Attach III - RFI - Geotech.pdf

PDF 636 KB Posted

Attached to
Z1DA--Upgrade Campus Electrical Systems. Project No. 610A4-23-101.
Solicitation number
36C25026B0006_1
Issued by

About this file

This is a Request for Information (RFI) issued by the Department of Veterans Affairs Network 10 Contracting Office for the Upgrade Campus Electrical System project at VA Northern Indiana Healthcare System in Fort Wayne, Indiana. The RFI number is 36C25026B0006, and the project number is 610A4-23-101. The document was issued on 1/9/2026 and responses will be provided by amendment(s) to SAM.gov or via email.

Geotech Services, Inc submitted three questions requesting: (1) availability of a geotechnical report for the project; (2) the elevation of the top of the sheet pile wall; and (3) a bid length for the helical piles for the sheet pile wall. The Government's responses indicate that structural engineering design was previously performed based on geotechnical information available at the time of design, with any updated or revised geotechnical report to be provided by the Geotechnical Engineer of Record for review. Sheet pile wall elevations are identified on drawing sheet CG101. Final/bid helical pile lengths will be determined by the Geotechnical Engineer and the helical pile specialty contractor based on soil conditions, installation criteria, and required capacities. Contractors submitting questions are required to reference specific specification and/or solicitation sections or drawing numbers to ensure timely Government responses.

View the file

Other files

File Type Posted
Attach I - RFI CM Buck 3.pdf PDF
36C25026B0006 0010.pdf PDF
36C25026B0006 0009.pdf PDF
Attach I - VAAR 852.236-92.pdf PDF
36C25026B0006 0008.pdf PDF
Attach IV - Revised Bid Schedule 2.24.2026.pdf PDF
Attach I - Addendum 1 - Summary.docx DOCX document
Attach III - Addendum 1 - Drawings.zip ZIP file
Attach V - RFI CMBuck Rd. 2 - Revised.pdf PDF
Attach II - Addendum 1 - Specs.zip ZIP file
36C25026B0006 0007.pdf PDF
36C25026B0006 0006.pdf PDF
Attach II - Bid Schedule Revised 2.11.2026.pdf PDF
36C25026B0006 0005.pdf PDF
Attach I - RFI Response CMBuck 2.pdf PDF
36C25026B0006 0004.pdf PDF
Attach II - RFI - Cornerstone.doc DOC document
Attach I - RFI - CMBuck.doc DOC document
Attach IV - RFI - IMS.doc DOC document
Attach V - RFI - Powergen.pdf PDF
Attach VII - RFI Valiant.docx DOCX document
36C25026B0006 0003.pdf PDF
Attach VI - RFI Richards.docx DOCX document
Attach I - Wage Determination 1.30.2026.txt TXT text file
Attach III - Notice to Bidders on Bid Depth for Piles.docx DOCX document
Attach VI - 3W Data Closet Example.pdf PDF
Attach VII - IT standards ver 3.0 21 Aug 20.pdf PDF
36C25026B0006 0002.pdf PDF
Attach IV - Fort Wayne Generator Information.pdf PDF
Attach VIII - Fort Wayne PA information.pdf PDF
Attach II - Final Geotechnical Report - 610A4-23-101.pdf PDF
Attach V - Fort Wayne ATS information.pdf PDF
Attach II - Site Visit Notes.pdf PDF
Attach I - Sign in Sheet.pdf PDF
36C25026B0006 0001.pdf PDF
Attach I - SOW - 610A4-23-101.pdf PDF
Attach IV - Appendix C.pdf PDF
Attach VI - Drawings Combined 610A4-23-101.pdf PDF
Attach VII - Specs Combined 610A4-23-101.pdf PDF
Attach IX - Wage Determination - Allen County 12.5.25.txt TXT text file
Attach X - VAAR 852.219-75 - 610A4-23-101.pdf PDF
Attach II - Appendix A.pdf PDF
Attach III - Appendix B.pdf PDF
IFB 36C25026B0006_1.pdf PDF
Attach V - Appendix D.pdf PDF
Attach VIII - VHA Directive 1192-01.pdf PDF
Attach XI - RFI 610A4-23-101.doc DOC document
Show all 47

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REQUEST FOR INFORMATION (RFI)

36C25026B0006

PROJECT NUMBER: 610A4-23-101 Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents. When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.

PROJECT TITLE: Upgrade Campus Electrical System

PROJECT LOCATION:

VA Northern Indiana Healthcare System 2121 Lake Ave Fort Wayne IN 46805-

Contractor Name Contact Info (Phone & Address)

TO: Brian Rosciszewski, Contract Specialist Department of Veterans Affairs Network 10 Contracting Office Brian.Rosciszewski@VA.gov

INFORMATION NEEDED: Write each in the form of a question. Use one document for all questions. Specify any referenced specs/drawings. Submit all questions on one document only to Brian.Rosciszewski@VA.gov.

Subject of the email must be: “RFI – {Solicitation #} – Firm Name”

2.

3.

Government Response: RFI’s will be answered by amendment(s) issued to SAM.gov or via email.

REPLY FROM:

ATTACHMENTS:

DATE:

COPY TO:

Geotech Services, Inc 350 Golden Oak Parkway, Cleveland, Ohio 44146 Robert Modic 216-276-4953

Is there a geotechnical report available for this project?

Can the elevation of the top of the sheet pile wall be provided?

Can a bid length for the helical piles for the sheet pile wall be provided?

chelsey.gallion Text Box

1. Is there a geotechnical report available for this project?

Structural engineering design was performed based on the geotechnical report available at the time of design (attached). Any updated or revised geotechnical report shall be provided by the Geotechnical Engineer of Record for review and confirmation of design assumptions.

2. Can the elevation of the top of the sheet pile wall be provided?

The top of sheet pile wall elevations are called out on sheet CG101.

3. Can a bid length for the helical piles for the sheet pile wall be provided?

Structural design requirements for the sheet pile wall and supporting helical piles were based on the available geotechnical information at the time of design and the assumed maximum wall height. Final/bid helical pile lengths shall be determined by the Geotechnical Engineer and the helical pile specialty contractor based on soil conditions, installation criteria, and required capacities.

~AES Group, Inc.

VHADAYRosciB Typewritten Text

CG, FFE

VHADAYRosciB Typewritten Text 1/9/2026

VHADAYRosciB Text Box Responses posted as amendment no. three to the solicitation.