Drawings_2020-07-15_reprint-2 of 3.pdf

PDF 5 MB Posted

Attached to
Y1DZ--Renovate Basement, Building 1 610A4-19-104
Solicitation number
36C25021B0018
Issued by

About this file

This is a solicitation for a renovation project at the VA Northern Indiana Health Care System campus in Fort Wayne, Indiana. The scope of work involves renovating space in the basement to modernize areas for Environmental Management Services, Biomedical Services, Pharmacy, Mailroom, Engineering Services, Office of Information Technology, Graduate Medical Education, and Medical Imaging. The project will be conducted in three phases over approximately 780 days to allow the hospital to maintain operations. Phase I will address rooms 15-26 and 45, 45A, and 45B over 300 days. Phase II will cover rooms 49A-59A and the east basement corridor in 210 days. Phase III will involve rooms 30-35 and 43, 44, and 44A and the west basement corridor over 270 days. The contractor will provide all labor, equipment, materials, and supervision to complete the renovations per the design and specifications while following OSHA guidelines for hazardous materials abatement.

View the file

Other files

File Type Posted
36C25021B0018 0010.docx DOCX document
36C25021B0018 0009.docx DOCX document
36C25021B0018 0008.docx DOCX document
36C25021B0018 0007.docx DOCX document
Fort Wayne_Interior Sign Spec r1.pdf PDF
RFI Responses 4-13-21.xlsx XLSX spreadsheet
RFI (PLUMBING) Response.pdf PDF
RFI - scan0001 - Amendment 0006.pdf PDF
36C25021B0018 0006.docx DOCX document
RFI 03 - Amendment 0006.pdf PDF
RFI 02 - Amendment 0006.pdf PDF
36C25021B0018 0005.docx DOCX document
RFI Received 3-18-21.pdf PDF
Handout Sheet - scheduled work stoppage.docx DOCX document
Breez Lighting Specs 3-22-21.pdf PDF
Pre-Bid Sign-In Sheet.pdf PDF
36C25021B0018 0004.docx DOCX document
CO Pre-Bid Remarks.pdf PDF
Sole Source JA - Breez lighting-signed.pdf PDF
Drawings_2020-07-15_reprint-3 of 3.pdf PDF
36C25021B0018 0003.docx DOCX document
Amendment 0002.docx DOCX document
36C25021B0018 0001.docx DOCX document
Drawings_2020-07-15_reprint-1 of 3.pdf PDF
RFI Form.pdf PDF
Contractor EMR Certification Form.pdf PDF
6-drawings-Renovate Basement.pdf PDF
36C25021B0018.docx DOCX document
5a-specs-Renovate Basement.pdf PDF
Wage Determination 02-26-2021.txt TXT text file
5b-specs-Renovate Basement.pdf PDF
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

S

T

ABBREVIATIONS

CONNECT TO EXISTING

FDC FIRE DEPARTMENT CONNECTION PIPING

ZONE FIFINGFZ#

SP SPRINKLER PIPING

DRY SYSTEM PIPINGDP

SLOPED CHANGE IN FIFE ELEVATION

ARROW INDICATES DIRECTION OF FLOW

FIRE HOSE VALVE CABINET

SPRINKLER FLOOR CONTROL VALVE ASSEMBLY

PITCH FIFE DOWN IN DIRECTION OF ARROW

ROOF MANIFOLD 3 WAY

WALL MOUNTED FIRE DEPARTMENT SIAMESE CONNECTION

FREE STANDING FIRE DEPARTMENT SIAMESE CONNECTION

NEW FIRE HYDRANT

EXISTING FIRE HYDRANT

TAMPER SWITCH

SMOKE DETECTOR ABOVE THE FLOOR

SIGHT GLASS

WATER FLOW SWITCH

# # HYDRAULIC REF. POINTS # ELEMENT # NODE

FSP FIRE STANDPIPE

INCOMING FIRE SERVICE/ MAIN/ BLDG. WET PIPINGF

SPRINKLER PIPING STREET PRESSURESPST

FIRE DEPT. HOSE VALVE WITH CAP AND CHAIN

HOSE BIBB

FLEXIBLE CONNECTION

BALL VALVE

GLOBE VALVE

MIXING VALVE

RELIEF VALVE

PLUG VALVE

BPA BACKFLOW PREVENTER ASSEMBLY

FLOAT VALVE

CHECK VALVE WITH A.B.D.

OS&Y OUTSIDE SCREW & YOKE VALVE

PRESSURE REDUCING VALVE FP.R.V.

SOLENOID VALVE

CHECK VALVE

GATE VALVE

VALVE IN VERTICAL

ELBOW TURNED UP / CONN. TO VERTICAL LINE

ELBOW TURNED DOWN

TOP PIPE CONNECTION

BOTTOM PIPE CONNECTION

THERMOMETER

PRESSURE GAUGE AND COCK

SLEEVE

WATER PROOF SLEEVE

ECCENTRIC REDUCER E.R.

REDUCER

UNION

RISER NUMBER

RISER SERVICE

DRAWING #

DETAIL #DETAIL DESIGNATION

RISER DESIGNATION

DWG. DRAWING

RHW RAIN HARVESTED WATER

L

AUTOMATIC BALL DRIPA.B.D.

PITCH PER FOOTPPF

INVERT ELEVATIONINV. EL.

CENTER LINEC

UP (PENETRATES FLOOR SLAB)UP

UNLESS OTHERWISE NOTEDUON

TYPICALTYP.

SQUARE FOOT

POUNDS PER SQUARE INCHPSI

OUTSIDE SCREW & YOKE GATE VALVEOS&Y

OUTSIDE DIAMETEROD

NOT TO SCALENTS

NORMALLY OPENNO

NOT IN THIS CONTRACTN.I.C.

NORMALLY CLOSEDNC

MINIMUMMIN.

MAXIMUMMAX.

INCHIN

INSIDE DIAMETERID

HUNG CEILINGHC

GALLONSGAL.

GALLONS PER MINUTEGPM

GENERAL CONTRACTORGC

FEETFT.

FLOORFLR.

ELEVATIONEL.

DRAINDR

DOWN (PENETRATES FLOOR SLAB)DN.

DIAMETERDIA

CONTINUATIONCONT.

CONNECTCONN

CEILINGCLG.

BOTTOM OF PIPEBOP

BUILDINGBLDG.

ABOVE FINISHED FLOORA.F.F.

CA COMPRESSED AIR

ELEVATORELEV.

EXISTING PIPING TO REMAIN

EXISTING PIPING TO BE REMOVED

DISCONNECT

POINT OF NEW CONNECTION TO EXISTING WORK

POINT OF DISCONNECTION

SQ.FT.

S

FIRE PROTECTION

LEGEND

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseArchitect/Engineer of Record StampConsultant

321 4 5 6 7 8 9 10

Sprinkler Status

WSP USA Buildings Inc.

One Penn Plaza, 2nd Floor New York, NY 10019

(212) 465-5000 www.wsp.com

BI

M

5_

Ft . W ay ne

V

AM

C B as em en t B ld g

1/

5_

W

SP

_P

LB

G

IT

_C en tra l 2

8.

rv t

7/

/2

4:

:5

PM

FP001

FIRE PROTECTION SYMBOLS AND

ABBREVIATIONSAE Works

209 SANDUSKY STREET

PITTSBURGH, PA 15212

412-287-7333 AEW Project No. 18025

RENOVATE BASEMENT,

BUILDING 1

2121 LAKE AVE, FORT WAYNE, IN 46805

610A4-19-104

07/15/2020 EG RR

BID DOCUMENTS

# Revisions Date

NOTE:

DEMOLISH ALL EXISTING SPRINKLER HEADS AND

ASSOCIATED BRANCH PIPING BACK TO EXISTING SPRINKLER

MAINS IN AREAS IN SCOPE OF WORK. PROVIDE FIRE WATCH

FOR ALL AFFECTED AREAS THAT WILL NOT BE ACTIVELY

COVERED DURING CONSTRUCTION.

E

F

G

H

C

B

A

2221201918A1615

I

J

131210876543A321

19A

22A

9 11 13A

D

18 20B17A 17B

EXISTING FHV TO

REMAIN (TYP.)

EXISTING FHV TO

REMAIN (TYP.)

1. THE DEMOLISH DRAWING SHOW THE APPROXIMATE

LOCATION OF THE EXISTING FIRE PROTECTION HEADS &

PIPINGS. THESE FIRE PROTECTION DRAWINGS HAVE BEEN

ISENTIFIED AND LOCATED AS ACCURATELY AS POSSIBLE

USING AVAILABLE RECORDS INFORMATION. THE CONTRACTOR

IS RESPONSIBLE FOR THE VERIFYING ALL EXISTING ACTUAL

LOCATIONS.

2. ALL PIPING AND HEADS REMOVAL SHALL INCLUDE REMOVAL

OF ALL APPURTENANCE CONTAINED THEREIN SUCH AS HANGER,

SUPPORTS & VALVES, ETC., COMLETE CAPS SHALL BE INSTALLED

AT ALL OPEN ENDS OF PIPING TO REMAIN AS REQUIRED.

2. REMOVE EXISTING HEADS AND BRANCH PIPING AS INDICATED

ON DRAWINGS. ANY DISCREPANCIES SHALL BE BROUGHT TO

ATTENTION OF ARCHITECT AND ENGINEER.

GENERAL NOTES:

MECH OFFICE

STORAGE

44A

MENS LOCKER RM

45A

LOGISTICS

LOGISTICS

25A

CRASH CARTS

LOGISTICS

MEDICAL SURGICAL

FIRE ALARM

WORK ROOM

MEN/WOMEN

SHWOER

18 TOILET

VESTIBULE

OFFICE

22A

DECONTAMINATION

AREA

MECHANICAL OFFICE

MECH OFFICE

MECH OFFICE

44A

ENGINEERING

42A

MENS

WOMENS

ENG. CLO.

EMS STORAGE

OFFICE

STORAGE

30D

EMS

EMS OFFICE

30A

CLEAN LINEN

STORAGE

30B

EMS OFFICE

30C

MECH (NIC)

B112

PHARMACY (NIC)

B117

STAIR 2 (NIC)

S2

ENGINEERING (NIC)

B105

ENGINEERING (NIC)

B106

SOILED (NIC)

B107

HVAC (NIC)

B108

FIRE PUMP ROOM

(NIC)

B109

BIOMED FILE ROOM

(NIC)

B110

FILE CLO. (NIC)

028a

WEST (BW) EAST (BE)

BASEMENT

GENERAL AREA OF

WORK (REFER TO

PLAN FOR DETALS)

BASEMENT

AREA OF FUTURE WORK

(NOT IN CONTRACT) NOT IN CONTRACT

NO

T

IN

C

ON

TR

AC

T

MA

TC

H

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseArchitect/Engineer of Record StampConsultant

321 4 5 6 7 8 9 10

Sprinkler Status

WSP USA Buildings Inc.

One Penn Plaza, 2nd Floor New York, NY 10019

(212) 465-5000 www.wsp.com

BI

M

5_

Ft . W ay ne

V

AM

C B as em en t B ld g

1/

5_

W

SP

_P

LB

G

IT

_C en tra l 2

8.

rv t

7/

/2

4:

:1

PM

FPD100W

FIRE PROTECTION DEMOLITION PLAN -

BASEMENT WESTAE Works

209 SANDUSKY STREET

PITTSBURGH, PA 15212

412-287-7333 AEW Project No. 18025

RENOVATE BASEMENT,

BUILDING 1

2121 LAKE AVE, FORT WAYNE, IN 46805

610A4-19-104

07/15/2020 EG RR

BID DOCUMENTS

8' 16'4'0

1/8" = 1'-0"1 BASEMENT - FIRE PROTECTION DEMO CEILING PLAN WEST

NORTH

TRUE NORTH=

PROJECT

88.50°

NOTE:

DEMOLISH ALL EXISTING SPRINKLER HEADS AND ASSOCIATED

BRANCH PIPING BACK TO EXISTING SPRINKLER MAINS IN

AREAS IN SCOPE OF WORK. PROVIDE FIRE WATCH FOR ALL

AFFECTED AREAS THAT WILL NOT BE ACTIVELY COVERED

DURING CONSTRUCTION.

E

F

G

H

C

3635343332312927252423 33A302826

B

A

22212019

I

J

19A

22A

D

20B

30A

EXISTING FHV TO REMAIN

EXISTING FCVA

TO REMAIN EXISTING 4" SPRINKLER MAIN TO REMAIN

1. THE DEMOLITION DRAWING SHOW THE APPROXIMATE

LOCATION OF THE EXISTING FIRE PROTECTION HEADS &

PIPINGS. THESE FIRE PROTECTION DRAWINGS HAVE BEEN

IDENTIFIED AND LOCATED AS ACCURATELY AS POSSIBLE

USING AVAILABLE RECORDS INFORMATION. THE CONTRACTOR

IS RESPONSIBLE FOR THE VERIFYING ALL EXISTING ACTUAL

LOCATIONS.

2. ALL PIPING AND HEADS REMOVAL SHALL INCLUDE REMOVAL

OF ALL APPURTENANCE CONTAINED THEREIN SUCH AS HANGER,

SUPPORTS & VALVES, ETC., COMPLETE CAPS SHALL BE INSTALLED

AT ALL OPEN ENDS OF PIPING TO REMAIN AS REQUIRED.

3. REMOVE EXISTING HEADS AND BRANCH PIPING AS INDICATED

ON DRAWINGS. ANY DISCREPANCIES SHALL BE BROUGHT TO

ATTENTION OF ARCHITECT AND ENGINEER.

GENERAL NOTES:

PHARMACY STORAGE

TOILET

ROOM

53B

OIT (NIC)

53A

STAIR

STOR (NIC)

VAC STOR (NIC)

BIOMED

ENGINEERING

CORRIDOR (NIC)

B-C-C2

OIT SERVER ROOM

MATERIAL MGMT.

SECTION

MAILROOM

49A

WOMEN'S LOCKER

RM

CORRIDOR

C4

STAIR

WATER TREATMENT

(NIC)

NEW SPS ADDITION

(NIC)

ENGINEERING (NIC)

SOILED

SOILED

MENS LOCKER RM

MECH OFFICE

STORAGE

44A

MORGUE

MENS LOCKER RM

45A

MENS LOCKER RM

45B

DECONTAMINATION

AREA

MECH OFFICE

MECH OFFICE

44A

WEST (BW) EAST (BE)

BASEMENT

GENERAL AREA OF

WORK (REFER TO

PLAN FOR DETALS)

BASEMENT

AREA OF FUTURE WORK

(NOT IN CONTRACT) NOT IN CONTRACT

NO

T

IN

C

ON

TR

AC

T

MA

TC

H

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseArchitect/Engineer of Record StampConsultant

321 4 5 6 7 8 9 10

Sprinkler Status

WSP USA Buildings Inc.

One Penn Plaza, 2nd Floor New York, NY 10019

(212) 465-5000 www.wsp.com

BI

M

5_

Ft . W ay ne

V

AM

C B as em en t B ld g

1/

5_

W

SP

_P

LB

G

IT

_C en tra l 2

8.

rv t

7/

/2

4:

:0

PM

FPD100E

FIRE PROTECTION DEMOLITION PLAN -

BASEMENT EASTAE Works

209 SANDUSKY STREET

PITTSBURGH, PA 15212

412-287-7333 AEW Project No. 18025

RENOVATE BASEMENT,

BUILDING 1

2121 LAKE AVE, FORT WAYNE, IN 46805

610A4-19-104

07/15/2020 EG RR

BID DOCUMENTS

8' 16'4'0

1/8" = 1'-0"1 BASEMENT - FIRE PROTECTION DEMO CEILING PLAN EAST

NORTH

TRUE NORTH=

PROJECT

EXISTING SPRINKLER

MAIN TO REMAIN (TYP.)

MA

TC

H

LI

NE

MA

TC

H

LI

NE

E

F

G

H

C

B

A

2221201918A1615

I

J

131210876543A321

19A

22A

9 11 13A

D

18 20B17A 17B

EXISTING FHV TO

REMAIN (TYP.)

EXISTING FHV TO

REMAIN (TYP.)

SPRINKLERS IN SHADED N.I.C. AREA TO

REMAIN.

NEW SPRINKLER HEADS LOCATIONS SHOWN.

CONTRACTOR TO MODIFY, ADD, RELOCATE

HEADS AND PIPING AS REQUIRED TO PROVIDE

CODE COMPLIANT COVERAGE. COORDINATE

WORK WITH ARCHITECTURAL, MECHANICAL &

ELECTRICAL DWGS. IF THERE IS A CONFLICT

BETWEEN THE LOCATION OF A LIGHTING

FIXTURES & MECHANICAL, CONTRACTOR

SHALL NOTIFY ARCHITECT AND ENGINEER

PRIOR TO MAKING ANY LOCATION

ADJUSTMENTS.

ALL NEW SPRINKLER HEADS LAYOUT SPACING

AND LOCATIONS SHALL BE IN ACCORDANCE

WITH NFPA 13 AND LOCAL BUILDING CODE.

GENERAL NOTES:

1.

2.

3.

X-RAY

B120E

TLT / CHANGING

B120F

CLEAN

B120G

CT SCANNING

B120D

STORAGE

B118

RECEPTION / WORK

B120A

WAITING

B119

SOILED HOLDING

B120C

WOMENS

B113

MENS

B114

CORRIDOR

C06

PHARMACY CACHE

B111

MECHANICAL OFFICE

B101

EMS SUPPLY

B104

EMS OFFICE 2

B100A

EMS OFFICE 1

B100B

EMS SUITE

B100

MENS DRESSING

B100E

CLEAN LINEN ROOM

B100C

RADIOLOGY

B120

CLOSET

B120B

GME LIBRARY

B116

RES. SLEEPING

ROOM

B115

RESIDENT TLT RM

B115A

CORRIDOR

C05

CORRIDOR

C04

EMS STORAGE

B103

CORRIDOR

C02

MECH

B102B

WOMENS DRESSING

B100D

HAC (NIC)

063A

DOCK (NIC)NUTRITION AND

FOOD SERVICES (NIC)

ENGINEERING (NIC)

033A

ENGINEERING (NIC)

B105

ENGINEERING (NIC)

B106

FIRE PUMP ROOM

(NIC)

B109

SOILED (NIC)

B107

HVAC (NIC)

B108

PHARMACY (NIC)

B117

WEST (BW) EAST (BE)

BASEMENT

GENERAL AREA OF

WORK (REFER TO

PLAN FOR DETALS)

BASEMENT

AREA OF FUTURE WORK

(NOT IN CONTRACT) NOT IN CONTRACT

NO

T

IN

C

ON

TR

AC

T

MA

TC

H

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseArchitect/Engineer of Record StampConsultant

321 4 5 6 7 8 9 10

Sprinkler Status

WSP USA Buildings Inc.

One Penn Plaza, 2nd Floor New York, NY 10019

(212) 465-5000 www.wsp.com

BI

M

5_

Ft . W ay ne

V

AM

C B as em en t B ld g

1/

5_

W

SP

_P

LB

G

IT

_C en tra l 2

8.

rv t

7/

/2

4:

:0

PM

FP100W

FIRE PROTECTION PLAN - BASEMENT WEST

AE Works

209 SANDUSKY STREET

PITTSBURGH, PA 15212

412-287-7333 AEW Project No. 18025

RENOVATE BASEMENT,

BUILDING 1

2121 LAKE AVE, FORT WAYNE, IN 46805

610A4-19-104

07/15/2020 EG RR

BID DOCUMENTS

0 1' 2'6"

1/8" = 1'-0"FP100W

1 BASEMENT - FIRE PROTECTION NEW CEILING PLAN WEST

NORTH

TRUE NORTH=

PROJECT

E

F

G

H

C

3635343332312927252423 33A302826

B

A

2221201918A

I

J

19A

22A

D

18 20B

30A

17A 17B

EXISTING FHV TO REMAIN

EXISTING FCVA

TO REMAIN EXISTING 4" SPRINKLER MAIN TO REMAIN

MA

TC

H

LI

NE

SPRINKLERS IN SHADED N.I.C. AREA TO

REMAIN.

NEW SPRINKLER HEADS LOCATIONS SHOWN.

CONTRACTOR TO MODIFY, ADD, RELOCATE

HEADS AND PIPING AS REQUIRED TO PROVIDE

CODE COMPLIANT COVERAGE. COORDINATE

WORK WITH ARCHITECTURAL, MECHANICAL &

ELECTRICAL DWGS. IF THERE IS A CONFLICT

BETWEEN THE LOCATION OF A LIGHTING

FIXTURES & MECHANICAL, CONTRACTOR

SHALL NOTIFY ARCHITECT AND ENGINEER

PRIOR TO MAKING ANY LOCATION

ADJUSTMENTS.

ALL NEW SPRINKLER HEADS LAYOUT SPACING

AND LOCATIONS SHALL BE IN ACCORDANCE

WITH NFPA 13 AND LOCAL BUILDING CODE.

GENERAL NOTES:

ISOLATION VALVE, WATER FLOW & TAMPER SWITCH

1.

2.

MA

TC

H

LI

NE

3.

MECHANICAL OFFICE

B101

MAILROOM

B300

EMS SUITE

B100

MENS DRESSING

B100E

MECH ROOM 1

B308

BIOMED STORAGE

B310

STORAGE

B316D

WORKSHOP

B316C

OFFICE

B316B

BIOMED

B316

OIT SERVER

B311

OIT OFFICE

B309

EMS STORAGE

B103

STOR / SOILED LINEN

CART

B306 BATTERY ROOM

B307

STORAGE

B316A

ENGINEERING

STORAGE

B312

MECH

B102B

CORRIDOR

C07

WOMENS DRESSING

B100D

VESTIBULE (NIC)

STAIR 4 (NIC)

S4

OIT (NIC)

053A

ENGINEERING (NIC)

B304

PUMP ROOM (NIC)

ENGINEERING (NIC)

B305

STAIR 3 (NIC)

S3

SPS ADDITION (NIC)

42B

HAC (NIC)

B302

SOILED (NIC)

B303

MORGUE (NIC)

HAC (NIC)

063A

DOCK (NIC)NUTRITION AND

FOOD SERVICES (NIC)

EXISTING SPR PROTECTION TO REMAIN

WEST (BW) EAST (BE)

BASEMENT

GENERAL AREA OF

WORK (REFER TO

PLAN FOR DETALS)

BASEMENT

AREA OF FUTURE WORK

(NOT IN CONTRACT) NOT IN CONTRACT

NO

T

IN

C

ON

TR

AC

T

MA

TC

H

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseArchitect/Engineer of Record StampConsultant

321 4 5 6 7 8 9 10

Sprinkler Status

WSP USA Buildings Inc.

One Penn Plaza, 2nd Floor New York, NY 10019

(212) 465-5000 www.wsp.com

BI

M

5_

Ft . W ay ne

V

AM

C B as em en t B ld g

1/

5_

W

SP

_P

LB

G

IT

_C en tra l 2

8.

rv t

7/

/2

4:

:5

PM

FP100E

FIRE PROTECTION PLAN - BASEMENT EAST

AE Works

209 SANDUSKY STREET

PITTSBURGH, PA 15212

412-287-7333 AEW Project No. 18025

RENOVATE BASEMENT,

BUILDING 1

2121 LAKE AVE, FORT WAYNE, IN 46805

610A4-19-104

07/15/2020 EG RR

BID DOCUMENTS

8' 16'4'0

1/8" = 1'-0"1 BASEMENT - FIRE PROTECTION NEW CEILING PLAN EAST

NORTH

TRUE NORTH=

PROJECT

CLEVIS HANGER ADJUSTABLE SWIVEL RING

2 27/ 32" D IA.

[72.2mm]

2 1/ 4" H OLE DIA.

[57.2mm]

1 15/ 16" D IA

[49.2mm]

1/ 8" [3.2mm]

PIPE AND INSULATION TO BE CENTERED

IN SLEEVE - DO NOT SUPPORT PIPE

FROM SLEEVE

SEALANT (SEE SPEC.)

TERMINATE SLEEVE FLUSH WITH

FINISHED WALL SURFACES

FINISHED WALL SURFACE

FINISHED ESCUTCHEON PLATE FLUSH

AGAINST WALL AND OF SIZE TO

COMPLETELY COVER OPENING

PIPE SLEEVE

4"

UPRIGHT HEAD

SPRINKLER BRANCH LINE

NOTES:

1. SPRINKLER CONTRACTOR SHALL

SPRINKLER ABOVE AND BELOW

DUCT OR OTHER OBSTRUCTION

OVER 48" IN WIDTH.

2. SPRINKLER CONTRACTOR SHALL

COORDINATE WITH THE HVAC

AND GENERAL CONTRACTOR.

DUCTWORK OR

OTHER OBSTRUCTION

OVER 48" IN WIDTH

UPRIGHT HEAD

GALVANIZED PROTECTION

SHIELD-18 GA.,12" LONG

WHEN PIPING IS INSULATED

LOCKNUTS

ELASTIC LOCKNUTS

THREADED ROD

(TYPICAL)

ELASTIC

THREADED ROD

DROP IN ANCHOR

BRANCH PIPE

1" DROP NIPPLE

1" x 1/2" COUPLING

(IF REQUIRED)

SUSPENDED CEILINGSPRINKLER HEAD

(SEE SPECIFICATION

& DWG FOR TYPE)

NEW SUSPENDED CEILING

EXISTING BRANCH TEE 1" OUTLET

SPRINKLER HANGER

1" EXTRA HEAVY NIPPLE

1" ELBOW

1 X 1/2 REDUCER

1 DROP NIPPLE

BRANCH LINE

NEW PARTIALLY RECESSED TYPE

SPRINKLER HEAD TO BE REMOVED

EXISTING SPRINKLER HEAD

PIPING TO NEW CEILING HEIGHT

ADJUST EXISTING SPRINKLER MAIN/BRANCH

NOTE:

ATTACH TO EXIST. BUILDING STRUCTURE USING

AN APPROVED METHOD OF SUPPORT (TYP.)

EXISTING ADJUSTABLE SPRINKLER

DROP TO BE REMOVED CAP PIPING

AS REQUIRED

WRENCH BOSS

TURN COLLAR

UNTIL TIGHT

AGAINST SPRINKLER

1" X 1/2" REDUCER

3/4"[19mm]

ADJUSTMENT

F1 ESCUTCHEON

1/2"[12.7mm]

ADJUSTMENT

F2 ESCUTCHEON

FACE OF FITTING

TO FACE OF CEILING DIMENSION

AT MAXIMUM RECESS = 1"[25.4mm] AT MINIMUM RECESS = 3/8"[9.5mm]

F1 ESCUTCHEON

AT MAXIMUM RECESS = 3/4"[19mm] AT MINIMUM RECESS = 3/8"[9.5mm]

F2 ESCUTCHEON

AT MAXIMUM RECESS = 7/8"[22.2mm] AT MINIMUM RECESS = 1-5/8"[41.3mm]

F1 ESCUTCHEON

AT MAXIMUM RECESS = 1-1/8"[28.6mm] AT MINIMUM RECESS = 1-5/8"[41.3mm]

F2 ESCUTCHEON

PIPE SLEEVE THRU INTERIOR WALL

N.T.S.

SPRINKLER HEAD CONNECTION

SPRINKLER DETAIL ABOVE AND

BELOW DUCT

HANGERS

SPRINKLER HEAD RELOCATION IN

SUSPENDED CEILING DETAIL

N.T.S. N.T.S. N.T.S.

N.T.S.

PARTIALLY RECESSED SPRINKLER

HEAD

N.T.S.

RESPONSE COVERAGE K FACTOR

MANUFACTURER & MODEL #

TYCOVIKING RELIABLE

TEMPERATURE(F°)

ORDINARY INTERMEDIATE HIGH

QUICK

RESPONSE

HAZARD FOR USE

LIGHT ORDINARY EXTRA DIMENSION

COVERAGE

MAX. SYMBOL

TYPE

5.6

5.6

5.6

STANDARD

(135~170) (175~225) (250~300)

N/AVK302 N/A

N/A

TY-FRB N/A

RF II

N/A

F1FR

F1FR

REMARK

(AREA APPLIED)

SPRINKLER HEAD SCHEDULE

UPRIGHT

RECESSED

MICROFAST

VK481 F1FRSIDEWALL

15FT X 15FT

15FT X 15FT

14FT X 14FT

PARTIALLY

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseArchitect/Engineer of Record StampConsultant

321 4 5 6 7 8 9 10

Sprinkler Status

WSP USA Buildings Inc.

One Penn Plaza, 2nd Floor New York, NY 10019

(212) 465-5000 www.wsp.com

BI

M

5_

Ft . W ay ne

V

AM

C B as em en t B ld g

1/

5_

W

SP

_P

LB

G

IT

_C en tra l 2

8.

rv t

7/

/2

4:

:0

PM

FP600

FIRE PROTECTION DETAILS AND SCHEDULE

AE Works

209 SANDUSKY STREET

PITTSBURGH, PA 15212

412-287-7333 AEW Project No. 18025

RENOVATE BASEMENT,

BUILDING 1

2121 LAKE AVE, FORT WAYNE, IN 46805

610A4-19-104

07/15/2020 EG RR

ST

PD

GW

AV

LW

LV

IW

EJ

SD

CL

M

A

(ST)

(ST)

PLUMBING LEGEND

ABBREVIATIONS

ABD AUTOMATIC BALL DRIP

AFF ABOVE FINISHED FLOOR

BLDG BUILDING

BOP BOTTOM OF PIPE

CO CLEANOUT

CODP CLEANOUT DECK PLATE

CV CHECK VALVE

CW COLD WATER

CLG CEILING

CONN CONNECT

CONT CONTINUATION

DIA DIAMETER

DN DOWN (PENETRATES FLOOR SLAB)

DR DRAIN

DWG DRAWING

ED EJECTOR DISCHARGE

EL ELEVATION

EWC ELECTRIC WATER COOLER

FAI FRESH AIR INLET

FD FLOOR DRAIN

FU FIXTURE UNIT

FL FLOOR

FT FEET

GC GENERAL CONTRACTOR

GD GARAGE DRAIN

GPM GALLONS PER MINUTE

GAL GALLONS

HB HOSE BIBB

H.CLG HUNG CEILING

HW HOT WATER

HWR HOT WATER RETURN

ID INSIDE DIAMETER

IW INDIRECT WASTE

IN INCH

LAV LAVATORY

MR MOP RECEPTOR

MAX MAXIMUM

MH MANHOLE

MIN MINIMUM

NC NORMALLY CLOSED

NIC NOT IN THIS CONTRACT

NO NORMALLY OPEN

NTS NOT TO SCALE

OD OUTSIDE DIAMETER

OS&Y OUTSIDE SCREW & YOKE GATE VALVE

PD PUMP DISCHARGE

PRV PRESSURE REDUCING VALVE

PSIA POUNDS PER SQUARE INCH (ABSOLUTE)

PSI POUNDS PER SQUARE INCH (GAUGE)

RT RUNNING TRAP

SA SHOCK ABSORBER

SPD SUMP PUMP DISCHARGE

SAN SANITARY

SQ FT SQUARE FOOT

TYP TYPICAL

ABBREVIATIONS (CONTINUED)

UON UNLESS OTHERWISE NOTED

UP UP (PENETRATES FLOOR SLAB)

UR URINAL

V VENT

VB VACUUM BREAKER

VTR VENT THROUGH ROOF

WC WATER CLOSET

WH WALL HYDRANT

LEGENDS

SANITARY PIPING

VENT PIPING (SANITARY)

STORM PIPING

PIPING BURIED (SERVICE NOTED)

PUMP DISCHARGE PIPING

GREASE WASTE PIPING

ACID VENT PIPING

LAB WASTE PIPING

LAB VENT PIPING

INDIRECT WASTE PIPING

EJECTOR DISCHARGE PIPING

SUMP DISCHARGE PIPING

DOMESTIC COLD WATER PIPING

DOMESTIC HOT WATER PIPING

DOMESTIC HOT WATER CIRCULATION PIPING

(Z-#) DOMESTIC COLD WATER ZONE PIPING

(Z-#) DOMESTIC HOT WATER ZONE PIPING

(Z-#) DOMESTIC HOT WATER CIRCULATION ZONE PIPING

DEIONIZED WATER PIPINGDE

DISTILLED WATER PIPINGDI

NON-POTABLE WATERNPW

GAS PIPINGG

COMPRESSED AIR PIPINGMA (MEDICAL)

COMPRESSED AIR PIPING (INDUSTRIAL)CA

IRRIGATION PIPINGIRR

VACUUM PIPINGV

NITROGEN PIPING2N

NITROUS OXIDE PIPINGNO

OXYGEN PIPINGO

HYDROGEN PIPINGH

SLOPED CHANGE IN PIPE ELEVATION

ARROW INDICATES DIRECTION OF FLOW

PITCH PIPE DOWN IN DIRECTION OF ARROW

INSULATED AND HEAT TRACED PIPING

POINT OF DISCONNECTION

SHOCK ABSORBER

LEGENDS (CONTINUED)

FLEXIBLE CONNECTION

EXPANSION LOOP SIZE( )X( ) LH

HOSE BIBB

WALL HYDRANT

FRESH AIR INLET

CLEAN-OUT / PLUG OUTLET

CLEAN-OUT DECK PLATE

"P" TRAP

RUNNING TRAP

DUPLEX STRAINER

BASKET STRAINER

Y STRAINER WITH BLOW OFF VALVE

VACUUM BREAKER

MANUAL AIR VENT

AUTOMATIC AIR VENT

BOTTOM PIPE CONNECTION

TOP PIPE CONNECTION

ELBOW TURNED DOWN

ELBOW TURNED UP / CONN. TO VERTICAL LINE

VALVE IN VERTICAL

VALVE (SEE SCHEDULE)

CHECK VALVE

SOLENOID VALVE

PRESSURE REDUCING VALVE (P.R.V.)

OS&Y (OUTSIDE SCREW & YOKE) VALVE

CHECK VALVE WITH A.B.D.

FLOAT VALVE

BACKFLOW PREVENTER ASSEMBLYBPA

RELIEF VALVE

MIXING VALVE

ANGLE RELIEF VALVE

UNION

REDUCER

ECCENTRIC REDUCER (E.R.)

WATER PROOF SLEEVE

SLEEVE

PRESSURE GAUGE AND COCK

THERMOMETER

OVERFLOW DRAIN

PUMP

METER

RISER DESIGNATION

DETAIL DESIGNATION DETAIL #

DRAWING #

CENTER LINE

AD AREA DRAIN

DRAIN

RISER SERVICE

RISER NUMBER

M

ELEVATOR SUMP PUMPESP

GASG

GW GARAGE WASTE

PLUMBING FIXTURE TYPE (SEE SPECIFICATION)P-?

STORMST

PRV STATIONPRV

S

S

CAP

ANCHOR

EXISTING PIPING TO REMAIN

EXISTING PIPING TO BE ABANDONED

EXISTING PIPING TO BE REMOVED

SLOP SINKSS

DOMESTIC COLD WATER (STREET PRESSURE)

DOMESTIC HOT WATER (STREET PRESSURE)

WAGD WASTE ANESTHESIA GAS DISPOSAL

POINT OF NEW CONNECTION TO EXISTING WORK

CONNECT TO EXISTING

DISCONNECT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseArchitect/Engineer of Record StampConsultant

321 4 5 6 7 8 9 10

Sprinkler Status

WSP USA Buildings Inc.

One Penn Plaza, 2nd Floor New York, NY 10019

(212) 465-5000 www.wsp.com

BI

M

5_

Ft . W ay ne

V

AM

C B as em en t B ld g

1/

5_

W

SP

_P

LB

G

IT

_C en tra l 2

8.

rv t

7/

/2

4:

:1

PM

P001

PLUMBING SYMBOLS AND ABBREVIATIONS

AE Works

209 SANDUSKY STREET

PITTSBURGH, PA 15212

412-287-7333 AEW Project No. 18025

RENOVATE BASEMENT,

BUILDING 1

2121 LAKE AVE, FORT WAYNE, IN 46805

610A4-19-104

07/15/2020 EG RR

E

F

G

H

C

B

A

201918A1615

I

J

131210876543A321

19A

9 11 13A

D

1817A 17B

LOGISTICS

LOGISTICS

25A

CRASH CARTS

LOGISTICS

MEDICAL SURGICAL

FIRE ALARM

WORK ROOM

MEN/WOMEN

SHWOER

18 TOILET

VESTIBULE

OFFICE

22A

DECONTAMINATION

AREA

MECHANICAL OFFICE

MECH OFFICE

MECH OFFICE

44A

ENGINEERING

42A

MENS

WOMENS

ENG. CLO.

EMS STORAGE

OFFICE

STORAGE

30D

EMS

EMS OFFICE

30A

CLEAN LINEN

STORAGE

30B

EMS OFFICE

30C

MECH (NIC)

B112

PHARMACY (NIC)

B117

STAIR 2 (NIC)

S2

ENGINEERING (NIC)

B105

ENGINEERING (NIC)

B106

SOILED (NIC)

B107

HVAC (NIC)

B108

FIRE PUMP ROOM

(NIC)

B109

BIOMED FILE ROOM

(NIC)

B110

FILE CLO. (NIC)

028a

WEST (BW) EAST (BE)

BASEMENT

GENERAL AREA OF

WORK (REFER TO

PLAN FOR DETALS)

BASEMENT

AREA OF FUTURE WORK

(NOT IN CONTRACT) NOT IN CONTRACT

NO

T

IN

C

ON

TR

AC

T

MA

TC

H

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseArchitect/Engineer of Record StampConsultant

321 4 5 6 7 8 9 10

Sprinkler Status

WSP USA Buildings Inc.

One Penn Plaza, 2nd Floor New York, NY 10019

(212) 465-5000 www.wsp.com

BI

M

5_

Ft . W ay ne

V

AM

C B as em en t B ld g

1/

5_

W

SP

_P

LB

G

IT

_C en tra l 2

8.

rv t

7/

/2

4:

:2

PM

PD100W

PLUMBING DEMOLITION PLAN - BASEMENT

WESTAE Works

209 SANDUSKY STREET

PITTSBURGH, PA 15212

412-287-7333 AEW Project No. 18025

RENOVATE BASEMENT,

BUILDING 1

2121 LAKE AVE, FORT WAYNE, IN 46805

610A4-19-104

07/15/2020 EG RR

BID DOCUMENTS

8' 16'4'0

1/8" = 1'-0"1 BASEMENT - PLUMBING DEMO FLOOR PLAN WEST

# KEYNOTES:

1. DEMOLISH EXISTING WATER CLOSET, LAVATORY SINK, SHOWER AND FLOOR

DRAIN. CUT EXISTING COLD WATER AND HOT WATER PIPE BACK TO NEAREST

ACTIVE MAIN AND PROVIDE SHUT OFF VALVES AS NEEDED. CUT AND CAP BOTH

SANITARY AND VENT PIPING BACK TO NEAREST ACTIVE MAIN.

2. DEMOLISH EXISTING WATER CLOSET, LAVATORY SINK AND FLOOR DRAIN. CUT

EXISTING COLD WATER AND HOT WATER PIPE BACK TO NEAREST ACTIVE MAIN

AND PROVIDE SHUT OFF VALVES AS NEEDED. CUT AND CAP BOTH SANITARY

AND VENT PIPING BACK TO NEAREST ACTIVE MAIN.

3. DEMOLISH EXISTING COLD WATER PIPE BACK TO NEAREST ACTIVE MAIN AND

PROVIDE SHUT OFF VALVES AS NEEDED.

4. DEMOLISH EXISTING SINKS, WATER FILTRATION SYSTEMS, AND FLOOR DRAINS.

CUT EXISTING COLD WATER AND HOT WATER PIPE BACK TO NEAREST ACTIVE

MAIN AND PROVIDE SHUT OFF VALVES AS NEEDED. CUT AND CAP BOTH

SANITARY AND VENT PIPING BACK TO NEAREST ACTIVE MAIN.

5. DEMOLISH EXISTING WATER CLOSET, URINAL, LAVATORY SINK, SHOWER AND

FLOOR DRAIN. CUT EXISTING COLD WATER AND HOT WATER PIPE BACK TO

NEAREST ACTIVE MAIN AND PROVIDE SHUT OFF VALVES AS NEEDED. CUT AND

CAP BOTH SANITARY AND VENT PIPING BACK TO NEAREST ACTIVE MAIN.

6. DEMOLISH EXISTING EYEWASH. CUT COLD AND HOT WATER PIPES BACK TO

NEAREST ACTIVE MAIN AND PROVIDE SHUT OFF VALVES AS NEEDED.

NORTH

TRUE NORTH=

PROJECT

88.50°

* UNDERGROUND PIPING CUT AT SLAB, LEAVE IN SLAB AND PATCH WITH

CONCRETE UNLESS NOTED OTHERWISE. CONTRACTOR VERIFY IN PLACE.

4E

F

G

H

C

3635343332312927252423 33A302826

B

A

22212019

I

J

19A

22A

D

20B

30A

EXISTING STORM RISER TO REMAIN

PHARMACY STORAGE

TOILET

ROOM

53B

OIT (NIC)

53A

STAIR

STOR (NIC)

VAC STOR (NIC)

BIOMED

ENGINEERING

CORRIDOR (NIC)

B-C-C2

OIT SERVER ROOM

MATERIAL MGMT.

SECTION

MAILROOM

49A

WOMEN'S LOCKER

RM

CORRIDOR

C4

STAIR

WATER TREATMENT

(NIC)

NEW SPS ADDITION

(NIC)

ENGINEERING (NIC)

SOILED

SOILED

MENS LOCKER RM

MECH OFFICE

STORAGE

44A

MORGUE

MENS LOCKER RM

45A

MENS LOCKER RM

45B

DECONTAMINATION

AREA

WEST (BW) EAST (BE)

BASEMENT

GENERAL AREA OF

WORK (REFER TO

PLAN FOR DETALS)

BASEMENT

AREA OF FUTURE WORK

(NOT IN CONTRACT) NOT IN CONTRACT

NO

T

IN

C

ON

TR

AC

T

MA

TC

H

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseArchitect/Engineer of Record StampConsultant

321 4 5 6 7 8 9 10

Sprinkler Status

WSP USA Buildings Inc.

One Penn Plaza, 2nd Floor New York, NY 10019

(212) 465-5000 www.wsp.com

BI

M

5_

Ft . W ay ne

V

AM

C B as em en t B ld g

1/

5_

W

SP

_P

LB

G

IT

_C en tra l 2

8.

rv t

7/

/2

4:

:2

PM

PD100E

PLUMBING DEMOLITION PLAN - BASEMENT

EASTAE Works

209 SANDUSKY STREET

PITTSBURGH, PA 15212

412-287-7333 AEW Project No. 18025

RENOVATE BASEMENT,

BUILDING 1

2121 LAKE AVE, FORT WAYNE, IN 46805

610A4-19-104

07/15/2020 EG RR

BID DOCUMENTS

8' 16'4'0

1/8" = 1'-0"1 BASEMENT - PLUMBING DEMO FLOOR PLAN EAST

# KEYNOTES:

1. DEMOLISH EXISTING WATER CLOSETS, LAVATORY SINKS, SHOWER AND FLOOR

DRAIN. CUT EXISTING COLD WATER AND HOT WATER PIPE BACK TO NEAREST

ACTIVE MAIN AND PROVIDE SHUT OFF VALVES AS NEEDED. CUT AND CAP BOTH

SANITARY AND VENT PIPING BACK TO NEAREST ACTIVE MAIN.

2. DEMOLISH EXISTING WATER CLOSETS, URINALS, LAVATORY SINKS, SHOWER

AND FLOOR DRAIN. CUT EXISTING COLD WATER AND HOT WATER PIPE BACK

TO NEAREST ACTIVE MAIN AND PROVIDE SHUT OFF VALVES AS NEEDED. CUT

AND CAP BOTH SANITARY AND VENT PIPING BACK TO NEAREST ACTIVE MAIN.

3. PLUMBING FIXTURES EXISTING TO REMAIN.

4. REMOVE EXISTING DRINKING FOUNTAIN AND CAP ALL EXISTING PLUMBING

PIPING FOR FUTURE CONNECTION. ALL EXISTING PIPING TO REMAIN.

5. REMOVE EXISTING DRINKING FOUNTAIN AND CAP ALL PIPING FOR FUTURE USE.

ALL EXISTING PIPING TO REMAIN.

6. DEMOLISH EXISTING FLOOR DRAIN. CUT EXISTING COLD WATER SUPPLY TO ICE

MACHINE PIPE BACK TO NEAREST ACTIVE MAIN AND PROVIDE SHUT OFF VALVE

AS NEEDED. CUT AND CAP BOTH SANITARY AND VENT PIPING BACK TO

NEAREST ACTIVE MAIN.

NORTH

TRUE NORTH=

PROJECT

88.50°

* UNDERGROUND PIPING CUT AT SLAB, LEAVE IN SLAB AND PATCH WITH

CONCRETE UNLESS NOTED OTHERWISE. CONTRACTOR VERIFY IN PLACE.

MA

TC

H

LI

NE

MA

TC

H

LI

NE

P-3

P-1A

2" SAN DN

1 1/2" VENT RISE & DROP

3/4" CW&HW DROP

1/2" HWR

P-8A P-2

P-1P-1AP-5

P-3

NEW 2" VENT, 1 1/2" CW, 1" HW

& 1/2" HWR CONNECT TO

NEAREST EXISTING IN CLG.

P-8A

P-6 E

F

G

H

C

B

A

201918A1615

I

J

131210876543A321

19A

9 11 13A

D

18 20B17A 17B

2" SAN DN

1 1/2" VENT RISE & DROP

3/4" CW&HW DROP

1/2" HWR

4" SAN DN

2" VENT RISE & DROP

NEW 2" VENT, 1 1/4" CW, 1" HW

& 1/2" HWR CONNECT TO NEAREST

EXISTING PIPING IN CLG.

P-3 P-3

P-3 P-3 P-1A

4" SAN DN

2" VENT RISE & DROP

1 1/2" CW DROP

2" SAN DN

1 1/2" VENT DROP & RISE

3/4" CW DROP

3/4" HW DROP

1/2" HWR

4" SAN DN

2" VENT DROP & RISE

1 1/4" CW DROP

3" FD

3" FD

3" FD

3" FD

1 1/2"ø

3/4"ø

1 1/4" CW DROP

3/4 HW" DROP

3/4" CW DROP

3/4" HW DROP

1. PLUMBING IN SHADED N.I.C. AREA TO REMAIN.

2. NEW SANITARY CONNECTIONS TO THE NEAREST

EXISTING PIPING BELOW GRADE SHALL BE VERIFIED IN

TERMS OF LOCATION AND SIZES IN FIELD.

ANY DISCREPANCIES SHALL BE BROUGHT

TO ATTENTION OF ARCHITECT AND ENGINEER.

GENERAL NOTES:

NEW DRINKING FOUNTAIN CONNECT TO EXIST. PLBG ROUGHING

3" SAN CONNECT TO

EXIST. 4" SAN UNDERGROUND

EXIST. 4" SAN

UNDERGROUND

EXIST. 4" SAN

UNDERGROUND

3" SAN CONNECT TO

EXIST. 4" SAN UNDERGROUND

3" FUNNEL BELOW SINK

FOR CONDENSATE DRAIN

P-1A

X-RAY

B120E

TLT / CHANGING

B120F

CLEAN

B120G

CT SCANNING

B120D

STORAGE

B118

RECEPTION / WORK

B120A

WAITING

B119

SOILED HOLDING

B120C

WOMENS

B113

MENS

B114

CORRIDOR

C06

PHARMACY CACHE

B111

MECHANICAL OFFICE

B101

EMS SUPPLY

B104

EMS OFFICE 2

B100A

EMS OFFICE 1

B100B

EMS SUITE

B100

MENS DRESSING

B100E

CLEAN LINEN ROOM

B100C

RADIOLOGY

B120

CLOSET

B120B

GME LIBRARY

B116

RES. SLEEPING

ROOM

B115

RESIDENT TLT RM

B115A

CORRIDOR

C05

CORRIDOR

C04

EMS STORAGE

B103

CORRIDOR

C02

MECH

B102B

WOMENS DRESSING

B100D

NUTRITION AND

FOOD SERVICES (NIC)

ENGINEERING (NIC)

033A

ENGINEERING (NIC)

B105

ENGINEERING (NIC)

B106

FIRE PUMP ROOM

(NIC)

B109

SOILED (NIC)

B107

HVAC (NIC)

B108

PHARMACY (NIC)

B117

NEW 1 1/2" VENT, 3/4" CW

CONNECT TO NEAREST

EXISTING IN CLG.

NEW 2" SAN DN

NEW 2" SAN

UNDERGROUND

EXIST 4" SAN

NEW 1 1/2" VENT,

3/4" CW DROP

WEST (BW) EAST (BE)

BASEMENT

GENERAL AREA OF

WORK (REFER TO

PLAN FOR DETALS)

BASEMENT

AREA OF FUTURE WORK

(NOT IN CONTRACT) NOT IN CONTRACT

NO

T

IN

C

ON

TR

AC

T

MA

TC

H

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseArchitect/Engineer of Record StampConsultant

321 4 5 6 7 8 9 10

Sprinkler Status

WSP USA Buildings Inc.

One Penn Plaza, 2nd Floor New York, NY 10019

(212) 465-5000 www.wsp.com

BI

M

5_

Ft . W ay ne

V

AM

C B as em en t B ld g

1/

5_

W

SP

_P

LB

G

IT

_C en tra l 2

8.

rv t

7/

/2

4:

:1

PM

P100W

PLUMBING PLAN - BASEMENT WEST

AE Works

209 SANDUSKY STREET

PITTSBURGH, PA 15212

412-287-7333 AEW Project No. 18025

RENOVATE BASEMENT,

BUILDING 1

2121 LAKE AVE, FORT WAYNE, IN 46805

610A4-19-104

07/15/2020 EG RR

BID DOCUMENTS

8' 16'4'0

1/8" = 1'-0"1 BASEMENT - PLUMBING NEW FLOOR PLAN WEST

# KEYNOTES:

1. PROVIDE OXYGEN AND CA CONNECTIONS.

NORTH

TRUE NORTH=

PROJECT

MA

TC

H

LI

NE

MA

TC

H

LI

NE

P-8A

2" SAN DN

1 1/2" VENT DROP & RISE

3/4" CW DROP

3/4" HW DROP

1/2" HWR

NEW 1 1/2" VENT & 3/4" CW &

HW CONNECT TO NEAREST

EXISTING PIPING IN CLG.

P-6 E

F

G

H

C

3635343332312927252423 33A302826

B

A

2221201918A

I

19A

22A

D

18 20B

30A

17B

3/4" WATER DROP

TO EYEWASH

NEW 3/4" CW & HW

CONNECT TO NEAREST

PIPING EXISTING IN CLG.PROVIDE TEMPERING

MIXING VALVE

1. PLUMBING IN SHADED N.I.C. AREA TO REMAIN.

2. NEW SANITARY CONNECTIONS TO THE NEAREST

EXISTING PIPING BELOW GRADE SHALL BE VERIFIED IN

TERMS OF LOCATION AND SIZES IN FIELD.

ANY DISCREPANCIES SHALL BE BROUGHT

TO ATTENTION OF ARCHITECT AND ENGINEER.

GENERAL NOTES:

EW

NEW DRINKING FOUNTAIN

CONNECT TO EXIST. PLBG

ROUGHING

1" MAKE-UP WATER FOR

HYDRONIC SYSTEM

1" RPZ

NEW 1" CW MAKE-UP WATER

CONNECT TO NEAREST

EXIST. PIPING IN CLG

EXIST

MECHANICAL OFFICE

B101

MAILROOM

B300

MENS DRESSING

B100E

MECH ROOM 1

B308

BIOMED STORAGE

B310

STORAGE

B316D

WORKSHOP

B316C

OFFICE

B316B

BIOMED

B316

OIT SERVER

B311

OIT OFFICE

B309

STOR / SOILED LINEN

CART

B306 BATTERY ROOM

B307

STORAGE

B316A

ENGINEERING

STORAGE

B312

CORRIDOR

C07

WOMENS DRESSING

B100D

VESTIBULE (NIC)

STAIR 4 (NIC)

S4

OIT (NIC)

053A

ENGINEERING (NIC)

B304

PUMP ROOM (NIC)

ENGINEERING (NIC)

B305

STAIR 3 (NIC)

S3

SPS ADDITION (NIC)

42B

HAC (NIC)

B302

SOILED (NIC)

B303

MORGUE (NIC)

HAC (NIC)

063A

NUTRITION AND

FOOD SERVICES (NIC)

NEW DRINKING

FOUNTAIN CONNECT TO

EXIST. PLBG ROUGHING

P-6

P-3P-1A

WEST (BW) EAST (BE)

BASEMENT

GENERAL AREA OF

WORK (REFER TO

PLAN FOR DETALS)

BASEMENT

AREA OF FUTURE WORK

(NOT IN CONTRACT) NOT IN CONTRACT

NO

T

IN

C

ON

TR

AC

T

MA

TC

H

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseArchitect/Engineer of Record StampConsultant

321 4 5 6 7 8 9 10

Sprinkler Status

WSP USA Buildings Inc.

One Penn Plaza, 2nd Floor New York, NY 10019

(212) 465-5000 www.wsp.com

BI

M

5_

Ft . W ay ne

V

AM

C B as em en t B ld g

1/

5_

W

SP

_P

LB

G

IT

_C en tra l 2

8.

rv t

7/

/2

4:

:1

PM

P100E

PLUMBING PLAN - BASEMENT EAST

AE Works

209 SANDUSKY STREET

PITTSBURGH, PA 15212

412-287-7333 AEW Project No. 18025

RENOVATE BASEMENT,

BUILDING 1

2121 LAKE AVE, FORT WAYNE, IN 46805

610A4-19-104

07/15/2020 EG RR

BID DOCUMENTS

8' 16'4'0

1/8" = 1'-0"1 BASEMENT - PLUMBING NEW FLOOR PLAN EAST

# KEYNOTES:

1. PROVIDE OXYGEN AND CA CONNECTIONS.

NORTH

TRUE NORTH=

PROJECT

NOTES:

1. EACH GS-PLUS SPRAY HEAD HAS A

"FLIP-TOP" DUST COVER, INTERNAL

FLOW CONTROL AND FILTER TO REMOVE

IMPURITIES FROM THE WATER FLOW.

2. UNIT SHOULD BE INSTALLED SUCH THAT

WATER FLOW PATTERN IS POSITIONED

BETWEEN 33" AND 53" ABOVE FLOOR.

5 1/4" ( 133 mm)

6 3/8" ( 162 mm)

1 60 .00 00 ( 203 mm)

�1 1 1/8" ( 283 mm)

6 7/8" ( 175 mm)

6 1/2" ( 165 mm)

2 75 .00 00 ( 349 mm)

6 6.17 38 ( 83 mm)

6 4.96 66 ( 83 mm)

9 2.50 00 ( 117 mm)

9 6.52 00 ( 124 mm)

1/2" IPS CHROME PLATED

BRASS STAY-OPEN BALL VALVE

9 6.89 96 ( 124 mm)

3" FUNNEL BELOW SINK

FOR CONDENSATE DRAIN.

COORDINATE EXACT

LOCATION IN FIELD

CEILING

PARTITION/WALL

VENT

WASTE

HANDSINK

2" CONDENSATE DRAIN LINE

FROM WALL AC UNIT

1"

2"

VERIFY EXACT SIZE IN FIELD

VERIFY EXACT SIZE IN FIELD

P

DETAIL "A"

MOUNTING BRACKET

1 1/4" NPT

FEMALE OUTLET

(3) ∅3/8"

MOUNTING

HOLES

STAINLESS STEEL BOWL

1/2" NPT

FEMALE INLET

POWDER COATED CAST

ALUMINUM WALL BRACKET

(SEE DETAIL "A")

POWDER COATED CAST

ALUMINUM FLAG HANDLE

(2) GS-PLUS

SPRAY HEADS

6' MAX

CLEVIS HANGER

WITH VAPOR

BARRIER INSULATION

PIPE

NO VAPOR

CLEVIS HANGER

BARRIER INSULATION

NOT TO SCALE

CLEAN OUT DETAIL PIPE SUPPORT DETAIL

NOT TO SCALE

NOTES:

1. REFER TO ARCHITECTURE DRAWINGS FOR EXACT

CONSTRUCTION CONDITIONS AND REQUIREMENTS.

NOTES:

2. THIS DETAIL SHALL BE APPLICABLE TO PLUMBING PIPING

SMALLER THAT 50.

1. ALL HANGERS FOR COPPER PIPING SHALL BE COPPER

COATED.

LOCKING NUT (TYPICAL)

16 GA. SHEET METAL

SADDLE 300 LONG

BLOCK SUPPORT

WHERE REQUIRED TO

ELIMINATE INSULATION

DAMAGE

VAPOR BARRIER

INSULATION

SUPPORT ADJUSTMENT

NUT (TYPICAL)

CONCRETE INSERT

ANCHOR TO

STRUCTURE ABOVE

CONCRETE

HANGER ROD

(TYPICAL)

HEAVY DUTY CLEVIS

HANGER (TYPICAL)

ALL THREAD

ROD (TYPICAL)

CONCRETE INSERT

ANCHOR TO

STRUCTURE

ABOVE

CONCRETE

TO SYSTEM

FLOOR

CLEANOUT WITH

COVER PLATE

3. THIS HANGAR METHOD CAN ONLY BE USED UNDER THE 2ND

FLOOR AS THE ROOF DOES NOT PROVIDE SUPPORT

DEIONIZED WATER FAUCET INSTALLATION

NOT TO SCALE NOT TO SCALE

TRAP PRIMER INSTALLATION

BATHROOM FLOOR DRAIN TRAP PRIMER

NOT TO SCALE

WATER HAMMER ARRESTOR INSTALLATION

NOT TO SCALE

CLEANOUT PLUG

FINISHED

WALL

FINISHED FLOOR

FLOOR DRAIN

PIPING IN WALL

AND UNDER FLOOR

WATER SAVER TRAP PRIMER

J.R. SMITH PRIME-EZE

1'x1' ACCESS DOOR

TRAP PRIMER

DOMESTIC COLD WATER LINE

FLOOR DRAIN

FINISHED FLOOR

TRAP ARM

TRAP

P.D.I. SYMBOLS

FIXTURE UNIT RATING 1-11 12-32 33-60 61-113 114-154 155-330

A B C D E F 5005 5010 5020 5030 5040 5050

WATER HAMMER ARRESTOR SCHEDULE

NOTE:

EXAMPLE:

COLD WATER BRANCH = 26 F.U. = JR. SMITH #5010 HYDROTROL

HOT WATER BRANCH = 6 F.U. = JR. SMITH #5005 HYDROTROL

WHEN HORIZONTAL BRANCH PIPING EXCEEDS 20' IN

LENGTH, AN ADDITIONAL ARRESTOR SHALL BE USED.

PLUG 1 LEG OF TEE WITH BARSTOCK,

DRILL & TAP FOR CONNECTION TO

FAUCET. LENGTH OF NIPPLE BETWEEN

TAPPED BARSTOCK & FAUCET TO BE

AS SHORT AS POSSIBLE.

ENFIELD ENSURE SCH 80

POLYPROPYLENE WITH

FUSION JOINTS.

TEE

SHEETMETAL

PIPE ENCLOSURE.

WALL

BASE

CABINET

FAUCET "WATER SAVER

FAUCET CO." MODEL L7833.

COUNTER

1 1/2"

6 SERRATION POLYPROPYLENE

HOSE END

ROUND NYLON

HANDLE

COMPRESSION CONTROL

DIAPHRAGM VALVE

J.R. SMITH/HYDROTROL #

NOTE:

REMOVE SLAB AND REPLACE AS REQUIRED

NOTE:

REMOVE SLAB AND REPLACE AS REQUIRED

DRAIN TO HANDSINK DETAIL

NTS

WALL MOUNTED EYE WASH

NTS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseArchitect/Engineer of Record StampConsultant

321 4 5 6 7 8 9 10

Sprinkler Status

WSP USA Buildings Inc.

One Penn Plaza, 2nd Floor New York, NY 10019

(212) 465-5000 www.wsp.com

BI

M

5_

Ft . W ay ne

V

AM

C B as em en t B ld g

1/

5_

W

SP

_P

LB

G

IT

_C en tra l 2

8.

rv t

7/

/2

4:

:1

PM

P600

PLUMBING DETAILS

AE Works

209 SANDUSKY STREET

PITTSBURGH, PA 15212

412-287-7333 AEW Project No. 18025

RENOVATE BASEMENT,

BUILDING 1

2121 LAKE AVE, FORT WAYNE, IN 46805

610A4-19-104

07/15/2020 EG RR

GA

TE

BA

LL

GL

OB

E

FLA

NG

ED

SC

RE

WE

D

REMARKSSTRAINERBODY

LE

SS

G

RA

TE

EX

TE

NS

IO

N

RA

IS

ED

LI

P

DO

ME

FL

AT

T

OP

FU

NN

EL

T

OP

BR

ON

ZE

M

ES

H

SC

RE

EN

TR

AC

TO

R

GR

AT

E

SA

TI

N

FI

NI

SH

PO

LIS

HE

D

FI

NI

SH

SE

CO

ND

AR

Y

ST

RA

IN

ER

SE

DI

ME

NT

B

UC

KE

T

CH

RO

ME

P

LA

TE

D

NI

CK

EL

B

RO

NZ

E

AL

L B

RO

NZ

E

CA

ST

IR

ON

FL

AN

GE

(W

AT

ER

P

RO

OF

IN

G)

SU

MP

R

EC

IE

VE

R

BA

CK

W

AT

ER

V

AL

VE

DE

CK

C

LA

MP

CL

AM

PI

NG

D

EV

IC

E

SE

CO

ND

AR

Y

CL

AM

P

AL

L B

RO

NZ

E

GA

LV

AN

IZ

ED

CA

ST

IR

ON

DE

SI

GN

AT

IO

N

SE

RI

ES

N

O.

JO

SA

M

SM

ITH

W

AD

E

ZU

RN

DRAIN SCHEDULE

PO

LY

PR

OP

YL

EN

E

ST

AI

NL

ES

S

ST

EE

L

ST

AI

NL

ES

S

ST

EE

L

BATHROOM2005FD

DOMESTIC WATER SYSTEM

3" AND LARGER

2½" AND SMALLER

WATER SERVICE

SHUT-OFF VALVES

VALVE SPECIFICATION

FLOOR DRAINS

T.W.

1½" ¾"VALVE

FLUSHOMETER

CARRIER

FIXTURE

1¼"4" 2"

SUPPLIES

2" - -

URINAL

637JR SMITH

0208Y

AMERICAN

STANDARD 6042.001EC.020

SELECTRONIC 6063.013.002

FOUNTAIN

DRINKING ELKAY

P-2

P-3

P-6 --½"1½"1½"

McGUIRE 167

JR SMITHP-TRAP

FAUCET AMERICAN

STANDARD 6114.110.002

0954.004EC

AMERICAN

STANDARDLAVATORY

2" 1½" ½" ½" -

MURRO UNIVERSAL DESIGN

FAUCET FLOW RATE 0.5 GPM

PROVIDE COVER ON SUPPLIES & TRAP.

TEMPERING VALVE POWERS EF-480

P-1/P-1A

JR SMITH

AMERICAN

STANDARD 3351.101

6065.761SELECTRONIC

EXTRA HEAVY DUTY SEATTOILET SEAT

FLUSHOMETER

VALVE

CARRIER

WATER CLOSET

FIXTURES DESIGNATION BASIS OF DESIGN

MANUFACTURER

BASIS OF DESIGN

MODEL #

PLUMBING FIXTURE SERVICE CONNECTION SCHEDULE

S V C.W. H.W. REMARKS

P-1 REGULAR MOUNT HEIGHT

P-1A MOUNT HEIGHT ADA COMPLIANT

HEIGHT, SEE ARCH. DWG FOR

DETAIL DUAL FLUSH 1.6/1.1 GPF

LVRCTL8WSK

FLUSH CYCLE - 0.125 GPF

P-5

P-TRAP

FAUCET

SHOWER

2" 1½" ½" ½" -

P-8A

P-TRAP McGUIRE

SINK

2" 1½" ½" ½" -FAUCET

EYEWASH WATEREW ½"-EW814SAVER

SPILL TO

FLOOR

EMERGENCY THERMOSTATIC MIXING VALVE

WATER SAVER-EW814

WALL MOUNTER, STAINLESS STEE BOWL

¾" ¾"

8902McGUIRE

ALL-IN-ONE MODULAR CASEWORK

UNIT INTEGRATED SINK, MATCH

HERMAN MILLER COMPASS

SYSTEM INSTALLED IN 3E SIDE

COMPASS SYSTEM

COMPASS SYSTEMHERMAN

MILLER

HERMAN

MILLER

FLOW CONTROL ( 1.5 GPM AT 45 PSI ),

METALLIC SHOWER HEAD WITH

TYPE T/P BALANCING VALVE SET.

TU662213.002

TU662213.002

REFER TO ARCH DRAWINGS FOR DETAILS.

AMERICAN

STANDARD

AMERICAN

STANDARD

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseArchitect/Engineer of Record StampConsultant

321 4 5 6 7 8 9 10

Sprinkler Status

WSP USA Buildings Inc.

One Penn Plaza, 2nd Floor New York, NY 10019

(212) 465-5000 www.wsp.com

BI

M

5_

Ft . W ay ne

V

AM

C B as em en t B ld g

1/

5_

W

SP

_P

LB

G

IT

_C en tra l 2

8.

rv t

7/

/2

4:

:1

PM

P700

PLUMBING SCHEDULES

AE Works

209 SANDUSKY STREET

PITTSBURGH, PA 15212

412-287-7333 AEW Project No. 18025

RENOVATE BASEMENT,

BUILDING 1

2121 LAKE AVE, FORT WAYNE, IN 46805

610A4-19-104

07/15/2020 EG RR

CO2

CO

H

HS

NO2

S

TH

TS

T

MS

CD

LPC

P-HWR

P-HWS

G

LPS

(E)

CONDENSATE DRAINAGE

CONDENSATE RETURN

NATURAL GAS

STEAM

RL

RS

REFRIGERANT-LIQUID

REFRIGERANT-SUCTION

2"

REF-HG REFRIGERANT-HOT GAS

HYDRONIC PIPING SYMBOLS

KEYNOTE

CONTINUATION SYMBOL

REVISION NUMBER - SHOWN ON PLANS

GENERAL MECHANICAL SYMBOLS

ROOM NAME AND NUMBER

POINT WHERE NEW CONNECTS TO EXISTING

EXISTING PIPE TAG

ITEM TO BE DEMOLISHED

PIPING BEING DEMOLISHED

ABOVE GROUND PIPING

PIPE SIZE TAG (DIAMETER)

BELOW GROUND PIPING

PIPE INVERT ELEVATION TAG

PIPE SLOPE TAG

* NOTE *

ALL OF GENERAL NOTES ON THIS SHEET ARE TO BE APPLIED TO ALL OTHER DRAWINGS IN THIS SET.THE

SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET MAY OR MAY NOT BE USED IN THIS SET OF

DRAWINGS.

PG PROPANE GAS

Room

INVERT: -10' - 1"

1/8" / 12" SLOPE

16"x8"

16"/8"

(E)

F

S

M

B

D

C

16"Ø

E/A

O/A

T/A

R/A

S/A

EXHAUST AIR

OUTSIDE AIR

RETURN AIR

SUPPLY AIR

TRANSFER AIR

GRILLES, REGISTERS & DIFFUSERS TAG

CFM

EXISTING DUCT TAG

OVAL DUCT SIZE TAG (WIDTH / HEIGHT)

SQUARE DUCT SIZE TAG (WIDTH x HEIGHT)

HVAC SYMBOLS

RECTANGULAR SUPPLY/OUTSIDE AIR DUCT RISE

RECTANGULAR RETURN/TRANSFER AIR DUCT RISE

MECHANICAL EQUIPMENT TAGS

ROUND DUCT SIZE TAG (DIAMETER)

DUCT BEING DEMOLISHED

ROUND SUPPLY/OUTSIDE AIR DUCT RISE

ROUND RETURN/TRANSFER AIR DUCT RISE

RECTANGULAR EXHAUST/RELIEF AIR DUCT RISE

ROUND EXHAUST/RELIEF AIR DUCT RISE

DROP

DROP

DROP

DROP

DROP

DROP

EXISTING EQUIPMENT

TO REMAIN(XR)VAV-XX

Ø ROUND

ABV ABOVE

AC AIR CONDITIONING

AD AREA DRAIN

ADD ADDENDUM

AFF ABOVE FINISHED FLOOR

AFUE ANNUAL FUEL UTILIZATION EFFICIENCY

ALT ALTERNATE

AP ACCESS PANEL

ARCH ARCHITECT/ARCHITECTURAL

BFF BELOW FINISHED FLOOR

BLW BELOW

BTU BRITISH THERMAL UNITS

BTUH BRITISH THERMAL UNITS PER HOUR

CAP CAPACITY

CB CATCH BASIN

CFM CUBIC FEET PER MINUTE

CLG CEILING

CV CONSTANT VOLUME

CW COLD WATER

D DEGREE

DB DRY BULB

DIA DIAMETER

DN DOWN

DW DISTILLED WATER

EA EACH

EAT ENTERING AIR TEMPERATURE

ELEC ELECTRICAL

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EWT ENTERING WATER TEMPERATURE

E/A EXHAUST AIR

EXIST EXISTING

F DEGREES FAHRENHEIT

FCO FLOOR CLEAN OUT

FD FLOOR DRAIN

FD FIRE DAMPER

FDV FIRE DEPARTMENT VALVE

FL FLOOR

FO FUEL OIL

FOV FUEL OIL VENT

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

FPM FEET PER MINUTE

FS FLOOR SINK

FT FOOT/FEET

FTR FIN TUBE RADIATION

GAL GALLON

GC GENERAL CONTRACTOR

GPM GALLONS PER MINUTE

GW GREASE WASTE

HB HOSE BIB

HP HORSE POWER

HTG HEATING

HTR HEATER

HW HOT WATER

HYD HYDRANT

ID INDIRECT

IN INCH

INV INVERT

LB POUND

LB/HR POUNDS PER HOUR

LAT LEAVING AIR TEMPERATURE

LP LOW PRESSURE

LPG LIQUEFIED PETROLEUM GAS

LVR LOUVER

LWT LEAVING WATER TEMPERATURE

M/A MIXED AIR

MAX MAXIMUM

MBH ONE THOUSAND BTU PER HOUR

MCF ONE THOUSAND CUBIC FEET

MD MOTORIZED DAMPER

MECH MECHANICAL

MFR MANUFACTURER

MIN MINIMUM

MISC MISCELLANEOUS

MTR MOTOR

MU/A MAKE-UP/AIR

NC NOISE CRITERIA

NC NORMALLY CLOSED

NIC NOT IN CONTRACT

NO NUMBER

NO NORMALLY OPEN

NTS NOT TO SCALE

O OXYGEN

O/A OUTSIDE AIR

ORD OVERFLOW ROOF DRAIN

PD PRESSURE DROP

PIV POST INDICATOR VALVE

PLBG PLUMBING

PRESS PRESSURE

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PSIG POUNDS PER SQUARE INCH GAUGE

PWR POWER

R DUCT RISER

R/A RETURN AIR

RCP RADIANT CEILING PANEL

RD ROOF DRAIN

REC RECESSED

RED REDUCER

RH RELATIVE HUMIDITY

RL/A RELIEF AIR

RM ROOM

RPM REVOLUTIONS PER MINUTE

RW RAIN WATER

SF SQUARE FOOT

S/A SUPPLY AIR

SAN SANITARY

SF SQUARE FOOT

SD SMOKE DAMPER

SM SURFACE MOUNT

SP STANDPIPE

SP STATIC PRESSURE

STM STEAM

T THERMOSTAT

TD TEMPERATURE DROP

TDR TRENCH DRAIN

TEMP TEMPERATURE

TYP TYPICAL

UG UNDERGROUND

VAC VACUUM

V VENT

VAV VARIABLE AIR VOLUME

VENT VENTILATION

VTR VENT THROUGH ROOF

W WASTE

WB WET BULB

WCO WALL CLEAN OUT

WH WALL HYDRANT

ABBREVIATIONS

AC AIR CONDITIONING UNIT

ACC AIR COOLED CONDENSER

ACCU AIR COOLING CONDENSING UNIT

AHU AIR HANDLING UNIT

AS AIR SEPARATOR

ATU AIR TERMINAL UNIT

B BOILER

BAS BUILDING AUTOMATION SYSTEM

CH CHILLER

CT COOLING TOWER

CUH CABINET UNIT HEATER

CWP CONDENSER WATER PUMP

CHWP CHILLED WATER PUMP

DBP DOMESTIC WATER BOOSTER PUMP

DC DUCT MOUNTED COIL

DCP DOMESTIC WATER CIRCULATING PUMP

ECC ENGINEERING CONTROL CENTER

EF EXHAUST FAN

EDC ELECTRIC DUCT COIL

ET EXPANSION TANK

EWH ELECTRIC WATER HEATER

FCU FAN COIL UNIT

FP FIRE PUMP

GI GREASE INTERCEPTOR

GRV GRAVITY ROOF VENTILATOR

HWP HEATING WATER PUMP

HX HEAT EXCHANGER

HRU HEAT RECOVERY UNIT

PRV POWER ROOF VENTILATOR

RE RETURN/EXHAUST FAN

RTU ROOFTOP UNIT

SEP SEWAGE EJECTOR PUMP

SF SUPPLY FAN

SP SUMP PUMP

UH UNIT HEATER

WH WATER HEATER

EQUIPMENT ABBREVIATIONS

SD-5

TYPE (SEE SCHEDULE)

SD-1

VAV-XX

VAV BOX

DATA DEVICE TAGS

DAMPER TAGS

VAV-XX

RTU-XX

EQUIPMENT ID

SYMBOL

MANUAL BALANCING DAMPER

BACKDRAFT DAMPER

COMBINATION FIRE/SMOKE

DAMPER

FIRE DAMPER

SMOKE DAMPER

MOTORIZED DAMPER

SENSOR

MANUAL SWITCH

THERMOSTAT

TEMPERATURE SENSOR

TEMPERATURE & HUMIDITY SENSOR

HUMIDITY SENSOR

NITROGEN DIOXIDE SENSOR

CARBON MONOXIDE SENSOR

CARBON DIOXIDE SENSOR

HUMIDISTAT

3-CONE DIFFUSER

ROUND DIFFUSER WITH

ADJUSTABLE PATTERNS

EGGCRATE RETURN/EXHAUST

GRILLE

POINT DISCONNECTION FROM EXISTING HWR

HWS

HEATING HOT WATER RETURN (PERIMETER)

HEATING HOT WATER SUPPLY (PERIMETER)

HEATING HOT WATER RETURN (REHEAT)

HEATING HOT WATER SUPPLY (REHEAT)

EG-2

SIMPLIFIED D/R/G TAG

AIRFLOW

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseArchitect/Engineer of Record StampConsultant

321 4 5 6 7 8 9 10

Sprinkler Status

B

IM

/1

F t.

W a y n e V

A M

C B a s e m e n t B ld g

/1

M

E P

C e n tr a l

.r v t

/1

/2

:5

:5

P

M

H001

HVAC SYMBOLS, ABBREVIATIONS, AND

GENERAL NOTESAE Works

209 SANDUSKY STREET

PITTSBURGH, PA 15212

412-287-7333

RENOVATE BASEMENT,

BUILDING 1

2121 LAKE AVE, FORT WAYNE, IN 46805

610A4-19-104

07/15/2020 MJC AC

BID DOCUMENTS

HVAC GENERAL NOTES

39 PROVIDE MANUFACTURER'S MATCHING ROOF CURBS FOR ALL ROOF MOUNTING EQUIPMENT.

COORDINATE ACTUAL ROOF PITCH AND CONSTRUCTION DETAILS WITH GENERAL

CONTRACTOR. PROVIDE SLOPED CURBS PER MANUFACTURER'S RECOMMENDATIONS.

GENERAL CONTRACTOR SHALL INSTALL ROOF CURBS AND FLASHING PER ROOFING

MANUFACTURER'S INSTALLATION REQUIREMENTS.

40 UNLESS OTHERWISE NOTED, ALL PIPING AND DUCTWORK IF OVERHEAD, TIGHT TO UNDERSIDE

OF STRUCTURE OR SLAB, WITH SPACE FOR INSULATION.

41 PROVIDE CHAINWHEEL OPERATORS FOR ALL EXPOSED VALVES MOUNTED GREATER THAN

8-FT, 0-IN ABOVE FINISHED FLOOR LEVEL. CHAIN SHALL EXTEND UNOBSTRUCTED TO 7-FT, 0-IN

ABOVE FLOOR LEVEL.

42 ALL PIPING AND DUCTWORK SHALL CLEAR DOORS, WINDOWS, EQUIPMENT CLEARANCES,

MAINTENANCE REQUIREMENTS, CODE SETBACKS, ETC. TO ASSURE PROPER OPERATION,

INSPECTION AND MAINTENANCE.

43 ALL VALVES SHALL BE ADJUSTED FOR SMOOTH AND EASY OPERATION.

44 PROVIDE ALL 90 DEGREE SQUARE ELBOWS WITH DOUBLE RADIUS TURNING VANES UNLESS

OTHERWISE INDICATED OR SPECIFIED. PROVIDE ACCESS DOORS UPSTREAM OF ALL ELBOWS

CONTAINING TURNING VANES.

45 ALL DUCTS SHALL BE BONDED ACROSS FLEXIBLE CONNECTIONS WITH FLEXIBLE COPPER

GROUNDING STRAPS. GROUNDING STRAPS SHALL BE BOLTED OR SOLDERED TO BOTH THE

EQUIPMENT AND THE DUCT.

46 ALL EQUIPMENT SUBMITTALS AND SHOP DRAWINGS REQUIRED BY THE SPECIFICATIONS SHALL

BE APPROVED BY THE ENGINEER PRIOR TO PURCHASE, FABRICATION AND INSTALLATION.

47 ALL HEATING DEVICES AND SURFACES WITH ELEVATED TEMPERATURES WHICH CAN BE

ACCESSED OR COME IN CONTACT WITH OWNER PERSONNEL SHALL BE PROTECTED,

INSULATED, OR CONTROLLED TO REMAIN BELOW 120º F.

48 PROVIDE MANUAL VOLUME DAMPERS IN ALL RUN-OUTS TO DIFFUSERS, BRANCH TAKE-OFFS

FROM MAIN SUPPLY DUCT, AND IN ALL OTHER AREAS REQUIRED TO PROVIDE PROPER SYSTEM

AIRFLOW BALANCING.

HVAC GENERAL NOTES

1 NOT ALL SYMBOLS ARE NECESSARILY USED.

2 COORDINATE FINAL LOCATIONS OF DIFFUSERS AND GRILLES WITH ARCHITECTURAL

REFLECTED CEILING PLANS.

3 CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK ARE DIAGRAMMATIC AND ARE

INTENDED TO CONVEY SCOPE AND GENERAL ARRANGEMENT ONLY. CONTRACTOR TO FIELD

VERIFY DUCT AND PIPE ROUTING AND COORDINATE INTERFERENCE BETWEEN TRADES PRIOR

TO INSTALLATION. CONTRACTOR SHALL BE RESPONSIBLE TO FIELD SURVEY ACTUAL SITE

CONDITIONS AND ACCOMODATE ACTUAL SITE CONDITIONS AS PART OF SCOPE OF WORK AT

NO COST TO OWNER.

4 ROOF OPENINGS, FLASHING, AND COUNTER FLASHING BY GENERAL CONTRACTOR. LOCATION

OF OPENINGS BY HEATING CONTRACTOR.ROOF OPENINGS, FLASHING, AND COUNTER

FLASHING BY GENERAL CONTRACTOR. LOCATION OF OPENINGS BY HEATING CONTRACTOR.

5 DUCTWORK TO BE INSTALLED TIGHT TO UNDERSIDE OF STRUCTURE ABOVE UNLESS NOTED

OTHERWISE.

6 PROVIDE ALL MATERIALS, EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL

COMPLETE AND OPERABLE MECHANICAL SYSTEMS AS INDICATED ON THE DRAWINGS, AS

SPECIFIED AND AS REQUIRED BY CODE.

7 INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN ACCORDANCE WITH

MANUFACTURER'S RECOMMENDATIONS, CONTRACT DOCUMENTS, APPLICABLE BUILDING,

STATE AND LOCAL CODES, SEISMIC REQUIREMENTS, ENERGY CODES AND INSURANCE

UNDERWRITER REQUIREMENTS.

8 COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH ARCHITECTURAL,

STRUCTURAL, CIVIL AND ELECTRICAL WORK, ETC. SHOWN ON OTHER CONTRACT DOCUMENT

DRAWINGS.

9 MAINTAIN A MINIMUM OF 6-FT, 8-IN CLEARANCE TO UNDERSIDE OF PIPES, DUCTS, CONDUITS, SUSPENDED EQUIPMENT, SUPPORTS, ETC., THROUGHOUT ACCESS ROUTES IN MECHANICAL

ROOMS.

10 ALL TESTS SHALL BE COMPLETED AND ACCEPTED BY THE INSPECTOR AND COR BEFORE ANY

MECHANICAL EQUIPMENT OR PIPING INSULATION IS APPLIED.

12 LOCATE ALL TEMPERATURE, PRESSURE AND FLOW MEASURING DEVICES IN ACCESSIBLE

LOCATIONS WITH STRAIGHT SECTION OF PIPE OR DUCT UPSTREAM AND DOWNSTREAM, AS

RECOMMENDED BY THE MANUFACTURER FOR ACCURACY.

13 TESTING ADJUSTING AND BALANCING (TAB) AGENCY SHALL BE A MEMBER OF THE ASSOCIATED

AIR BALANCING COUNCIL (AABC) OR THE NATIONAL ENVIRONMENTAL BALANCING BUREAU

(NEBB). TAB FIRM SHALL HAVE A MINIMUM OF 5 YEARS EXPERIENCE ON SIMILAR PROJECTS.

PERFORM TAB IN ACCORDANCE WITH THE REQUIREMENTS OF THE TAB PROCEDURAL

STANDARD RECOMMENDED BY THE TAB TRADE ASSOCIATION THAT APPROVED THE TAB FIRM'S

QUALIFICATIONS.

14 WHERE TWO OR MORE ITEMS OF THE SAME TYPE OF EQUIPMENT ARE REQUIRED, THE

PRODUCTS OF A SINGLE MANUFACTURER SHALL BE USED.

15 COORDINATE ALL FINAL EQUIPMENT CONNECTIONS WITH THE MANUFACTURERS' CERTIFIED

DRAWINGS. COORDINATE AND PROVIDE ALL DUCTWORK AND PIPING TRANSITIONS REQUIRED

FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT. FIELD VERIFY AND

COORDINATE ALL DUCTWORK AND PIPING DIMENSIONS BEFORE FABRICATION.

16 ALL CONTROL WIRE AND CONDUIT SHALL COMPLY WITH THE NATIONAL ELECTRIC CODE,

DIVISION 26 OF THE SPECIFICATIONS, ALL LOCAL CODES, AND OWNER'S INSURANCE

UNDERWRITER REQUIREMENTS.

17 THE LOCATIONS AND SIZES OF ALL ITEMS SHOWN ON THE DRAWINGS OR CALLED FOR IN THE

SPECIFICATIONS THAT ARE NOT DEFINITELY FIXED BY DIMENSIONS ARE APPROXIMATE ONLY.

THE EXACT LOCATIONS AND SIZES NECESSARY TO SECURE THE BEST CONDITIONS AND

RESULTS SHALL BE DETERMINED BY THE PROJECT SITE CONDITIONS AND SHALL HAVE THE

APPROVAL OF THE ENGINEER BEFORE BEING INSTALLED. DO NOT SCALE DRAWINGS.

18 PLAN DRAWINGS AND SECTIONS CUTS WHICH SPECIFICALLY IDENTIFY SERVICE ROUTE

OFFSETS, ELEVATION CHANGES, OBSTRUCTIONS, ACCESS DOORS, BALANCING DEVICES, ETC.

ARE SHOWN FOR CLARITY WHERE SPECIFIC KNOWN CONDITIONS EXIST. MECHANICAL

CONTRACTOR SHALL COORDINATE EQUIPMENT, DUCTWORK, AND PIPING ROUTINGS WITH ALL

OTHER TRADES. REQUIREMENTS NOT SPECIFICALLY IDENTIFIED SHALL NOT BE INTERPRETED

AS EXCLUSION FROM CONTRACTOR'S SCOPE OF WORK. CONTRACTOR SHALL BE RESPONSIBLE

FOR ACTUAL SITE CONDITIONS AND SHALL INCLUDE SUCH CONDITIONS IN SCOPE OF WORK AT

NO ADDITIONAL COST TO THE OWNER.

19 ALL MISCELLANEOUS STEEL REQUIRED TO ENSURE PROPER INSTALLATION AND SUPPORT OF

MECHANICAL WORK AS SHOWN IN DETAILS FOR PIPING, DUCTWORK AND EQUIPMENT (UNLESS

OTHERWISE NOTED) SHALL BE FURNISHED AND INSTALLED BY THE MECHANICAL CONTRACTOR

AT NO ADDITIONAL COST TO THE OWNER.

20 ALL EQUIPMENT, PIPING, DUCTWORK, ETC., SHALL BE SUPPORTED AS DETAILED, SPECIFIED

AND AS REQUIRED TO PROVIDE A VIBRATION FREE INSTALLATION.

21 ALL OPENINGS IN FIRE RATED WALLS AND SMOKE PARTITIONS DUE TO DUCTWORK, PIPING, CONDUIT, ETC., SHALL BE FIRE STOPPED WITH APPROVED FIRESTOPPING MATERIALS.

22 REFER TO TYPICAL DETAILS FOR DUCTWORK, PIPING AND EQUIPMENT INSTALLATION.

23 UNLESS OTHERWISE SHOWN, LOCATE ALL ROOM THERMOSTATS WITH TOP AT 48-IN ABOVE

FINISHED FLOOR IN ACCORDANCE WITH ADA REQUIREMENTS. NOTIFY THE ENGINEER OF ANY

ROOMS WHERE THE ABOVE LOCATION CAN NOT BE MAINTAINED OR WHERE THERE IS A

QUESTION ON LOCATION. COORDINATE FINAL LOCATIONS WITH OWNER.

24 LOCATE ALL MECHANICAL EQUIPMENT (VAV BOXES, CABINET HEATERS, UNIT HEATERS, ETC.,)

FOR UNOBSTRUCTED ACCESS TO UNIT ACCESS PANELS, FILTERS, CONTROLS AND VALVING.

DO NOT LOCATE FAN POWERED VAV BOXES ABOVE LIGHTING FIXTURES.

25 PROVIDE FLEXIBLE CONNECTIONS IN ALL DUCTWORK SYSTEMS (SUPPLY, RETURN AND

EXHAUST) CONNECTED TO FANS AND OTHER EQUIPMENT WHICH REQUIRE VIBRATION

ISOLATION. FLEXIBLE CONNECTIONS SHALL BE PROVIDED AT THE POINT OF CONNECTION TO

THE EQUIPMENT UNLESS OTHERWISE INDICATED.

26 ALL LOUVERS SHALL BE FURNISHED AND INSTALLED BY THE GENERAL CONTRACTOR (UNLESS

OTHERWISE NOTED). GENERAL CONTRACTOR SHALL COORDINATE SIZES, LOCATIONS, AND

CONNECTIONS WITH MECHANICAL CONTRACTOR. DUCTWORK CONNECTIONS TO LOUVERS

SHALL BE FURNISHED AND INSTALLED BY MECHANICAL CONTRACTOR.

27 PROVIDE AN AIR VENT AT THE HIGH POINT OF EACH DROP IN HYDRONIC WATER PIPING

SYSTEMS. ALL PIPING SHALL SLOPE TO LOW POINTS. PROVIDE HOSE END DRAIN VALVES AT

THE BOTTOM OF ALL RISERS AND LOW POINTS.

28 INSTALL PIPING SO THAT ALL VALVES, STRAINERS, UNIONS, TRAPS, FLANGES AND OTHER

APPURTENANCES REQUIRING ACCESS ARE ACCESSIBLE.

29 ALL ISOLATION VALVES SHALL BE IN LOCATION AND ELEVATION WHICH ALLOWS FOR

EQUIPMENT AND BRANCH PIPING REMOVAL, WHILE MAINTAINING SERVICE UPSTREAM OF THE

ISOLATION VALVE.

30 ALL BALANCING VALVES AND ISOLATION VALVES USED TO ADJUST FLOW RATES SHALL BE

PROVIDED WITH POSITIONS INDICATORS AND MAXIMUM ADJUSTABLE STOPS (MEMORY STOPS).

31 ALL…

This is the start of the file's text. The full file is on GovTribe.