please confirm1- Proposed new Fire Alarm panels are not specific to one manufacturer. 2- All existing equipment is required to be removed or replaced as shown.Specification 28 31 00, section 1.1.A., Drawing G-002 General Note 1
156Please specify all the types of third integrations (For Ex: Elevator, Fire Smoke Damper, Kitchen Hood Suppression system, Door holders, Security Access door, Staircase Pressurization System) to be considered with the new Fire Alarm SystemSee drawings and specifications for requested information.Drawing sheet G-004 detail 15
157Please confirm whether the existing Booster Power Supply can be reused with Notification appliances.All existing equipment is required to be removed or replaced as shown.Specification 28 31 00, section 1.1.A., Drawing G-002 General Note 1
158Please confirm whether the peer-to-peer connection between the fire alarm panels to be Single Mode or Multimode.Communication between fire alarm panels is via 2 HR Rated copper wire system, not fiber optic, so question does not apply to this Work.

File details come from the government source that posted it. Updated .