Drawings_2020-07-15_reprint-3 of 3.pdf

PDF 5 MB Posted

Attached to
Y1DZ--Renovate Basement, Building 1 610A4-19-104
Solicitation number
36C25021B0018
Issued by

About this file

This document contains details for a federal contract solicitation to renovate a basement at a Veterans Health Administration facility. The solicitation requests contractors provide all labor, equipment, materials and supervision necessary to renovate space in the basement of Building 1 at the VA Northern Indiana Health Care System campus in Fort Wayne, Indiana. Renovations are needed for Environmental Management Services, Biomedical, Pharmacy, Mailroom, Engineering Services, Office of Information Technology, Graduate Medical Education, and Medical Imaging areas. The project is divided into three phases, with Phase I expected to take 300 days, Phase II expected to take 210 days, and Phase III expected to take 270 days. All work must be completed at the VA Northern Indiana Health Care campus located at 2121 Lake Ave, Fort Wayne, IN 46805.

View the file

Other files

File Type Posted
36C25021B0018 0010.docx DOCX document
36C25021B0018 0009.docx DOCX document
36C25021B0018 0008.docx DOCX document
36C25021B0018 0007.docx DOCX document
Fort Wayne_Interior Sign Spec r1.pdf PDF
RFI Responses 4-13-21.xlsx XLSX spreadsheet
RFI (PLUMBING) Response.pdf PDF
RFI - scan0001 - Amendment 0006.pdf PDF
36C25021B0018 0006.docx DOCX document
RFI 03 - Amendment 0006.pdf PDF
RFI 02 - Amendment 0006.pdf PDF
36C25021B0018 0005.docx DOCX document
RFI Received 3-18-21.pdf PDF
Handout Sheet - scheduled work stoppage.docx DOCX document
Breez Lighting Specs 3-22-21.pdf PDF
Pre-Bid Sign-In Sheet.pdf PDF
36C25021B0018 0004.docx DOCX document
CO Pre-Bid Remarks.pdf PDF
Sole Source JA - Breez lighting-signed.pdf PDF
36C25021B0018 0003.docx DOCX document
Drawings_2020-07-15_reprint-2 of 3.pdf PDF
Amendment 0002.docx DOCX document
36C25021B0018 0001.docx DOCX document
Drawings_2020-07-15_reprint-1 of 3.pdf PDF
RFI Form.pdf PDF
Contractor EMR Certification Form.pdf PDF
6-drawings-Renovate Basement.pdf PDF
36C25021B0018.docx DOCX document
5a-specs-Renovate Basement.pdf PDF
Wage Determination 02-26-2021.txt TXT text file
5b-specs-Renovate Basement.pdf PDF
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

L

J

PB

J

P

P

J

R

OS

LS

P C

TC

H

T

1P 1 POLE (2P, 3P, 4P, ETC.)

A AMPERE

AC ABOVE COUNTER OR AIR

CONDITIONER

ACLG ABOVE CEILING

ADO AUTOMATIC DOOR OPENER

AF ARC FAULT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFI ARC FAULT CIRCUIT INTERRUPTER

AHU AIR HANDLING UNIT

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

AMPL AMPLIFIER

ANNUN ANNUNCIATOR

APPROX APPROXIMATELY

AQ-STAT AQUASTAT

ARCH ARCHITECT, ARCHITECTURAL

AS AMP SWITCH

AT AMP TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

AWG AMERICAN WIRE GAUGE

BATT BATTERY

BD BOARD

BLDG BUILDING

BMS BUILDING MANAGEMENT SYSTEM

C CONDUIT

CAB CABINET

CAT CATALOG

CATV CABLE TELEVISION

CB CIRCUIT BREAKER

CCTV CLOSED CIRCUIT TELEVISION

CKT CIRCUIT

CLG CEILING

COMB COMBINATION

CMPR COMPRESSOR

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUATION OR CONTINUOUS

CONTR CONTRACTOR

CONV CONVECTOR

CP CIRCULATING PUMP

CRT CATHODE-RAY TUBE

CT CURRENT TRANSFORMER

CTR CENTER

CU COPPER

DCP DOMESTIC WATER CIRCULATING PUMP

DEPT DEPARTMENT

DET DETAIL

DIA DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DPR DAMPER

DS SAFETY DISCONNECT SWITCH

DT DOUBLE THROW

DWG DRAWING

EC ELECTRICAL CONTRACTOR

ELEC ELECTRIC, ELECTRICAL

ELEV ELEVATOR

EM EMERGENCY

EMS ENERGY MANAGEMENT SYSTEM

EMT ELECTRICAL METALLIC TUBING

EP ELECTRIC PNEUMATIC

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EXIST EXISTING

EXH EXHAUST

EXP EXPLOSION PROOF

FA FIRE ALARM

FABP FIRE ALARM BOOSTER POWER

SUPPLY PANEL

FACP FIRE ALARM CONTROL PANEL

FCU FAN COIL UNIT

FIXT FIXTURE

FLR FLOOR

FLUOR FLUORESCENT

FU FUSE

FUDS FUSED SAFETY DISCONNECT SWITCH

GA GAUGE

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR

GFI GROUND FAULT CIRCUIT

INTERRUPTER

GFP GROUND FAULT PROTECTOR

GND GROUND

GRS GALVANIZED RIGID STEEL (CONDUIT)

GYP BD GYPSUM BOARD

HOA HANDS-OFF-AUTOMATIC SWITCH

HORIZ HORIZONTAL

HP HORSEPOWER

HPF HIGH POWER FACTOR

HT HEIGHT

HTG HEATING

HTR HEATER

HV HIGH VOLTAGE

HVAC HEATING, VENTILATING AND

AIR CONDITIONING

HWP HYDRONIC WATER PUMP

IC INTERRUPTING CAPACITY

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

I/W INTERLOCK WITH

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAR KILOVOLT-AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

LOC LOCATE OR LOCATION

LT LIGHT

LTG LIGHTING

LTNG LIGHTNING

LV LOW VOLTAGE

MAX MAXIMUM

MAG.S MAGNETIC STARTER

M/C MOMENTARY CONTACT

MC MECHANICAL CONTRACTOR

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDC MAIN DISTRIBUTION CENTER

MDP MAIN DISTRIBUTION PANEL

MFR MANUFACTURER

MFS MAIN FUSED DISCONNECT SWITCH

MH MANHOLE

MIC MICROPHONE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MMS MANUAL MOTOR STARTER

MOA MULTIOUTLET ASSEMBLY

MSP MOTOR STARTER PANELBOARD

MSBD MAIN SWITCHBOARD

MT MOUNT

MT.C EMPTY CONDUIT

MTS MANUAL TRANSFER SWITCH

MTR MOTOR, MOTORIZED

N.C. NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURER'S ASSOCIATION

NFDS NON-FUSED SAFETY

DISCONNECT SWITCH

NIC NOT IN CONTRACT

NL NIGHT LIGHT

N.O. NORMALLY OPEN

NPF NORMAL POWER FACTOR

NTS NOT TO SCALE

OH OVERHEAD

OL OVERLOADS

PA PUBLIC ADDRESS

PB PULL BOX OR PUSHBUTTON

PE PNEUMATIC ELECTRIC

PED PEDESTAL

PF POWER FACTOR

PH PHASE

PIV POST INDICATING VALVE

PNL PANEL

PP POWER POLE

PR PAIR

PRI PRIMARY

PROJ PROJECTION

PRV POWER ROOF VENTILATOR

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE (CONDUIT)

PWR POWER

QUAN QUANTITY

RCPT RECEPTACLE

REQD REQUIRED

RM ROOM

RSC RIGID STEEL CONDUIT

RTU ROOF TOP UNIT

SC SURFACE CONDUIT

SEC SECONDARY

SHT SHEET

SIM SIMILAR

S/N SOLID NEUTRAL

SPEC SPECIFICATION

SPKR SPEAKER

SP SPARE

SR SURFACE RACEWAY

SS STAINLESS STEEL

SSW SELECTOR SWITCH

S/S STOP/START PUSHBUTTONS

STA STATION

STD STANDARD

SURF SURFACE MOUNTED

SW SWITCH

ELECTRICAL ABBREVIATIONS LIST

SWBD SWITCHBOARD

SYM SYMMETRICAL

SYS SYSTEM

TEL TELEPHONE

TERM TERMINAL

TL TWIST LOCK

TR TAMPER RESISTANT

T-STAT THERMOSTAT

TTC TELEPHONE TERMINAL CABINET

TV TELEVISION

TVTC TELEVISION TERMINAL CABINET

TYP TYPICAL

UC UNDER COUNTER

UE UNDERGROUND ELECTRICAL

UG UNDERGROUND

UH UNIT HEATER

UT UNDERGROUND TELEPHONE

UTIL UTILITY

UV UNIT VENTILATOR OR ULTRAVIOLET

V VOLT

VA VOLT-AMPERES

VDT VIDEO DISPLAY TERMINAL

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VOL VOLUME

W WATT

W/ WITH

WG WIRE GUARD

WH WATER HEATER

W/O WITHOUT

WP WEATHERPROOF

XFMR TRANSFORMER

XFR TRANSFER

@ AT

' FEET

" INCHES

# NUMBER

Ø PHASE

C CENTER LINE

P PLATE

RECEPTACLES, FURNITURE FEEDS

THE ABOVE MOUNTING ELEVATIONS ARE TO CENTER OF DEVICE AND SHALL BE ADHERED

TO UNLESS SPECIFICALLY NOTED OR DETAILED OTHERWISE ON THE DRAWINGS AND/OR

SPECIFICATIONS.

IN FLOOR JUNCTION BOXES FLUSH TO

FINISHED FLOOR (FF)

IN MASONRY CONSTRUCTION THE MOUNTING HEIGHTS SHALL BE USED FOR REFERENCE TO

THE NEAREST BLOCK OR BRICK COURSING.

COORDINATE THE INSTALLATION AND MOUNTING ELEVATIONS OF ALL EQUIPMENT, DEVICES,

CONTROLS AND APPURTENANCES WITH ARCHITECT AND ALL AFFECTED TRADES PRIOR TO

INSTALLATION. DOCUMENT ALL MOUNTING ELEVATIONS FOR ALL EQUIPMENT, DEVICES,

CONTROLS AND APPURTENANCES AT THE TIME OF SHOP DRAWING SUBMITTAL.

3.

2.

1.

0'-0"

1'-5" A.F.F.

STANDARD MOUNTING HEIGHTS

RECESSED LIGHTING FIXTURES, CEILING

MOUNTED RECEPTACLES, INDICATING LIGHTS,

ETC.

CEILING

ABOVE COUNTER DEVICES, GFI RECEPTACLES IN

RESTROOMS.

3'-6" A.F.F.

WALL SWITCHES, THERMOSTATS, CONTROL DEVICES,

TO CENTER OF BOX

3'-8" A.F.F.

TOP OF PANELBOARDS (<6'-0" TALL)6'-0" A.F.F.

TOP MOST PORTION OF OPERATING HANDLE OF

DISCONNECT SWITCHES / CIRCUIT BREAKERS

6'-6" A.F.F.

WALL MOUNTED LIGHTS IN STAIRS, MECH ROOMS,

ETC.

7'-0" A.F.F.

ADA INSTALLATION GUIDELINES

34"

46"

MAX.

(NOTE #2)

44"

MAX.

(FOR 20-25")

(NOTE #2)

10-24" 25" MAX.

48"

MAX.

(FOR 20")

(NOTE #2)

OBSTRUCTED HIGH

SIDE REACH

OBSTRUCTED HIGH

FORWARD REACH

48"

MAX.

(NOTE #2)

10"

MAX.

15"

MIN.

48"

MAX.

(NOTE #2)

15"

MIN.

OBSTRUCTED

SIDE REACH

OBSTRUCTED

FORWARD REACH

NOTES:

1. THESE GUIDELINES SHALL BE USED FOR THE INSTALLATION OF THE FOLLOWING DEVICES:

- WALL SWITCHES

-CONTROL SWITCHES

-RECEPTACLES

-VISUAL DISPLAY TOUCH PANELS

2. NOTE THAT THIS HEIGHT IS TO THE TOP-MOST PART OF THE DEVICE THAT AN OCCUPANT

REQUIRES ACCESS TO.

THIS PROJECT WILL REQUIRE SHUT-DOWNS TO THE NORMAL POWER SYSTEM OF THE HOSPITAL, WHICH WILL REQUIRE SECOND OR THIRD SHIFT WORK, AS WELL AS WEEKEND WORK. THE CONTRACTOR SHALL

COORDINATE THIS WORK WITH THE COR, AND PLAN HIS WORK ACCORDINGLY.

CONTRACTOR SHALL PROVIDE A MINIMUM TWO WEEKS WRITTEN NOTICE PRIOR TO ANY SHUT DOWN. NOTICE IS

TO INCLUDE BUT IS NOT LIMITED TO THE LOCATION, PANELS AND DURATION OF SHUT DOWN.

DURING ALL UTILITY SHUT-DOWNS OF THE NORMAL POWER SYSTEM, THE CONTRACTOR SHALL HAVE AN EMERGENCY GENERATOR ON SITE WITH 24 HOURS OF FUEL. THE CONTRACTOR SHALL HAVE SUITABLE TEMPORARY CABLES NEEDED TO PROVIDE EMERGENCY CONNECTIONS TO THE SWITCHGEAR IN THE EVENT

THERE IS A PROBLEM.

THE CONTRACTOR SHALL GENERATE A DETAILED METHOD OF PROCEDURE (MOP) DOCUMENT INDICATING HOW HE/SHE INTENDS TO PERFORM EACH STEP IN THE PROJECT. THIS MOP SHALL BE PRESENTED TO THE OWNER AND ENGINEER PRIOR TO STARTING THE PROJECT, FOR SIGN OFF.THE MOP MAY BE REVISED BASED ON CHANGES IN THE PROJECT CONSTRUCTION, ETC. AT ALL POINTS IN THE PROJECT THE COR SHALL BE MADE AWARE OF CHANGES TO THE MOP, AND A REVISED MOP SHALL BE PRESENTED TO THE COR AND ENGINEER

FOR SIGN OFF.

1.

UTILITY SHUTDOWNS

2.

3.

4.

RELAY

SYMBOL SYMBOL

ELECTRICAL SYMBOL LEGEND

J

2 POLE SINGLE THROW SW.

SINGLE POLE SW.

LIGHT ON CORD REEL (TYPE DENOTED)

LIGHTING CHANNEL WIRE (TYPE DENOTED)

DIMMER SWITCH

MOMENTARY CONTACT SWITCH

OCCUPANCY SENSOR SWITCH

EMERGENCY PUSH BUTTON

SINGLE RECEPT.

KEYED SWITCH

SPLIT DUPLEX RECEPT.

FOURPLEX RECEPT.

DUPLEX RECEPT.

RECEPT ON EMERGENCY CKT (DUPLEX SHOWN)

ISOLATED GROUND RECEPT (DUPLEX SHOWN)

240 VOLT RECEPT.

RECEPT ON DROP CORD (DUPLEX SHOWN)

RECEPT ON CORD REEL (DUPLEX SHOWN)

FLOOR RECEPT. (DUPLEX SHOWN)

TIMER SWITCH (1, 2, 4, 6, & 12 HOUR OPTIONS)

VACANCY SENSOR SWITCH

SW. W/PILOT

3-WAY SW.

4-WAY SW.

DESCRIPTION

WALL MOUNTED FLOODLIGHT (TYPE DENOTED)

POLE MOUNTED LIGHT (TYPE DENOTED)

RECESSED LIGHT (TYPE DENOTED)

SURFACE LIGHT (TYPE DENOTED)

EXIT SIGN (TYPE DENOTED)

SUSPENDED OR PENDANT LIGHT (TYPE DENOTED)

TRACK AND TRACK LIGHT (TYPES DENOTED)

SURFACE LINEAR LIGHT (TYPE DENOTED)

STRIP LIGHT (TYPE DENOTED)

EMERGENCY BATTERY LIGHT (TYPE DENOTED)

RECESSED LINEAR LIGHT (TYPE DENOTED)

POLE MOUNTED FLOODLIGHT (TYPE DENOTED)

FOURPLEX RECEPTACLE ON EMERGENCY CIRCUIT

LIGHT FIXTURE ON (EM) LIFE SAFETY BRANCH

LIGHT FIXTURE ON (EM) CRITICAL BRANCH

CIRCUIT BREAKER PANEL

DASHED SYMBOL INDICATES REMOVED

HALFTONE SYMBOL INDICATES EXISTING

SOLENOID VALVE

BUS DUCT WITH PLUG IN DISCONNECT (FUSED)

LIGHT LEVEL SENSOR - TYPE DENOTED

TIME CONTROL SWITCH (TIME SWITCH)

HUMIDISTAT

THERMOSTAT

PHOTOCELL

ENCLOSED CIRCUIT BREAKER

PRESSURE SWITCH

SAFETY DISC. SW. (FUSED)

SAFETY DISC. SW. (NON-FUSED)

COMB. MOTOR STARTER (FUSED)

POWER OR DISTRIBUTION PANEL

TRANSFORMER (TYPE DENOTED)

STATIC GROUND RECEPTACLE (TYPE DENOTED)

SPECIAL RECEPT. OR CONN. (SEE SCHEDULE)

JUNCTION BOX

PULL BOX

GROUND ROD (PLAN VIEW)

LIGHTNING PROTECTION AIR TERMINAL

SURGERY SERVICE COLUMN

CLOCK (TYPE DENOTED)

POWER POLE (OPEN OFFICE STYLE)

MULTIOUTLET ASSEMBLY (TYPE DENOTED)

DESCRIPTION

LIGHTNING PROTECTION CONDUCTOR SPLICE

UTILITY SERVICE POWER POLE (SITE)

OCCUPANCY SENSOR - TYPE DENOTED

FLOAT SWITCH

V D

VACANCY SENSOR DIMMER SWITCH

MULTI BUTTON LOW VOLTAGE SWITCHLV

K

M C

T V

S D

O S

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseArchitect/Engineer of Record StampConsultant

321 4 5 6 7 8 9 10

Sprinkler Status

B

IM

/1

F t.

W a y n e V

A M

C B a s e m e n t B ld g

/1

M

E P

C e n tr a l

.r v t

/1

/2

:2

:3

P

M

E001

ELEC SYMBOLS, ABBREVIATIONS, AND

GENERAL NOTESAE Works

209 SANDUSKY STREET

PITTSBURGH, PA 15212

412-287-7333

RENOVATE BASEMENT,

BUILDING 1

2121 LAKE AVE, FORT WAYNE, IN 46805

610A4-19-104

07/15/2020 BK TJR

BID DOCUMENTS

ELECTRICAL GENERAL NOTES

1 THE FOLLOWING GENERAL NOTES AS LISTED BELOW SHALL APPLY TO ALL ELECTRICAL REQUIREMENTS AS INDICATED ON ALL 'E' SERIES CONTRACT

DRAWINGS.

2 THE CONTRACTOR IS RESPONSIBLE FOR THE ENTIRE DOCUMENT SET. I.E. IF WORK IS SHOWN ON OTHER DRAWINGS AS "BY CONTRACTOR" THE CONTRACTOR

IS RESPONSIBLE FOR THAT WORK.

3 DRAWINGS FOR THIS WORK ARE DIAGRAMMATIC AND INTENDED TO CONVEY THE EXTENT, GENERAL ARRANGEMENT AND LOCATIONS OF THE WORK.

BECAUSE OF THE SCALE OF THE DRAWINGS, CERTAIN BASIC ITEMS SUCH AS ACCESS PANELS, CONDUITS, CABINET SIZES, PENETRATION SLEEVES, PULL BOXES, BACKBOXES AND JUNCTION BOXES MAY NOT BE SHOWN. INCLUDE ALL ITEMS WHERE REQUIRED BY CODE, MANUFACTURER AND RELATED

SPECIFICATION SECTIONS FOR THE PROPER INSTALLATION OF ALL WORK.

4 DUE TO SCALE OF THE DRAWINGS, ALL ELECTRICAL DEVICE SYMBOLS ARE SHOWN ON DRAWINGS AS CLOSE AS POSSIBLE TO THEIR INTENDED LOCATION.

CONTRACTOR SHALL COORDINATE IN THE FIELD THE PROPER INSTALLATION OF ALL EQUIPMENT, DEVICES, CONTROLS AND CONDUITS. REFER TO RELATED

SPECIFICATION SECTIONS FOR ADDITIONAL REQUIREMENTS.

5 COORDINATE WITH ALL TRADES AND SYSTEM INTEGRATORS ANY CONDITIONS RELATED TO THE INSTALLATION OF ALL SYSTEMS. THE CONTRACTOR SHALL COORDINATE WITH THE APPROPRIATE TRADE ALL INSTALLATION REQUIREMENTS IMPACTING THE PLACEMENT OF ALL SYSTEM COMPONENTS TO THE

SATISFACTION OF ALL CONCERNED TRADES.

6 COORDINATE EXACT LOCATION(S) OF ALL DATA AND TELEPHONE OUTLETS, ELECTRICAL RECEPTACLES WITH THE ARCHITECTURAL PLANS, FURNITURE PLANS

AND ALL AFFECTED TRADES PRIOR TO INSTALLATION.

7 ALL CONDUITS SHALL BE SIZED AND INSTALLED IN ACCORDANCE WITH NFPA 70 AND PROJECT SPECIFICATIONS. ALL CONDUITS SHALL BE A MINIMUM OF 3/4"

UNLESS OTHERWISE NOTED.

8 PROVIDE ALL EQUIPMENT CLEARANCES IN ACCORDANCE WITH NEC REQUIREMENTS. ARRANGE EQUIPMENT TO FACILITATE UNRESTRICTED ACCESS FOR MAINTENANCE AND SERVICE AROUND ALL EQUIPMENT, COMPONENTS AND/OR CABLE TERMINATIONS.

9 WHERE EQUIPMENT AND/OR JUNCTION BOXES ARE INSTALLED ABOVE FINISHED CEILINGS, THE CONTRACTOR SHALL PROVIDE ACCESS HATCHES LISTED FOR THE INTENDED APPLICATION. ACCESS HATCHES SHALL BE LOCATED SO THAT SERVICE ACCESS TO THE EQUIPMENT AND/OR JUNCTION BOXES IS UNIMPEDED.

10 ALL PENETRATIONS OF WALLS AND/OR FLOORS SHALL BE FIRE STOPPED IN ACCORDANCE WITH THE ASTM AND NFPA REQUIREMENTS. REFER TO RELATED SPECIFICATION SECTIONS FOR ADDITIONAL INFORMATION. INSTALLATION OF FIRE-STOPS SHALL BE PERFORMED BY APPLICATOR/INSTALLER QUALIFIED AND TRAINED BY THE MANUFACTURER. INSTALLATION SHALL BE PERFORMED IN STRICT ACCORDANCE WITH MANUFACTURER'S DETAILED INSTALLATION

PROCEDURES.

11 ALL EQUIPMENT ENCLOSURES LOCATED OUTSIDE OR IN ALL AREAS WITH HIGH MOISTURE OR A RELATIVE HUMIDITY OF 75% OR GREATER SHALL BE NEMA 4X

STAINLESS STEEL AND RATED FOR THAT APPLICATION.

12 ALL DEVICES, COMPONENTS OR EQUIPMENT INSTALLED ON THE EXTERIOR OF THE FACILITY SHALL BE PROVIDED IN ACCORDANCE WITH ALL MANUFACTURERS' REQUIREMENTS TO ENSURE THE PROPER OPERATION WHEN EXPOSED TO THE ENVIRONMENTAL CONDITIONS AND/OR AVERAGE ANNUAL LOWEST TEMPERATURE THAT CAN BE ANTICIPATED FOR THE GEOGRAPHIC REGION OF THE FACILITY.

13 ALL INTERIOR AND/OR EXTERIOR COMPONENTS, DEVICES OR SYSTEMS EQUIPMENT EXPOSED TO THE GENERAL POPULATION SHALL BE INSTALLED IN SECURED EQUIPMENT ENCLOSURES WITH TAMPER SWITCHES AND INSTALLED IN SUCH A MANNER THAT RESISTS TAMPERING AND/OR REMOVAL WITHOUT

THE USE OF SPECIALIZED TOOLS.

14 FOR EQUIPMENT INSTALLATIONS REQUIRING COORDINATION WITH OTHER TRADES THE CONTRACTOR SHALL PROVIDE ALL TEMPLATES, BACKBOXES AND EQUIPMENT ANCHOR BOLTS FOR MOUNTING OR FLUSH MOUNTING PREPARATION, (E.G. PEDESTALS OR OTHER DEVICES REQUIRING MOUNTING ON WALLS, CONCRETE PADS OR OTHER MATERIALS). COORDINATE DELIVERY OF TEMPLATES AND EQUIPMENT WITH ALL AFFECTED CONTRACTORS.

15 ALL ELECTRICAL WORK SHALL BE DONE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE (LATEST VERSION BEING ENFORCED), AND ALL OTHER APPLICABLE CODES AND STANDARDS BEING ENFORCED BY THE AUTHORITY HAVING JURISDICTION.

16 THESE DRAWINGS DO NOT INCLUDE NECESSARY COMPONENTS OR INSTRUCTIONS FOR CONSTRUCTION SAFETY. THE ENGINEER ASSUMES NO RESPONSIBILITY FOR ANY WORKMAN'S OR TRANSIENT'S SAFETY, OR FOR THE ADEQUACY OF EQUIPMENT, BUILDING COMPONENTS, WORK AIDS, OR ANY NECESSITY TO WORK ON ENERGIZED ELECTRICAL COMPONENTS. FURTHER, NO SUPERINTENDENCE IS INCLUDED OR IMPLIED.

17 ALL SYSTEMS AND EQUIPMENT SHALL BE INSTALLED AND WIRED ACCORDING TO THE MANUFACTURER'S RECOMMENDATIONS.

18 ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES, AND EQUIPMENT SHALL BE TESTED AND LISTED BY A NATIONALLY RECOGNIZED TESTING LABORATORY.

19 THE CONTRACTOR SHALL COORDINATE CONDUIT ROUTING (PLAN AND ELEVATION) WITH THE LIGHTING, CEILING ELEVATION, STRUCTURE, DUCTWORK, PIPING, ETC. REQUIRED FOR THE COMPLETION OF THE PROJECT, PRIOR TO INSTALLATION.

20 THE CONTRACTOR SHALL SECURE AND PROTECT THE BUILDING AND/OR WORK AREA WITH FIRE RETARDANT TEMPORARY PLYWOOD PARTITIONS (WITH LOCKING DOORS), ETC. CLOSE ALL OPENINGS AS REQUIRED. COORDINATE THIS WORK WITH THE OWNERS REPRESENTATIVE PRIOR TO STARTING. IF

TEMPORARY PARTITIONS IMPEDE THE FLOW OF EGRESS TO REQUIRED EGRESS DOORS AND STAIRS, THE CONTRACTOR SHALL PROVIDE EXIT SIGNS, AND

SIGNAGE INDICATING SUCH.

21 THE CONTRACTOR SHALL CAULK ALL JOINTS BETWEEN METAL FRAMES. THIS APPLIES TO BOTH INTERIOR AND EXTERIOR INSTALLATIONS.

22 THE DIMENSIONS SHOWN ON THE DRAWINGS ARE FOR THE CONVENIENCE OF THE CONTRACTOR ONLY. VERIFY ALL DIMENSIONS IN THE FIELD PRIOR TO

PERFORMING ANY WORK.

23 THE CONTRACTOR SHALL INSTALL ALL CONDUITS CONCEALED UNLESS NOTED OTHERWISE. EXPOSED CONDUIT SHALL ONLY BE INSTALLED IN CHASES, EXPOSED CEILING AREAS, JANITOR CLOSETS, AND MECHANICAL/ELECTRICAL ROOMS. EXPOSED CONDUIT INSTALLATION IS ACCEPTABLE IN ROOMS OR AREAS WITH EXPOSED CEILINGS. CONCEALED CONDUITS ARE REQUIRED IN ALL ROOMS WITH ACT OR DRYWALL CEILINGS.

24 ALL ELECTRICAL EQUIPMENT SHALL BE GROUNDED AND/OR BONDED PER THE REQUIREMENTS OF THE NATIONAL ELECTRIC CODE. PROVIDE ALL GROUNDING

AND/OR BONDING COMPONENTS NOT EXPLICITLY SHOWN ON THE DOCUMENTS.

25 THE CONTRACTOR SHALL PROVIDE TYPEWRITTEN PANELBOARD DIRECTORIES, INDICATING THE LOADS SERVED BY THE RESPECTIVE PANELS. AMEND AS REQUIRED FOR AS-BUILT CONDITIONS. PROVIDE ELECTRONIC VERSIONS OF THE PANELBOARD SCHEDULES FOR FUTURE USE TO THE OWNER.

26 THE CONTRACTOR SHALL REVIEW THE WORK REQUIRED WITH THE APPLICABLE UTILITY COMPANIES SERVING THE PROJECT. ALL WORK PERFORMED SHALL

BE IN ACCORDANCE WITH THE REQUIREMENTS OF THE INDIVIDUAL UTILITY COMPANIES.

27 THE CONTRACTOR SHALL COORDINATE ALL WORK WITH THE OWNER PRIOR TO STARTING ALL PHASES OF THE PROJECT. THE CONTRACTOR SHALL COORDINATE WITH THE OWNER WHAT WORK, IF ANY, HAS TO BE COMPLETED DURING SECOND OR THIRD SHIFT.

28 THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY POWER CONNECTIONS TO KEEP AREAS UP AND OPERATIONAL DURING THE CONSTRUCTION. THE

CONTRACTOR SHALL COORDINATE THESE REQUIREMENTS WITH THE OWNER.

29 THE VERBIAGE ON THE DRAWINGS INDICATING TYPES OF MATERIALS TO BE ENCOUNTERED IS INTENDED TO AID THE ELECTRICAL CONTRACTOR IN UNDERSTANDING THE VARIOUS CONDITIONS LIKELY TO BE ENCOUNTERED. THE CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING QUANTITIES OF

MATERIALS REQUIRED TO COMPLETE THE PROJECT.

30 THE LOCATIONS OF UTILITIES, STRUCTURE AND OTHER CONDITIONS SHOWN ON THE PLANS ARE APPROXIMATE. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE WITH THE UTILITY PROVIDERS AND REPORT ANY DISCREPANCIES TO THE REPRESENTATIVE PRIOR TO BEGINNING ANY WORK.

31 THE CONTRACTOR SHALL PROVIDE ALL OPENINGS IN PARTITIONS, EXTERIOR WALLS, FLOORS, AND ROOFS FOR THE INSTALLATION OF ANY ELECTRICAL WORK. FURNISH AND INSTALL ALL REQUIRED LINTELS AND SLEEVES FOR THIS WORK. ALL CONDUITS SHALL HAVE SLEEVES INSTALLED. ALL SLEEVES

INSTALLED THROUGH EXTERIOR WALLS SHALL HAVE LINK SEALS INSTALLED.

32 THE CONTRACTOR SHALL PROTECT ALL MATERIALS THAT ARE TO REMAIN IN PLACE FROM DAMAGE. ANY DAMAGE TO FINISHES, MATERIALS, ETC., SHALL BE

REPLACED BY THE CONTRACTOR TO MATCH THE ADJACENT FINISH.

33 THE CONTRACTOR SHALL MAINTAIN THE BUILDING IN WEATHERTIGHT AND WATERPROOF CONDITION THROUGHOUT THE DURATION OF THEIR WORK. DO NOT LEAVE HOLES THROUGH WALLS AND/OR ROOFS OPEN TO THE ELEMENTS WHEN NO WORK IS OCCURRING IN THOSE AREAS.

34 PROVIDE ALL JUNCTION BOXES, PULL BOXES AND OTHER PULL POINTS AS REQUIRED TO MEET THE MAXIMUM NUMBER OF BENDS PER NEC REQUIREMENTS.

NOT ALL CONDUITS, PULL BOXES AND OTHER RACEWAY ITEMS ARE INDICATED ON THE DOCUMENTS. THE CONTRACTOR SHALL PROVIDE A COMPLETE RACEWAY SYSTEM MEETING THE REQUIREMENTS OUTLINED IN THE DRAWINGS AND SPECIFICATIONS.

35 DISTRIBUTION EQUIPMENT SHALL BE AIC RATED, AND ANY CIRCUIT BREAKERS SELECTED AND SET BASED ON THE OUTCOME OF THE CONTRACTORS OVERCURRENT PROTECTIVE DEVICE COODINATION STUDY. STUDY SHALL INCLUDE ALL ELEMENTS OF THE DISTRIBUTION SYSTEM REQUIRED TO ACCURATELY

SIZE AND RATE THE EQUIPMENT ADDED AS PART OF THIS PROJECT.

36 ARC FLASH LABELS SHALL BE PROVIDED TO ALL EQUIPMENT BASED ON THE OUTCOME OF THE CONTRACTORS ARC FLASH STUDY (SEE NOTE 35 ABOVE FOR ADDITIONAL STUDY REQUIREMENTS). ANY EQUIPMENT MODIFIED AS PART OF THIS PROJECT SHALL ALSO BE INCLUDED IN THE ARC FLASH STUDY, AND RE

LABELLED AS REQUIRED.

37 THESE DRAWINGS DO NOT INDICATE ALL CONDUITS INTERCONNECTING EQUIPMENT, AND WHERE CONDUITS ARE INDICATED, THE ROUTING IS APPROXIMATE.

THE CONTRACTOR IS RESPONSIBLE FOR THE ROUTING AND INSTALLATION OF ALL CONDUIT IN COORDINATION WITH OTHER TRADES AND FIELD CONDITIONS.

38 PROVIDE ALL JUNCTION BOXES AND OTHER PULL POINTS AS REQUIRED FOR EASE OF PULLING AND A CODE COMPLIANT INSTALLATION. ALL JUNCTION BOXES

AND OTHER PULL POINTS SHALL BE ACCESSIBLE

39 MULTIWIRE BRANCH CIRCUITS ARE NOT PERMITTED, ALL SINGLE POLE BRANCH CIRCUITS SHALL HAVE A DEDICATED NEUTRAL AND GROUND.

40 MULTIPLE SMALL 20A/1P BRANCH CIRCUITS MAY SHARE A SINGLE CONDUIT PROVIDED THE CONTRACTOR UPSIZES THE CONDUIT AS REQUIRED, AND THE AMPACITY ADJUSTMENTS FROM TABLE 310.15(B)(3)(a) HAVE BEEN APPLIED.

# Revisions Date 07/15/2020

(XR)AHU-9

(X)EF

E

F

G

H

C

B

A

2221201918A1615

I

J

13121087

43A3

19A

9 11 13A

D

18 20B17A 17B

(XR)CU-9

LPL

LP-BD

LP-BC

M A

T C

H L

IN

E

EM-B

LPE1

EXISTING

LIGHT FIXTURE

EXISTING

LIGHT FIXTURE

4 4

EQ-B

CR-B

WEST (BW) EAST (BE)

BASEMENT

GENERAL AREA OF

WORK (REFER TO

PLAN FOR DETALS)

BASEMENT

AREA OF FUTURE WORK

(NOT IN CONTRACT)

NOT IN CONTRACT

N O

T

IN

C O

N T

R A

C T

M A

T C

H

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseArchitect/Engineer of Record StampConsultant

321 4 5 6 7 8 9 10

Sprinkler Status

B

IM

/1

F t.

W a y n e V

A M

C B a s e m e n t B ld g

/1

M

E P

C e n tr a l

.r v t

/1

/2

:2

:3

P

M

ED101W

ELECTRICAL DEMOLITION PLAN - BASEMENT

WESTAE Works

209 SANDUSKY STREET

PITTSBURGH, PA 15212

412-287-7333

RENOVATE BASEMENT,

BUILDING 1

2121 LAKE AVE, FORT WAYNE, IN 46805

610A4-19-104

07/15/2020 BK TJR

BID DOCUMENTS

ELECTRICAL DEMOLITION GENERAL NOTES

1 UNLESS NOTED OTHERWISE, REMOVE ALL ELECTRICAL DEVICES FROM WITHIN THE AREA OF DEMOLITION WORK

IDENTIFIED WITHOUT SHADED BOUNDARIES. SHADED BOUNDARIES INDICATE OUT OF SCOPE AREAS. THE DEVICES TO BE REMOVED INCLUDE BUT ARE NOT LIMITED TO: RECEPTACLES, SWITCHES, JUNCTION BOXES, LIGHTS, LIGHTING CONTROLS, PANELBOARDS IN POOR CONDITION AND FLOOR BOXES. REMOVE ALL ASSOCIATED CONDUIT AND WIRE BACK TO THE UPSTREAM DISTRIBUTION DEVICE. THE INTENT IS FOR ALL DEVICES TO BE REMOVED FROM FLOOR TO ALLOW THE RENOVATION AND INSTALLATION OF ALL NEW DEVICES AS SHOWN ON THE NEW WORK DOCUMENTS. EXISTING DEVICES SHOWN ARE DIAGRAMMATIC AND BASED ON FIELD SURVEYS AND/OR RECORD DRAWINGS PROVIDED BY THE OWNER AND DOES NOT REPRESENT THE FULL SCOPE OF DEMOLITION WORK. THE ACTUAL CONDITIONS MAY VARY. ALL EXISTING CONDITIONS MUST BE VERIFIED PRIOR TO BID. THE PLANS ARE INTENDED TO SHOW THE LOCATIONS OF EXISTING DEVICES AND IN NO WAY RELIEVES THE CONTRACTOR FROM PROVIDING ANY AND ALL COORDINATION NECESSARY TO COMPLETE THE NEW WORK. FIELD CONDITIONS SHALL GOVERN. FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR TO COMMENCEMENT OF WORK AND OBTAIN CLARIFICATIONS FROM ARCHITECT/ENGINEER

IF NECESSARY.

2 OWNER SHALL HAVE RIGHT OF FIRST REFUSAL TO ANY EQUIPMENT, DEVICES, LUMINAIRES, ETC. DEMOLISHED

FROM RENOVATION AREA PRIOR TO DISPOSAL.

3 MAINTAIN CONTINUITY OF SERVICE TO AREAS OUTSIDE THE PROJECT BOUNDARY. PATCH AND REPAIR ALL CIRCUITS CUT OFF DURING DEMOLITION BY WIRING METHODS COMPATIBLE WITH THE EXISTING INSTALLATION.

4 THE ELECTRICAL CONTRACTOR SHALL REVIEW THE DRAWING OF ALL OTHER TRADES IN THIS CONTRACT. THE REMOVAL OF ELECTRICAL SERVICE TO ALL EQUIPMENT IDENTIFIED ON OTHER TRADE DRAWINGS IS THE

RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.

5 EXERCISE EXTREME CAUTION WHEN REMOVING/ RELOCATING WIRING AND EQUIPMENT. IT IS THE CONTRACTOR'S RESPONSIBILITY TO ENSURE THAT OTHER WIRING DEVICES, EQUIPMENT AND LIGHT FIXTURES

THAT MAY BE CONNECTED TO THE SAME CIRCUIT REMAIN OPERATIONAL AND ACTIVE.

NORTH

TRUE NORTH=

PROJECT

88.5°

8' 16'4'0 1/8" = 1'-0"1

ELECTRICAL DEMOLITION PLAN - BASEMENT WEST

# ELECTRICAL DEMOLITION KEYNOTES

1 EXISTING PAENLBOARD TO REMAIN. DEMOLISH EXISTING BRANCH CIRCUITS OF DEMOLISHED

DEVICES IN THEIR ENTIRETY INCLUDING BUT NOT LIMITED TO WIRING, CONDUIT, AND HANGERS. THE

EXISTING CIRCUIT BREAKERS ARE TO REMAIN IN PLACE.

2 DEMOLISH EXISTING BRANCH CIRCUIT TO MECHANICAL EQUIPMENT IN ITS ENTIRETY BACK TO THE SOURCE PANEL. INCLUDING BUT NOT LIMITED TO DISCONNECTING DEVICE, STARTER, CONDUIT, WIRING, AND HANGERS. THE EXISTING CIRCUIT BREAKERS ARE TO REMAIN IN PLACE.

3 THE EXISTING BRANCH CIRCUIT FOR THE NOTED MECHANICAL EQUIPMENT IS TO REMAIN IN PLACE

AND BE KEPT ENERGIZED.

4 EXISTING LIGHT FIXTURE SHALL REMAIN. CONTRACTOR SHALL ENSURE THAT ELECTRICAL

CONNECTIONS AND FIXTURE MOUNTING IS PRESERVED THROUGHOUT THE CONSTRUCTION

PROCESS.

5 EXISTING PANELBOARD TO BE REPLACED WITH NEW PANELBOARD. ALL EXISTING TO REMAIN

CIRCUITS SHALL BE RE-FED FROM THE NEW PANEL. REFERENCE SHEET E401 FOR PANELBOARD

INFORMATION AND ONE-LINE DIAGRAM ON SHEET E301.

6 EXISTING ELECTRICAL EQUIPMENT TO REMAIN. DEMOLISH EXISTING BRANCH CIRCUITS OF

DEMOLISHED DEVICES IN THEIR ENTIRETY INCLUDING BUT NOT LIMITED TO WIRING, CONDUIT, AND HANGERS. CIRCUIT BREAKERS WITH EXISTING LOADS OR LOADS OUTSIDE OF THE SCOPE OF WORK

ARE TO REMAIN IN PLACE.

WEST (BW) EAST (BE)

BASEMENT

GENERAL AREA OF

WORK (REFER TO

PLAN FOR DETALS)

BASEMENT

AREA OF FUTURE WORK

(NOT IN CONTRACT)

NOT IN CONTRACT

N O

T

IN

C O

N T

R A

C T

M A

T C

H

(X)AHU

(XR)AHU

(XR)CU-N

(XR)CU-CAN

(XR)CU-4

(XR)CU-52 (XR)CU-S

(XR)CH-1

(X)CU-50

E

F

G

H

C

363534333231

2927252423

33A

302826

B

A

I

22A20B 30A

M A

T C

H L

IN

E

LP-BA

PP-2

LP-BB

EXISTING

BATTERY

RACK

EXISTING

DATA

RACK

(TYP.)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseArchitect/Engineer of Record StampConsultant

321 4 5 6 7 8 9 10

Sprinkler Status

B

IM

/1

F t.

W a y n e V

A M

C B a s e m e n t B ld g

/1

M

E P

C e n tr a l

.r v t

/1

/2

:2

:4

P

M

ED102E

ELECTRICAL DEMOLITION PLAN - BASEMENT

EASTAE Works

209 SANDUSKY STREET

PITTSBURGH, PA 15212

412-287-7333

RENOVATE BASEMENT,

BUILDING 1

2121 LAKE AVE, FORT WAYNE, IN 46805

610A4-19-104

07/15/2020 BK TJR

BID DOCUMENTS

NORTH

TRUE NORTH=

PROJECT

88.5°

8' 16'4'0 1/8" = 1'-0"1

ELECTRICAL DEMOLITION PLAN - BASEMENT EAST

ELECTRICAL DEMOLITION GENERAL NOTES

1 UNLESS NOTED OTHERWISE, REMOVE ALL ELECTRICAL DEVICES FROM WITHIN THE AREA OF DEMOLITION WORK

IDENTIFIED WITHOUT SHADED BOUNDARIES. SHADED BOUNDARIES INDICATE OUT OF SCOPE AREAS. THE DEVICES TO BE REMOVED INCLUDE BUT ARE NOT LIMITED TO: RECEPTACLES, SWITCHES, JUNCTION BOXES, LIGHTS, LIGHTING CONTROLS, PANELBOARDS IN POOR CONDITION AND FLOOR BOXES. REMOVE ALL ASSOCIATED CONDUIT AND WIRE BACK TO THE UPSTREAM DISTRIBUTION DEVICE. THE INTENT IS FOR ALL DEVICES TO BE REMOVED FROM FLOOR TO ALLOW THE RENOVATION AND INSTALLATION OF ALL NEW DEVICES AS SHOWN ON THE NEW WORK DOCUMENTS. EXISTING DEVICES SHOWN ARE DIAGRAMMATIC AND BASED ON FIELD SURVEYS AND/OR RECORD DRAWINGS PROVIDED BY THE OWNER AND DOES NOT REPRESENT THE FULL SCOPE OF DEMOLITION WORK. THE ACTUAL CONDITIONS MAY VARY. ALL EXISTING CONDITIONS MUST BE VERIFIED PRIOR TO BID. THE PLANS ARE INTENDED TO SHOW THE LOCATIONS OF EXISTING DEVICES AND IN NO WAY RELIEVES THE CONTRACTOR FROM PROVIDING ANY AND ALL COORDINATION NECESSARY TO COMPLETE THE NEW WORK. FIELD CONDITIONS SHALL GOVERN. FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR TO COMMENCEMENT OF WORK AND OBTAIN CLARIFICATIONS FROM ARCHITECT/ENGINEER

IF NECESSARY.

2 OWNER SHALL HAVE RIGHT OF FIRST REFUSAL TO ANY EQUIPMENT, DEVICES, LUMINAIRES, ETC. DEMOLISHED

FROM RENOVATION AREA PRIOR TO DISPOSAL.

3 MAINTAIN CONTINUITY OF SERVICE TO AREAS OUTSIDE THE PROJECT BOUNDARY. PATCH AND REPAIR ALL CIRCUITS CUT OFF DURING DEMOLITION BY WIRING METHODS COMPATIBLE WITH THE EXISTING INSTALLATION.

4 THE ELECTRICAL CONTRACTOR SHALL REVIEW THE DRAWING OF ALL OTHER TRADES IN THIS CONTRACT. THE REMOVAL OF ELECTRICAL SERVICE TO ALL EQUIPMENT IDENTIFIED ON OTHER TRADE DRAWINGS IS THE

RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.

5 EXERCISE EXTREME CAUTION WHEN REMOVING/ RELOCATING WIRING AND EQUIPMENT. IT IS THE CONTRACTOR'S RESPONSIBILITY TO ENSURE THAT OTHER WIRING DEVICES, EQUIPMENT AND LIGHT FIXTURES

THAT MAY BE CONNECTED TO THE SAME CIRCUIT REMAIN OPERATIONAL AND ACTIVE.

# Revisions Date

# ELECTRICAL DEMOLITION KEYNOTES

1 EXISTING PAENLBOARD TO REMAIN. DEMOLISH EXISTING BRANCH CIRCUITS OF DEMOLISHED

DEVICES IN THEIR ENTIRETY INCLUDING BUT NOT LIMITED TO WIRING, CONDUIT, AND

HANGERS. THE EXISTING CIRCUIT BREAKERS ARE TO REMAIN IN PLACE.

2 DEMOLISH EXISTING BRANCH CIRCUIT TO MECHANICAL EQUIPMENT IN ITS ENTIRETY BACK TO

THE SOURCE PANEL. INCLUDING BUT NOT LIMITED TO DISCONNECTING DEVICE, STARTER,

CONDUIT, WIRING, AND HANGERS. THE EXISTING CIRCUIT BREAKERS ARE TO REMAIN IN

PLACE.

3 THE EXISTING BRANCH CIRCUIT FOR THE NOTED MECHANICAL EQUIPMENT IS TO REMAIN IN

PLACE AND BE KEPT ENERGIZED.

4 ALL ELECTRICAL EQUIPMENT IN THIS ROOM IS EXISTING TO REMAIN. THE DISCONNECT

SWITCH, QUAD OUTLET AND ALL OTHER OUTLETS IN THE AREA ARE TO REMAIN IN PLACE AND

MAINTAIN OPERATION THROUGHOUT THE ARCHITECTURAL NEW WORK INSTALLATION.

BATTERY RACK AND DATA RACK SHALL BE RELOCATED TO THE RAISED FLOOR PLATFORM

AFTER ARCHITECTURAL NEW WORK IS COMPLETE. ANY ELECTRICAL DEVICES THAT MAY FALL

BELOW THE RAISED FLOOR SHALL BE RELOCATED.

5 EXISTING ELECTRICAL EQUIPMENT, RECEPTACLE, AND CIRCUITS TO REMAIN AND MAINTAIN

OPERATION THROUGHOUT THE NEW WORK INSTALLATION.

6 EXISTING ELECTRICAL EQUIPMENT TO REMAIN. DEMOLISH EXISTING BRANCH CIRCUITS OF

DEMOLISHED DEVICES IN THEIR ENTIRETY INCLUDING BUT NOT LIMITED TO WIRING, CONDUIT, AND HANGERS. CIRCUIT BREAKERS WITH EXISTING LOADS OR LOADS OUTSIDE OF THE SCOPE

OF WORK ARE TO REMAIN IN PLACE.

07/15/2020

OS

VS

VS

OS

OS OS OS

VS

VS

VS

VS

VS

OS

VS

OS OS

OS

OS

OS

OS OS OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

VS

OS

VS

VS

VS

OS

X-RAY

B120E

TLT / CHANGING

B120F

CLEAN

B120G

RADIOLOGY

B120

CT SCANNING

B120D

SOILED HOLDING

B120C

WAITING

B119

CORRIDOR

C06

STAIR 2 (NIC)

S2

MENS

B114

WOMENS

B113

CORRIDOR

C04

CORRIDOR

C02

PHARMACY CACHE

B111

EMS SUPPLY

B104

EMS SUITE

B100

EMS OFFICE 2

B100A

EMS OFFICE 1

B100B

CLEAN LINEN ROOM

B100C

MENS DRESSING

B100E

SERV ELEV

SE1

ELEVATOR (NIC)

E1

ELEVATOR (NIC)

E2

MECHANICAL OFFICE

B101

E

F

G

H

C

B

2221201918A1615

I

J

13121087

43A321

19A

9 11 13A

D

18 20B17A 17B

T3T3

T3 T3

T3 T3

T3 T3 T3 T3

T3 T3 T3 T3

T2 T1

T3 T3 T3 T3 T3 T3 T3

T3 T3 T3 T3 T3 T3 T3

TS2

TS2 TS2 TS2

TS1

T1

TS1 TS1

TS1

TS1

TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1

TS1 TS1

TS1TS1

TS1

TS1

TS1

TS1

TS1

TS1

TS1

T3

T2

T2

P1

T1

T3

T1 T1

T1

T1

T1

T2

T2 T2 T2

T2T2

T1

T1

T1

T1

T1 T1

T1

T2

T1T1 T2

T2

T2

T2

T1

D1

D1

D2

M A

T C

H L

IN

E

EMS STORAGE

B103

TS1

CLOSET

B120B

RECEPTION / WORK

B120A

STORAGE

B118 GME LIBRARY

B116

RES. SLEEPING

ROOM

B115

RESIDENT TLT RM

B115A

P3 P3

P3P3

T3 T3

T3T3

T1 D1

T2 T2

T2T2

TS2

T1

TS1

LV

LV

LV

LV

D D

VS

K K

3 3

D D

D

D D

W1

E1

E2

E1 E1

E1

E1

E1

E1

E1

VS

a b a,b

E2

X1 a a a a a a a a a bbbbbbbbb a,b a,b ba a b ba

WOMENS DRESSING

B100D

MECH

B102B

STORAGE

B100F

P1

T1 T1

CR-B - 13

CR-B - 13 CR-B - 13

LPL - 5

LPL - 5 LPL - 5

LPL - 5

CR-B - 13

CR-B - 13 CR-B - 13 CR-B - 13

CR-B - 13CR-B - 13 CR-B - 13

LPL - 5

LPL - 5 LPL - 5

LPL - 5

LPL - 5

LPL - 5

LPL - 5

LPL - 5

CORRIDOR

C05

LP-BC - 9 LP-BC - 9

LP-BC - 9 LP-BC - 9LP-BC - 9 LP-BC - 9 LP-BC - 9

LP-BC - 9

LPE1 - 18

LP-BC - 9 LPE1 - 18 LP-BC - 9

LP-BC - 9

LP-BC - 9

LP-BC - 9

LPE1 - 18

LPE1 - 18

LP-BB - 18LP-BC - 9LP-BC - 9

LP-BC - 9LP-BC - 9

LP-BC - 9

EQ-B - 11 EQ-B - 11

LP-BC - 9LP-BC - 9

LP-BC - 9

LP-BC - 9LP-BC - 9

CR-B - 10

LP-BD - 12LP-BD - 12

LP-BD - 12

LP-BD - 12LP-BD - 12

LP-BD - 12

LP-BD - 12LP-BD - 12

LP-BD - 12

LPE1 - 1

LP-BD - 12LP-BD - 12

LP-BD - 12

LP-BD - 12LP-BD - 12

LP-BD - 12

CORRIDOR

C03

CORRIDOR

C01

E2

LPE1 - 18

LPE1 - 18

LPE1 - 18

LPE1 - 18

LPE1 - 18

LPE1 - 18 LPE1 - 18

LPE1 - 18

LPE1 - 18

LPE1 - 18

LPE1 - 18

LPE1 - 18

LPE1 - 18

LPE1 - 18

E2

LPE1 - 18

LPE1 - 18

LPE1 - 18

LPE1 - 18

LPE1 - 18 LPE1 - 18

LPE1 - 18LPE1 - 18

LPE1 - 1

LPE1 - 1

LPE1 - 1

LPE1 - 1

LPE1 - 1

LPE1 - 1LPE1 - 1LPE1 - 1 LPE1 - 1

LPE1 - 1

LPE1 - 1

LPE1 - 1

LPE1 - 18

LPE1 - 1

LPE1 - 1

LPE1 - 1

LPE1 - 1

LPE1 - 1

LPE1 - 1

LPE1 - 1

LPE1 - 1LPE1 - 1

LPE1 - 1

LPE1 - 1

LPE1 - 1

LPE1 - 1

LPE1 - 1

LPE1 - 1

LPE1 - 1

LPE1 - 1

LPE1 - 1

LPE1 - 1

LPE1 - 1

LPE1 - 1

LPE1 - 1

CR-B - 10 CR-B - 10

CR-B - 10 CR-B - 10 CR-B - 10

CR-B - 10 CR-B - 10 CR-B - 10

CR-B - 10 CR-B - 10 CR-B - 10

CR-B - 10

MCMCMC

V S

VS

VS VS

VS

a a bb c b a b ba a,b,c b b c a,b,c b a,b,c a,b,c M C

TS1

TS1 TS1

LP-BD - 12

LP-BD - 12 LPE1 - 1

D a b b b b b aaa a,b

MC

P1

P1

LPE1 - 18

LPE1 - 18

MC

a,b

EXISTING

LIGHT FIXTURE

EXISTING

LIGHT FIXTURE

T

E1 LPE1 - 1

a,b,c a, b, c

WEST (BW) EAST (BE)

BASEMENT

GENERAL AREA OF

WORK (REFER TO

PLAN FOR DETALS)

BASEMENT

AREA OF FUTURE WORK

(NOT IN CONTRACT)

NOT IN CONTRACT

N O

T

IN

C O

N T

R A

C T

M A

T C

H

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseArchitect/Engineer of Record StampConsultant

321 4 5 6 7 8 9 10

Sprinkler Status

B

IM

/1

F t.

W a y n e V

A M

C B a s e m e n t B ld g

/1

M

E P

C e n tr a l

.r v t

/1

/2

:2

:3

P

M

E101W

ELECTRICAL LIGHTING PLAN - BASEMENT

WESTAE Works

209 SANDUSKY STREET

PITTSBURGH, PA 15212

412-287-7333

RENOVATE BASEMENT,

BUILDING 1

2121 LAKE AVE, FORT WAYNE, IN 46805

610A4-19-104

07/15/2020 BK TJR

BID DOCUMENTS

NORTH

TRUE NORTH=

PROJECT

88.5°

LIGHTING PLAN GENERAL NOTES

1 ALL EXIT SIGNS SHALL BE POWERED FROM THE CIRCUIT INDICATED AND UNSWITCHED.

2 ALL LIGHTING FIXTURES POWERED FROM AN EMERGENCY GENERATOR CIRCUIT SHALL BE PROVIDED WITH A UL924

LISTED AUTOMATIC LOAD CONTROL RELAY TO PERMIT LOCAL CONTROL WITH ADJACENT

FIXTURES AND BY-PASS OF LOCAL CONTROL (INCLUDING BUT NOT LIMITED TO SWITCHES, OCCUPANCY SENSORS AND

DIMMERS) IN THE ABSENCE OF NORMAL POWER. UPON LOSS OF NORMAL POWER, THE

LIGHTING CONTROL SHALL BE BY-PASSED, DIMMED FIXTURES SHALL COME TO FULL ILLUMINATION AND SHALL NOT BE

ALLOWED TO TURN OFF.

3 COORDINATE FINAL LOCATIONS OF FIXTURES WITH THE REFLECTED CEILING PLAN. ANY CONFLICTS SHALL BE

BROUGHT TO THE ATTENTION OF THE ARCHITECT AND ENGINEER.

4 COORDINATE ALL MOUNTING HEIGHTS WITH THE ARCHITECT AND ENGINEER PRIOR TO ROUGH-IN.

5 WHERE MORE THAN ONE SWITCH OCCURS IN THE SAME LOCATION, THEY SHALL BE INSTALLED IN GANG TYPE BOX UNDER THE COVERPLATE, MINIMUM CONDUIT SIZE IS 3/4" MINIMUM WIRE SIZE SHALL BE #12 AWG. ALL WIRE TO BE

STRANDED COPPER.

6 THE OCCUPANCY SENSORS INDICATED ON THE DRAWINGS ARE SHOWN FOR DESIGN INTENT ONLY. THE EXACT QUANTITY OF SENSORS SHALL BE DETERMINED BY THE ELECTRICAL CONTRACTOR PRIOR TO INSTALLING SENSORS BASED ON THE MANUFACTURER'S RECOMMENDATION. PROVIDE 100% COVERAGE OF EACH INDIVIDUAL ROOM/SPACE SHOWN ON THE DRAWINGS. DO NOT INSTALL SENSORS PRIOR TO SUBMITTING COVERAGE LAYOUTS FOR EACH INDIVIDUAL ROOM/SPACE TO THE ENGINEER FOR APPROVAL. DO NOT INSTALL SENSORS SUCH THAT THEY CAN POTENTIALLY "SEE" THROUGH OPEN DOORWAYS. INSTALL ALL LOW VOLTAGE POWER PACKS DIRECTLY ABOVE LOCAL WALL SWITCHES IN THE AREA. DO NOT INSTALL ULTRASONIC OR DUAL TECHNOLOGY SENSORS WITHIN 24" OF SUPPLY

DIFFUSERS.

7 ALL EMERGENCY EGRESS ILLUMINATION SHALL BE AVERAGE 1FC AND A MINIMUM OF 0.1FC FOR PATH OF EGRESS.

8 PROVIDE EQUIPMENT GROUND CONDUCTOR IN ALL RACEWAYS. REFER TO PANELBOARD SCHEDULES.

9 ROUTE CONDUIT HIGH AGAINST STRUCTURE AND OFFSET UP BETWEEN JOISTS WHERE NECESSARY TO AVOID DUCT

WORK AND HVAC SYSTEM.

10 PROVIDE CONDUIT AND WIRING AS REQUIRED TO MEET CIRCUITING SHOWN TO CONFORM TO NEC REQUIREMENTS.

8' 16'4'0 1/8" = 1'-0"1

ELECTRICAL LIGHTING PLAN - BASEMENT WEST

# LIGHTING PLAN KEYNOTES

1 PROVIDE A ROOM BASED LOW VOLTAGE LIGHTING CONTROL SYSTEM WITH MULTI BUTTON

LOW VOLTAGE SWITCH CONTROL FOR THE FIXTURES WITHIN THE INDICATED ROOM ON

PLAN. REFER TO DETAIL 6 ON SHEET E301.

2 LIGHTING FIXTURES SHALL BE COORDINATED WITH MECHANICAL EQUIPMENT AND

DUCTWORK/PIPING. LIGHTING FIXTURES SHALL BE INSTALLED BELOW DUCT AND PIPE RUNS

TO AVOID OBSTRUCTIONS.

3 NEW EXTERIOR LIGHT FIXTURE SHALL BE POWERED AND CONTROLLED FROM THE SAME

CIRCUIT AND CONTROL SYSTEM AS THE EXISTING TO REMAIN EXTERIOR LIGHT FIXTURES.

CONDUIT AND WIRING SHALL BE ROUTED CONCEALED.

OS

OS

OS

OS

OS OS

VS

OS

VS

OS

VS

VS

VS

VS

VS

WEST (BW) EAST (BE)

BASEMENT

GENERAL AREA OF

WORK (REFER TO

PLAN FOR DETALS)

BASEMENT

AREA OF FUTURE WORK

(NOT IN CONTRACT)

NOT IN CONTRACT

N O

T

IN

C O

N T

R A

C T

M A

T C

H

OIT OFFICE

B309

MECH ROOM 1

B308

BIOMED STORAGE

B310 STORAGE

B316D

BIOMED

B316

WORKSHOP

B316C

OFFICE

B316B

TOILET ROOM

B315

STAIR 4 (NIC)

S4

E

F

G

H

C

36353433323129272524

33A302826

B

A

I

J

22A

D

20B

30A

TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1 TS1

T2

T2T2

T2

T2

T2

T2 T2

TS1

TS1

T3

T3

T3

T3 T3

T3

T3 T3

MAILROOM

B300

STOR / SOILED LINEN

CART

B306

BATTERY ROOM

B307

M A

T C

H L

IN

E

STORAGE

B316A

PACKAGE LOCKER

B301

T2

TS2 TS2

T2

T2

TS2

D1

TS2

P1 P1 P1

P1P1P1

P1

P1

P2 P2

P2P2

P2 P2

P2P2

T2

T2 T2

T2T2

T2

D

T

V D

E2

E1

E2 E1

E1

STAIR 3 (NIC)

S3

D a a a a a b b b b a,b a,b

E2

VESTIBULE (NIC)

OIT SERVER

B311

T1 T1

T1T1

ENGINEERING

STORAGE

B312

T2

CORRIDOR

C07

LP-BB - 18 LP-BB - 18 LP-BB - 18 LP-BB - 18 LP-BB - 18 LP-BB - 18 LP-BB - 18

LP-BB - 18LP-BB - 18

LP-BB - 18

LP-BB - 18 LP-BB - 18LP-BB - 18

LP-BB - 18

LP-BB - 18

LP-BB - 18 LP-BB - 18 LP-BB - 18 LP-BB - 18

LP-BB - 18

LP-BB - 18

LP-BB - 18

LP-BB - 18

LP-BB - 18 LP-BB - 18 LP-BB - 18 LP-BB - 18

LP-BA - 14 LP-BA - 14

LP-BA - 14

LP-BA - 14

LP-BA - 14

LP-BA - 14

LP-BA - 14

LP-BA - 14 LP-BA - 14

LP-BA - 14

LP-BA - 14LP-BA - 14

LP-BA - 14

LP-BA - 14

LP-BA - 14

LP-BA - 14

LPE1 - 5

LPE1 - 5

LPE1 - 5

LPE1 - 5

LPE1 - 5

LPE1 - 5

LPE1 - 5

LPE1 - 5LPE1 - 5

LPE1 - 5

LPE1 - 5

LPE1 - 5

LPE1 - 5

LPE1 - 5LPE1 - 5

LPE1 - 5LPE1 - 5

LPE1 - 5

LPE1 - 5

LPE1 - 5

LPE1 - 5

LPE1 - 5LPE1 - 5

LPE1 - 5

LPE1 - 5LPE1 - 5LPE1 - 5

LPE1 - 5

LPE1 - 5

LPE1 - 5 LPE1 - 5

LPE1 - 5

LPE1 - 5

V S a b a b ba a b a b a a a b b

V S

MCMC

M C

M C

VS

b

DD

D a b a b ba a,b

OS

TS1

LP-BB - 18

T T b D

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseArchitect/Engineer of Record StampConsultant

321 4 5 6 7 8 9 10

Sprinkler Status

B

IM

/1

F t.

W a y n e V

A M

C B a s e m e n t B ld g

/1

M

E P

C e n tr a l

.r v t

/1

/2

:2

:3

P

M

E102E

ELECTRICAL LIGHTING PLAN - BASEMENT EAST

AE Works

209 SANDUSKY STREET

PITTSBURGH, PA 15212

412-287-7333

RENOVATE BASEMENT,

BUILDING 1

2121 LAKE AVE, FORT WAYNE, IN 46805

610A4-19-104

07/15/2020 BK TJR

BID DOCUMENTS

NORTH

TRUE NORTH=

PROJECT

88.5°

LIGHTING PLAN GENERAL NOTES

1 ALL EXIT SIGNS SHALL BE POWERED FROM THE CIRCUIT INDICATED AND UNSWITCHED.

2 ALL LIGHTING FIXTURES POWERED FROM AN EMERGENCY GENERATOR CIRCUIT SHALL BE PROVIDED WITH A UL924

LISTED AUTOMATIC LOAD CONTROL RELAY TO PERMIT LOCAL CONTROL WITH ADJACENT

FIXTURES AND BY-PASS OF LOCAL CONTROL (INCLUDING BUT NOT LIMITED TO SWITCHES, OCCUPANCY SENSORS AND

DIMMERS) IN THE ABSENCE OF NORMAL POWER. UPON LOSS OF NORMAL POWER, THE

LIGHTING CONTROL SHALL BE BY-PASSED, DIMMED FIXTURES SHALL COME TO FULL ILLUMINATION AND SHALL NOT BE

ALLOWED TO TURN OFF.

3 COORDINATE FINAL LOCATIONS OF FIXTURES WITH THE REFLECTED CEILING PLAN. ANY CONFLICTS SHALL BE

BROUGHT TO THE ATTENTION OF THE ARCHITECT AND ENGINEER.

4 COORDINATE ALL MOUNTING HEIGHTS WITH THE ARCHITECT AND ENGINEER PRIOR TO ROUGH-IN.

5 WHERE MORE THAN ONE SWITCH OCCURS IN THE SAME LOCATION, THEY SHALL BE INSTALLED IN GANG TYPE BOX UNDER THE COVERPLATE, MINIMUM CONDUIT SIZE IS 3/4" MINIMUM WIRE SIZE SHALL BE #12 AWG. ALL WIRE TO BE

STRANDED COPPER.

6 THE OCCUPANCY SENSORS INDICATED ON THE DRAWINGS ARE SHOWN FOR DESIGN INTENT ONLY. THE EXACT QUANTITY OF SENSORS SHALL BE DETERMINED BY THE ELECTRICAL CONTRACTOR PRIOR TO INSTALLING SENSORS BASED ON THE MANUFACTURER'S RECOMMENDATION. PROVIDE 100% COVERAGE OF EACH INDIVIDUAL ROOM/SPACE SHOWN ON THE DRAWINGS. DO NOT INSTALL SENSORS PRIOR TO SUBMITTING COVERAGE LAYOUTS FOR EACH INDIVIDUAL ROOM/SPACE TO THE ENGINEER FOR APPROVAL. DO NOT INSTALL SENSORS SUCH THAT THEY CAN POTENTIALLY "SEE" THROUGH OPEN DOORWAYS. INSTALL ALL LOW VOLTAGE POWER PACKS DIRECTLY ABOVE LOCAL WALL SWITCHES IN THE AREA. DO NOT INSTALL ULTRASONIC OR DUAL TECHNOLOGY SENSORS WITHIN 24" OF SUPPLY

DIFFUSERS.

7 ALL EMERGENCY EGRESS ILLUMINATION SHALL BE AVERAGE 1FC AND A MINIMUM OF 0.1FC FOR PATH OF EGRESS.

8 PROVIDE EQUIPMENT GROUND CONDUCTOR IN ALL RACEWAYS. REFER TO PANELBOARD SCHEDULES.

9 ROUTE CONDUIT HIGH AGAINST STRUCTURE AND OFFSET UP BETWEEN JOISTS WHERE NECESSARY TO AVOID DUCT

WORK AND HVAC SYSTEM.

10 PROVIDE CONDUIT AND WIRING AS REQUIRED TO MEET CIRCUITING SHOWN TO CONFORM TO NEC REQUIREMENTS.

8' 16'4'0 1/8" = 1'-0"1

ELECTRICAL LIGHTING PLAN - BASEMENT EAST

# Revisions Date

LIGHTING PLAN KEYNOTES

1 LIGHTING FIXTURES SHALL BE COORDINATED WITH MECHANICAL EQUIPMENT AND

DUCTWORK/PIPING. LIGHTING FIXTURES SHALL BE INSTALLED BELOW DUCT AND

PIPE RUNS TO AVOID OBSTRUCTIONS.

AC

GFI

GFI

A C

G

FI

AC

GFI

AC

GFI

48"

GFI

A C

G

FI

G

FI

J

J

J

CLNG

J

CLNG

J

CLNG

J

CLNG

J

CLNG

J

CLNG

J

CLNG

J

CLNG

CLNG

(XR)AHU-9

X-RAY

B120E

TLT / CHANGING

B120F

CLEAN

B120G

WAITING

B119

SOILED HOLDING

B120CCT SCANNING

B120D

RECEPTION / WORK

B120A

MENS

B114

WOMENS

B113

STAIR 2 (NIC)

S2

ELEVATOR (NIC)

E2

ELEVATOR (NIC)

E1

SERV ELEV

SE1

MENS DRESSING

B100E

CLEAN LINEN ROOM

B100CEMS OFFICE 1

B100B

EMS OFFICE 2

B100A

CORRIDOR

C02

CORRIDOR

C02

EMS SUPPLY

B104

EMS SUITE

B100

PHARMACY CACHE

B111

CORRIDOR

C04

CORRIDOR

C06

54"

(XR)CU-9

E

F

G

H

C

B

A

2221201918A1615

I

J

13121087

43A321

19A

9 11 13A

D

18 20B17A 17B

MECHANICAL OFFICE

B101

M A

T C

H L

IN

E

EMS STORAGE

B103

STORAGE

B118

RES. SLEEPING

ROOM

B115

RESIDENT TLT RM

B115A

GME LIBRARY

B116

AHU-B4

AHU-B3

60"

LPL

LP-BD

LP-BC

CR-B

EQ-B

EM-B

LPE1

WOMENS DRESSING

B100D

STORAGE

B100F

MECH

B102B

CP-2

CLOSET

B120B

LPL-12

LPL-12

LPL-12

LPL-12

LPL-12

LPL-12

RADIOLOGY

B120

LPL-18

LPL-14 LPL-14

LPL-16

LPL-18

LPL-18

LP-BD-29LP-BD-23

LP-BD-29

LP-BD-29

LP-BD-29

LP-BD-29

LP-BD-27

LP-BD-27

LP-BD-25

LP-BD-25

LP-BD-11

LP-BD-11

LP-BD-11

LP-BD-11

LP-BD-9

LP-BD-9

CORRIDOR

C05 LP-BD-9

LP-BC-22

LP-BC-10

LP-BC-10

LP-BC-12

LP-BC-10

LP-BC-14

LP-BC-14LP-BC-16

LP-BC-16

LP-BC-10

LP-BC-10

LP-BC-12

LP-BC-12

LP-BC-12

LP-BC-18

LP-BD-7

LP-BD-7

LP-BC-18

LP-BC-20

LP-BD-7LP-BD-7

LP-BC-20

LP-BC-22

LP-BC-22

EQ-B-8

EQ-B-8

EQ-B-15 EQ-B-15 EQ-B-11

EQ-B-11 EQ-B-11 EQ-B-11

EQ-B-11

LP-BD-19

LP-BD-17 LP-BD-17 LP-BD-17 LP-BD-17

LP-BD-17

LP-BD-19

LP-BD-19

CR-B-12

CR-B-8

LP-BD-19

MLP-BD-30

LP-BD-18,20,22

LP-BD-24,26,28

CR-B-12

CR-B-12

COPIER

PRINTER

CR-B-12

ENGINEERING (NIC)

B105

CR-B-18

CR-B-18 CR-B-18CR-B-18

CR-B-18

CR-B-20

CR-B-19

CR-B-22

CR-B-22

CR-B-22

CR-B-22

CR-B-23

CR-B-23

CR-B-23

CR-B-24CR-B-24

CR-B-24

CR-B-24

CR-B-25CR-B-26

FCU-B120D

FCU-B120E

FCU/CU-B120E

FCU/CU-B120D

CR-B-28,30

CR-B-27,29 2

(TYPICAL)

LP-BC-15

EXISTING TO REMAIN

EXISTING TO REMAIN

CR-B-23

AF

AF

AF

EQ-B-17 EQ-B-17 EQ-B-17 EQ-B-17

EQ-B-19

EQ-B-19

EQ-B-19

CORRIDOR

C03

CR-B-21

CR-B-21

66 6 6

6 6

WEST (BW) EAST (BE)

BASEMENT

GENERAL AREA OF

WORK (REFER TO

PLAN FOR DETALS)

BASEMENT

AREA OF FUTURE WORK

(NOT IN CONTRACT)

NOT IN CONTRACT

N O

T

IN

C O

N T

R A

C T

M A

T C

H

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseArchitect/Engineer of Record StampConsultant

321 4 5 6 7 8 9 10

Sprinkler Status

B

IM

/1

F t.

W a y n e V

A M

C B a s e m e n t B ld g

/1

M

E P

C e n tr a l

.r v t

/1

/2

:2

:3

P

M

E201W

ELECTRICAL POWER PLAN - BASEMENT WEST

AE Works

209 SANDUSKY STREET

PITTSBURGH, PA 15212

412-287-7333

RENOVATE BASEMENT,

BUILDING 1

2121 LAKE AVE, FORT WAYNE, IN 46805

610A4-19-104

07/15/2020 BK TJR

BID DOCUMENTS

8' 16'4'0 1/8" = 1'-0"1

ELECTRICAL POWER PLAN - BASEMENT WEST

POWER PLAN GENERAL NOTES

1 FINAL LOCATION OF ALL EQUIPMENT SHALL BE DETERMINED IN THE FIELD AND SHALL BE

INSTALLED AS DIRECTED BY THE ARCHITECT OR OWNER'S REPRESENTATIVE. WHERE

STRUCTURAL OPENINGS ARE NOT AVAILABLE, THE CONTRACTOR SHALL CORE DRILL WALLS AND

FLOORS AS REQUIRED TO PERMIT PASSAGE OF CONDUITS. THE ELECTRICAL CONTRACTOR SHALL

PROVIDE A MARKED-UP PLAN WITH LOCATION PENETRATIONS FOR REVIEW AND APPROVAL OF

THE STRUCTURAL ENGINEER BEFORE ROUGH-IN BEGINS.

2 RECEPTACLES FOR ALL EQUIPMENT SHALL BE COMPLETE WITH PLUGS FOR THIS EQUIPMENT. THE

ELECTRICAL CONTRACTOR SHALL VERIFY NEMA CONFIGURATIONS OF PLUGS AND RECEPTACLES

FOR EQUIPMENT IN THE SPACE.

3 DURING THE BIDDING PROCESS, THE ELECTRICAL CONTRACTOR SHALL REVIEW DRAWINGS AND SPECIFICATIONS OF ALL OTHER TRADES (ARCHITECTURAL, SITE/LANDSCAPING, HVAC, PLUMBING

AND SPECIALTY TRADES). ALL ITEMS REQUIRING POWER INDICATED ON THESE DRAWINGS BUT

INDICATED ON THE ELECTRICAL DRAWINGS SHALL BE CONSIDERED A PART OF THE ELECTRICAL

CONTRACTOR'S WORK. THIS WORK SHALL BE INSTALLED AS PER NEC REQUIREMENTS AT NO

ADDITIONAL COST TO THE OWNER.

4 THE CONTRACTOR SHALL MAKE EVERY EFFORT TO MAKE ALL FEEDER RUNS CONTINUOUS (NO

CABLE BREAKS). IF SPLICING CABLES IN BOXES BECOMES NECESSARY, USE O.Z.G. TYPE "XW"

CABLE TAPS, OR APPROVED EQUAL, AND TAPE EACH TAP IN APPROVED MANNER.

5 THE MECHANICAL CONTRACTOR SHALL PROVIDE DISCONNECT SWITCHES, VFD'S. OR

COMBINATION STARTERS FOR ALL OF THEIR UNITS. THE ELECTRICAL CONTRACTOR SHALL

RECEIVE THESE ITEMS FROM THE MECHANICAL CONTRACTOR FOR INSTALLATION BY THE

ELECTRICAL CONTRACTOR.

6 THE ELECTRICAL CONTRACTOR SHALL COORDINATE CONDUIT PENETRATIONS FOR ROOFTOP

EQUIPMENT WITH MECHANICAL AND ROOFING CONTRACTORS. IF PROVISIONS ARE NOT IN PLACE

FOR THESE PENETRATIONS THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR MAKING

OWN PENETRATIONS AND CONTRACTING THE ROOF CONTRACTOR FOR SEALING THE ROOF

PENETRATIONS.

7 REFER TO MECHANICAL DRAWINGS FOR EXACT LOCATION OF ALL MECHANICAL EQUIPMENT.

8 PROVIDE CONDUIT AND WIRING AS REQUIRED TO MEET CIRCUITING SHOWN TO CONFORM TO NEC

REQUIREMENTS.

9 PROVIDE EQUIPMENT GROUND CONDUCTOR IN ALL RACEWAYS. REFER TO PANELBOARD

SCHEDULES.

10 REFER TO EQUIPMENT CONNECTION SCHEDULE FOR ELECTRICAL REQUIREMENTS AND CIRCUIT

DESIGNATIONS.

11 ROUTE CONDUIT HIGH AGAINST STRUCTURE AND OFFSET UP BETWEEN JOISTS WHERE

NECESSARY TO AVOID DUCT WORK AND HVAC SYSTEM.

12 VERIFY AND COORDINATE EXACT ELECTRICAL REQUIREMENTS OF ALL EQUIPMENT WITH

MANUFACTURER'S RECOMMENDATIONS PRIOR TO INSTALLATION OF EQUIPMENT.

NORTH

TRUE NORTH=

PROJECT

88.5°

# POWER PLAN KEYNOTES

1 EXISTING POWER INSTALLATION ASSOCIATED WITH INDICATED MECHANICAL EQUIPMENT

SHALL REMAIN IN PLACE AND OPERATIONAL .

2 PROVIDE A STANDALONE UNISTRUT FOR MOUNTING OF DISCONNECT SWITCH. DISCONNECTS

SHALL BE NEMA 3R AND LOCKABLE. ENSURE PROPER CLEARANCE AND ACCESS PER NEC IS

PROVIDED. THE CU/FCU IS A SINGLE POINT POWER CONNECTION. THE FCU IS FED FROM ITS

RESPECTIVE CU. PROVIDE ALL REQUIRED CONNECTIONS PER THE MANUFACTURER WIRING

DIAGRAM. PROVIDE RECEPTACLE FOR SUPPORTING CONDENSATE PUMP UNIT LOCATED

ABOVE CEILING.

3 EXISTING CORRIDOR RECEPTACLES TO REMAIN. EXISTING RECEPTACLES LOCATED ON

EXISTING TO BE DEMOLISHED WALLS SHALL BE REMOVED AND RELOCATED TO NEW WALLS.

CONTRACTOR TO ENSURE THAT CORRIDOR RECEPTACLE QUANTITY OF NEW WORK MATCHES

CORRIDOR RECEPTACLE QUANTITY OF EXISTING CONDITIONS.

4 ELECTRICAL CONTRACTOR TO COORDINATE WITH MECHANICAL CONTRACTOR AND PROVIDE

POWER TO VAV TRANSFORMERS AS NECESSARY. DETERMINE EXACT LOCATION OF

TRANSFORMERS IN FIELD.

5 IMAGING EQUIPMENT TO BE INSTALLED IN A FUTURE PROJECT. BASIS OF DESIGN SHOWN FOR

COORDINATION PURPOSES ONLY. ELECTRICAL DESIGN FOR IMAGING EQUIPMENT AND

ASSOCIATED EQUIPMENT TO BE DESIGNED IN A FUTURE PROJECT.

6 PROVIDE A 20A/120V CIRCUIT ABOVE CEILING FOR POWER TO DOOR HARDWARE ACCESS

CONTROL PANEL. COORDINATE EXACT LOCATION WITH THE RESPECTIVE CONTRACTOR.

A C

A C

A C

AC AC

A C

G

FI

J

J J

J

J

J

GFI

G

FI

G

FI

GFI

GFI

WP

J

GFI

GFICLNG

J

WEST (BW) EAST (BE)

BASEMENT

GENERAL AREA OF

WORK (REFER TO

PLAN FOR DETALS)

BASEMENT

AREA OF FUTURE WORK

(NOT IN CONTRACT)

NOT IN CONTRACT

N O

T

IN

C O

N T

R A

C T

M A

T C

H

(XR)CH-1

(XR)CU-4

(XR)CU-CAN

(XR)CU-S

(XR)CU-52

CU-B5

AHU-B1

AHU-B2

CU-B2

CU-B1

CU-B3

(XR)AHU

MAILROOM

B300

OIT OFFICE

B309

MECH ROOM 1

B308

BIOMED STORAGE

B310

WORKSHOP

B316C

BIOMED

B316

OFFICE

B316B

TOILET ROOM

B315

VESTIBULE (NIC)

STAIR 4 (NIC)

S4

STAIR 3 (NIC)

S3

STORAGE

B316D

E

F

G

H

C

36353433

32312927252423

33A

302826

B

A

I

22A

D

20B 30A

M A

T C

H L

IN

E

BATTERY ROOM

B307

STOR / SOILED LINEN

CART

B306

PACKAGE LOCKER

B301

STORAGE

B316A

AHU-B5

EF-B307

EF-B300

HWP-1 HWP-2

HWP-2

HWP-1

OIT SERVER

B311

LP-BB

PP-2

LP-BA

(XR)CU-N

M

M

SURFACE METAL

RACEWAY (TYPICAL)

CU-B4

ENGINEERING

STORAGE

B312

CP-1

EXISTING

BATTERY

RACK

EXISTING

DATA

RACK

M

EF-B306

LP-BC-32

LP-BC-30

LP-BC-30

LP-BC-36

LP-BC-32

LP-BC-32

LP-BC-32

LP-BC-30

LP-BB-9

LP-BB-11

LP-BB-32

LP-BB-32LP-BB-32

LP-BB-32

LP-BB-12LP-BB-14

LP-BB-12

LP-BB-14

LP-BB-14

LP-BA-2

LP-BB-14 LP-BB-16

LP-BB-16 LP-BB-16

LP-BB-16

LP-BA-16

LP-BA-9

LP-BA-21

LP-BA-21

LP-BA-21

LP-BA-21

LP-BA-19 LP-BA-19 LP-BA-29

LP-BA-29

LP-BA-29LP-BA-21

LP-BA-16

LP-BA-16

LP-BA-16

LP-BA-32

LP-BA-32

LP-BA-22

LP-BA-22

LP-BA-28

LP-BA-28 LP-BA-30

LP-BA-30

LP-BA-20LP-BA-18

LP-BA-18

LP-BA-20

M

EQ-B-12

LP-BB-22

EQ-B-20

LP-BB-42 LP-BB-33,35

LP-BB-29,31

LP-BB-37,39,41

LP-BB-2,4,6

LP-BB-1,3,5

LP-BB-13,15,17LP-BB-36,38,40

LP-BB-26,28,30

COPIER

COPIER

LP-BB-14

LP-BB-32

LP-BA-11,13

LP-BB-7

CORRIDOR

C07

(TYPICAL)

LP-BA-35,37

NEMA 6-20R

NEMA 6-20R7

LP-BA-5

LP-BA-1,3

LP-BA-4,6

EXISTING

TO

REMAINEXISTING TO REMAIN

LP-BA-2

LP-BA-2EQ-B-198

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseArchitect/Engineer of Record StampConsultant

321 4 5 6 7 8 9 10

Sprinkler Status

B

IM

/1

F t.

W a y n e V

A M

C B a s e m e n t B ld g

/1

M

E P

C e n tr a l

.r v t

/1

/2

:2

:3

P

M

E202E

ELECTRICAL POWER PLAN - BASEMENT EAST

AE Works

209 SANDUSKY STREET

PITTSBURGH, PA 15212

412-287-7333

RENOVATE BASEMENT,

BUILDING 1

2121 LAKE AVE, FORT WAYNE, IN 46805

610A4-19-104

07/15/2020 BK TJR

BID DOCUMENTS

NORTH

TRUE NORTH=

PROJECT

88.5°

8' 16'4'0 1/8" = 1'-0"1

ELECTRICAL POWER PLAN - BASEMENT EAST

POWER PLAN GENERAL NOTES

1 FINAL LOCATION OF ALL EQUIPMENT SHALL BE DETERMINED IN THE FIELD AND SHALL BE

INSTALLED AS DIRECTED BY THE ARCHITECT OR OWNER'S REPRESENTATIVE. WHERE

STRUCTURAL OPENINGS ARE NOT AVAILABLE, THE CONTRACTOR SHALL CORE DRILL WALLS AND

FLOORS AS REQUIRED TO PERMIT PASSAGE OF CONDUITS. THE ELECTRICAL CONTRACTOR SHALL

PROVIDE A MARKED-UP PLAN WITH LOCATION PENETRATIONS FOR REVIEW AND APPROVAL OF

THE STRUCTURAL ENGINEER BEFORE ROUGH-IN BEGINS.

2 RECEPTACLES FOR ALL EQUIPMENT SHALL BE COMPLETE WITH PLUGS FOR THIS EQUIPMENT. THE

ELECTRICAL CONTRACTOR SHALL VERIFY NEMA CONFIGURATIONS OF PLUGS AND RECEPTACLES

FOR EQUIPMENT IN THE SPACE.

3 DURING THE BIDDING PROCESS, THE ELECTRICAL CONTRACTOR SHALL REVIEW DRAWINGS AND SPECIFICATIONS OF ALL OTHER TRADES (ARCHITECTURAL, SITE/LANDSCAPING, HVAC, PLUMBING

AND SPECIALTY TRADES). ALL ITEMS REQUIRING POWER INDICATED ON THESE DRAWINGS BUT

INDICATED ON THE ELECTRICAL DRAWINGS SHALL BE CONSIDERED A PART OF THE ELECTRICAL

CONTRACTOR'S WORK. THIS WORK SHALL BE INSTALLED AS PER NEC REQUIREMENTS AT NO

ADDITIONAL COST TO THE OWNER.

4 THE CONTRACTOR SHALL MAKE EVERY EFFORT TO MAKE ALL FEEDER RUNS CONTINUOUS (NO

CABLE BREAKS). IF SPLICING CABLES IN BOXES BECOMES NECESSARY, USE O.Z.G. TYPE "XW"

CABLE TAPS, OR APPROVED EQUAL, AND TAPE EACH TAP IN APPROVED MANNER.

5 THE MECHANICAL CONTRACTOR SHALL PROVIDE DISCONNECT SWITCHES, VFD'S. OR

COMBINATION STARTERS FOR ALL OF THEIR UNITS. THE ELECTRICAL CONTRACTOR SHALL

RECEIVE THESE ITEMS FROM THE MECHANICAL CONTRACTOR FOR INSTALLATION BY THE

ELECTRICAL CONTRACTOR.

6 THE ELECTRICAL CONTRACTOR SHALL COORDINATE CONDUIT PENETRATIONS FOR ROOFTOP

EQUIPMENT WITH MECHANICAL AND ROOFING CONTRACTORS. IF PROVISIONS ARE NOT IN PLACE

FOR THESE PENETRATIONS THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR MAKING

OWN PENETRATIONS AND CONTRACTING THE ROOF CONTRACTOR FOR SEALING THE ROOF

PENETRATIONS.

7 REFER TO MECHANICAL DRAWINGS FOR EXACT LOCATION OF ALL MECHANICAL EQUIPMENT.

8 PROVIDE CONDUIT AND WIRING AS REQUIRED TO MEET CIRCUITING SHOWN TO CONFORM TO NEC

REQUIREMENTS.

9 PROVIDE EQUIPMENT GROUND CONDUCTOR IN ALL RACEWAYS. REFER TO PANELBOARD

SCHEDULES.

10 REFER TO EQUIPMENT CONNECTION SCHEDULE FOR ELECTRICAL REQUIREMENTS AND CIRCUIT

DESIGNATIONS.

11 ROUTE CONDUIT HIGH AGAINST STRUCTURE AND OFFSET UP BETWEEN JOISTS WHERE

NECESSARY TO AVOID DUCT WORK…

This is the start of the file's text. The full file is on GovTribe.