Attach V - RFI - Powergen.pdf

PDF 258 KB Posted

Attached to
Z1DA--Upgrade Campus Electrical Systems. Project No. 610A4-23-101.
Solicitation number
36C25026B0006_1
Issued by

About this file

This is a Request for Information (RFI) and Government Response document for federal contract solicitation 36C25026B0006, Project Number 610A4-23-101, issued by the Department of Veterans Affairs, Network 10 Contracting Office. The project involves upgrading the campus electrical system at VA Northern Indiana Healthcare System located at 2121 Lake Ave, Fort Wayne, Indiana 46805-5100.

Powergen Controls submitted a clarification question regarding the acceptable UL listing for switchboards associated with substations and paralleling systems. The contractor requested confirmation that UL 891 compartmentalized switchboards would be acceptable as an alternative to UL 1558, asserting that UL 891 construction could meet all specified functional, performance, protection, monitoring, and safety requirements including circuit breaker specifications, EPMS metering and monitoring, control and safety functions, and compliance with NFPA 70, NFPA 70E, and applicable VA standards. The Government Response, posted with Amendment No. Three to the original solicitation and signed by Matt Graham (HEAPY) on 1/30/26, explicitly rejected this request, stating: "UL 891 is NOT permitted. Comply with specifications." This response clarifies that contractors must use UL 1558 construction and cannot deviate to UL 891 alternatives regardless of claimed functional equivalency.

View the file

Other files

File Type Posted
Attach I - RFI CM Buck 3.pdf PDF
36C25026B0006 0010.pdf PDF
Attach I - VAAR 852.236-92.pdf PDF
36C25026B0006 0009.pdf PDF
36C25026B0006 0008.pdf PDF
Attach IV - Revised Bid Schedule 2.24.2026.pdf PDF
Attach I - Addendum 1 - Summary.docx DOCX document
Attach III - Addendum 1 - Drawings.zip ZIP file
Attach V - RFI CMBuck Rd. 2 - Revised.pdf PDF
Attach II - Addendum 1 - Specs.zip ZIP file
36C25026B0006 0007.pdf PDF
36C25026B0006 0006.pdf PDF
36C25026B0006 0005.pdf PDF
Attach II - Bid Schedule Revised 2.11.2026.pdf PDF
Attach I - RFI Response CMBuck 2.pdf PDF
36C25026B0006 0004.pdf PDF
Attach I - RFI - CMBuck.doc DOC document
Attach II - RFI - Cornerstone.doc DOC document
Attach IV - RFI - IMS.doc DOC document
Attach VII - RFI Valiant.docx DOCX document
36C25026B0006 0003.pdf PDF
Attach III - RFI - Geotech.pdf PDF
Attach VI - RFI Richards.docx DOCX document
36C25026B0006 0002.pdf PDF
Attach I - Wage Determination 1.30.2026.txt TXT text file
Attach III - Notice to Bidders on Bid Depth for Piles.docx DOCX document
Attach VI - 3W Data Closet Example.pdf PDF
Attach VII - IT standards ver 3.0 21 Aug 20.pdf PDF
Attach IV - Fort Wayne Generator Information.pdf PDF
Attach VIII - Fort Wayne PA information.pdf PDF
Attach II - Final Geotechnical Report - 610A4-23-101.pdf PDF
Attach V - Fort Wayne ATS information.pdf PDF
Attach II - Site Visit Notes.pdf PDF
Attach I - Sign in Sheet.pdf PDF
36C25026B0006 0001.pdf PDF
Attach VII - Specs Combined 610A4-23-101.pdf PDF
Attach IX - Wage Determination - Allen County 12.5.25.txt TXT text file
Attach X - VAAR 852.219-75 - 610A4-23-101.pdf PDF
Attach I - SOW - 610A4-23-101.pdf PDF
Attach IV - Appendix C.pdf PDF
Attach VI - Drawings Combined 610A4-23-101.pdf PDF
Attach II - Appendix A.pdf PDF
Attach III - Appendix B.pdf PDF
IFB 36C25026B0006_1.pdf PDF
Attach V - Appendix D.pdf PDF
Attach VIII - VHA Directive 1192-01.pdf PDF
Attach XI - RFI 610A4-23-101.doc DOC document
Show all 47

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REQUEST FOR INFORMATION (RFI)

36C25026B0006

PROJECT NUMBER: 610A4-23-101 Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents. When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.

PROJECT TITLE:

Upgrade Campus Electrical System

PROJECT LOCATION:

VA Northern Indiana

Healthcare System

2121 Lake Ave

Fort Wayne IN 46805-

TO: Brian Rosciszewski, Contract Specialist Department of Veterans Affairs Network 10 Contracting Office Brian.Rosciszewski@VA.gov

INFORMATION NEEDED: Write each in the form of a question. Use one document for all questions. Specify any referenced specs/drawings. Submit all questions on one document only to Brian.Rosciszewski@VA.gov.

Subject of the email must be: “RFI – {Solicitation #} – Firm Name”

1. We respectfully request confirmation regarding the acceptable UL listing for the switchboards associated with the substations and paralleling systems for this project.

Based on our review of the contract documents, specifications, and drawings, all functional, performance, protection, monitoring, and safety requirements are clearly defined. For this application, UL 891 compartmentalized switchboards can be designed and constructed to fully comply with all specified requirements, including:

• Specified circuit breaker frames, ratings, and interrupting capacities

• Complete EPMS metering, monitoring, and communications

• All control, protection, interlocking, and safety functions

• Compliance with NFPA 70, NFPA 70E, and all applicable VA standards

The proposed UL 891 construction would maintain full compartmentalization, accessibility, and safety, and would not result in any reduction in performance, reliability, or code compliance when compared to UL 1558 construction for the specified application.

Accordingly, we request confirmation that UL 891 compartmentalized switchboards are acceptable for the substations and paralleling switchboards under the conditions outlined above.

This request is limited solely to confirmation of the acceptable UL listing and does not propose any deviation from the specified technical, functional, or safety requirements.

Thank you for your guidance to ensure full compliance with the project requirements.

Contractor Name Contact Info (Phone & Address)

Powergen Controls

Attn: Juan Pablo Restrepo

(832) 235 6007

8600 Telephone Rd

Houston, TX 77061 mailto:Brian.Rosciszewski@VA.gov

Government Response: Posted with amendment no. three to the original solicitation.

REPLY FROM: DATE:

ATTACHMENTS: COPY TO:

Matt Graham Text Box UL 891 is NOT permitted. Comply with specifications. Matt Graham, HEAPY 1/30/26