Drawings_2020-07-15_reprint-3 of 3.pdf
PDF 5 MB Posted
- Attached to
- Y1DZ--Renovate Basement, Building 1 610A4-19-104
- Solicitation number
- 36C25021B0018
About this file
This document contains details for a federal contract solicitation to renovate a basement at a Veterans Health Administration facility. The solicitation requests contractors provide all labor, equipment, materials and supervision necessary to renovate space in the basement of Building 1 at the VA Northern Indiana Health Care System campus in Fort Wayne, Indiana. Renovations are needed for Environmental Management Services, Biomedical, Pharmacy, Mailroom, Engineering Services, Office of Information Technology, Graduate Medical Education, and Medical Imaging areas. The project is divided into three phases, with Phase I expected to take 300 days, Phase II expected to take 210 days, and Phase III expected to take 270 days. All work must be completed at the VA Northern Indiana Health Care campus located at 2121 Lake Ave, Fort Wayne, IN 46805.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
L
J
PB
J
P
P
J
R
OS
LS
P C
TC
H
T
1P 1 POLE (2P, 3P, 4P, ETC.)
A AMPERE
AC ABOVE COUNTER OR AIR
CONDITIONER
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPENER
AF ARC FAULT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT CIRCUIT INTERRUPTER
AHU AIR HANDLING UNIT
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
AMPL AMPLIFIER
ANNUN ANNUNCIATOR
APPROX APPROXIMATELY
AQ-STAT AQUASTAT
ARCH ARCHITECT, ARCHITECTURAL
AS AMP SWITCH
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BATT BATTERY
BD BOARD
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
C CONDUIT
CAB CABINET
CAT CATALOG
CATV CABLE TELEVISION
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CKT CIRCUIT
CLG CEILING
COMB COMBINATION
CMPR COMPRESSOR
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONTR CONTRACTOR
CONV CONVECTOR
CP CIRCULATING PUMP
CRT CATHODE-RAY TUBE
CT CURRENT TRANSFORMER
CTR CENTER
CU COPPER
DCP DOMESTIC WATER CIRCULATING PUMP
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DPR DAMPER
DS SAFETY DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EC ELECTRICAL CONTRACTOR
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EP ELECTRIC PNEUMATIC
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EXIST EXISTING
EXH EXHAUST
EXP EXPLOSION PROOF
FA FIRE ALARM
FABP FIRE ALARM BOOSTER POWER
SUPPLY PANEL
FACP FIRE ALARM CONTROL PANEL
FCU FAN COIL UNIT
FIXT FIXTURE
FLR FLOOR
FLUOR FLUORESCENT
FU FUSE
FUDS FUSED SAFETY DISCONNECT SWITCH
GA GAUGE
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT
INTERRUPTER
GFP GROUND FAULT PROTECTOR
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
GYP BD GYPSUM BOARD
HOA HANDS-OFF-AUTOMATIC SWITCH
HORIZ HORIZONTAL
HP HORSEPOWER
HPF HIGH POWER FACTOR
HT HEIGHT
HTG HEATING
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND
AIR CONDITIONING
HWP HYDRONIC WATER PUMP
IC INTERRUPTING CAPACITY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
I/W INTERLOCK WITH
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LOC LOCATE OR LOCATION
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MAX MAXIMUM
MAG.S MAGNETIC STARTER
M/C MOMENTARY CONTACT
MC MECHANICAL CONTRACTOR
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDC MAIN DISTRIBUTION CENTER
MDP MAIN DISTRIBUTION PANEL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MMS MANUAL MOTOR STARTER
MOA MULTIOUTLET ASSEMBLY
MSP MOTOR STARTER PANELBOARD
MSBD MAIN SWITCHBOARD
MT MOUNT
MT.C EMPTY CONDUIT
MTS MANUAL TRANSFER SWITCH
MTR MOTOR, MOTORIZED
N.C. NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NFDS NON-FUSED SAFETY
DISCONNECT SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
N.O. NORMALLY OPEN
NPF NORMAL POWER FACTOR
NTS NOT TO SCALE
OH OVERHEAD
OL OVERLOADS
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PE PNEUMATIC ELECTRIC
PED PEDESTAL
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
PP POWER POLE
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (CONDUIT)
PWR POWER
QUAN QUANTITY
RCPT RECEPTACLE
REQD REQUIRED
RM ROOM
RSC RIGID STEEL CONDUIT
RTU ROOF TOP UNIT
SC SURFACE CONDUIT
SEC SECONDARY
SHT SHEET
SIM SIMILAR
S/N SOLID NEUTRAL
SPEC SPECIFICATION
SPKR SPEAKER
SP SPARE
SR SURFACE RACEWAY
SS STAINLESS STEEL
SSW SELECTOR SWITCH
S/S STOP/START PUSHBUTTONS
STA STATION
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
ELECTRICAL ABBREVIATIONS LIST
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
TEL TELEPHONE
TERM TERMINAL
TL TWIST LOCK
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTC TELEPHONE TERMINAL CABINET
TV TELEVISION
TVTC TELEVISION TERMINAL CABINET
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UT UNDERGROUND TELEPHONE
UTIL UTILITY
UV UNIT VENTILATOR OR ULTRAVIOLET
V VOLT
VA VOLT-AMPERES
VDT VIDEO DISPLAY TERMINAL
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT
W/ WITH
WG WIRE GUARD
WH WATER HEATER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
@ AT
' FEET
" INCHES
# NUMBER
Ø PHASE
C CENTER LINE
P PLATE
RECEPTACLES, FURNITURE FEEDS
THE ABOVE MOUNTING ELEVATIONS ARE TO CENTER OF DEVICE AND SHALL BE ADHERED
TO UNLESS SPECIFICALLY NOTED OR DETAILED OTHERWISE ON THE DRAWINGS AND/OR
SPECIFICATIONS.
IN FLOOR JUNCTION BOXES FLUSH TO
FINISHED FLOOR (FF)
IN MASONRY CONSTRUCTION THE MOUNTING HEIGHTS SHALL BE USED FOR REFERENCE TO
THE NEAREST BLOCK OR BRICK COURSING.
COORDINATE THE INSTALLATION AND MOUNTING ELEVATIONS OF ALL EQUIPMENT, DEVICES,
CONTROLS AND APPURTENANCES WITH ARCHITECT AND ALL AFFECTED TRADES PRIOR TO
INSTALLATION. DOCUMENT ALL MOUNTING ELEVATIONS FOR ALL EQUIPMENT, DEVICES,
CONTROLS AND APPURTENANCES AT THE TIME OF SHOP DRAWING SUBMITTAL.
3.
2.
1.
0'-0"
1'-5" A.F.F.
STANDARD MOUNTING HEIGHTS
RECESSED LIGHTING FIXTURES, CEILING
MOUNTED RECEPTACLES, INDICATING LIGHTS,
ETC.
CEILING
ABOVE COUNTER DEVICES, GFI RECEPTACLES IN
RESTROOMS.
3'-6" A.F.F.
WALL SWITCHES, THERMOSTATS, CONTROL DEVICES,
TO CENTER OF BOX
3'-8" A.F.F.
TOP OF PANELBOARDS (<6'-0" TALL)6'-0" A.F.F.
TOP MOST PORTION OF OPERATING HANDLE OF
DISCONNECT SWITCHES / CIRCUIT BREAKERS
6'-6" A.F.F.
WALL MOUNTED LIGHTS IN STAIRS, MECH ROOMS,
ETC.
7'-0" A.F.F.
ADA INSTALLATION GUIDELINES
34"
46"
MAX.
(NOTE #2)
44"
MAX.
(FOR 20-25")
(NOTE #2)
10-24" 25" MAX.
48"
MAX.
(FOR 20")
(NOTE #2)
OBSTRUCTED HIGH
SIDE REACH
OBSTRUCTED HIGH
FORWARD REACH
48"
MAX.
(NOTE #2)
10"
MAX.
15"
MIN.
48"
MAX.
(NOTE #2)
15"
MIN.
OBSTRUCTED
SIDE REACH
OBSTRUCTED
FORWARD REACH
NOTES:
1. THESE GUIDELINES SHALL BE USED FOR THE INSTALLATION OF THE FOLLOWING DEVICES:
- WALL SWITCHES
-CONTROL SWITCHES
-RECEPTACLES
-VISUAL DISPLAY TOUCH PANELS
2. NOTE THAT THIS HEIGHT IS TO THE TOP-MOST PART OF THE DEVICE THAT AN OCCUPANT
REQUIRES ACCESS TO.
THIS PROJECT WILL REQUIRE SHUT-DOWNS TO THE NORMAL POWER SYSTEM OF THE HOSPITAL, WHICH WILL REQUIRE SECOND OR THIRD SHIFT WORK, AS WELL AS WEEKEND WORK. THE CONTRACTOR SHALL
COORDINATE THIS WORK WITH THE COR, AND PLAN HIS WORK ACCORDINGLY.
CONTRACTOR SHALL PROVIDE A MINIMUM TWO WEEKS WRITTEN NOTICE PRIOR TO ANY SHUT DOWN. NOTICE IS
TO INCLUDE BUT IS NOT LIMITED TO THE LOCATION, PANELS AND DURATION OF SHUT DOWN.
DURING ALL UTILITY SHUT-DOWNS OF THE NORMAL POWER SYSTEM, THE CONTRACTOR SHALL HAVE AN EMERGENCY GENERATOR ON SITE WITH 24 HOURS OF FUEL. THE CONTRACTOR SHALL HAVE SUITABLE TEMPORARY CABLES NEEDED TO PROVIDE EMERGENCY CONNECTIONS TO THE SWITCHGEAR IN THE EVENT
THERE IS A PROBLEM.
THE CONTRACTOR SHALL GENERATE A DETAILED METHOD OF PROCEDURE (MOP) DOCUMENT INDICATING HOW HE/SHE INTENDS TO PERFORM EACH STEP IN THE PROJECT. THIS MOP SHALL BE PRESENTED TO THE OWNER AND ENGINEER PRIOR TO STARTING THE PROJECT, FOR SIGN OFF.THE MOP MAY BE REVISED BASED ON CHANGES IN THE PROJECT CONSTRUCTION, ETC. AT ALL POINTS IN THE PROJECT THE COR SHALL BE MADE AWARE OF CHANGES TO THE MOP, AND A REVISED MOP SHALL BE PRESENTED TO THE COR AND ENGINEER
FOR SIGN OFF.
1.
UTILITY SHUTDOWNS
2.
3.
4.
RELAY
SYMBOL SYMBOL
ELECTRICAL SYMBOL LEGEND
J
2 POLE SINGLE THROW SW.
SINGLE POLE SW.
LIGHT ON CORD REEL (TYPE DENOTED)
LIGHTING CHANNEL WIRE (TYPE DENOTED)
DIMMER SWITCH
MOMENTARY CONTACT SWITCH
OCCUPANCY SENSOR SWITCH
EMERGENCY PUSH BUTTON
SINGLE RECEPT.
KEYED SWITCH
SPLIT DUPLEX RECEPT.
FOURPLEX RECEPT.
DUPLEX RECEPT.
RECEPT ON EMERGENCY CKT (DUPLEX SHOWN)
ISOLATED GROUND RECEPT (DUPLEX SHOWN)
240 VOLT RECEPT.
RECEPT ON DROP CORD (DUPLEX SHOWN)
RECEPT ON CORD REEL (DUPLEX SHOWN)
FLOOR RECEPT. (DUPLEX SHOWN)
TIMER SWITCH (1, 2, 4, 6, & 12 HOUR OPTIONS)
VACANCY SENSOR SWITCH
SW. W/PILOT
3-WAY SW.
4-WAY SW.
DESCRIPTION
WALL MOUNTED FLOODLIGHT (TYPE DENOTED)
POLE MOUNTED LIGHT (TYPE DENOTED)
RECESSED LIGHT (TYPE DENOTED)
SURFACE LIGHT (TYPE DENOTED)
EXIT SIGN (TYPE DENOTED)
SUSPENDED OR PENDANT LIGHT (TYPE DENOTED)
TRACK AND TRACK LIGHT (TYPES DENOTED)
SURFACE LINEAR LIGHT (TYPE DENOTED)
STRIP LIGHT (TYPE DENOTED)
EMERGENCY BATTERY LIGHT (TYPE DENOTED)
RECESSED LINEAR LIGHT (TYPE DENOTED)
POLE MOUNTED FLOODLIGHT (TYPE DENOTED)
FOURPLEX RECEPTACLE ON EMERGENCY CIRCUIT
LIGHT FIXTURE ON (EM) LIFE SAFETY BRANCH
LIGHT FIXTURE ON (EM) CRITICAL BRANCH
CIRCUIT BREAKER PANEL
DASHED SYMBOL INDICATES REMOVED
HALFTONE SYMBOL INDICATES EXISTING
SOLENOID VALVE
BUS DUCT WITH PLUG IN DISCONNECT (FUSED)
LIGHT LEVEL SENSOR - TYPE DENOTED
TIME CONTROL SWITCH (TIME SWITCH)
HUMIDISTAT
THERMOSTAT
PHOTOCELL
ENCLOSED CIRCUIT BREAKER
PRESSURE SWITCH
SAFETY DISC. SW. (FUSED)
SAFETY DISC. SW. (NON-FUSED)
COMB. MOTOR STARTER (FUSED)
POWER OR DISTRIBUTION PANEL
TRANSFORMER (TYPE DENOTED)
STATIC GROUND RECEPTACLE (TYPE DENOTED)
SPECIAL RECEPT. OR CONN. (SEE SCHEDULE)
JUNCTION BOX
PULL BOX
GROUND ROD (PLAN VIEW)
LIGHTNING PROTECTION AIR TERMINAL
SURGERY SERVICE COLUMN
CLOCK (TYPE DENOTED)
POWER POLE (OPEN OFFICE STYLE)
MULTIOUTLET ASSEMBLY (TYPE DENOTED)
DESCRIPTION
LIGHTNING PROTECTION CONDUCTOR SPLICE
UTILITY SERVICE POWER POLE (SITE)
OCCUPANCY SENSOR - TYPE DENOTED
FLOAT SWITCH
V D
VACANCY SENSOR DIMMER SWITCH
MULTI BUTTON LOW VOLTAGE SWITCHLV
K
M C
T V
S D
O S
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
B
IM
/1
F t.
W a y n e V
A M
C B a s e m e n t B ld g
/1
M
E P
C e n tr a l
.r v t
/1
/2
:2
:3
P
M
E001
ELEC SYMBOLS, ABBREVIATIONS, AND
GENERAL NOTESAE Works
209 SANDUSKY STREET
PITTSBURGH, PA 15212
412-287-7333
RENOVATE BASEMENT,
BUILDING 1
2121 LAKE AVE, FORT WAYNE, IN 46805
610A4-19-104
07/15/2020 BK TJR
BID DOCUMENTS
ELECTRICAL GENERAL NOTES
1 THE FOLLOWING GENERAL NOTES AS LISTED BELOW SHALL APPLY TO ALL ELECTRICAL REQUIREMENTS AS INDICATED ON ALL 'E' SERIES CONTRACT
DRAWINGS.
2 THE CONTRACTOR IS RESPONSIBLE FOR THE ENTIRE DOCUMENT SET. I.E. IF WORK IS SHOWN ON OTHER DRAWINGS AS "BY CONTRACTOR" THE CONTRACTOR
IS RESPONSIBLE FOR THAT WORK.
3 DRAWINGS FOR THIS WORK ARE DIAGRAMMATIC AND INTENDED TO CONVEY THE EXTENT, GENERAL ARRANGEMENT AND LOCATIONS OF THE WORK.
BECAUSE OF THE SCALE OF THE DRAWINGS, CERTAIN BASIC ITEMS SUCH AS ACCESS PANELS, CONDUITS, CABINET SIZES, PENETRATION SLEEVES, PULL BOXES, BACKBOXES AND JUNCTION BOXES MAY NOT BE SHOWN. INCLUDE ALL ITEMS WHERE REQUIRED BY CODE, MANUFACTURER AND RELATED
SPECIFICATION SECTIONS FOR THE PROPER INSTALLATION OF ALL WORK.
4 DUE TO SCALE OF THE DRAWINGS, ALL ELECTRICAL DEVICE SYMBOLS ARE SHOWN ON DRAWINGS AS CLOSE AS POSSIBLE TO THEIR INTENDED LOCATION.
CONTRACTOR SHALL COORDINATE IN THE FIELD THE PROPER INSTALLATION OF ALL EQUIPMENT, DEVICES, CONTROLS AND CONDUITS. REFER TO RELATED
SPECIFICATION SECTIONS FOR ADDITIONAL REQUIREMENTS.
5 COORDINATE WITH ALL TRADES AND SYSTEM INTEGRATORS ANY CONDITIONS RELATED TO THE INSTALLATION OF ALL SYSTEMS. THE CONTRACTOR SHALL COORDINATE WITH THE APPROPRIATE TRADE ALL INSTALLATION REQUIREMENTS IMPACTING THE PLACEMENT OF ALL SYSTEM COMPONENTS TO THE
SATISFACTION OF ALL CONCERNED TRADES.
6 COORDINATE EXACT LOCATION(S) OF ALL DATA AND TELEPHONE OUTLETS, ELECTRICAL RECEPTACLES WITH THE ARCHITECTURAL PLANS, FURNITURE PLANS
AND ALL AFFECTED TRADES PRIOR TO INSTALLATION.
7 ALL CONDUITS SHALL BE SIZED AND INSTALLED IN ACCORDANCE WITH NFPA 70 AND PROJECT SPECIFICATIONS. ALL CONDUITS SHALL BE A MINIMUM OF 3/4"
UNLESS OTHERWISE NOTED.
8 PROVIDE ALL EQUIPMENT CLEARANCES IN ACCORDANCE WITH NEC REQUIREMENTS. ARRANGE EQUIPMENT TO FACILITATE UNRESTRICTED ACCESS FOR MAINTENANCE AND SERVICE AROUND ALL EQUIPMENT, COMPONENTS AND/OR CABLE TERMINATIONS.
9 WHERE EQUIPMENT AND/OR JUNCTION BOXES ARE INSTALLED ABOVE FINISHED CEILINGS, THE CONTRACTOR SHALL PROVIDE ACCESS HATCHES LISTED FOR THE INTENDED APPLICATION. ACCESS HATCHES SHALL BE LOCATED SO THAT SERVICE ACCESS TO THE EQUIPMENT AND/OR JUNCTION BOXES IS UNIMPEDED.
10 ALL PENETRATIONS OF WALLS AND/OR FLOORS SHALL BE FIRE STOPPED IN ACCORDANCE WITH THE ASTM AND NFPA REQUIREMENTS. REFER TO RELATED SPECIFICATION SECTIONS FOR ADDITIONAL INFORMATION. INSTALLATION OF FIRE-STOPS SHALL BE PERFORMED BY APPLICATOR/INSTALLER QUALIFIED AND TRAINED BY THE MANUFACTURER. INSTALLATION SHALL BE PERFORMED IN STRICT ACCORDANCE WITH MANUFACTURER'S DETAILED INSTALLATION
PROCEDURES.
11 ALL EQUIPMENT ENCLOSURES LOCATED OUTSIDE OR IN ALL AREAS WITH HIGH MOISTURE OR A RELATIVE HUMIDITY OF 75% OR GREATER SHALL BE NEMA 4X
STAINLESS STEEL AND RATED FOR THAT APPLICATION.
12 ALL DEVICES, COMPONENTS OR EQUIPMENT INSTALLED ON THE EXTERIOR OF THE FACILITY SHALL BE PROVIDED IN ACCORDANCE WITH ALL MANUFACTURERS' REQUIREMENTS TO ENSURE THE PROPER OPERATION WHEN EXPOSED TO THE ENVIRONMENTAL CONDITIONS AND/OR AVERAGE ANNUAL LOWEST TEMPERATURE THAT CAN BE ANTICIPATED FOR THE GEOGRAPHIC REGION OF THE FACILITY.
13 ALL INTERIOR AND/OR EXTERIOR COMPONENTS, DEVICES OR SYSTEMS EQUIPMENT EXPOSED TO THE GENERAL POPULATION SHALL BE INSTALLED IN SECURED EQUIPMENT ENCLOSURES WITH TAMPER SWITCHES AND INSTALLED IN SUCH A MANNER THAT RESISTS TAMPERING AND/OR REMOVAL WITHOUT
THE USE OF SPECIALIZED TOOLS.
14 FOR EQUIPMENT INSTALLATIONS REQUIRING COORDINATION WITH OTHER TRADES THE CONTRACTOR SHALL PROVIDE ALL TEMPLATES, BACKBOXES AND EQUIPMENT ANCHOR BOLTS FOR MOUNTING OR FLUSH MOUNTING PREPARATION, (E.G. PEDESTALS OR OTHER DEVICES REQUIRING MOUNTING ON WALLS, CONCRETE PADS OR OTHER MATERIALS). COORDINATE DELIVERY OF TEMPLATES AND EQUIPMENT WITH ALL AFFECTED CONTRACTORS.
15 ALL ELECTRICAL WORK SHALL BE DONE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE (LATEST VERSION BEING ENFORCED), AND ALL OTHER APPLICABLE CODES AND STANDARDS BEING ENFORCED BY THE AUTHORITY HAVING JURISDICTION.
16 THESE DRAWINGS DO NOT INCLUDE NECESSARY COMPONENTS OR INSTRUCTIONS FOR CONSTRUCTION SAFETY. THE ENGINEER ASSUMES NO RESPONSIBILITY FOR ANY WORKMAN'S OR TRANSIENT'S SAFETY, OR FOR THE ADEQUACY OF EQUIPMENT, BUILDING COMPONENTS, WORK AIDS, OR ANY NECESSITY TO WORK ON ENERGIZED ELECTRICAL COMPONENTS. FURTHER, NO SUPERINTENDENCE IS INCLUDED OR IMPLIED.
17 ALL SYSTEMS AND EQUIPMENT SHALL BE INSTALLED AND WIRED ACCORDING TO THE MANUFACTURER'S RECOMMENDATIONS.
18 ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES, AND EQUIPMENT SHALL BE TESTED AND LISTED BY A NATIONALLY RECOGNIZED TESTING LABORATORY.
19 THE CONTRACTOR SHALL COORDINATE CONDUIT ROUTING (PLAN AND ELEVATION) WITH THE LIGHTING, CEILING ELEVATION, STRUCTURE, DUCTWORK, PIPING, ETC. REQUIRED FOR THE COMPLETION OF THE PROJECT, PRIOR TO INSTALLATION.
20 THE CONTRACTOR SHALL SECURE AND PROTECT THE BUILDING AND/OR WORK AREA WITH FIRE RETARDANT TEMPORARY PLYWOOD PARTITIONS (WITH LOCKING DOORS), ETC. CLOSE ALL OPENINGS AS REQUIRED. COORDINATE THIS WORK WITH THE OWNERS REPRESENTATIVE PRIOR TO STARTING. IF
TEMPORARY PARTITIONS IMPEDE THE FLOW OF EGRESS TO REQUIRED EGRESS DOORS AND STAIRS, THE CONTRACTOR SHALL PROVIDE EXIT SIGNS, AND
SIGNAGE INDICATING SUCH.
21 THE CONTRACTOR SHALL CAULK ALL JOINTS BETWEEN METAL FRAMES. THIS APPLIES TO BOTH INTERIOR AND EXTERIOR INSTALLATIONS.
22 THE DIMENSIONS SHOWN ON THE DRAWINGS ARE FOR THE CONVENIENCE OF THE CONTRACTOR ONLY. VERIFY ALL DIMENSIONS IN THE FIELD PRIOR TO
PERFORMING ANY WORK.
23 THE CONTRACTOR SHALL INSTALL ALL CONDUITS CONCEALED UNLESS NOTED OTHERWISE. EXPOSED CONDUIT SHALL ONLY BE INSTALLED IN CHASES, EXPOSED CEILING AREAS, JANITOR CLOSETS, AND MECHANICAL/ELECTRICAL ROOMS. EXPOSED CONDUIT INSTALLATION IS ACCEPTABLE IN ROOMS OR AREAS WITH EXPOSED CEILINGS. CONCEALED CONDUITS ARE REQUIRED IN ALL ROOMS WITH ACT OR DRYWALL CEILINGS.
24 ALL ELECTRICAL EQUIPMENT SHALL BE GROUNDED AND/OR BONDED PER THE REQUIREMENTS OF THE NATIONAL ELECTRIC CODE. PROVIDE ALL GROUNDING
AND/OR BONDING COMPONENTS NOT EXPLICITLY SHOWN ON THE DOCUMENTS.
25 THE CONTRACTOR SHALL PROVIDE TYPEWRITTEN PANELBOARD DIRECTORIES, INDICATING THE LOADS SERVED BY THE RESPECTIVE PANELS. AMEND AS REQUIRED FOR AS-BUILT CONDITIONS. PROVIDE ELECTRONIC VERSIONS OF THE PANELBOARD SCHEDULES FOR FUTURE USE TO THE OWNER.
26 THE CONTRACTOR SHALL REVIEW THE WORK REQUIRED WITH THE APPLICABLE UTILITY COMPANIES SERVING THE PROJECT. ALL WORK PERFORMED SHALL
BE IN ACCORDANCE WITH THE REQUIREMENTS OF THE INDIVIDUAL UTILITY COMPANIES.
27 THE CONTRACTOR SHALL COORDINATE ALL WORK WITH THE OWNER PRIOR TO STARTING ALL PHASES OF THE PROJECT. THE CONTRACTOR SHALL COORDINATE WITH THE OWNER WHAT WORK, IF ANY, HAS TO BE COMPLETED DURING SECOND OR THIRD SHIFT.
28 THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY POWER CONNECTIONS TO KEEP AREAS UP AND OPERATIONAL DURING THE CONSTRUCTION. THE
CONTRACTOR SHALL COORDINATE THESE REQUIREMENTS WITH THE OWNER.
29 THE VERBIAGE ON THE DRAWINGS INDICATING TYPES OF MATERIALS TO BE ENCOUNTERED IS INTENDED TO AID THE ELECTRICAL CONTRACTOR IN UNDERSTANDING THE VARIOUS CONDITIONS LIKELY TO BE ENCOUNTERED. THE CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING QUANTITIES OF
MATERIALS REQUIRED TO COMPLETE THE PROJECT.
30 THE LOCATIONS OF UTILITIES, STRUCTURE AND OTHER CONDITIONS SHOWN ON THE PLANS ARE APPROXIMATE. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE WITH THE UTILITY PROVIDERS AND REPORT ANY DISCREPANCIES TO THE REPRESENTATIVE PRIOR TO BEGINNING ANY WORK.
31 THE CONTRACTOR SHALL PROVIDE ALL OPENINGS IN PARTITIONS, EXTERIOR WALLS, FLOORS, AND ROOFS FOR THE INSTALLATION OF ANY ELECTRICAL WORK. FURNISH AND INSTALL ALL REQUIRED LINTELS AND SLEEVES FOR THIS WORK. ALL CONDUITS SHALL HAVE SLEEVES INSTALLED. ALL SLEEVES
INSTALLED THROUGH EXTERIOR WALLS SHALL HAVE LINK SEALS INSTALLED.
32 THE CONTRACTOR SHALL PROTECT ALL MATERIALS THAT ARE TO REMAIN IN PLACE FROM DAMAGE. ANY DAMAGE TO FINISHES, MATERIALS, ETC., SHALL BE
REPLACED BY THE CONTRACTOR TO MATCH THE ADJACENT FINISH.
33 THE CONTRACTOR SHALL MAINTAIN THE BUILDING IN WEATHERTIGHT AND WATERPROOF CONDITION THROUGHOUT THE DURATION OF THEIR WORK. DO NOT LEAVE HOLES THROUGH WALLS AND/OR ROOFS OPEN TO THE ELEMENTS WHEN NO WORK IS OCCURRING IN THOSE AREAS.
34 PROVIDE ALL JUNCTION BOXES, PULL BOXES AND OTHER PULL POINTS AS REQUIRED TO MEET THE MAXIMUM NUMBER OF BENDS PER NEC REQUIREMENTS.
NOT ALL CONDUITS, PULL BOXES AND OTHER RACEWAY ITEMS ARE INDICATED ON THE DOCUMENTS. THE CONTRACTOR SHALL PROVIDE A COMPLETE RACEWAY SYSTEM MEETING THE REQUIREMENTS OUTLINED IN THE DRAWINGS AND SPECIFICATIONS.
35 DISTRIBUTION EQUIPMENT SHALL BE AIC RATED, AND ANY CIRCUIT BREAKERS SELECTED AND SET BASED ON THE OUTCOME OF THE CONTRACTORS OVERCURRENT PROTECTIVE DEVICE COODINATION STUDY. STUDY SHALL INCLUDE ALL ELEMENTS OF THE DISTRIBUTION SYSTEM REQUIRED TO ACCURATELY
SIZE AND RATE THE EQUIPMENT ADDED AS PART OF THIS PROJECT.
36 ARC FLASH LABELS SHALL BE PROVIDED TO ALL EQUIPMENT BASED ON THE OUTCOME OF THE CONTRACTORS ARC FLASH STUDY (SEE NOTE 35 ABOVE FOR ADDITIONAL STUDY REQUIREMENTS). ANY EQUIPMENT MODIFIED AS PART OF THIS PROJECT SHALL ALSO BE INCLUDED IN THE ARC FLASH STUDY, AND RE
LABELLED AS REQUIRED.
37 THESE DRAWINGS DO NOT INDICATE ALL CONDUITS INTERCONNECTING EQUIPMENT, AND WHERE CONDUITS ARE INDICATED, THE ROUTING IS APPROXIMATE.
THE CONTRACTOR IS RESPONSIBLE FOR THE ROUTING AND INSTALLATION OF ALL CONDUIT IN COORDINATION WITH OTHER TRADES AND FIELD CONDITIONS.
38 PROVIDE ALL JUNCTION BOXES AND OTHER PULL POINTS AS REQUIRED FOR EASE OF PULLING AND A CODE COMPLIANT INSTALLATION. ALL JUNCTION BOXES
AND OTHER PULL POINTS SHALL BE ACCESSIBLE
39 MULTIWIRE BRANCH CIRCUITS ARE NOT PERMITTED, ALL SINGLE POLE BRANCH CIRCUITS SHALL HAVE A DEDICATED NEUTRAL AND GROUND.
40 MULTIPLE SMALL 20A/1P BRANCH CIRCUITS MAY SHARE A SINGLE CONDUIT PROVIDED THE CONTRACTOR UPSIZES THE CONDUIT AS REQUIRED, AND THE AMPACITY ADJUSTMENTS FROM TABLE 310.15(B)(3)(a) HAVE BEEN APPLIED.
# Revisions Date 07/15/2020
(XR)AHU-9
(X)EF
E
F
G
H
C
B
A
2221201918A1615
I
J
13121087
43A3
19A
9 11 13A
D
18 20B17A 17B
(XR)CU-9
LPL
LP-BD
LP-BC
M A
T C
H L
IN
E
EM-B
LPE1
EXISTING
LIGHT FIXTURE
EXISTING
LIGHT FIXTURE
4 4
EQ-B
CR-B
WEST (BW) EAST (BE)
BASEMENT
GENERAL AREA OF
WORK (REFER TO
PLAN FOR DETALS)
BASEMENT
AREA OF FUTURE WORK
(NOT IN CONTRACT)
NOT IN CONTRACT
N O
T
IN
C O
N T
R A
C T
M A
T C
H
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
B
IM
/1
F t.
W a y n e V
A M
C B a s e m e n t B ld g
/1
M
E P
C e n tr a l
.r v t
/1
/2
:2
:3
P
M
ED101W
ELECTRICAL DEMOLITION PLAN - BASEMENT
WESTAE Works
209 SANDUSKY STREET
PITTSBURGH, PA 15212
412-287-7333
RENOVATE BASEMENT,
BUILDING 1
2121 LAKE AVE, FORT WAYNE, IN 46805
610A4-19-104
07/15/2020 BK TJR
BID DOCUMENTS
ELECTRICAL DEMOLITION GENERAL NOTES
1 UNLESS NOTED OTHERWISE, REMOVE ALL ELECTRICAL DEVICES FROM WITHIN THE AREA OF DEMOLITION WORK
IDENTIFIED WITHOUT SHADED BOUNDARIES. SHADED BOUNDARIES INDICATE OUT OF SCOPE AREAS. THE DEVICES TO BE REMOVED INCLUDE BUT ARE NOT LIMITED TO: RECEPTACLES, SWITCHES, JUNCTION BOXES, LIGHTS, LIGHTING CONTROLS, PANELBOARDS IN POOR CONDITION AND FLOOR BOXES. REMOVE ALL ASSOCIATED CONDUIT AND WIRE BACK TO THE UPSTREAM DISTRIBUTION DEVICE. THE INTENT IS FOR ALL DEVICES TO BE REMOVED FROM FLOOR TO ALLOW THE RENOVATION AND INSTALLATION OF ALL NEW DEVICES AS SHOWN ON THE NEW WORK DOCUMENTS. EXISTING DEVICES SHOWN ARE DIAGRAMMATIC AND BASED ON FIELD SURVEYS AND/OR RECORD DRAWINGS PROVIDED BY THE OWNER AND DOES NOT REPRESENT THE FULL SCOPE OF DEMOLITION WORK. THE ACTUAL CONDITIONS MAY VARY. ALL EXISTING CONDITIONS MUST BE VERIFIED PRIOR TO BID. THE PLANS ARE INTENDED TO SHOW THE LOCATIONS OF EXISTING DEVICES AND IN NO WAY RELIEVES THE CONTRACTOR FROM PROVIDING ANY AND ALL COORDINATION NECESSARY TO COMPLETE THE NEW WORK. FIELD CONDITIONS SHALL GOVERN. FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR TO COMMENCEMENT OF WORK AND OBTAIN CLARIFICATIONS FROM ARCHITECT/ENGINEER
IF NECESSARY.
2 OWNER SHALL HAVE RIGHT OF FIRST REFUSAL TO ANY EQUIPMENT, DEVICES, LUMINAIRES, ETC. DEMOLISHED
FROM RENOVATION AREA PRIOR TO DISPOSAL.
3 MAINTAIN CONTINUITY OF SERVICE TO AREAS OUTSIDE THE PROJECT BOUNDARY. PATCH AND REPAIR ALL CIRCUITS CUT OFF DURING DEMOLITION BY WIRING METHODS COMPATIBLE WITH THE EXISTING INSTALLATION.
4 THE ELECTRICAL CONTRACTOR SHALL REVIEW THE DRAWING OF ALL OTHER TRADES IN THIS CONTRACT. THE REMOVAL OF ELECTRICAL SERVICE TO ALL EQUIPMENT IDENTIFIED ON OTHER TRADE DRAWINGS IS THE
RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.
5 EXERCISE EXTREME CAUTION WHEN REMOVING/ RELOCATING WIRING AND EQUIPMENT. IT IS THE CONTRACTOR'S RESPONSIBILITY TO ENSURE THAT OTHER WIRING DEVICES, EQUIPMENT AND LIGHT FIXTURES
THAT MAY BE CONNECTED TO THE SAME CIRCUIT REMAIN OPERATIONAL AND ACTIVE.
NORTH
TRUE NORTH=
PROJECT
88.5°
8' 16'4'0 1/8" = 1'-0"1
ELECTRICAL DEMOLITION PLAN - BASEMENT WEST
# ELECTRICAL DEMOLITION KEYNOTES
1 EXISTING PAENLBOARD TO REMAIN. DEMOLISH EXISTING BRANCH CIRCUITS OF DEMOLISHED
DEVICES IN THEIR ENTIRETY INCLUDING BUT NOT LIMITED TO WIRING, CONDUIT, AND HANGERS. THE
EXISTING CIRCUIT BREAKERS ARE TO REMAIN IN PLACE.
2 DEMOLISH EXISTING BRANCH CIRCUIT TO MECHANICAL EQUIPMENT IN ITS ENTIRETY BACK TO THE SOURCE PANEL. INCLUDING BUT NOT LIMITED TO DISCONNECTING DEVICE, STARTER, CONDUIT, WIRING, AND HANGERS. THE EXISTING CIRCUIT BREAKERS ARE TO REMAIN IN PLACE.
3 THE EXISTING BRANCH CIRCUIT FOR THE NOTED MECHANICAL EQUIPMENT IS TO REMAIN IN PLACE
AND BE KEPT ENERGIZED.
4 EXISTING LIGHT FIXTURE SHALL REMAIN. CONTRACTOR SHALL ENSURE THAT ELECTRICAL
CONNECTIONS AND FIXTURE MOUNTING IS PRESERVED THROUGHOUT THE CONSTRUCTION
PROCESS.
5 EXISTING PANELBOARD TO BE REPLACED WITH NEW PANELBOARD. ALL EXISTING TO REMAIN
CIRCUITS SHALL BE RE-FED FROM THE NEW PANEL. REFERENCE SHEET E401 FOR PANELBOARD
INFORMATION AND ONE-LINE DIAGRAM ON SHEET E301.
6 EXISTING ELECTRICAL EQUIPMENT TO REMAIN. DEMOLISH EXISTING BRANCH CIRCUITS OF
DEMOLISHED DEVICES IN THEIR ENTIRETY INCLUDING BUT NOT LIMITED TO WIRING, CONDUIT, AND HANGERS. CIRCUIT BREAKERS WITH EXISTING LOADS OR LOADS OUTSIDE OF THE SCOPE OF WORK
ARE TO REMAIN IN PLACE.
WEST (BW) EAST (BE)
BASEMENT
GENERAL AREA OF
WORK (REFER TO
PLAN FOR DETALS)
BASEMENT
AREA OF FUTURE WORK
(NOT IN CONTRACT)
NOT IN CONTRACT
N O
T
IN
C O
N T
R A
C T
M A
T C
H
(X)AHU
(XR)AHU
(XR)CU-N
(XR)CU-CAN
(XR)CU-4
(XR)CU-52 (XR)CU-S
(XR)CH-1
(X)CU-50
E
F
G
H
C
363534333231
2927252423
33A
302826
B
A
I
22A20B 30A
M A
T C
H L
IN
E
LP-BA
PP-2
LP-BB
EXISTING
BATTERY
RACK
EXISTING
DATA
RACK
(TYP.)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
B
IM
/1
F t.
W a y n e V
A M
C B a s e m e n t B ld g
/1
M
E P
C e n tr a l
.r v t
/1
/2
:2
:4
P
M
ED102E
ELECTRICAL DEMOLITION PLAN - BASEMENT
EASTAE Works
209 SANDUSKY STREET
PITTSBURGH, PA 15212
412-287-7333
RENOVATE BASEMENT,
BUILDING 1
2121 LAKE AVE, FORT WAYNE, IN 46805
610A4-19-104
07/15/2020 BK TJR
BID DOCUMENTS
NORTH
TRUE NORTH=
PROJECT
88.5°
8' 16'4'0 1/8" = 1'-0"1
ELECTRICAL DEMOLITION PLAN - BASEMENT EAST
ELECTRICAL DEMOLITION GENERAL NOTES
1 UNLESS NOTED OTHERWISE, REMOVE ALL ELECTRICAL DEVICES FROM WITHIN THE AREA OF DEMOLITION WORK
IDENTIFIED WITHOUT SHADED BOUNDARIES. SHADED BOUNDARIES INDICATE OUT OF SCOPE AREAS. THE DEVICES TO BE REMOVED INCLUDE BUT ARE NOT LIMITED TO: RECEPTACLES, SWITCHES, JUNCTION BOXES, LIGHTS, LIGHTING CONTROLS, PANELBOARDS IN POOR CONDITION AND FLOOR BOXES. REMOVE ALL ASSOCIATED CONDUIT AND WIRE BACK TO THE UPSTREAM DISTRIBUTION DEVICE. THE INTENT IS FOR ALL DEVICES TO BE REMOVED FROM FLOOR TO ALLOW THE RENOVATION AND INSTALLATION OF ALL NEW DEVICES AS SHOWN ON THE NEW WORK DOCUMENTS. EXISTING DEVICES SHOWN ARE DIAGRAMMATIC AND BASED ON FIELD SURVEYS AND/OR RECORD DRAWINGS PROVIDED BY THE OWNER AND DOES NOT REPRESENT THE FULL SCOPE OF DEMOLITION WORK. THE ACTUAL CONDITIONS MAY VARY. ALL EXISTING CONDITIONS MUST BE VERIFIED PRIOR TO BID. THE PLANS ARE INTENDED TO SHOW THE LOCATIONS OF EXISTING DEVICES AND IN NO WAY RELIEVES THE CONTRACTOR FROM PROVIDING ANY AND ALL COORDINATION NECESSARY TO COMPLETE THE NEW WORK. FIELD CONDITIONS SHALL GOVERN. FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR TO COMMENCEMENT OF WORK AND OBTAIN CLARIFICATIONS FROM ARCHITECT/ENGINEER
IF NECESSARY.
2 OWNER SHALL HAVE RIGHT OF FIRST REFUSAL TO ANY EQUIPMENT, DEVICES, LUMINAIRES, ETC. DEMOLISHED
FROM RENOVATION AREA PRIOR TO DISPOSAL.
3 MAINTAIN CONTINUITY OF SERVICE TO AREAS OUTSIDE THE PROJECT BOUNDARY. PATCH AND REPAIR ALL CIRCUITS CUT OFF DURING DEMOLITION BY WIRING METHODS COMPATIBLE WITH THE EXISTING INSTALLATION.
4 THE ELECTRICAL CONTRACTOR SHALL REVIEW THE DRAWING OF ALL OTHER TRADES IN THIS CONTRACT. THE REMOVAL OF ELECTRICAL SERVICE TO ALL EQUIPMENT IDENTIFIED ON OTHER TRADE DRAWINGS IS THE
RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.
5 EXERCISE EXTREME CAUTION WHEN REMOVING/ RELOCATING WIRING AND EQUIPMENT. IT IS THE CONTRACTOR'S RESPONSIBILITY TO ENSURE THAT OTHER WIRING DEVICES, EQUIPMENT AND LIGHT FIXTURES
THAT MAY BE CONNECTED TO THE SAME CIRCUIT REMAIN OPERATIONAL AND ACTIVE.
# Revisions Date
# ELECTRICAL DEMOLITION KEYNOTES
1 EXISTING PAENLBOARD TO REMAIN. DEMOLISH EXISTING BRANCH CIRCUITS OF DEMOLISHED
DEVICES IN THEIR ENTIRETY INCLUDING BUT NOT LIMITED TO WIRING, CONDUIT, AND
HANGERS. THE EXISTING CIRCUIT BREAKERS ARE TO REMAIN IN PLACE.
2 DEMOLISH EXISTING BRANCH CIRCUIT TO MECHANICAL EQUIPMENT IN ITS ENTIRETY BACK TO
THE SOURCE PANEL. INCLUDING BUT NOT LIMITED TO DISCONNECTING DEVICE, STARTER,
CONDUIT, WIRING, AND HANGERS. THE EXISTING CIRCUIT BREAKERS ARE TO REMAIN IN
PLACE.
3 THE EXISTING BRANCH CIRCUIT FOR THE NOTED MECHANICAL EQUIPMENT IS TO REMAIN IN
PLACE AND BE KEPT ENERGIZED.
4 ALL ELECTRICAL EQUIPMENT IN THIS ROOM IS EXISTING TO REMAIN. THE DISCONNECT
SWITCH, QUAD OUTLET AND ALL OTHER OUTLETS IN THE AREA ARE TO REMAIN IN PLACE AND
MAINTAIN OPERATION THROUGHOUT THE ARCHITECTURAL NEW WORK INSTALLATION.
BATTERY RACK AND DATA RACK SHALL BE RELOCATED TO THE RAISED FLOOR PLATFORM
AFTER ARCHITECTURAL NEW WORK IS COMPLETE. ANY ELECTRICAL DEVICES THAT MAY FALL
BELOW THE RAISED FLOOR SHALL BE RELOCATED.
5 EXISTING ELECTRICAL EQUIPMENT, RECEPTACLE, AND CIRCUITS TO REMAIN AND MAINTAIN
OPERATION THROUGHOUT THE NEW WORK INSTALLATION.
6 EXISTING ELECTRICAL EQUIPMENT TO REMAIN. DEMOLISH EXISTING BRANCH CIRCUITS OF
DEMOLISHED DEVICES IN THEIR ENTIRETY INCLUDING BUT NOT LIMITED TO WIRING, CONDUIT, AND HANGERS. CIRCUIT BREAKERS WITH EXISTING LOADS OR LOADS OUTSIDE OF THE SCOPE
OF WORK ARE TO REMAIN IN PLACE.
07/15/2020
OS
VS
VS
OS
OS OS OS
VS
VS
VS
VS
VS
OS
VS
OS OS
OS
OS
OS
OS OS OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
VS
OS
VS
VS
VS
OS
X-RAY
B120E
TLT / CHANGING
B120F
CLEAN
B120G
RADIOLOGY
B120
CT SCANNING
B120D
SOILED HOLDING
B120C
WAITING
B119
CORRIDOR
C06
STAIR 2 (NIC)
S2
MENS
B114
WOMENS
B113
CORRIDOR
C04
CORRIDOR
C02
PHARMACY CACHE
B111
EMS SUPPLY
B104
EMS SUITE
B100
EMS OFFICE 2
B100A
EMS OFFICE 1
B100B
CLEAN LINEN ROOM
B100C
MENS DRESSING
B100E
SERV ELEV
SE1
ELEVATOR (NIC)
E1
ELEVATOR (NIC)
E2
MECHANICAL OFFICE
B101
E
F
G
H
C
B
2221201918A1615
I
J
13121087
43A321
19A
9 11 13A
D
18 20B17A 17B
T3T3
T3 T3
T3 T3
T3 T3 T3 T3
T3 T3 T3 T3
T2 T1
T3 T3 T3 T3 T3 T3 T3
T3 T3 T3 T3 T3 T3 T3
TS2
TS2 TS2 TS2
TS1
T1
TS1 TS1
TS1
TS1
TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1
TS1 TS1
TS1TS1
TS1
TS1
TS1
TS1
TS1
TS1
TS1
T3
T2
T2
P1
T1
T3
T1 T1
T1
T1
T1
T2
T2 T2 T2
T2T2
T1
T1
T1
T1
T1 T1
T1
T2
T1T1 T2
T2
T2
T2
T1
D1
D1
D2
M A
T C
H L
IN
E
EMS STORAGE
B103
TS1
CLOSET
B120B
RECEPTION / WORK
B120A
STORAGE
B118 GME LIBRARY
B116
RES. SLEEPING
ROOM
B115
RESIDENT TLT RM
B115A
P3 P3
P3P3
T3 T3
T3T3
T1 D1
T2 T2
T2T2
TS2
T1
TS1
LV
LV
LV
LV
D D
VS
K K
3 3
D D
D
D D
W1
E1
E2
E1 E1
E1
E1
E1
E1
E1
VS
a b a,b
E2
X1 a a a a a a a a a bbbbbbbbb a,b a,b ba a b ba
WOMENS DRESSING
B100D
MECH
B102B
STORAGE
B100F
P1
T1 T1
CR-B - 13
CR-B - 13 CR-B - 13
LPL - 5
LPL - 5 LPL - 5
LPL - 5
CR-B - 13
CR-B - 13 CR-B - 13 CR-B - 13
CR-B - 13CR-B - 13 CR-B - 13
LPL - 5
LPL - 5 LPL - 5
LPL - 5
LPL - 5
LPL - 5
LPL - 5
LPL - 5
CORRIDOR
C05
LP-BC - 9 LP-BC - 9
LP-BC - 9 LP-BC - 9LP-BC - 9 LP-BC - 9 LP-BC - 9
LP-BC - 9
LPE1 - 18
LP-BC - 9 LPE1 - 18 LP-BC - 9
LP-BC - 9
LP-BC - 9
LP-BC - 9
LPE1 - 18
LPE1 - 18
LP-BB - 18LP-BC - 9LP-BC - 9
LP-BC - 9LP-BC - 9
LP-BC - 9
EQ-B - 11 EQ-B - 11
LP-BC - 9LP-BC - 9
LP-BC - 9
LP-BC - 9LP-BC - 9
CR-B - 10
LP-BD - 12LP-BD - 12
LP-BD - 12
LP-BD - 12LP-BD - 12
LP-BD - 12
LP-BD - 12LP-BD - 12
LP-BD - 12
LPE1 - 1
LP-BD - 12LP-BD - 12
LP-BD - 12
LP-BD - 12LP-BD - 12
LP-BD - 12
CORRIDOR
C03
CORRIDOR
C01
E2
LPE1 - 18
LPE1 - 18
LPE1 - 18
LPE1 - 18
LPE1 - 18
LPE1 - 18 LPE1 - 18
LPE1 - 18
LPE1 - 18
LPE1 - 18
LPE1 - 18
LPE1 - 18
LPE1 - 18
LPE1 - 18
E2
LPE1 - 18
LPE1 - 18
LPE1 - 18
LPE1 - 18
LPE1 - 18 LPE1 - 18
LPE1 - 18LPE1 - 18
LPE1 - 1
LPE1 - 1
LPE1 - 1
LPE1 - 1
LPE1 - 1
LPE1 - 1LPE1 - 1LPE1 - 1 LPE1 - 1
LPE1 - 1
LPE1 - 1
LPE1 - 1
LPE1 - 18
LPE1 - 1
LPE1 - 1
LPE1 - 1
LPE1 - 1
LPE1 - 1
LPE1 - 1
LPE1 - 1
LPE1 - 1LPE1 - 1
LPE1 - 1
LPE1 - 1
LPE1 - 1
LPE1 - 1
LPE1 - 1
LPE1 - 1
LPE1 - 1
LPE1 - 1
LPE1 - 1
LPE1 - 1
LPE1 - 1
LPE1 - 1
LPE1 - 1
CR-B - 10 CR-B - 10
CR-B - 10 CR-B - 10 CR-B - 10
CR-B - 10 CR-B - 10 CR-B - 10
CR-B - 10 CR-B - 10 CR-B - 10
CR-B - 10
MCMCMC
V S
VS
VS VS
VS
a a bb c b a b ba a,b,c b b c a,b,c b a,b,c a,b,c M C
TS1
TS1 TS1
LP-BD - 12
LP-BD - 12 LPE1 - 1
D a b b b b b aaa a,b
MC
P1
P1
LPE1 - 18
LPE1 - 18
MC
a,b
EXISTING
LIGHT FIXTURE
EXISTING
LIGHT FIXTURE
T
E1 LPE1 - 1
a,b,c a, b, c
WEST (BW) EAST (BE)
BASEMENT
GENERAL AREA OF
WORK (REFER TO
PLAN FOR DETALS)
BASEMENT
AREA OF FUTURE WORK
(NOT IN CONTRACT)
NOT IN CONTRACT
N O
T
IN
C O
N T
R A
C T
M A
T C
H
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
B
IM
/1
F t.
W a y n e V
A M
C B a s e m e n t B ld g
/1
M
E P
C e n tr a l
.r v t
/1
/2
:2
:3
P
M
E101W
ELECTRICAL LIGHTING PLAN - BASEMENT
WESTAE Works
209 SANDUSKY STREET
PITTSBURGH, PA 15212
412-287-7333
RENOVATE BASEMENT,
BUILDING 1
2121 LAKE AVE, FORT WAYNE, IN 46805
610A4-19-104
07/15/2020 BK TJR
BID DOCUMENTS
NORTH
TRUE NORTH=
PROJECT
88.5°
LIGHTING PLAN GENERAL NOTES
1 ALL EXIT SIGNS SHALL BE POWERED FROM THE CIRCUIT INDICATED AND UNSWITCHED.
2 ALL LIGHTING FIXTURES POWERED FROM AN EMERGENCY GENERATOR CIRCUIT SHALL BE PROVIDED WITH A UL924
LISTED AUTOMATIC LOAD CONTROL RELAY TO PERMIT LOCAL CONTROL WITH ADJACENT
FIXTURES AND BY-PASS OF LOCAL CONTROL (INCLUDING BUT NOT LIMITED TO SWITCHES, OCCUPANCY SENSORS AND
DIMMERS) IN THE ABSENCE OF NORMAL POWER. UPON LOSS OF NORMAL POWER, THE
LIGHTING CONTROL SHALL BE BY-PASSED, DIMMED FIXTURES SHALL COME TO FULL ILLUMINATION AND SHALL NOT BE
ALLOWED TO TURN OFF.
3 COORDINATE FINAL LOCATIONS OF FIXTURES WITH THE REFLECTED CEILING PLAN. ANY CONFLICTS SHALL BE
BROUGHT TO THE ATTENTION OF THE ARCHITECT AND ENGINEER.
4 COORDINATE ALL MOUNTING HEIGHTS WITH THE ARCHITECT AND ENGINEER PRIOR TO ROUGH-IN.
5 WHERE MORE THAN ONE SWITCH OCCURS IN THE SAME LOCATION, THEY SHALL BE INSTALLED IN GANG TYPE BOX UNDER THE COVERPLATE, MINIMUM CONDUIT SIZE IS 3/4" MINIMUM WIRE SIZE SHALL BE #12 AWG. ALL WIRE TO BE
STRANDED COPPER.
6 THE OCCUPANCY SENSORS INDICATED ON THE DRAWINGS ARE SHOWN FOR DESIGN INTENT ONLY. THE EXACT QUANTITY OF SENSORS SHALL BE DETERMINED BY THE ELECTRICAL CONTRACTOR PRIOR TO INSTALLING SENSORS BASED ON THE MANUFACTURER'S RECOMMENDATION. PROVIDE 100% COVERAGE OF EACH INDIVIDUAL ROOM/SPACE SHOWN ON THE DRAWINGS. DO NOT INSTALL SENSORS PRIOR TO SUBMITTING COVERAGE LAYOUTS FOR EACH INDIVIDUAL ROOM/SPACE TO THE ENGINEER FOR APPROVAL. DO NOT INSTALL SENSORS SUCH THAT THEY CAN POTENTIALLY "SEE" THROUGH OPEN DOORWAYS. INSTALL ALL LOW VOLTAGE POWER PACKS DIRECTLY ABOVE LOCAL WALL SWITCHES IN THE AREA. DO NOT INSTALL ULTRASONIC OR DUAL TECHNOLOGY SENSORS WITHIN 24" OF SUPPLY
DIFFUSERS.
7 ALL EMERGENCY EGRESS ILLUMINATION SHALL BE AVERAGE 1FC AND A MINIMUM OF 0.1FC FOR PATH OF EGRESS.
8 PROVIDE EQUIPMENT GROUND CONDUCTOR IN ALL RACEWAYS. REFER TO PANELBOARD SCHEDULES.
9 ROUTE CONDUIT HIGH AGAINST STRUCTURE AND OFFSET UP BETWEEN JOISTS WHERE NECESSARY TO AVOID DUCT
WORK AND HVAC SYSTEM.
10 PROVIDE CONDUIT AND WIRING AS REQUIRED TO MEET CIRCUITING SHOWN TO CONFORM TO NEC REQUIREMENTS.
8' 16'4'0 1/8" = 1'-0"1
ELECTRICAL LIGHTING PLAN - BASEMENT WEST
# LIGHTING PLAN KEYNOTES
1 PROVIDE A ROOM BASED LOW VOLTAGE LIGHTING CONTROL SYSTEM WITH MULTI BUTTON
LOW VOLTAGE SWITCH CONTROL FOR THE FIXTURES WITHIN THE INDICATED ROOM ON
PLAN. REFER TO DETAIL 6 ON SHEET E301.
2 LIGHTING FIXTURES SHALL BE COORDINATED WITH MECHANICAL EQUIPMENT AND
DUCTWORK/PIPING. LIGHTING FIXTURES SHALL BE INSTALLED BELOW DUCT AND PIPE RUNS
TO AVOID OBSTRUCTIONS.
3 NEW EXTERIOR LIGHT FIXTURE SHALL BE POWERED AND CONTROLLED FROM THE SAME
CIRCUIT AND CONTROL SYSTEM AS THE EXISTING TO REMAIN EXTERIOR LIGHT FIXTURES.
CONDUIT AND WIRING SHALL BE ROUTED CONCEALED.
OS
OS
OS
OS
OS OS
VS
OS
VS
OS
VS
VS
VS
VS
VS
WEST (BW) EAST (BE)
BASEMENT
GENERAL AREA OF
WORK (REFER TO
PLAN FOR DETALS)
BASEMENT
AREA OF FUTURE WORK
(NOT IN CONTRACT)
NOT IN CONTRACT
N O
T
IN
C O
N T
R A
C T
M A
T C
H
OIT OFFICE
B309
MECH ROOM 1
B308
BIOMED STORAGE
B310 STORAGE
B316D
BIOMED
B316
WORKSHOP
B316C
OFFICE
B316B
TOILET ROOM
B315
STAIR 4 (NIC)
S4
E
F
G
H
C
36353433323129272524
33A302826
B
A
I
J
22A
D
20B
30A
TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1
T2
T2T2
T2
T2
T2
T2 T2
TS1
TS1
T3
T3
T3
T3 T3
T3
T3 T3
MAILROOM
B300
STOR / SOILED LINEN
CART
B306
BATTERY ROOM
B307
M A
T C
H L
IN
E
STORAGE
B316A
PACKAGE LOCKER
B301
T2
TS2 TS2
T2
T2
TS2
D1
TS2
P1 P1 P1
P1P1P1
P1
P1
P2 P2
P2P2
P2 P2
P2P2
T2
T2 T2
T2T2
T2
D
T
V D
E2
E1
E2 E1
E1
STAIR 3 (NIC)
S3
D a a a a a b b b b a,b a,b
E2
VESTIBULE (NIC)
OIT SERVER
B311
T1 T1
T1T1
ENGINEERING
STORAGE
B312
T2
CORRIDOR
C07
LP-BB - 18 LP-BB - 18 LP-BB - 18 LP-BB - 18 LP-BB - 18 LP-BB - 18 LP-BB - 18
LP-BB - 18LP-BB - 18
LP-BB - 18
LP-BB - 18 LP-BB - 18LP-BB - 18
LP-BB - 18
LP-BB - 18
LP-BB - 18 LP-BB - 18 LP-BB - 18 LP-BB - 18
LP-BB - 18
LP-BB - 18
LP-BB - 18
LP-BB - 18
LP-BB - 18 LP-BB - 18 LP-BB - 18 LP-BB - 18
LP-BA - 14 LP-BA - 14
LP-BA - 14
LP-BA - 14
LP-BA - 14
LP-BA - 14
LP-BA - 14
LP-BA - 14 LP-BA - 14
LP-BA - 14
LP-BA - 14LP-BA - 14
LP-BA - 14
LP-BA - 14
LP-BA - 14
LP-BA - 14
LPE1 - 5
LPE1 - 5
LPE1 - 5
LPE1 - 5
LPE1 - 5
LPE1 - 5
LPE1 - 5
LPE1 - 5LPE1 - 5
LPE1 - 5
LPE1 - 5
LPE1 - 5
LPE1 - 5
LPE1 - 5LPE1 - 5
LPE1 - 5LPE1 - 5
LPE1 - 5
LPE1 - 5
LPE1 - 5
LPE1 - 5
LPE1 - 5LPE1 - 5
LPE1 - 5
LPE1 - 5LPE1 - 5LPE1 - 5
LPE1 - 5
LPE1 - 5
LPE1 - 5 LPE1 - 5
LPE1 - 5
LPE1 - 5
V S a b a b ba a b a b a a a b b
V S
MCMC
M C
M C
VS
b
DD
D a b a b ba a,b
OS
TS1
LP-BB - 18
T T b D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
B
IM
/1
F t.
W a y n e V
A M
C B a s e m e n t B ld g
/1
M
E P
C e n tr a l
.r v t
/1
/2
:2
:3
P
M
E102E
ELECTRICAL LIGHTING PLAN - BASEMENT EAST
AE Works
209 SANDUSKY STREET
PITTSBURGH, PA 15212
412-287-7333
RENOVATE BASEMENT,
BUILDING 1
2121 LAKE AVE, FORT WAYNE, IN 46805
610A4-19-104
07/15/2020 BK TJR
BID DOCUMENTS
NORTH
TRUE NORTH=
PROJECT
88.5°
LIGHTING PLAN GENERAL NOTES
1 ALL EXIT SIGNS SHALL BE POWERED FROM THE CIRCUIT INDICATED AND UNSWITCHED.
2 ALL LIGHTING FIXTURES POWERED FROM AN EMERGENCY GENERATOR CIRCUIT SHALL BE PROVIDED WITH A UL924
LISTED AUTOMATIC LOAD CONTROL RELAY TO PERMIT LOCAL CONTROL WITH ADJACENT
FIXTURES AND BY-PASS OF LOCAL CONTROL (INCLUDING BUT NOT LIMITED TO SWITCHES, OCCUPANCY SENSORS AND
DIMMERS) IN THE ABSENCE OF NORMAL POWER. UPON LOSS OF NORMAL POWER, THE
LIGHTING CONTROL SHALL BE BY-PASSED, DIMMED FIXTURES SHALL COME TO FULL ILLUMINATION AND SHALL NOT BE
ALLOWED TO TURN OFF.
3 COORDINATE FINAL LOCATIONS OF FIXTURES WITH THE REFLECTED CEILING PLAN. ANY CONFLICTS SHALL BE
BROUGHT TO THE ATTENTION OF THE ARCHITECT AND ENGINEER.
4 COORDINATE ALL MOUNTING HEIGHTS WITH THE ARCHITECT AND ENGINEER PRIOR TO ROUGH-IN.
5 WHERE MORE THAN ONE SWITCH OCCURS IN THE SAME LOCATION, THEY SHALL BE INSTALLED IN GANG TYPE BOX UNDER THE COVERPLATE, MINIMUM CONDUIT SIZE IS 3/4" MINIMUM WIRE SIZE SHALL BE #12 AWG. ALL WIRE TO BE
STRANDED COPPER.
6 THE OCCUPANCY SENSORS INDICATED ON THE DRAWINGS ARE SHOWN FOR DESIGN INTENT ONLY. THE EXACT QUANTITY OF SENSORS SHALL BE DETERMINED BY THE ELECTRICAL CONTRACTOR PRIOR TO INSTALLING SENSORS BASED ON THE MANUFACTURER'S RECOMMENDATION. PROVIDE 100% COVERAGE OF EACH INDIVIDUAL ROOM/SPACE SHOWN ON THE DRAWINGS. DO NOT INSTALL SENSORS PRIOR TO SUBMITTING COVERAGE LAYOUTS FOR EACH INDIVIDUAL ROOM/SPACE TO THE ENGINEER FOR APPROVAL. DO NOT INSTALL SENSORS SUCH THAT THEY CAN POTENTIALLY "SEE" THROUGH OPEN DOORWAYS. INSTALL ALL LOW VOLTAGE POWER PACKS DIRECTLY ABOVE LOCAL WALL SWITCHES IN THE AREA. DO NOT INSTALL ULTRASONIC OR DUAL TECHNOLOGY SENSORS WITHIN 24" OF SUPPLY
DIFFUSERS.
7 ALL EMERGENCY EGRESS ILLUMINATION SHALL BE AVERAGE 1FC AND A MINIMUM OF 0.1FC FOR PATH OF EGRESS.
8 PROVIDE EQUIPMENT GROUND CONDUCTOR IN ALL RACEWAYS. REFER TO PANELBOARD SCHEDULES.
9 ROUTE CONDUIT HIGH AGAINST STRUCTURE AND OFFSET UP BETWEEN JOISTS WHERE NECESSARY TO AVOID DUCT
WORK AND HVAC SYSTEM.
10 PROVIDE CONDUIT AND WIRING AS REQUIRED TO MEET CIRCUITING SHOWN TO CONFORM TO NEC REQUIREMENTS.
8' 16'4'0 1/8" = 1'-0"1
ELECTRICAL LIGHTING PLAN - BASEMENT EAST
# Revisions Date
LIGHTING PLAN KEYNOTES
1 LIGHTING FIXTURES SHALL BE COORDINATED WITH MECHANICAL EQUIPMENT AND
DUCTWORK/PIPING. LIGHTING FIXTURES SHALL BE INSTALLED BELOW DUCT AND
PIPE RUNS TO AVOID OBSTRUCTIONS.
AC
GFI
GFI
A C
G
FI
AC
GFI
AC
GFI
48"
GFI
A C
G
FI
G
FI
J
J
J
CLNG
J
CLNG
J
CLNG
J
CLNG
J
CLNG
J
CLNG
J
CLNG
J
CLNG
CLNG
(XR)AHU-9
X-RAY
B120E
TLT / CHANGING
B120F
CLEAN
B120G
WAITING
B119
SOILED HOLDING
B120CCT SCANNING
B120D
RECEPTION / WORK
B120A
MENS
B114
WOMENS
B113
STAIR 2 (NIC)
S2
ELEVATOR (NIC)
E2
ELEVATOR (NIC)
E1
SERV ELEV
SE1
MENS DRESSING
B100E
CLEAN LINEN ROOM
B100CEMS OFFICE 1
B100B
EMS OFFICE 2
B100A
CORRIDOR
C02
CORRIDOR
C02
EMS SUPPLY
B104
EMS SUITE
B100
PHARMACY CACHE
B111
CORRIDOR
C04
CORRIDOR
C06
54"
(XR)CU-9
E
F
G
H
C
B
A
2221201918A1615
I
J
13121087
43A321
19A
9 11 13A
D
18 20B17A 17B
MECHANICAL OFFICE
B101
M A
T C
H L
IN
E
EMS STORAGE
B103
STORAGE
B118
RES. SLEEPING
ROOM
B115
RESIDENT TLT RM
B115A
GME LIBRARY
B116
AHU-B4
AHU-B3
60"
LPL
LP-BD
LP-BC
CR-B
EQ-B
EM-B
LPE1
WOMENS DRESSING
B100D
STORAGE
B100F
MECH
B102B
CP-2
CLOSET
B120B
LPL-12
LPL-12
LPL-12
LPL-12
LPL-12
LPL-12
RADIOLOGY
B120
LPL-18
LPL-14 LPL-14
LPL-16
LPL-18
LPL-18
LP-BD-29LP-BD-23
LP-BD-29
LP-BD-29
LP-BD-29
LP-BD-29
LP-BD-27
LP-BD-27
LP-BD-25
LP-BD-25
LP-BD-11
LP-BD-11
LP-BD-11
LP-BD-11
LP-BD-9
LP-BD-9
CORRIDOR
C05 LP-BD-9
LP-BC-22
LP-BC-10
LP-BC-10
LP-BC-12
LP-BC-10
LP-BC-14
LP-BC-14LP-BC-16
LP-BC-16
LP-BC-10
LP-BC-10
LP-BC-12
LP-BC-12
LP-BC-12
LP-BC-18
LP-BD-7
LP-BD-7
LP-BC-18
LP-BC-20
LP-BD-7LP-BD-7
LP-BC-20
LP-BC-22
LP-BC-22
EQ-B-8
EQ-B-8
EQ-B-15 EQ-B-15 EQ-B-11
EQ-B-11 EQ-B-11 EQ-B-11
EQ-B-11
LP-BD-19
LP-BD-17 LP-BD-17 LP-BD-17 LP-BD-17
LP-BD-17
LP-BD-19
LP-BD-19
CR-B-12
CR-B-8
LP-BD-19
MLP-BD-30
LP-BD-18,20,22
LP-BD-24,26,28
CR-B-12
CR-B-12
COPIER
PRINTER
CR-B-12
ENGINEERING (NIC)
B105
CR-B-18
CR-B-18 CR-B-18CR-B-18
CR-B-18
CR-B-20
CR-B-19
CR-B-22
CR-B-22
CR-B-22
CR-B-22
CR-B-23
CR-B-23
CR-B-23
CR-B-24CR-B-24
CR-B-24
CR-B-24
CR-B-25CR-B-26
FCU-B120D
FCU-B120E
FCU/CU-B120E
FCU/CU-B120D
CR-B-28,30
CR-B-27,29 2
(TYPICAL)
LP-BC-15
EXISTING TO REMAIN
EXISTING TO REMAIN
CR-B-23
AF
AF
AF
EQ-B-17 EQ-B-17 EQ-B-17 EQ-B-17
EQ-B-19
EQ-B-19
EQ-B-19
CORRIDOR
C03
CR-B-21
CR-B-21
66 6 6
6 6
WEST (BW) EAST (BE)
BASEMENT
GENERAL AREA OF
WORK (REFER TO
PLAN FOR DETALS)
BASEMENT
AREA OF FUTURE WORK
(NOT IN CONTRACT)
NOT IN CONTRACT
N O
T
IN
C O
N T
R A
C T
M A
T C
H
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
B
IM
/1
F t.
W a y n e V
A M
C B a s e m e n t B ld g
/1
M
E P
C e n tr a l
.r v t
/1
/2
:2
:3
P
M
E201W
ELECTRICAL POWER PLAN - BASEMENT WEST
AE Works
209 SANDUSKY STREET
PITTSBURGH, PA 15212
412-287-7333
RENOVATE BASEMENT,
BUILDING 1
2121 LAKE AVE, FORT WAYNE, IN 46805
610A4-19-104
07/15/2020 BK TJR
BID DOCUMENTS
8' 16'4'0 1/8" = 1'-0"1
ELECTRICAL POWER PLAN - BASEMENT WEST
POWER PLAN GENERAL NOTES
1 FINAL LOCATION OF ALL EQUIPMENT SHALL BE DETERMINED IN THE FIELD AND SHALL BE
INSTALLED AS DIRECTED BY THE ARCHITECT OR OWNER'S REPRESENTATIVE. WHERE
STRUCTURAL OPENINGS ARE NOT AVAILABLE, THE CONTRACTOR SHALL CORE DRILL WALLS AND
FLOORS AS REQUIRED TO PERMIT PASSAGE OF CONDUITS. THE ELECTRICAL CONTRACTOR SHALL
PROVIDE A MARKED-UP PLAN WITH LOCATION PENETRATIONS FOR REVIEW AND APPROVAL OF
THE STRUCTURAL ENGINEER BEFORE ROUGH-IN BEGINS.
2 RECEPTACLES FOR ALL EQUIPMENT SHALL BE COMPLETE WITH PLUGS FOR THIS EQUIPMENT. THE
ELECTRICAL CONTRACTOR SHALL VERIFY NEMA CONFIGURATIONS OF PLUGS AND RECEPTACLES
FOR EQUIPMENT IN THE SPACE.
3 DURING THE BIDDING PROCESS, THE ELECTRICAL CONTRACTOR SHALL REVIEW DRAWINGS AND SPECIFICATIONS OF ALL OTHER TRADES (ARCHITECTURAL, SITE/LANDSCAPING, HVAC, PLUMBING
AND SPECIALTY TRADES). ALL ITEMS REQUIRING POWER INDICATED ON THESE DRAWINGS BUT
INDICATED ON THE ELECTRICAL DRAWINGS SHALL BE CONSIDERED A PART OF THE ELECTRICAL
CONTRACTOR'S WORK. THIS WORK SHALL BE INSTALLED AS PER NEC REQUIREMENTS AT NO
ADDITIONAL COST TO THE OWNER.
4 THE CONTRACTOR SHALL MAKE EVERY EFFORT TO MAKE ALL FEEDER RUNS CONTINUOUS (NO
CABLE BREAKS). IF SPLICING CABLES IN BOXES BECOMES NECESSARY, USE O.Z.G. TYPE "XW"
CABLE TAPS, OR APPROVED EQUAL, AND TAPE EACH TAP IN APPROVED MANNER.
5 THE MECHANICAL CONTRACTOR SHALL PROVIDE DISCONNECT SWITCHES, VFD'S. OR
COMBINATION STARTERS FOR ALL OF THEIR UNITS. THE ELECTRICAL CONTRACTOR SHALL
RECEIVE THESE ITEMS FROM THE MECHANICAL CONTRACTOR FOR INSTALLATION BY THE
ELECTRICAL CONTRACTOR.
6 THE ELECTRICAL CONTRACTOR SHALL COORDINATE CONDUIT PENETRATIONS FOR ROOFTOP
EQUIPMENT WITH MECHANICAL AND ROOFING CONTRACTORS. IF PROVISIONS ARE NOT IN PLACE
FOR THESE PENETRATIONS THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR MAKING
OWN PENETRATIONS AND CONTRACTING THE ROOF CONTRACTOR FOR SEALING THE ROOF
PENETRATIONS.
7 REFER TO MECHANICAL DRAWINGS FOR EXACT LOCATION OF ALL MECHANICAL EQUIPMENT.
8 PROVIDE CONDUIT AND WIRING AS REQUIRED TO MEET CIRCUITING SHOWN TO CONFORM TO NEC
REQUIREMENTS.
9 PROVIDE EQUIPMENT GROUND CONDUCTOR IN ALL RACEWAYS. REFER TO PANELBOARD
SCHEDULES.
10 REFER TO EQUIPMENT CONNECTION SCHEDULE FOR ELECTRICAL REQUIREMENTS AND CIRCUIT
DESIGNATIONS.
11 ROUTE CONDUIT HIGH AGAINST STRUCTURE AND OFFSET UP BETWEEN JOISTS WHERE
NECESSARY TO AVOID DUCT WORK AND HVAC SYSTEM.
12 VERIFY AND COORDINATE EXACT ELECTRICAL REQUIREMENTS OF ALL EQUIPMENT WITH
MANUFACTURER'S RECOMMENDATIONS PRIOR TO INSTALLATION OF EQUIPMENT.
NORTH
TRUE NORTH=
PROJECT
88.5°
# POWER PLAN KEYNOTES
1 EXISTING POWER INSTALLATION ASSOCIATED WITH INDICATED MECHANICAL EQUIPMENT
SHALL REMAIN IN PLACE AND OPERATIONAL .
2 PROVIDE A STANDALONE UNISTRUT FOR MOUNTING OF DISCONNECT SWITCH. DISCONNECTS
SHALL BE NEMA 3R AND LOCKABLE. ENSURE PROPER CLEARANCE AND ACCESS PER NEC IS
PROVIDED. THE CU/FCU IS A SINGLE POINT POWER CONNECTION. THE FCU IS FED FROM ITS
RESPECTIVE CU. PROVIDE ALL REQUIRED CONNECTIONS PER THE MANUFACTURER WIRING
DIAGRAM. PROVIDE RECEPTACLE FOR SUPPORTING CONDENSATE PUMP UNIT LOCATED
ABOVE CEILING.
3 EXISTING CORRIDOR RECEPTACLES TO REMAIN. EXISTING RECEPTACLES LOCATED ON
EXISTING TO BE DEMOLISHED WALLS SHALL BE REMOVED AND RELOCATED TO NEW WALLS.
CONTRACTOR TO ENSURE THAT CORRIDOR RECEPTACLE QUANTITY OF NEW WORK MATCHES
CORRIDOR RECEPTACLE QUANTITY OF EXISTING CONDITIONS.
4 ELECTRICAL CONTRACTOR TO COORDINATE WITH MECHANICAL CONTRACTOR AND PROVIDE
POWER TO VAV TRANSFORMERS AS NECESSARY. DETERMINE EXACT LOCATION OF
TRANSFORMERS IN FIELD.
5 IMAGING EQUIPMENT TO BE INSTALLED IN A FUTURE PROJECT. BASIS OF DESIGN SHOWN FOR
COORDINATION PURPOSES ONLY. ELECTRICAL DESIGN FOR IMAGING EQUIPMENT AND
ASSOCIATED EQUIPMENT TO BE DESIGNED IN A FUTURE PROJECT.
6 PROVIDE A 20A/120V CIRCUIT ABOVE CEILING FOR POWER TO DOOR HARDWARE ACCESS
CONTROL PANEL. COORDINATE EXACT LOCATION WITH THE RESPECTIVE CONTRACTOR.
A C
A C
A C
AC AC
A C
G
FI
J
J J
J
J
J
GFI
G
FI
G
FI
GFI
GFI
WP
J
GFI
GFICLNG
J
WEST (BW) EAST (BE)
BASEMENT
GENERAL AREA OF
WORK (REFER TO
PLAN FOR DETALS)
BASEMENT
AREA OF FUTURE WORK
(NOT IN CONTRACT)
NOT IN CONTRACT
N O
T
IN
C O
N T
R A
C T
M A
T C
H
(XR)CH-1
(XR)CU-4
(XR)CU-CAN
(XR)CU-S
(XR)CU-52
CU-B5
AHU-B1
AHU-B2
CU-B2
CU-B1
CU-B3
(XR)AHU
MAILROOM
B300
OIT OFFICE
B309
MECH ROOM 1
B308
BIOMED STORAGE
B310
WORKSHOP
B316C
BIOMED
B316
OFFICE
B316B
TOILET ROOM
B315
VESTIBULE (NIC)
STAIR 4 (NIC)
S4
STAIR 3 (NIC)
S3
STORAGE
B316D
E
F
G
H
C
36353433
32312927252423
33A
302826
B
A
I
22A
D
20B 30A
M A
T C
H L
IN
E
BATTERY ROOM
B307
STOR / SOILED LINEN
CART
B306
PACKAGE LOCKER
B301
STORAGE
B316A
AHU-B5
EF-B307
EF-B300
HWP-1 HWP-2
HWP-2
HWP-1
OIT SERVER
B311
LP-BB
PP-2
LP-BA
(XR)CU-N
M
M
SURFACE METAL
RACEWAY (TYPICAL)
CU-B4
ENGINEERING
STORAGE
B312
CP-1
EXISTING
BATTERY
RACK
EXISTING
DATA
RACK
M
EF-B306
LP-BC-32
LP-BC-30
LP-BC-30
LP-BC-36
LP-BC-32
LP-BC-32
LP-BC-32
LP-BC-30
LP-BB-9
LP-BB-11
LP-BB-32
LP-BB-32LP-BB-32
LP-BB-32
LP-BB-12LP-BB-14
LP-BB-12
LP-BB-14
LP-BB-14
LP-BA-2
LP-BB-14 LP-BB-16
LP-BB-16 LP-BB-16
LP-BB-16
LP-BA-16
LP-BA-9
LP-BA-21
LP-BA-21
LP-BA-21
LP-BA-21
LP-BA-19 LP-BA-19 LP-BA-29
LP-BA-29
LP-BA-29LP-BA-21
LP-BA-16
LP-BA-16
LP-BA-16
LP-BA-32
LP-BA-32
LP-BA-22
LP-BA-22
LP-BA-28
LP-BA-28 LP-BA-30
LP-BA-30
LP-BA-20LP-BA-18
LP-BA-18
LP-BA-20
M
EQ-B-12
LP-BB-22
EQ-B-20
LP-BB-42 LP-BB-33,35
LP-BB-29,31
LP-BB-37,39,41
LP-BB-2,4,6
LP-BB-1,3,5
LP-BB-13,15,17LP-BB-36,38,40
LP-BB-26,28,30
COPIER
COPIER
LP-BB-14
LP-BB-32
LP-BA-11,13
LP-BB-7
CORRIDOR
C07
(TYPICAL)
LP-BA-35,37
NEMA 6-20R
NEMA 6-20R7
LP-BA-5
LP-BA-1,3
LP-BA-4,6
EXISTING
TO
REMAINEXISTING TO REMAIN
LP-BA-2
LP-BA-2EQ-B-198
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
B
IM
/1
F t.
W a y n e V
A M
C B a s e m e n t B ld g
/1
M
E P
C e n tr a l
.r v t
/1
/2
:2
:3
P
M
E202E
ELECTRICAL POWER PLAN - BASEMENT EAST
AE Works
209 SANDUSKY STREET
PITTSBURGH, PA 15212
412-287-7333
RENOVATE BASEMENT,
BUILDING 1
2121 LAKE AVE, FORT WAYNE, IN 46805
610A4-19-104
07/15/2020 BK TJR
BID DOCUMENTS
NORTH
TRUE NORTH=
PROJECT
88.5°
8' 16'4'0 1/8" = 1'-0"1
ELECTRICAL POWER PLAN - BASEMENT EAST
POWER PLAN GENERAL NOTES
1 FINAL LOCATION OF ALL EQUIPMENT SHALL BE DETERMINED IN THE FIELD AND SHALL BE
INSTALLED AS DIRECTED BY THE ARCHITECT OR OWNER'S REPRESENTATIVE. WHERE
STRUCTURAL OPENINGS ARE NOT AVAILABLE, THE CONTRACTOR SHALL CORE DRILL WALLS AND
FLOORS AS REQUIRED TO PERMIT PASSAGE OF CONDUITS. THE ELECTRICAL CONTRACTOR SHALL
PROVIDE A MARKED-UP PLAN WITH LOCATION PENETRATIONS FOR REVIEW AND APPROVAL OF
THE STRUCTURAL ENGINEER BEFORE ROUGH-IN BEGINS.
2 RECEPTACLES FOR ALL EQUIPMENT SHALL BE COMPLETE WITH PLUGS FOR THIS EQUIPMENT. THE
ELECTRICAL CONTRACTOR SHALL VERIFY NEMA CONFIGURATIONS OF PLUGS AND RECEPTACLES
FOR EQUIPMENT IN THE SPACE.
3 DURING THE BIDDING PROCESS, THE ELECTRICAL CONTRACTOR SHALL REVIEW DRAWINGS AND SPECIFICATIONS OF ALL OTHER TRADES (ARCHITECTURAL, SITE/LANDSCAPING, HVAC, PLUMBING
AND SPECIALTY TRADES). ALL ITEMS REQUIRING POWER INDICATED ON THESE DRAWINGS BUT
INDICATED ON THE ELECTRICAL DRAWINGS SHALL BE CONSIDERED A PART OF THE ELECTRICAL
CONTRACTOR'S WORK. THIS WORK SHALL BE INSTALLED AS PER NEC REQUIREMENTS AT NO
ADDITIONAL COST TO THE OWNER.
4 THE CONTRACTOR SHALL MAKE EVERY EFFORT TO MAKE ALL FEEDER RUNS CONTINUOUS (NO
CABLE BREAKS). IF SPLICING CABLES IN BOXES BECOMES NECESSARY, USE O.Z.G. TYPE "XW"
CABLE TAPS, OR APPROVED EQUAL, AND TAPE EACH TAP IN APPROVED MANNER.
5 THE MECHANICAL CONTRACTOR SHALL PROVIDE DISCONNECT SWITCHES, VFD'S. OR
COMBINATION STARTERS FOR ALL OF THEIR UNITS. THE ELECTRICAL CONTRACTOR SHALL
RECEIVE THESE ITEMS FROM THE MECHANICAL CONTRACTOR FOR INSTALLATION BY THE
ELECTRICAL CONTRACTOR.
6 THE ELECTRICAL CONTRACTOR SHALL COORDINATE CONDUIT PENETRATIONS FOR ROOFTOP
EQUIPMENT WITH MECHANICAL AND ROOFING CONTRACTORS. IF PROVISIONS ARE NOT IN PLACE
FOR THESE PENETRATIONS THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR MAKING
OWN PENETRATIONS AND CONTRACTING THE ROOF CONTRACTOR FOR SEALING THE ROOF
PENETRATIONS.
7 REFER TO MECHANICAL DRAWINGS FOR EXACT LOCATION OF ALL MECHANICAL EQUIPMENT.
8 PROVIDE CONDUIT AND WIRING AS REQUIRED TO MEET CIRCUITING SHOWN TO CONFORM TO NEC
REQUIREMENTS.
9 PROVIDE EQUIPMENT GROUND CONDUCTOR IN ALL RACEWAYS. REFER TO PANELBOARD
SCHEDULES.
10 REFER TO EQUIPMENT CONNECTION SCHEDULE FOR ELECTRICAL REQUIREMENTS AND CIRCUIT
DESIGNATIONS.
11 ROUTE CONDUIT HIGH AGAINST STRUCTURE AND OFFSET UP BETWEEN JOISTS WHERE
NECESSARY TO AVOID DUCT WORK…