This is a Request for Information (RFI) document for Solicitation 36C25026B0006, Project Number 610A4-23-101, issued by the Department of Veterans Affairs Network 10 Contracting Office for the Upgrade Campus Electrical System project at VA Northern Indiana Healthcare System in Fort Wayne, Indiana. The RFI contains two contractor questions with government responses, addressing clarifications on MVSG Specification 26 13 13 requirements. The first question sought clarification on what hardware components should be included in the Future Compartment section, and the government confirmed that all referenced items including CTs, PTs, 700G relays, circuit breaker control switches, lockout devices, and fused control devices should be included. The second question clarified that both MVSG Future Generator input sections should be designated as "Prepared Spaces," with a note indicating missing text from the original specification.
The RFI was submitted to Brian Rosciszewski, Contract Specialist, with responses posted as an attachment to Amendment No. 3 of the solicitation, dated 2/6/26. Contractors submitting questions are required to reference specific specifications, solicitation sections, or drawing numbers and submit all inquiries in a single document with the email subject line formatted as "RFI - {Solicitation #} - Firm Name." This document serves as clarification supporting the larger electrical system upgrade project, which includes a 6,600 square foot addition to Building 1, three 600 kW standby generators, three emergency generators, three new unit substations, and associated automatic transfer switches.
View the file
Other files
Show all 47
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REQUEST FOR INFORMATION (RFI)
36C25026B0006
| PROJECT NUMBER: |
| 610A4-23-101 |
| Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents. When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner. |
| PROJECT TITLE: |
| Upgrade Campus Electrical System |
| PROJECT LOCATION: |
| VA Northern Indiana Healthcare System |
2121 Lake Ave
Fort Wayne IN 46805-5100
Contractor Name Contact Info (Phone & Address)
TO: Brian Rosciszewski, Contract Specialist Department of Veterans Affairs Network 10 Contracting Office
Brian.Rosciszewski@VA.gov INFORMATION NEEDED: Write each in the form of a question. Use one document for all questions. Specify any referenced specs/drawings. Submit all questions on one document only to Brian.Rosciszewski@VA.gov. Subject of the email must be: “RFI – {Solicitation #} – Firm Name”
1. Please clarify exactly what is required for MVSG Spec 26 13 13 – 2.1 A 8 – Future Compartment. Do you want any hardware items such as CT’s/PT’s, 700G relay, circuit breaker control switches lockout devices, fused control devices, etc.
2. Please clarify both MVSG Future Generator input sections should be “Prepared Spaces”.
Government Response: Posted as attachment to amendment no. three of the solicitation.
1. Yes, include all of those components please. MG, HEAPY 2/2/26.
2. Yes, both should be prepared spaces. Looks like text from one is missing on the single line. MG, HEAPY 2/2/26.
REPLY FROM:
NCO 10
DATE: 2/6/26
ATTACHMENTS:
COPY TO:
CM Buck & Associates
6850 Guin Rd
Indianapolis, IN 46268