This solicitation package is for a construction project to replace obsolete fire alarm devices at the Jesse Brown VA Medical Center in Chicago, Illinois. The contractor will provide all labor, materials, and supervision to install new fire alarm systems and exit signs in multiple buildings in accordance with the design plans and specifications. Work must be completed within 581 calendar days of receiving a notice to proceed. As a Service-Disabled Veteran-Owned Small Business set-aside, only SDVOSBs classified as electrical contractors under NAICS 238210 with revenues under $16.5 million may bid. Bids are due by January 14, 2021 in response to a solicitation that will be posted on November 25, 2020 to SAM.gov. The pre-bid site visit details will be included in the solicitation. The project value is estimated between $2-5 million.
View the file
Other files for this federal contract opportunity
Show all 33
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL NOTES
ELECTRICAL NOTES
FIRE ALARM SYSTEM NOTES
INFECTIOUS CONTROL NOTES – DURING PROJECT CONSTRUCTION
PHASING
EXISTING CONDITIONS
139 Old Creek Road Palos Park, IL 60464 and 12200 Bunya Lane Ruther Glen, VA 22546
Tel: 703-477-5928 Email: dale.wheeler@systechfire.com
, INC.
AutoCAD SHX Text
1. THIS DESCRIPTION IS INTENDED TO PROVIDE AN OVERVIEW ONLY. REFER TO DRAWINGS AND SPECIFICATIONS. PROJECT PROVIDES FOR ALL WORK, AutoCAD SHX Text PRODUCTS, MATERIALS, INSTALLATION, PROGRAMMING, AND EXECUTION ASSOCIATED WITH REMOVAL OF EXISTING FIRE ALARM SYSTEM AND INSTALLATION OF A
AutoCAD SHX Text NEW FIRE ALARM SYSTEM IN BUILDINGS 01, 05, 06, 11, 15, 18, 21, 26, 27, 30, 32/TMB, 40 & 42. UNLESS OTHERWISE NOTED EACH BUILDING IS TO RECEIVE A FIRE
AutoCAD SHX Text ALARM CONTROL PANEL, INITIATING AND INDICATING DEVICES, ALONG WITH ALL ASSOCIATED EQUIPMENT FOR A FULL AND COMPLETE FUNCTIONING SYSTEM IN
AutoCAD SHX Text EACH BUILDING. ALL FIRE ALARM CONTROL PANELS ARE TO BE INTERCONNECTED TO EACH OTHER FOR FULL AND COMPLETE PEER TO PEER COMMUNICATION OF
AutoCAD SHX Text ALL ASPECTS OF EACH SYSTEM AMONG ALL CONNECTED SYSTEMS. THE WORK INCLUDES ALL ASSOCIATED ASPECTS, INCLUDING BUT NOT LIMITED TO PRIMARY
AutoCAD SHX Text
POWER SUPPLY, CUTTING AND PATCHING, AND REPAIR OF FINISHES.
AutoCAD SHX Text
2. CONTRACTOR SHALL PREPARE A SCHEDULE FOR THE PROJECT. THE SCHEDULE SHALL INDICATE WHICH AREAS ARE TO BE INVOLVED IN DEMOLITION, AutoCAD SHX Text CONSTRUCTION, OR ANY ACTIVITY. THE SCHEDULE SHALL INCLUDE DAY BY DAY DETAILS FOR THE UPCOMING TWO WEEK PERIOD. THE SCHEDULE SHALL BE
AutoCAD SHX Text
UPDATED AND SUBMITTED WEEKLY TO THE COR.
AutoCAD SHX Text
3. CONTRACTOR'S EMPLOYEES SHALL BE SUBJECT TO PRE-SCREENING AND/OR BADGING AT THE DISCRETION OF THE VA. A JOB FOREMAN OR
AutoCAD SHX Text SUPERVISOR SHALL BE PRESENT AT THE JOB SITE AT ANY TIME IN WHICH THE CONTRACTOR IS WORKING. THE FOREMAN OR SUPERVISOR SHALL BE
AutoCAD SHX Text
AVAILABLE FOR CONTACT BY THE COR VIA TELEPHONE AT ALL WORKING HOURS.
AutoCAD SHX Text
4. WORK HOURS RESTRICTIONS
AutoCAD SHX Text
5. ANY SYSTEM OUTAGES, INCLUDING FIRE ALARM SYSTEM OUTAGES, SHALL BE COORDINATED WITH THE COR IN WRITING AT LEAST ONE WEEK PRIOR TO
AutoCAD SHX Text OUTAGE. INDIVIDUAL OUTAGES SHALL NOT EXCEED 24 HOURS. FIRE WATCH FOR FIRE ALARM OUTAGE SHALL BE PROVIDED BY THE CONTRACTOR.
AutoCAD SHX Text
6. CONTRACTOR SHALL BE PERMITTED TO STORE MATERIALS, AT THE CONTRACTOR'S RISK, ON THE JOB SITE AT LOCATIONS AND IN CONTAINERS AS
AutoCAD SHX Text APPROVED BY THE COR. THE VA SHALL NOT BE RESPONSIBLE FOR SECURITY, LOSS, OR DAMAGE TO SUCH MATERIALS.
AutoCAD SHX Text
7. WORK IS TO BE PERFORMED IN OCCUPIED AREAS. CONTRACTOR SHALL MINIMIZE DISRUPTION, NOISE, AND DEBRIS. CONTRACTOR SHALL REMOVE ALL
AutoCAD SHX Text DEBRIS RESULTING FROM THIS WORK DAILY, TO INCLUDE BROOM-CLEANING OF ALL DRY-DEBRIS AND MOPPING OF ANY ARE WET BY THIS WORK. ANY
AutoCAD SHX Text CEILING TILES REMOVED OR BROKEN AS A RESULT OF THIS WORK SHALL BE REPLACED AT THE END OF EACH DAY. CONTRACTOR SHALL NOT USE MORE
AutoCAD SHX Text
THAN ONE HALF OF ANY CORRIDOR WIDTH AT ANY TIME.
AutoCAD SHX Text
9. A MOBILE CONTAINMENT SYSTEM SHALL BE USED FOR REMOVAL OF CEILING TILES AND ANY DUST PRODUCING ACTIVITY.
AutoCAD SHX Text DRILLING AND CONCRETE CUTTING OPERATIONS SHALL REQUIRE TOOLS TO BE EQUIPPED WITH POWER-DUSTCOLLECTION EQUIPMENT WITH HEPA FILTERS.
AutoCAD SHX Text
10. DIMENSIONS AND LOCATION OF ALL EQUIPMENT INDICATED IN THESE DRAWINGS ARE APPROXIMATE AND ARE FOR GRAPHIC REPRESENTATION ONLY.
AutoCAD SHX Text CONTRACTOR IS RESPONSIBLE FOR FILED VERIFICATION AND ADJUSTMENT AS NEEDED TO MEET ALL CRITERIA.
AutoCAD SHX Text
11. NEW EQUIPMENT SHALL BE FLUSH MOUNTED IN FINISHED AREAS AND SURFACE MOUNTED IN ALL OTHER AREAS. NEW CONDUIT IS TO BE CONCEALED
AutoCAD SHX Text
IN FINISHED AREAS AND SURFACE MOUNTED IN UNFINISHED AREAS.
AutoCAD SHX Text
12. FIRE PARTITION, SMOKE PARTITIONS AND SMOKE TIGHT WALLS ARE AS INDICATED IN THE DRAWINGS. IN ADDITION, FLOOR CONSTRUCTION IS 2 HOUR FIRE RATED.
AutoCAD SHX Text CONTRACTOR SHALL REPAIR ALL PENETRATIONS OF SMOKE AND FIRE RATED CONSTRUCTION IN ACCORDANCE WITH THE SPECIFICATIONS. A DETAILED LOG OF
AutoCAD SHX Text ALL SUCH PENETRATIONS SHALL BE PREPARED IN CHART FORM AND MAINTAINED BY THE CONTRACTOR. THE LOG SHALL INDICATE THE FOLLOWING
AutoCAD SHX Text INFORMATION, IN CHART FORM: LOCATION OF PENETRATION, TYPE OF FIRE OR SMOKE RATING, TYPE OF SEALANT OR THROUGH-STOP PENETRATION SYSTEM
AutoCAD SHX Text REPAIR USED, DATE SEALED, NAME OF CONTRACTOR EMPLOYEE PERFORMING WORK, DATE AND SIGNATURE OF CONTRACTOR SUPERVISOR CONFIRMING
AutoCAD SHX Text OBSERVATION OF REPAIR OF EACH REPAIR, BLANK SPACES AVAILABLE FOR DATE AND SIGNATURE OF VERIFICATION BY COR OR A/E. THE LOG SHALL BE
AutoCAD SHX Text CONTINUALLY UPDATED BY THE CONTRACTOR, SHALL BE AVAILABLE AT ALL TIMES TO THE COR, AND SHALL BE SUBMITTED WEEKLY BY THE CONTRACTOR TO
AutoCAD SHX Text
THE COR.
AutoCAD SHX Text
13. THE WORK INCLUDES INTERCONNECTION WITH ELEVATOR CONTROLS. CONTRACTOR SHALL ARRANGE, COORDINATE, AND PAY FOR WORK BY A
AutoCAD SHX Text
VA-SELECTED AND APPROVED ELEVATOR CONTRACTOR TO PERFORM THAT WORK.
AutoCAD SHX Text
1. ALL NEW WIRING SHALL BE IN METAL CONDUIT. EMT AND FLEXIBLE METAL CONDUIT MAY BE USED IN ACCORDANCE WITH THE SPECIFICATIONS.
AutoCAD SHX Text SEPARATE CONDUITS SHALL BE PROVIDED FOR PRIMARY POWER WIRING, FIRE ALARM INDICATING CIRCUITS, AND FIRE ALARM INITIATING CIRCUITS.
AutoCAD SHX Text
2. ALL NEW FIRE ALARM CONDUIT SHALL BE FACTORY PAINTED RED PRIOR TO INSTALLATION.
AutoCAD SHX Text
3. NEW AND EXISTING CONDUIT IS NOT SHOWN ON THE DRAWINGS.
AutoCAD SHX Text
4. EXISTING CONDUIT IS TO BE REMOVED WHEREVER ACCESSIBLE, EXCEPT AS NOTED. NON ACCESSIBLE CONDUIT, SUCH AS CONDUIT BURIED WITHIN A
AutoCAD SHX Text WALL CAVITY, IS TO BE CUT OFF AT A POINT ADJACENT TO ACCESS. EXISTING EXPOSED CONDUIT AND EXISTING CONDUIT BETWEEN DROP-IN CEILING TILES
AutoCAD SHX Text AND THE FLOOR SLAB ABOVE IS CONSIDERED ACCESSIBLE. IN LOCATIONS WHERE EXISTING WALL MOUNTED DEVICES HAVE BEEN REMOVED THE EXISTING
AutoCAD SHX Text
5. NEW CONDUIT SHALL BE
AutoCAD SHX Text 3/4"
AutoCAD SHX Text INCH MINIMUM AND SHALL BE PROVIDED AND INSTALLED AS REQUIRED BT THE DRAWINGS, SPECIFICATIONS AND
AutoCAD SHX Text
MANUFACTURERS REQUIREMENTS. CONDUIT RISERS SHALL BE MINIMUM 2 INCH.
AutoCAD SHX Text 6.
AutoCAD SHX Text
1. ALARM OUTPUT SHALL BE AUTOMATIC DIGITIZED VOICE, TONES, AND STROBES AS INDICATED:
AutoCAD SHX Text HEALTHCARE BUILDINGS OUTPUT WITHIN THE ZONE OF ALARM SHALL BE EVACUATION ALARM TEMPORAL PATTERN AND ACTIVATION OF STROBES IN THE ZONE
AutoCAD SHX Text OF ALARM. AUDIBLE DEVICES SHALL OPERATE FOR FIVE MINUTES THEN STOP. STROBES SHALL OPERATE UNTIL MANUALLY RESET AT THE FACP.
AutoCAD SHX Text OUTPUT IN ALL OTHER ZONES AND IN ALL OTHER BUILDINGS SHALL BE AUDIBLE AUTOMATIC VOICE NOTIFICATION WITH NO ACTIVATION OF STROBES IN THOSE AREAS.
AutoCAD SHX Text THE VOICE NOTIFICATION SHALL BE PRECEDED BY A TONE ALERT FOLLOWED BY THREE ROUNDS OF A VOICE MESSAGE. THE VOICE MESSAGE SHALL BE AS
AutoCAD SHX Text FOLLOWS: "CODE RED, ____ FLOOR, ____ WING, WITH THE FLOOR NUMBER AND WING DESIGNATION SOUNDED AS APPLICABLE. ONLY THE
AutoCAD SHX Text VOICE ALERT SHALL BE ANNOUNCED IN THREE ROUNDS. THE TONE ALERT SHALL SOUND ONLY ONCE.
AutoCAD SHX Text MANUAL OPERATION OF THE VOICE SYSTEM SHALL OVERRIDE ALL AUTOMATIC VOICE MESSAGES IN THE SYSTEM.
AutoCAD SHX Text OTHER AUTOMATIC RESPONSES AND ACTIVATIONS SHALL BE AS INDICATED IN THE INPUT/OUTPUT MATRIX IN THE DRAWINGS.
AutoCAD SHX Text ALARM ZONES IN HEALTHCARE BUILDINGS 1 AND 40 SHALL STRICTLY COORDINATE WITH EXISTING SMOKE ZONES. SMOKE ZONES ARE DESIGNATED AND SEPARATED
AutoCAD SHX Text VIA SMOKE AND FIRE BARRIER PARTITIONS. HEALTHCARE ALARM ZONES ARE SHOWN ON THE FLOOR PLAN. ALARM ZONES IN NON HEALTHCARE BUILDINGS
AutoCAD SHX Text
2. NON HEALTHCARE BUILDINGS ALARM OUTPUT SHALL BE CONTINUOUS SOUNDING OF TEMPORAL PATTERN GENERAL ALARM AND
AutoCAD SHX Text CONTINUOUS ACTIVATION OF ALL STROBES THROUGHOUT THE BUILDING IN WHICH THE ALARM ACTIVATED UNTIL RESET AT THE FACP WITHIN THE BUILDING OF
AutoCAD SHX Text ALARM. ALARM OUTPUT IN ALL OTHER BUILDINGS SHALL BE CODE RED BUILDING. OTHER AUTOMATIC RESPONSES AND ACTIVATIONS SHALL BE AS INDICATED
AutoCAD SHX Text
3. EXISTING SPRINKLER VALVE TAMPER SWITCHES, SPRINKLER WATER FLOW SWITCHES MAY REMAIN AND BE
AutoCAD SHX Text CONNECTED TO THE NEW FIRE ALARM SYSTEM AT THE OPTION OF THE CONTRACTOR. IF REUSED AS INDICATED, ALL SUCH DEVICES SHALL BE THE FULL
AutoCAD SHX Text RESPONSIBILITY OF THE CONTRACTOR AND SHALL BE WARRANTED BY THE CONTRACTOR AS NEW.
AutoCAD SHX Text
4. ALL EXISTING SMOKE DUCT DETECTORS ARE TO BE REPLACED. INTERCONNECTION OF THOSE DEVICES WITH OTHER EXISTING EQUIPMENT, SUCH AS AIR
AutoCAD SHX Text HANDLERS, DAMPERS, AND OTHER DEVICES IS TO BE IN ACCORDANCE WITH THE CURRENT ARRANGEMENT AND IS TO ACCOMPLISH THE SAME RESPONSE AS
AutoCAD SHX Text
THE CURRENT ARRANGEMENT.
AutoCAD SHX Text
5. MANUAL FIRE ALARM STATIONS INDICATED TO BE IN APPROXIMATELY THE SAME LOCATION AS EXISTING MANUAL FIRE ALARM STATIONS, AND FOR WHICH
AutoCAD SHX Text THE EXISTING MOUNTING HEIGHT IS WITHIN 4 INCHES OF THE SPECIFIED HEIGHT OF 48 INCHES, MAY BE INSTALLED AS INDICATED IN THE DRAWING DETAILS, AutoCAD SHX Text
USING EXISTING CONDUIT WITH THE WALL CAVITY, AND THE EXISTING BACK BOX.
AutoCAD SHX Text
6. SMOKE DETECTORS FOR DOOR RELEASE SHALL BE INSTALLED WITHIN FIVE FEET OF THE DOOR EXCEPT AS NOTED.
AutoCAD SHX Text
7. VALVE TAMPER AND WATER FLOW SWITCHES SHALL BE COORDINATED WITH SMOKE ZONE PROTECTED BY THAT PORTION OF THE SPRINKLER SYSTEM FOR
AutoCAD SHX Text
ALARM ACTIVATION AND CUSTOM LABEL.
AutoCAD SHX Text
8. IN ADDITION TO SHOP DRAWINGS REQUIRED BY THE SPECIFICATIONS, PRIOR TO BEGINNING WORK, CONTRACTOR SHALL SUBMIT, IN ACCORDANCE WITH
AutoCAD SHX Text DRAWING SUBMITTAL REQUIREMENTS, A SEPARATE SET OF DRAWINGS INDICATING THE LOCATION OF ALARM ZONES COORDINATED WITH SMOKE ZONES.
AutoCAD SHX Text
9. CARE SHALL BE TAKEN TO PROGRAM ALL DEVICES TO BE ASSOCIATED WITH THE PROPER ZONE. IN PARTICULAR, SPECIAL ATTENTION SHOULD BE GIVEN
AutoCAD SHX Text TO THE CORE STAIR MANUAL STATIONS TO PROGRAM THE ALARM SIGNAL AND VOICE ANNOUNCEMENT ACCORDING TO WHERE THE ZONE WHERE THE PULL
AutoCAD SHX Text
STATION IS LOCATED.
AutoCAD SHX Text ANY CEILING TILES REMOVED AS A RESULT OF THIS WORK SHALL BE RE-INSTALLED AT THE END OF EACH DAY. CONTRACTOR SHALL FURNISH AND INSTALL ANY TILE DAMAGED DURING CONSTRUCTION AT THE END OF EACH DAY. CONTRACTOR SHALL FURNISH AND INSTALL A NEW TILE WHERE EXISTING EQUIPMENT DAY. CONTRACTOR SHALL FURNISH AND INSTALL A NEW TILE WHERE EXISTING EQUIPMENT HAS BEEN REMOVED AS A RESULT OF THIS WORK. NEW CEILING TILES SHALL BE MEET ASTM E1264 FOR MINERAL FIBER, SHALL BE 3/4 PSF WEIGHT, MINIMUM, E1264 FOR MINERAL FIBER, SHALL BE 3/4 PSF WEIGHT, MINIMUM, PSF WEIGHT, MINIMUM, WITH WATER_BASED PAINTED FINISH MAXIMUM 10 G/L VOC; FORM 2 - WATER FELTED, MINIMUM 16 MM (5/8 INCH) THICK.MM (5/8 INCH) THICK.INCH) THICK.
AutoCAD SHX Text 8.
AutoCAD SHX Text
1. ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS TO BE DONE TO PREVENT CONTAMINATION OF DUCT SYSTEM.
AutoCAD SHX Text
2. COMPLETE ALL CRITICAL BARRIERS I.E. SHEETROCK, PLYWOOD, PLASTIC, TO SEAL AREA FROM NON-WORK AREA OR IMPLEMENT CONTROL CUBE METHOD
AutoCAD SHX Text
3. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SPACE, BY DISCHARGING AIR TO EXTERIOR. CONTRACTOR MAY USE TEMPORARY FAN THAT HAS A HEPA FILTER
AutoCAD SHX Text
WITH DISCHARGE TO EXTERIOR SPACE OUTSIDE MECHANICAL ROOM.
AutoCAD SHX Text
4. SEAL ALL HOLES, PIPES, CONDUITS, PENETRATIONS OR PUNCTURES WITHIN ENVELOPE OF WORK AREA IN APPROPRIATE MANNER.
AutoCAD SHX Text (CART WITH PLASTIC COVERING AND SEALED CONNECTION TO WORK SITE WITH HEAPA VACUUM PRIOR TO VACUUMING PRIOR TO EXIT) BEFORE CONSTRUCTION BEGINS.
AutoCAD SHX Text
5. CONSTRUCT "ANTE-ROOM" AND REQUIRE ALL PERSONNEL TO PASS THROUGH THIS ROOM SO THEY CAN BE VACUUMED USING A HEPA VACUUM CLEANER
AutoCAD SHX Text BEFORE LEAVING WORK SITE OR THEY CAN WEAR CLOTH OR PAPER COVERALLS THAT ARE REMOVED EACH TIME THEY LEAVE THE WORK SITE. KEEP AREA ADJACENT
AutoCAD SHX Text
TO THE "ANTE-ROOM" MOPPED CLEAN AS REQUIRED BY PROJECT TRAFFIC.
AutoCAD SHX Text
6. DURING DEMOLITION OR ANY DUST PRODUCING WORK OR WORK IN CEILING, DISPOSABLE SHOES OR SHOE COVERS MUST BE WORN AND REMOVED IN THE
AutoCAD SHX Text
"ANTE-ROOM" WHEN THE WORKER EXITS THE WORK SITE.
AutoCAD SHX Text
7. DO NOT REMOVE CONSTRUCTION BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT IS SIGNED OFF BY ENGINEER AND VA'S INFECTION CONTROL
AutoCAD SHX Text
DEPARTMENT, AND THOROUGHLY CLEANED BY VA'S ENVIRONMENTAL SERVICES DEPARTMENT.
AutoCAD SHX Text
8. PROVIDE DUST "STICKY" MAT ENTRANCE/EXIT OF CONSTRUCTION AREA AND REPLACE OR CLEAN WHEN NO LONGER EFFECTIVE.
AutoCAD SHX Text
9. KEEP AREA BROOM CLEAN AND REMOVE DEBRIS DAILY IN MANNER IN MANNER/PATH AS NOTED.
AutoCAD SHX Text
10. REMOVE BARRIER MATERIAL CAREFULLY TO MINIMIZE SPREADING OF DIRT AND DEBRIS ASSOCIATED WITH CONSTRUCTION.
AutoCAD SHX Text
11. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS.
AutoCAD SHX Text
12. COVER TRANSPORT RECEPTACLES OR CARTS, TAPE COVERING UNLESS SOLID LID.
AutoCAD SHX Text
13. VACUUM WORK AREA WITH HEPA FILTERED VACUUM.
AutoCAD SHX Text
14. WET MOP WORK AREA WITH DISINFECTANT.
AutoCAD SHX Text
15. REMOVE ISOLATION OF HVAC SYSTEMS IN AREAS WHERE WORK IS BEING PERFORMED.
AutoCAD SHX Text
16. WIPE CASEWORK AND HORIZONTAL SURFACES AT COMPLETION OF PROJECT.
AutoCAD SHX Text
1. CONTRACTOR IS TO INSTALL BUILDING 1 NEW FIRE ALARM CONTROL PANELS.
AutoCAD SHX Text
2. INSTALLATION OF FIELD EQUIPMENT SHALL BEGIN ON THE HIGHEST FLOOR LEVEL OF BUILDING 1 WORKING DOWNWARD.
AutoCAD SHX Text
3. AFTER INSTALLATION COMPLETION OF ALL FLOOR LEVELS IN BUILDING 1, CONTRACTOR SHALL BEGIN INSTALLATION IN THE IDENTIFIED PROJECT OUTBUILDINGS.
AutoCAD SHX Text
4. NEW FIRE ALARM SYSTEM SHALL BE INSTALLED AND COMPLETELY OPERATIONAL FOR A MINIMUM OF 30 DAYS PRIOR TO THE REMOVAL OF THE OLD SYSTEM.
AutoCAD SHX Text PROVIDE AND INSTALL NEW 120 VOLT POWER SUPPLY CIRCUITS FOR ALL NEW EQUIPMENT NEEDING 120 VOLT POWER SUPPLY, INCLUDING BUT NOT
AutoCAD SHX Text LIMITED TO FIRE ALARM CONTROL PANELS, OPERATOR WORK STATIONS, FIRE COMMAND CENTER, PRINTERS. REFER TO DRAWINGS FOR LOCATION OF
AutoCAD SHX Text NEAREST EXISTING ELECTRICAL PANELS HAVING AVAILABLE SPACE. IF EXISTING ELECTRICAL PANEL IS NOT CONNECTED TO EMERGENCY POWER OR
AutoCAD SHX Text IF A SPARE CIRCUIT IS NOT PRESENT CONTRACTOR SHALL CONNECT TO THE NEXT NEAREST PANEL. REFER TO SPECIFICATIONS FOR CIRCUITS
AutoCAD SHX Text REQUIRED TO BE CONNECTED TO POWER SUPPLY HAVING EMERGENCY BACK UP OR FOR CIRCUITS REQUIRED TO BE A SPECIFIED LIFE SAFETY
AutoCAD SHX Text
CIRCUIT.
AutoCAD SHX Text
IN THE INPUT/OUTPUT MATRIX IN THE DRAWINGS.
AutoCAD SHX Text
1. CEILING HEIGHT IN BUILDINGS 1, 11, 30, AND 32 IS 90" - 97", UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
2. HEIGHT FROM CEILING TO DECK IN BUILDINGS 1, 11, 30, AND 32 IS 32" - 45", UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
3. HEIGHT FROM FLOOR TO DECK IN BUILDINGS 1, 11, 30, AND 32 IS 120" - 141", UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
4. CEILING HEIGHT IN BUILDING 40 IS 107" - 109", UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
5. HEIGHT FROM CEILING TO DECK IN BUILDING 40 IS 68" - 88", UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
6. HEIGHT FROM FLOOR TO DECK IN BUILDING 40 IS 176" - 197", UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
7. CEILING TYPE IS 2' X 4' ACOUSTICAL CEILING TILE, UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
8. AREAS WITH VERY HEAVY CONGESTION ABOVE CEILING SPACE ARE NOTED.
AutoCAD SHX Text
9. WALL TYPE IN BUILDING 1 IS CLAY TILE WITH PARGING COAT, UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
10. WALL TYPE IN BUILDINGS 5, 11, 30, 32, AND 40 IS GYPSUM WALL BOARD, UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
11. WALL FINISH IS PAINT, UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
12. FLOORS ARE CONCRETE, WAFFLE SLAB, OR CONCRETE OVER METAL PAN DECK, UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
13. MECHANICAL SPACES ARE OPEN TO DECK ABOVE.
AutoCAD SHX Text
BACKBOX SHALL BE COVERED BY A BLANK STAINLESS-STEEL COVER PLATE.
AutoCAD SHX Text
WITHOUT SMOKE COMPARTMENTS SHALL BE CONFIGURED WITH ONE ALARM ZONE PER FLOOR.
AutoCAD SHX Text
10. STROBES SHALL BE MINIMUM 15 CANDELA IN TOILET ROOMS AND 75 CANDELA IN ALL OTHER AREAS UNLESS OTHERWISE NOTED.
AutoCAD SHX Text ALL NEW DEVICES SHALL BE TAGGED NOT IN SERVICE UNTIL THE 30 DAY OPERATIONAL PERIOD IS COMPLETED AND EXISTING DEVICES HAVE BEEN REMOVED.
AutoCAD SHX Text
STROBES SHALL BE SYNCHRONIZED AS REQUIRED BY NFPA 72.
AutoCAD SHX Text A. NORMAL CONSTRUCTION HOURS (WORKDAY) 4:00PM TO 6:00AM MONDAY THROUGH FRIDAY EXCEPT THE FOLLOWING:
AutoCAD SHX Text WORK AFFECTING DIALYSIS, SPS, AND KITCHEN OPERATIONS SHALL BE PERFORMED SATURDAY 10:00PM TO 3:00AM.
AutoCAD SHX Text WORK AFFECTING IN-PATIENT ROOMS SHALL BE PERFORMED SATURDAYS 10:00AM TO 4:00PM SUNDAY.
AutoCAD SHX Text WORK AFFECTING THE OPERATING ROOMS SHALL BE PERFORMED SATURDAYS 10:00AM TO NOON SUNDAY. THIS ALLOWS TIME FOR THE VA TO
AutoCAD SHX Text
TERMINAL CLEANING THE OPERATING ROOMS AND BE READY FOR SURGERIES THE NEXT DAY.
AutoCAD SHX Text B. NORMAL CONSTRUCTION WORK HOURS CAN ONLY BE MODIFIED WITH WRITTEN APPROVAL OF THE VA CONTRACTING OFFICER.
AutoCAD SHX Text C. NO WORK BY THE CONTRACTOR ON FEDERAL HOLIDAYS, AND NO WORK ON THE ASSOCIATED WEEKEND WHEN THE FEDERAL HOLIDAY IS ON THE
AutoCAD SHX Text
RESPECTIVE MONDAY OR FRIDAY.
AutoCAD SHX Text D. ANY WORK INCLUDING, BUT NOT LIMITED TO: NOISE, VIBRATION, DUST, ODORS, CORE DRILLING, HAMMER-DRILLING, SAW-CUTTING, EQUIPMENT MOVING
AutoCAD SHX Text IN PUBLIC CORRIDORS, OR SIMILAR NOISE-PRODUCING ACTIVITIES ADJACENT TO A PATIENT ROOM (FLOOR ABOVE AND BELOW INCLUDED) SHALL BE
AutoCAD SHX Text
PERFORMED WHEN SUCH ROOM IS UNOCCUPIED.
AutoCAD SHX Text
E. CRANE LIFTS SHALL BE DURING LOW PATIENT TIME AND PERFORMED SUNDAYS.
AutoCAD SHX Text F. ANY WORK THAT CLOSES DRIVE AISLES, CLOSES BUILDING ENTRIES OR CLOSES PUBLIC CORRIDORS SHALL BE DURING LOW PATIENT TIME AND PERFORMED SUNDAYS.
AutoCAD SHX Text
FIRE ALARM DETAILS
AutoCAD SHX Text G-002
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Approved: Project Director
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Location
AutoCAD SHX Text Checked
AutoCAD SHX Text Building Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Office of Construction and Facilities Management
AutoCAD SHX Text
ENGINEERS + CONSULTANTS:
AutoCAD SHX Text 537-16-101
AutoCAD SHX Text
CHICAGO, ILLINOIS
AutoCAD SHX Text
FIRE ALARM CORRECTIONS
AutoCAD SHX Text
TCG
AutoCAD SHX Text
DW/JW/BR
AutoCAD SHX Text 06/04/2020
AutoCAD SHX Text
FINAL - CONSTRUCTION DOCUMENTS
AutoCAD SHX Text
SITE PLAN:
AutoCAD SHX Text
OGDEN AVENUE
AutoCAD SHX Text
POLK STREET
AutoCAD SHX Text
DAMEN AVENUE
AutoCAD SHX Text
TAYLOR STREET
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
ENGINEERS + CONSULTANTS:
AutoCAD SHX Text
SEAL
AutoCAD SHX Text 01, 05, 06, 11, 15, 18, 21, 26
AutoCAD SHX Text
27, 30, 32/TMB, 40, 42
AutoCAD SHX Text Updated
AutoCAD SHX Text 01/13/2021