This is a solicitation for a renovation project at the VA Northern Indiana Health Care System campus in Fort Wayne, Indiana. The scope of work involves renovating space in the basement to modernize areas for Environmental Management Services, Biomedical Services, Pharmacy, Mailroom, Engineering Services, Office of Information Technology, Graduate Medical Education, and Medical Imaging. The project will be conducted in three phases over approximately 780 days to allow the hospital to maintain operations. Phase I will address rooms 15-26 and 45, 45A, and 45B over 300 days. Phase II will cover rooms 49A-59A and the east basement corridor in 210 days. Phase III will involve rooms 30-35 and 43, 44, and 44A and the west basement corridor over 270 days. The contractor will provide all labor, equipment, materials, and supervision to complete the renovations per the design and specifications while following OSHA guidelines for hazardous materials abatement.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
S
T
ABBREVIATIONS
CONNECT TO EXISTING
FDC FIRE DEPARTMENT CONNECTION PIPING
ZONE FIFINGFZ#
SP SPRINKLER PIPING
DRY SYSTEM PIPINGDP
SLOPED CHANGE IN FIFE ELEVATION
ARROW INDICATES DIRECTION OF FLOW
FIRE HOSE VALVE CABINET
SPRINKLER FLOOR CONTROL VALVE ASSEMBLY
PITCH FIFE DOWN IN DIRECTION OF ARROW
ROOF MANIFOLD 3 WAY
WALL MOUNTED FIRE DEPARTMENT SIAMESE CONNECTION
FREE STANDING FIRE DEPARTMENT SIAMESE CONNECTION
NEW FIRE HYDRANT
EXISTING FIRE HYDRANT
TAMPER SWITCH
SMOKE DETECTOR ABOVE THE FLOOR
SIGHT GLASS
WATER FLOW SWITCH
# # HYDRAULIC REF. POINTS # ELEMENT # NODE
FSP FIRE STANDPIPE
INCOMING FIRE SERVICE/ MAIN/ BLDG. WET PIPINGF
SPRINKLER PIPING STREET PRESSURESPST
FIRE DEPT. HOSE VALVE WITH CAP AND CHAIN
HOSE BIBB
FLEXIBLE CONNECTION
BALL VALVE
GLOBE VALVE
MIXING VALVE
RELIEF VALVE
PLUG VALVE
BPA BACKFLOW PREVENTER ASSEMBLY
FLOAT VALVE
CHECK VALVE WITH A.B.D.
OS&Y OUTSIDE SCREW & YOKE VALVE
PRESSURE REDUCING VALVE FP.R.V.
SOLENOID VALVE
CHECK VALVE
GATE VALVE
VALVE IN VERTICAL
ELBOW TURNED UP / CONN. TO VERTICAL LINE
ELBOW TURNED DOWN
TOP PIPE CONNECTION
BOTTOM PIPE CONNECTION
THERMOMETER
PRESSURE GAUGE AND COCK
SLEEVE
WATER PROOF SLEEVE
ECCENTRIC REDUCER E.R.
REDUCER
UNION
RISER NUMBER
RISER SERVICE
DRAWING #
DETAIL #DETAIL DESIGNATION
RISER DESIGNATION
DWG. DRAWING
RHW RAIN HARVESTED WATER
L
AUTOMATIC BALL DRIPA.B.D.
PITCH PER FOOTPPF
INVERT ELEVATIONINV. EL.
CENTER LINEC
UP (PENETRATES FLOOR SLAB)UP
UNLESS OTHERWISE NOTEDUON
TYPICALTYP.
SQUARE FOOT
POUNDS PER SQUARE INCHPSI
OUTSIDE SCREW & YOKE GATE VALVEOS&Y
OUTSIDE DIAMETEROD
NOT TO SCALENTS
NORMALLY OPENNO
NOT IN THIS CONTRACTN.I.C.
NORMALLY CLOSEDNC
MINIMUMMIN.
MAXIMUMMAX.
INCHIN
INSIDE DIAMETERID
HUNG CEILINGHC
GALLONSGAL.
GALLONS PER MINUTEGPM
GENERAL CONTRACTORGC
FEETFT.
FLOORFLR.
ELEVATIONEL.
DRAINDR
DOWN (PENETRATES FLOOR SLAB)DN.
DIAMETERDIA
CONTINUATIONCONT.
CONNECTCONN
CEILINGCLG.
BOTTOM OF PIPEBOP
BUILDINGBLDG.
ABOVE FINISHED FLOORA.F.F.
CA COMPRESSED AIR
ELEVATORELEV.
EXISTING PIPING TO REMAIN
EXISTING PIPING TO BE REMOVED
DISCONNECT
POINT OF NEW CONNECTION TO EXISTING WORK
POINT OF DISCONNECTION
SQ.FT.
S
FIRE PROTECTION
LEGEND
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
WSP USA Buildings Inc.
One Penn Plaza, 2nd Floor New York, NY 10019
(212) 465-5000 www.wsp.com
BI
M
5_
Ft . W ay ne
V
AM
C B as em en t B ld g
1/
5_
W
SP
_P
LB
G
IT
_C en tra l 2
8.
rv t
7/
/2
4:
:5
PM
FP001
FIRE PROTECTION SYMBOLS AND
ABBREVIATIONSAE Works
209 SANDUSKY STREET
PITTSBURGH, PA 15212
412-287-7333 AEW Project No. 18025
RENOVATE BASEMENT,
BUILDING 1
2121 LAKE AVE, FORT WAYNE, IN 46805
610A4-19-104
07/15/2020 EG RR
BID DOCUMENTS
# Revisions Date
NOTE:
DEMOLISH ALL EXISTING SPRINKLER HEADS AND
ASSOCIATED BRANCH PIPING BACK TO EXISTING SPRINKLER
MAINS IN AREAS IN SCOPE OF WORK. PROVIDE FIRE WATCH
FOR ALL AFFECTED AREAS THAT WILL NOT BE ACTIVELY
COVERED DURING CONSTRUCTION.
E
F
G
H
C
B
A
2221201918A1615
I
J
131210876543A321
19A
22A
9 11 13A
D
18 20B17A 17B
EXISTING FHV TO
REMAIN (TYP.)
EXISTING FHV TO
REMAIN (TYP.)
1. THE DEMOLISH DRAWING SHOW THE APPROXIMATE
LOCATION OF THE EXISTING FIRE PROTECTION HEADS &
PIPINGS. THESE FIRE PROTECTION DRAWINGS HAVE BEEN
ISENTIFIED AND LOCATED AS ACCURATELY AS POSSIBLE
USING AVAILABLE RECORDS INFORMATION. THE CONTRACTOR
IS RESPONSIBLE FOR THE VERIFYING ALL EXISTING ACTUAL
LOCATIONS.
2. ALL PIPING AND HEADS REMOVAL SHALL INCLUDE REMOVAL
OF ALL APPURTENANCE CONTAINED THEREIN SUCH AS HANGER,
SUPPORTS & VALVES, ETC., COMLETE CAPS SHALL BE INSTALLED
AT ALL OPEN ENDS OF PIPING TO REMAIN AS REQUIRED.
2. REMOVE EXISTING HEADS AND BRANCH PIPING AS INDICATED
ON DRAWINGS. ANY DISCREPANCIES SHALL BE BROUGHT TO
ATTENTION OF ARCHITECT AND ENGINEER.
GENERAL NOTES:
MECH OFFICE
STORAGE
44A
MENS LOCKER RM
45A
LOGISTICS
LOGISTICS
25A
CRASH CARTS
LOGISTICS
MEDICAL SURGICAL
FIRE ALARM
WORK ROOM
MEN/WOMEN
SHWOER
18 TOILET
VESTIBULE
OFFICE
22A
DECONTAMINATION
AREA
MECHANICAL OFFICE
MECH OFFICE
MECH OFFICE
44A
ENGINEERING
42A
MENS
WOMENS
ENG. CLO.
EMS STORAGE
OFFICE
STORAGE
30D
EMS
EMS OFFICE
30A
CLEAN LINEN
STORAGE
30B
EMS OFFICE
30C
MECH (NIC)
B112
PHARMACY (NIC)
B117
STAIR 2 (NIC)
S2
ENGINEERING (NIC)
B105
ENGINEERING (NIC)
B106
SOILED (NIC)
B107
HVAC (NIC)
B108
FIRE PUMP ROOM
(NIC)
B109
BIOMED FILE ROOM
(NIC)
B110
FILE CLO. (NIC)
028a
WEST (BW) EAST (BE)
BASEMENT
GENERAL AREA OF
WORK (REFER TO
PLAN FOR DETALS)
BASEMENT
AREA OF FUTURE WORK
(NOT IN CONTRACT) NOT IN CONTRACT
NO
T
IN
C
ON
TR
AC
T
MA
TC
H
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
WSP USA Buildings Inc.
One Penn Plaza, 2nd Floor New York, NY 10019
(212) 465-5000 www.wsp.com
BI
M
5_
Ft . W ay ne
V
AM
C B as em en t B ld g
1/
5_
W
SP
_P
LB
G
IT
_C en tra l 2
8.
rv t
7/
/2
4:
:1
PM
FPD100W
FIRE PROTECTION DEMOLITION PLAN -
BASEMENT WESTAE Works
209 SANDUSKY STREET
PITTSBURGH, PA 15212
412-287-7333 AEW Project No. 18025
RENOVATE BASEMENT,
BUILDING 1
2121 LAKE AVE, FORT WAYNE, IN 46805
610A4-19-104
07/15/2020 EG RR
BID DOCUMENTS
8' 16'4'0
1/8" = 1'-0"1 BASEMENT - FIRE PROTECTION DEMO CEILING PLAN WEST
NORTH
TRUE NORTH=
PROJECT
88.50°
NOTE:
DEMOLISH ALL EXISTING SPRINKLER HEADS AND ASSOCIATED
BRANCH PIPING BACK TO EXISTING SPRINKLER MAINS IN
AREAS IN SCOPE OF WORK. PROVIDE FIRE WATCH FOR ALL
AFFECTED AREAS THAT WILL NOT BE ACTIVELY COVERED
DURING CONSTRUCTION.
E
F
G
H
C
3635343332312927252423 33A302826
B
A
22212019
I
J
19A
22A
D
20B
30A
EXISTING FHV TO REMAIN
EXISTING FCVA
TO REMAIN EXISTING 4" SPRINKLER MAIN TO REMAIN
1. THE DEMOLITION DRAWING SHOW THE APPROXIMATE
LOCATION OF THE EXISTING FIRE PROTECTION HEADS &
PIPINGS. THESE FIRE PROTECTION DRAWINGS HAVE BEEN
IDENTIFIED AND LOCATED AS ACCURATELY AS POSSIBLE
USING AVAILABLE RECORDS INFORMATION. THE CONTRACTOR
IS RESPONSIBLE FOR THE VERIFYING ALL EXISTING ACTUAL
LOCATIONS.
2. ALL PIPING AND HEADS REMOVAL SHALL INCLUDE REMOVAL
OF ALL APPURTENANCE CONTAINED THEREIN SUCH AS HANGER,
SUPPORTS & VALVES, ETC., COMPLETE CAPS SHALL BE INSTALLED
AT ALL OPEN ENDS OF PIPING TO REMAIN AS REQUIRED.
3. REMOVE EXISTING HEADS AND BRANCH PIPING AS INDICATED
ON DRAWINGS. ANY DISCREPANCIES SHALL BE BROUGHT TO
ATTENTION OF ARCHITECT AND ENGINEER.
GENERAL NOTES:
PHARMACY STORAGE
TOILET
ROOM
53B
OIT (NIC)
53A
STAIR
STOR (NIC)
VAC STOR (NIC)
BIOMED
ENGINEERING
CORRIDOR (NIC)
B-C-C2
OIT SERVER ROOM
MATERIAL MGMT.
SECTION
MAILROOM
49A
WOMEN'S LOCKER
RM
CORRIDOR
C4
STAIR
WATER TREATMENT
(NIC)
NEW SPS ADDITION
(NIC)
ENGINEERING (NIC)
SOILED
SOILED
MENS LOCKER RM
MECH OFFICE
STORAGE
44A
MORGUE
MENS LOCKER RM
45A
MENS LOCKER RM
45B
DECONTAMINATION
AREA
MECH OFFICE
MECH OFFICE
44A
WEST (BW) EAST (BE)
BASEMENT
GENERAL AREA OF
WORK (REFER TO
PLAN FOR DETALS)
BASEMENT
AREA OF FUTURE WORK
(NOT IN CONTRACT) NOT IN CONTRACT
NO
T
IN
C
ON
TR
AC
T
MA
TC
H
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
WSP USA Buildings Inc.
One Penn Plaza, 2nd Floor New York, NY 10019
(212) 465-5000 www.wsp.com
BI
M
5_
Ft . W ay ne
V
AM
C B as em en t B ld g
1/
5_
W
SP
_P
LB
G
IT
_C en tra l 2
8.
rv t
7/
/2
4:
:0
PM
FPD100E
FIRE PROTECTION DEMOLITION PLAN -
BASEMENT EASTAE Works
209 SANDUSKY STREET
PITTSBURGH, PA 15212
412-287-7333 AEW Project No. 18025
RENOVATE BASEMENT,
BUILDING 1
2121 LAKE AVE, FORT WAYNE, IN 46805
610A4-19-104
07/15/2020 EG RR
BID DOCUMENTS
8' 16'4'0
1/8" = 1'-0"1 BASEMENT - FIRE PROTECTION DEMO CEILING PLAN EAST
NORTH
TRUE NORTH=
PROJECT
EXISTING SPRINKLER
MAIN TO REMAIN (TYP.)
MA
TC
H
LI
NE
MA
TC
H
LI
NE
E
F
G
H
C
B
A
2221201918A1615
I
J
131210876543A321
19A
22A
9 11 13A
D
18 20B17A 17B
EXISTING FHV TO
REMAIN (TYP.)
EXISTING FHV TO
REMAIN (TYP.)
SPRINKLERS IN SHADED N.I.C. AREA TO
REMAIN.
NEW SPRINKLER HEADS LOCATIONS SHOWN.
CONTRACTOR TO MODIFY, ADD, RELOCATE
HEADS AND PIPING AS REQUIRED TO PROVIDE
CODE COMPLIANT COVERAGE. COORDINATE
WORK WITH ARCHITECTURAL, MECHANICAL &
ELECTRICAL DWGS. IF THERE IS A CONFLICT
BETWEEN THE LOCATION OF A LIGHTING
FIXTURES & MECHANICAL, CONTRACTOR
SHALL NOTIFY ARCHITECT AND ENGINEER
PRIOR TO MAKING ANY LOCATION
ADJUSTMENTS.
ALL NEW SPRINKLER HEADS LAYOUT SPACING
AND LOCATIONS SHALL BE IN ACCORDANCE
WITH NFPA 13 AND LOCAL BUILDING CODE.
GENERAL NOTES:
1.
2.
3.
X-RAY
B120E
TLT / CHANGING
B120F
CLEAN
B120G
CT SCANNING
B120D
STORAGE
B118
RECEPTION / WORK
B120A
WAITING
B119
SOILED HOLDING
B120C
WOMENS
B113
MENS
B114
CORRIDOR
C06
PHARMACY CACHE
B111
MECHANICAL OFFICE
B101
EMS SUPPLY
B104
EMS OFFICE 2
B100A
EMS OFFICE 1
B100B
EMS SUITE
B100
MENS DRESSING
B100E
CLEAN LINEN ROOM
B100C
RADIOLOGY
B120
CLOSET
B120B
GME LIBRARY
B116
RES. SLEEPING
ROOM
B115
RESIDENT TLT RM
B115A
CORRIDOR
C05
CORRIDOR
C04
EMS STORAGE
B103
CORRIDOR
C02
MECH
B102B
WOMENS DRESSING
B100D
HAC (NIC)
063A
DOCK (NIC)NUTRITION AND
FOOD SERVICES (NIC)
ENGINEERING (NIC)
033A
ENGINEERING (NIC)
B105
ENGINEERING (NIC)
B106
FIRE PUMP ROOM
(NIC)
B109
SOILED (NIC)
B107
HVAC (NIC)
B108
PHARMACY (NIC)
B117
WEST (BW) EAST (BE)
BASEMENT
GENERAL AREA OF
WORK (REFER TO
PLAN FOR DETALS)
BASEMENT
AREA OF FUTURE WORK
(NOT IN CONTRACT) NOT IN CONTRACT
NO
T
IN
C
ON
TR
AC
T
MA
TC
H
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
WSP USA Buildings Inc.
One Penn Plaza, 2nd Floor New York, NY 10019
(212) 465-5000 www.wsp.com
BI
M
5_
Ft . W ay ne
V
AM
C B as em en t B ld g
1/
5_
W
SP
_P
LB
G
IT
_C en tra l 2
8.
rv t
7/
/2
4:
:0
PM
FP100W
FIRE PROTECTION PLAN - BASEMENT WEST
AE Works
209 SANDUSKY STREET
PITTSBURGH, PA 15212
412-287-7333 AEW Project No. 18025
RENOVATE BASEMENT,
BUILDING 1
2121 LAKE AVE, FORT WAYNE, IN 46805
610A4-19-104
07/15/2020 EG RR
BID DOCUMENTS
0 1' 2'6"
1/8" = 1'-0"FP100W
1 BASEMENT - FIRE PROTECTION NEW CEILING PLAN WEST
NORTH
TRUE NORTH=
PROJECT
E
F
G
H
C
3635343332312927252423 33A302826
B
A
2221201918A
I
J
19A
22A
D
18 20B
30A
17A 17B
EXISTING FHV TO REMAIN
EXISTING FCVA
TO REMAIN EXISTING 4" SPRINKLER MAIN TO REMAIN
MA
TC
H
LI
NE
SPRINKLERS IN SHADED N.I.C. AREA TO
REMAIN.
NEW SPRINKLER HEADS LOCATIONS SHOWN.
CONTRACTOR TO MODIFY, ADD, RELOCATE
HEADS AND PIPING AS REQUIRED TO PROVIDE
CODE COMPLIANT COVERAGE. COORDINATE
WORK WITH ARCHITECTURAL, MECHANICAL &
ELECTRICAL DWGS. IF THERE IS A CONFLICT
BETWEEN THE LOCATION OF A LIGHTING
FIXTURES & MECHANICAL, CONTRACTOR
SHALL NOTIFY ARCHITECT AND ENGINEER
PRIOR TO MAKING ANY LOCATION
ADJUSTMENTS.
ALL NEW SPRINKLER HEADS LAYOUT SPACING
AND LOCATIONS SHALL BE IN ACCORDANCE
WITH NFPA 13 AND LOCAL BUILDING CODE.
GENERAL NOTES:
ISOLATION VALVE, WATER FLOW & TAMPER SWITCH
1.
2.
MA
TC
H
LI
NE
3.
MECHANICAL OFFICE
B101
MAILROOM
B300
EMS SUITE
B100
MENS DRESSING
B100E
MECH ROOM 1
B308
BIOMED STORAGE
B310
STORAGE
B316D
WORKSHOP
B316C
OFFICE
B316B
BIOMED
B316
OIT SERVER
B311
OIT OFFICE
B309
EMS STORAGE
B103
STOR / SOILED LINEN
CART
B306 BATTERY ROOM
B307
STORAGE
B316A
ENGINEERING
STORAGE
B312
MECH
B102B
CORRIDOR
C07
WOMENS DRESSING
B100D
VESTIBULE (NIC)
STAIR 4 (NIC)
S4
OIT (NIC)
053A
ENGINEERING (NIC)
B304
PUMP ROOM (NIC)
ENGINEERING (NIC)
B305
STAIR 3 (NIC)
S3
SPS ADDITION (NIC)
42B
HAC (NIC)
B302
SOILED (NIC)
B303
MORGUE (NIC)
HAC (NIC)
063A
DOCK (NIC)NUTRITION AND
FOOD SERVICES (NIC)
EXISTING SPR PROTECTION TO REMAIN
WEST (BW) EAST (BE)
BASEMENT
GENERAL AREA OF
WORK (REFER TO
PLAN FOR DETALS)
BASEMENT
AREA OF FUTURE WORK
(NOT IN CONTRACT) NOT IN CONTRACT
NO
T
IN
C
ON
TR
AC
T
MA
TC
H
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
WSP USA Buildings Inc.
One Penn Plaza, 2nd Floor New York, NY 10019
(212) 465-5000 www.wsp.com
BI
M
5_
Ft . W ay ne
V
AM
C B as em en t B ld g
1/
5_
W
SP
_P
LB
G
IT
_C en tra l 2
8.
rv t
7/
/2
4:
:5
PM
FP100E
FIRE PROTECTION PLAN - BASEMENT EAST
AE Works
209 SANDUSKY STREET
PITTSBURGH, PA 15212
412-287-7333 AEW Project No. 18025
RENOVATE BASEMENT,
BUILDING 1
2121 LAKE AVE, FORT WAYNE, IN 46805
610A4-19-104
07/15/2020 EG RR
BID DOCUMENTS
8' 16'4'0
1/8" = 1'-0"1 BASEMENT - FIRE PROTECTION NEW CEILING PLAN EAST
NORTH
TRUE NORTH=
PROJECT
CLEVIS HANGER ADJUSTABLE SWIVEL RING
2 27/ 32" D IA.
[72.2mm]
2 1/ 4" H OLE DIA.
[57.2mm]
1 15/ 16" D IA
[49.2mm]
1/ 8" [3.2mm]
PIPE AND INSULATION TO BE CENTERED
IN SLEEVE - DO NOT SUPPORT PIPE
FROM SLEEVE
SEALANT (SEE SPEC.)
TERMINATE SLEEVE FLUSH WITH
FINISHED WALL SURFACES
FINISHED WALL SURFACE
FINISHED ESCUTCHEON PLATE FLUSH
AGAINST WALL AND OF SIZE TO
COMPLETELY COVER OPENING
PIPE SLEEVE
4"
UPRIGHT HEAD
SPRINKLER BRANCH LINE
NOTES:
1. SPRINKLER CONTRACTOR SHALL
SPRINKLER ABOVE AND BELOW
DUCT OR OTHER OBSTRUCTION
OVER 48" IN WIDTH.
2. SPRINKLER CONTRACTOR SHALL
COORDINATE WITH THE HVAC
AND GENERAL CONTRACTOR.
DUCTWORK OR
OTHER OBSTRUCTION
OVER 48" IN WIDTH
UPRIGHT HEAD
GALVANIZED PROTECTION
SHIELD-18 GA.,12" LONG
WHEN PIPING IS INSULATED
LOCKNUTS
ELASTIC LOCKNUTS
THREADED ROD
(TYPICAL)
ELASTIC
THREADED ROD
DROP IN ANCHOR
BRANCH PIPE
1" DROP NIPPLE
1" x 1/2" COUPLING
(IF REQUIRED)
SUSPENDED CEILINGSPRINKLER HEAD
(SEE SPECIFICATION
& DWG FOR TYPE)
NEW SUSPENDED CEILING
EXISTING BRANCH TEE 1" OUTLET
SPRINKLER HANGER
1" EXTRA HEAVY NIPPLE
1" ELBOW
1 X 1/2 REDUCER
1 DROP NIPPLE
BRANCH LINE
NEW PARTIALLY RECESSED TYPE
SPRINKLER HEAD TO BE REMOVED
EXISTING SPRINKLER HEAD
PIPING TO NEW CEILING HEIGHT
ADJUST EXISTING SPRINKLER MAIN/BRANCH
NOTE:
ATTACH TO EXIST. BUILDING STRUCTURE USING
AN APPROVED METHOD OF SUPPORT (TYP.)
EXISTING ADJUSTABLE SPRINKLER
DROP TO BE REMOVED CAP PIPING
AS REQUIRED
WRENCH BOSS
TURN COLLAR
UNTIL TIGHT
AGAINST SPRINKLER
1" X 1/2" REDUCER
3/4"[19mm]
ADJUSTMENT
F1 ESCUTCHEON
1/2"[12.7mm]
ADJUSTMENT
F2 ESCUTCHEON
FACE OF FITTING
TO FACE OF CEILING DIMENSION
AT MAXIMUM RECESS = 1"[25.4mm] AT MINIMUM RECESS = 3/8"[9.5mm]
F1 ESCUTCHEON
AT MAXIMUM RECESS = 3/4"[19mm] AT MINIMUM RECESS = 3/8"[9.5mm]
F2 ESCUTCHEON
AT MAXIMUM RECESS = 7/8"[22.2mm] AT MINIMUM RECESS = 1-5/8"[41.3mm]
F1 ESCUTCHEON
AT MAXIMUM RECESS = 1-1/8"[28.6mm] AT MINIMUM RECESS = 1-5/8"[41.3mm]
F2 ESCUTCHEON
PIPE SLEEVE THRU INTERIOR WALL
N.T.S.
SPRINKLER HEAD CONNECTION
SPRINKLER DETAIL ABOVE AND
BELOW DUCT
HANGERS
SPRINKLER HEAD RELOCATION IN
SUSPENDED CEILING DETAIL
N.T.S. N.T.S. N.T.S.
N.T.S.
PARTIALLY RECESSED SPRINKLER
HEAD
N.T.S.
RESPONSE COVERAGE K FACTOR
MANUFACTURER & MODEL #
TYCOVIKING RELIABLE
TEMPERATURE(F°)
ORDINARY INTERMEDIATE HIGH
QUICK
RESPONSE
HAZARD FOR USE
LIGHT ORDINARY EXTRA DIMENSION
COVERAGE
MAX. SYMBOL
TYPE
5.6
5.6
5.6
STANDARD
(135~170) (175~225) (250~300)
N/AVK302 N/A
N/A
TY-FRB N/A
RF II
N/A
F1FR
F1FR
REMARK
(AREA APPLIED)
SPRINKLER HEAD SCHEDULE
UPRIGHT
RECESSED
MICROFAST
VK481 F1FRSIDEWALL
15FT X 15FT
15FT X 15FT
14FT X 14FT
PARTIALLY
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
WSP USA Buildings Inc.
One Penn Plaza, 2nd Floor New York, NY 10019
(212) 465-5000 www.wsp.com
BI
M
5_
Ft . W ay ne
V
AM
C B as em en t B ld g
1/
5_
W
SP
_P
LB
G
IT
_C en tra l 2
8.
rv t
7/
/2
4:
:0
PM
FP600
FIRE PROTECTION DETAILS AND SCHEDULE
AE Works
209 SANDUSKY STREET
PITTSBURGH, PA 15212
412-287-7333 AEW Project No. 18025
RENOVATE BASEMENT,
BUILDING 1
2121 LAKE AVE, FORT WAYNE, IN 46805
610A4-19-104
07/15/2020 EG RR
ST
PD
GW
AV
LW
LV
IW
EJ
SD
CL
M
A
(ST)
(ST)
PLUMBING LEGEND
ABBREVIATIONS
ABD AUTOMATIC BALL DRIP
AFF ABOVE FINISHED FLOOR
BLDG BUILDING
BOP BOTTOM OF PIPE
CO CLEANOUT
CODP CLEANOUT DECK PLATE
CV CHECK VALVE
CW COLD WATER
CLG CEILING
CONN CONNECT
CONT CONTINUATION
DIA DIAMETER
DN DOWN (PENETRATES FLOOR SLAB)
DR DRAIN
DWG DRAWING
ED EJECTOR DISCHARGE
EL ELEVATION
EWC ELECTRIC WATER COOLER
FAI FRESH AIR INLET
FD FLOOR DRAIN
FU FIXTURE UNIT
FL FLOOR
FT FEET
GC GENERAL CONTRACTOR
GD GARAGE DRAIN
GPM GALLONS PER MINUTE
GAL GALLONS
HB HOSE BIBB
H.CLG HUNG CEILING
HW HOT WATER
HWR HOT WATER RETURN
ID INSIDE DIAMETER
IW INDIRECT WASTE
IN INCH
LAV LAVATORY
MR MOP RECEPTOR
MAX MAXIMUM
MH MANHOLE
MIN MINIMUM
NC NORMALLY CLOSED
NIC NOT IN THIS CONTRACT
NO NORMALLY OPEN
NTS NOT TO SCALE
OD OUTSIDE DIAMETER
OS&Y OUTSIDE SCREW & YOKE GATE VALVE
PD PUMP DISCHARGE
PRV PRESSURE REDUCING VALVE
PSIA POUNDS PER SQUARE INCH (ABSOLUTE)
PSI POUNDS PER SQUARE INCH (GAUGE)
RT RUNNING TRAP
SA SHOCK ABSORBER
SPD SUMP PUMP DISCHARGE
SAN SANITARY
SQ FT SQUARE FOOT
TYP TYPICAL
ABBREVIATIONS (CONTINUED)
UON UNLESS OTHERWISE NOTED
UP UP (PENETRATES FLOOR SLAB)
UR URINAL
V VENT
VB VACUUM BREAKER
VTR VENT THROUGH ROOF
WC WATER CLOSET
WH WALL HYDRANT
LEGENDS
SANITARY PIPING
VENT PIPING (SANITARY)
STORM PIPING
PIPING BURIED (SERVICE NOTED)
PUMP DISCHARGE PIPING
GREASE WASTE PIPING
ACID VENT PIPING
LAB WASTE PIPING
LAB VENT PIPING
INDIRECT WASTE PIPING
EJECTOR DISCHARGE PIPING
SUMP DISCHARGE PIPING
DOMESTIC COLD WATER PIPING
DOMESTIC HOT WATER PIPING
DOMESTIC HOT WATER CIRCULATION PIPING
(Z-#) DOMESTIC COLD WATER ZONE PIPING
(Z-#) DOMESTIC HOT WATER ZONE PIPING
(Z-#) DOMESTIC HOT WATER CIRCULATION ZONE PIPING
DEIONIZED WATER PIPINGDE
DISTILLED WATER PIPINGDI
NON-POTABLE WATERNPW
GAS PIPINGG
COMPRESSED AIR PIPINGMA (MEDICAL)
COMPRESSED AIR PIPING (INDUSTRIAL)CA
IRRIGATION PIPINGIRR
VACUUM PIPINGV
NITROGEN PIPING2N
NITROUS OXIDE PIPINGNO
OXYGEN PIPINGO
HYDROGEN PIPINGH
SLOPED CHANGE IN PIPE ELEVATION
ARROW INDICATES DIRECTION OF FLOW
PITCH PIPE DOWN IN DIRECTION OF ARROW
INSULATED AND HEAT TRACED PIPING
POINT OF DISCONNECTION
SHOCK ABSORBER
LEGENDS (CONTINUED)
FLEXIBLE CONNECTION
EXPANSION LOOP SIZE( )X( ) LH
HOSE BIBB
WALL HYDRANT
FRESH AIR INLET
CLEAN-OUT / PLUG OUTLET
CLEAN-OUT DECK PLATE
"P" TRAP
RUNNING TRAP
DUPLEX STRAINER
BASKET STRAINER
Y STRAINER WITH BLOW OFF VALVE
VACUUM BREAKER
MANUAL AIR VENT
AUTOMATIC AIR VENT
BOTTOM PIPE CONNECTION
TOP PIPE CONNECTION
ELBOW TURNED DOWN
ELBOW TURNED UP / CONN. TO VERTICAL LINE
VALVE IN VERTICAL
VALVE (SEE SCHEDULE)
CHECK VALVE
SOLENOID VALVE
PRESSURE REDUCING VALVE (P.R.V.)
OS&Y (OUTSIDE SCREW & YOKE) VALVE
CHECK VALVE WITH A.B.D.
FLOAT VALVE
BACKFLOW PREVENTER ASSEMBLYBPA
RELIEF VALVE
MIXING VALVE
ANGLE RELIEF VALVE
UNION
REDUCER
ECCENTRIC REDUCER (E.R.)
WATER PROOF SLEEVE
SLEEVE
PRESSURE GAUGE AND COCK
THERMOMETER
OVERFLOW DRAIN
PUMP
METER
RISER DESIGNATION
DETAIL DESIGNATION DETAIL #
DRAWING #
CENTER LINE
AD AREA DRAIN
DRAIN
RISER SERVICE
RISER NUMBER
M
ELEVATOR SUMP PUMPESP
GASG
GW GARAGE WASTE
PLUMBING FIXTURE TYPE (SEE SPECIFICATION)P-?
STORMST
PRV STATIONPRV
S
S
CAP
ANCHOR
EXISTING PIPING TO REMAIN
EXISTING PIPING TO BE ABANDONED
EXISTING PIPING TO BE REMOVED
SLOP SINKSS
DOMESTIC COLD WATER (STREET PRESSURE)
DOMESTIC HOT WATER (STREET PRESSURE)
WAGD WASTE ANESTHESIA GAS DISPOSAL
POINT OF NEW CONNECTION TO EXISTING WORK
CONNECT TO EXISTING
DISCONNECT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
WSP USA Buildings Inc.
One Penn Plaza, 2nd Floor New York, NY 10019
(212) 465-5000 www.wsp.com
BI
M
5_
Ft . W ay ne
V
AM
C B as em en t B ld g
1/
5_
W
SP
_P
LB
G
IT
_C en tra l 2
8.
rv t
7/
/2
4:
:1
PM
P001
PLUMBING SYMBOLS AND ABBREVIATIONS
AE Works
209 SANDUSKY STREET
PITTSBURGH, PA 15212
412-287-7333 AEW Project No. 18025
RENOVATE BASEMENT,
BUILDING 1
2121 LAKE AVE, FORT WAYNE, IN 46805
610A4-19-104
07/15/2020 EG RR
E
F
G
H
C
B
A
201918A1615
I
J
131210876543A321
19A
9 11 13A
D
1817A 17B
LOGISTICS
LOGISTICS
25A
CRASH CARTS
LOGISTICS
MEDICAL SURGICAL
FIRE ALARM
WORK ROOM
MEN/WOMEN
SHWOER
18 TOILET
VESTIBULE
OFFICE
22A
DECONTAMINATION
AREA
MECHANICAL OFFICE
MECH OFFICE
MECH OFFICE
44A
ENGINEERING
42A
MENS
WOMENS
ENG. CLO.
EMS STORAGE
OFFICE
STORAGE
30D
EMS
EMS OFFICE
30A
CLEAN LINEN
STORAGE
30B
EMS OFFICE
30C
MECH (NIC)
B112
PHARMACY (NIC)
B117
STAIR 2 (NIC)
S2
ENGINEERING (NIC)
B105
ENGINEERING (NIC)
B106
SOILED (NIC)
B107
HVAC (NIC)
B108
FIRE PUMP ROOM
(NIC)
B109
BIOMED FILE ROOM
(NIC)
B110
FILE CLO. (NIC)
028a
WEST (BW) EAST (BE)
BASEMENT
GENERAL AREA OF
WORK (REFER TO
PLAN FOR DETALS)
BASEMENT
AREA OF FUTURE WORK
(NOT IN CONTRACT) NOT IN CONTRACT
NO
T
IN
C
ON
TR
AC
T
MA
TC
H
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
WSP USA Buildings Inc.
One Penn Plaza, 2nd Floor New York, NY 10019
(212) 465-5000 www.wsp.com
BI
M
5_
Ft . W ay ne
V
AM
C B as em en t B ld g
1/
5_
W
SP
_P
LB
G
IT
_C en tra l 2
8.
rv t
7/
/2
4:
:2
PM
PD100W
PLUMBING DEMOLITION PLAN - BASEMENT
WESTAE Works
209 SANDUSKY STREET
PITTSBURGH, PA 15212
412-287-7333 AEW Project No. 18025
RENOVATE BASEMENT,
BUILDING 1
2121 LAKE AVE, FORT WAYNE, IN 46805
610A4-19-104
07/15/2020 EG RR
BID DOCUMENTS
8' 16'4'0
1/8" = 1'-0"1 BASEMENT - PLUMBING DEMO FLOOR PLAN WEST
# KEYNOTES:
1. DEMOLISH EXISTING WATER CLOSET, LAVATORY SINK, SHOWER AND FLOOR
DRAIN. CUT EXISTING COLD WATER AND HOT WATER PIPE BACK TO NEAREST
ACTIVE MAIN AND PROVIDE SHUT OFF VALVES AS NEEDED. CUT AND CAP BOTH
SANITARY AND VENT PIPING BACK TO NEAREST ACTIVE MAIN.
2. DEMOLISH EXISTING WATER CLOSET, LAVATORY SINK AND FLOOR DRAIN. CUT
EXISTING COLD WATER AND HOT WATER PIPE BACK TO NEAREST ACTIVE MAIN
AND PROVIDE SHUT OFF VALVES AS NEEDED. CUT AND CAP BOTH SANITARY
AND VENT PIPING BACK TO NEAREST ACTIVE MAIN.
3. DEMOLISH EXISTING COLD WATER PIPE BACK TO NEAREST ACTIVE MAIN AND
PROVIDE SHUT OFF VALVES AS NEEDED.
4. DEMOLISH EXISTING SINKS, WATER FILTRATION SYSTEMS, AND FLOOR DRAINS.
CUT EXISTING COLD WATER AND HOT WATER PIPE BACK TO NEAREST ACTIVE
MAIN AND PROVIDE SHUT OFF VALVES AS NEEDED. CUT AND CAP BOTH
SANITARY AND VENT PIPING BACK TO NEAREST ACTIVE MAIN.
5. DEMOLISH EXISTING WATER CLOSET, URINAL, LAVATORY SINK, SHOWER AND
FLOOR DRAIN. CUT EXISTING COLD WATER AND HOT WATER PIPE BACK TO
NEAREST ACTIVE MAIN AND PROVIDE SHUT OFF VALVES AS NEEDED. CUT AND
CAP BOTH SANITARY AND VENT PIPING BACK TO NEAREST ACTIVE MAIN.
6. DEMOLISH EXISTING EYEWASH. CUT COLD AND HOT WATER PIPES BACK TO
NEAREST ACTIVE MAIN AND PROVIDE SHUT OFF VALVES AS NEEDED.
NORTH
TRUE NORTH=
PROJECT
88.50°
* UNDERGROUND PIPING CUT AT SLAB, LEAVE IN SLAB AND PATCH WITH
CONCRETE UNLESS NOTED OTHERWISE. CONTRACTOR VERIFY IN PLACE.
4E
F
G
H
C
3635343332312927252423 33A302826
B
A
22212019
I
J
19A
22A
D
20B
30A
EXISTING STORM RISER TO REMAIN
PHARMACY STORAGE
TOILET
ROOM
53B
OIT (NIC)
53A
STAIR
STOR (NIC)
VAC STOR (NIC)
BIOMED
ENGINEERING
CORRIDOR (NIC)
B-C-C2
OIT SERVER ROOM
MATERIAL MGMT.
SECTION
MAILROOM
49A
WOMEN'S LOCKER
RM
CORRIDOR
C4
STAIR
WATER TREATMENT
(NIC)
NEW SPS ADDITION
(NIC)
ENGINEERING (NIC)
SOILED
SOILED
MENS LOCKER RM
MECH OFFICE
STORAGE
44A
MORGUE
MENS LOCKER RM
45A
MENS LOCKER RM
45B
DECONTAMINATION
AREA
WEST (BW) EAST (BE)
BASEMENT
GENERAL AREA OF
WORK (REFER TO
PLAN FOR DETALS)
BASEMENT
AREA OF FUTURE WORK
(NOT IN CONTRACT) NOT IN CONTRACT
NO
T
IN
C
ON
TR
AC
T
MA
TC
H
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
WSP USA Buildings Inc.
One Penn Plaza, 2nd Floor New York, NY 10019
(212) 465-5000 www.wsp.com
BI
M
5_
Ft . W ay ne
V
AM
C B as em en t B ld g
1/
5_
W
SP
_P
LB
G
IT
_C en tra l 2
8.
rv t
7/
/2
4:
:2
PM
PD100E
PLUMBING DEMOLITION PLAN - BASEMENT
EASTAE Works
209 SANDUSKY STREET
PITTSBURGH, PA 15212
412-287-7333 AEW Project No. 18025
RENOVATE BASEMENT,
BUILDING 1
2121 LAKE AVE, FORT WAYNE, IN 46805
610A4-19-104
07/15/2020 EG RR
BID DOCUMENTS
8' 16'4'0
1/8" = 1'-0"1 BASEMENT - PLUMBING DEMO FLOOR PLAN EAST
# KEYNOTES:
1. DEMOLISH EXISTING WATER CLOSETS, LAVATORY SINKS, SHOWER AND FLOOR
DRAIN. CUT EXISTING COLD WATER AND HOT WATER PIPE BACK TO NEAREST
ACTIVE MAIN AND PROVIDE SHUT OFF VALVES AS NEEDED. CUT AND CAP BOTH
SANITARY AND VENT PIPING BACK TO NEAREST ACTIVE MAIN.
2. DEMOLISH EXISTING WATER CLOSETS, URINALS, LAVATORY SINKS, SHOWER
AND FLOOR DRAIN. CUT EXISTING COLD WATER AND HOT WATER PIPE BACK
TO NEAREST ACTIVE MAIN AND PROVIDE SHUT OFF VALVES AS NEEDED. CUT
AND CAP BOTH SANITARY AND VENT PIPING BACK TO NEAREST ACTIVE MAIN.
3. PLUMBING FIXTURES EXISTING TO REMAIN.
4. REMOVE EXISTING DRINKING FOUNTAIN AND CAP ALL EXISTING PLUMBING
PIPING FOR FUTURE CONNECTION. ALL EXISTING PIPING TO REMAIN.
5. REMOVE EXISTING DRINKING FOUNTAIN AND CAP ALL PIPING FOR FUTURE USE.
ALL EXISTING PIPING TO REMAIN.
6. DEMOLISH EXISTING FLOOR DRAIN. CUT EXISTING COLD WATER SUPPLY TO ICE
MACHINE PIPE BACK TO NEAREST ACTIVE MAIN AND PROVIDE SHUT OFF VALVE
AS NEEDED. CUT AND CAP BOTH SANITARY AND VENT PIPING BACK TO
NEAREST ACTIVE MAIN.
NORTH
TRUE NORTH=
PROJECT
88.50°
* UNDERGROUND PIPING CUT AT SLAB, LEAVE IN SLAB AND PATCH WITH
CONCRETE UNLESS NOTED OTHERWISE. CONTRACTOR VERIFY IN PLACE.
MA
TC
H
LI
NE
MA
TC
H
LI
NE
P-3
P-1A
2" SAN DN
1 1/2" VENT RISE & DROP
3/4" CW&HW DROP
1/2" HWR
P-8A P-2
P-1P-1AP-5
P-3
NEW 2" VENT, 1 1/2" CW, 1" HW
& 1/2" HWR CONNECT TO
NEAREST EXISTING IN CLG.
P-8A
P-6 E
F
G
H
C
B
A
201918A1615
I
J
131210876543A321
19A
9 11 13A
D
18 20B17A 17B
2" SAN DN
1 1/2" VENT RISE & DROP
3/4" CW&HW DROP
1/2" HWR
4" SAN DN
2" VENT RISE & DROP
NEW 2" VENT, 1 1/4" CW, 1" HW
& 1/2" HWR CONNECT TO NEAREST
EXISTING PIPING IN CLG.
P-3 P-3
P-3 P-3 P-1A
4" SAN DN
2" VENT RISE & DROP
1 1/2" CW DROP
2" SAN DN
1 1/2" VENT DROP & RISE
3/4" CW DROP
3/4" HW DROP
1/2" HWR
4" SAN DN
2" VENT DROP & RISE
1 1/4" CW DROP
3" FD
3" FD
3" FD
3" FD
1 1/2"ø
3/4"ø
1 1/4" CW DROP
3/4 HW" DROP
3/4" CW DROP
3/4" HW DROP
1. PLUMBING IN SHADED N.I.C. AREA TO REMAIN.
2. NEW SANITARY CONNECTIONS TO THE NEAREST
EXISTING PIPING BELOW GRADE SHALL BE VERIFIED IN
TERMS OF LOCATION AND SIZES IN FIELD.
ANY DISCREPANCIES SHALL BE BROUGHT
TO ATTENTION OF ARCHITECT AND ENGINEER.
GENERAL NOTES:
NEW DRINKING FOUNTAIN CONNECT TO EXIST. PLBG ROUGHING
3" SAN CONNECT TO
EXIST. 4" SAN UNDERGROUND
EXIST. 4" SAN
UNDERGROUND
EXIST. 4" SAN
UNDERGROUND
3" SAN CONNECT TO
EXIST. 4" SAN UNDERGROUND
3" FUNNEL BELOW SINK
FOR CONDENSATE DRAIN
P-1A
X-RAY
B120E
TLT / CHANGING
B120F
CLEAN
B120G
CT SCANNING
B120D
STORAGE
B118
RECEPTION / WORK
B120A
WAITING
B119
SOILED HOLDING
B120C
WOMENS
B113
MENS
B114
CORRIDOR
C06
PHARMACY CACHE
B111
MECHANICAL OFFICE
B101
EMS SUPPLY
B104
EMS OFFICE 2
B100A
EMS OFFICE 1
B100B
EMS SUITE
B100
MENS DRESSING
B100E
CLEAN LINEN ROOM
B100C
RADIOLOGY
B120
CLOSET
B120B
GME LIBRARY
B116
RES. SLEEPING
ROOM
B115
RESIDENT TLT RM
B115A
CORRIDOR
C05
CORRIDOR
C04
EMS STORAGE
B103
CORRIDOR
C02
MECH
B102B
WOMENS DRESSING
B100D
NUTRITION AND
FOOD SERVICES (NIC)
ENGINEERING (NIC)
033A
ENGINEERING (NIC)
B105
ENGINEERING (NIC)
B106
FIRE PUMP ROOM
(NIC)
B109
SOILED (NIC)
B107
HVAC (NIC)
B108
PHARMACY (NIC)
B117
NEW 1 1/2" VENT, 3/4" CW
CONNECT TO NEAREST
EXISTING IN CLG.
NEW 2" SAN DN
NEW 2" SAN
UNDERGROUND
EXIST 4" SAN
NEW 1 1/2" VENT,
3/4" CW DROP
WEST (BW) EAST (BE)
BASEMENT
GENERAL AREA OF
WORK (REFER TO
PLAN FOR DETALS)
BASEMENT
AREA OF FUTURE WORK
(NOT IN CONTRACT) NOT IN CONTRACT
NO
T
IN
C
ON
TR
AC
T
MA
TC
H
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
WSP USA Buildings Inc.
One Penn Plaza, 2nd Floor New York, NY 10019
(212) 465-5000 www.wsp.com
BI
M
5_
Ft . W ay ne
V
AM
C B as em en t B ld g
1/
5_
W
SP
_P
LB
G
IT
_C en tra l 2
8.
rv t
7/
/2
4:
:1
PM
P100W
PLUMBING PLAN - BASEMENT WEST
AE Works
209 SANDUSKY STREET
PITTSBURGH, PA 15212
412-287-7333 AEW Project No. 18025
RENOVATE BASEMENT,
BUILDING 1
2121 LAKE AVE, FORT WAYNE, IN 46805
610A4-19-104
07/15/2020 EG RR
BID DOCUMENTS
8' 16'4'0
1/8" = 1'-0"1 BASEMENT - PLUMBING NEW FLOOR PLAN WEST
# KEYNOTES:
1. PROVIDE OXYGEN AND CA CONNECTIONS.
NORTH
TRUE NORTH=
PROJECT
MA
TC
H
LI
NE
MA
TC
H
LI
NE
P-8A
2" SAN DN
1 1/2" VENT DROP & RISE
3/4" CW DROP
3/4" HW DROP
1/2" HWR
NEW 1 1/2" VENT & 3/4" CW &
HW CONNECT TO NEAREST
EXISTING PIPING IN CLG.
P-6 E
F
G
H
C
3635343332312927252423 33A302826
B
A
2221201918A
I
19A
22A
D
18 20B
30A
17B
3/4" WATER DROP
TO EYEWASH
NEW 3/4" CW & HW
CONNECT TO NEAREST
PIPING EXISTING IN CLG.PROVIDE TEMPERING
MIXING VALVE
1. PLUMBING IN SHADED N.I.C. AREA TO REMAIN.
2. NEW SANITARY CONNECTIONS TO THE NEAREST
EXISTING PIPING BELOW GRADE SHALL BE VERIFIED IN
TERMS OF LOCATION AND SIZES IN FIELD.
ANY DISCREPANCIES SHALL BE BROUGHT
TO ATTENTION OF ARCHITECT AND ENGINEER.
GENERAL NOTES:
EW
NEW DRINKING FOUNTAIN
CONNECT TO EXIST. PLBG
ROUGHING
1" MAKE-UP WATER FOR
HYDRONIC SYSTEM
1" RPZ
NEW 1" CW MAKE-UP WATER
CONNECT TO NEAREST
EXIST. PIPING IN CLG
EXIST
MECHANICAL OFFICE
B101
MAILROOM
B300
MENS DRESSING
B100E
MECH ROOM 1
B308
BIOMED STORAGE
B310
STORAGE
B316D
WORKSHOP
B316C
OFFICE
B316B
BIOMED
B316
OIT SERVER
B311
OIT OFFICE
B309
STOR / SOILED LINEN
CART
B306 BATTERY ROOM
B307
STORAGE
B316A
ENGINEERING
STORAGE
B312
CORRIDOR
C07
WOMENS DRESSING
B100D
VESTIBULE (NIC)
STAIR 4 (NIC)
S4
OIT (NIC)
053A
ENGINEERING (NIC)
B304
PUMP ROOM (NIC)
ENGINEERING (NIC)
B305
STAIR 3 (NIC)
S3
SPS ADDITION (NIC)
42B
HAC (NIC)
B302
SOILED (NIC)
B303
MORGUE (NIC)
HAC (NIC)
063A
NUTRITION AND
FOOD SERVICES (NIC)
NEW DRINKING
FOUNTAIN CONNECT TO
EXIST. PLBG ROUGHING
P-6
P-3P-1A
WEST (BW) EAST (BE)
BASEMENT
GENERAL AREA OF
WORK (REFER TO
PLAN FOR DETALS)
BASEMENT
AREA OF FUTURE WORK
(NOT IN CONTRACT) NOT IN CONTRACT
NO
T
IN
C
ON
TR
AC
T
MA
TC
H
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
WSP USA Buildings Inc.
One Penn Plaza, 2nd Floor New York, NY 10019
(212) 465-5000 www.wsp.com
BI
M
5_
Ft . W ay ne
V
AM
C B as em en t B ld g
1/
5_
W
SP
_P
LB
G
IT
_C en tra l 2
8.
rv t
7/
/2
4:
:1
PM
P100E
PLUMBING PLAN - BASEMENT EAST
AE Works
209 SANDUSKY STREET
PITTSBURGH, PA 15212
412-287-7333 AEW Project No. 18025
RENOVATE BASEMENT,
BUILDING 1
2121 LAKE AVE, FORT WAYNE, IN 46805
610A4-19-104
07/15/2020 EG RR
BID DOCUMENTS
8' 16'4'0
1/8" = 1'-0"1 BASEMENT - PLUMBING NEW FLOOR PLAN EAST
# KEYNOTES:
1. PROVIDE OXYGEN AND CA CONNECTIONS.
NORTH
TRUE NORTH=
PROJECT
NOTES:
1. EACH GS-PLUS SPRAY HEAD HAS A
"FLIP-TOP" DUST COVER, INTERNAL
FLOW CONTROL AND FILTER TO REMOVE
IMPURITIES FROM THE WATER FLOW.
2. UNIT SHOULD BE INSTALLED SUCH THAT
WATER FLOW PATTERN IS POSITIONED
BETWEEN 33" AND 53" ABOVE FLOOR.
5 1/4" ( 133 mm)
6 3/8" ( 162 mm)
1 60 .00 00 ( 203 mm)
�1 1 1/8" ( 283 mm)
6 7/8" ( 175 mm)
6 1/2" ( 165 mm)
2 75 .00 00 ( 349 mm)
6 6.17 38 ( 83 mm)
6 4.96 66 ( 83 mm)
9 2.50 00 ( 117 mm)
9 6.52 00 ( 124 mm)
1/2" IPS CHROME PLATED
BRASS STAY-OPEN BALL VALVE
9 6.89 96 ( 124 mm)
3" FUNNEL BELOW SINK
FOR CONDENSATE DRAIN.
COORDINATE EXACT
LOCATION IN FIELD
CEILING
PARTITION/WALL
VENT
WASTE
HANDSINK
2" CONDENSATE DRAIN LINE
FROM WALL AC UNIT
1"
2"
VERIFY EXACT SIZE IN FIELD
VERIFY EXACT SIZE IN FIELD
P
DETAIL "A"
MOUNTING BRACKET
1 1/4" NPT
FEMALE OUTLET
(3) ∅3/8"
MOUNTING
HOLES
STAINLESS STEEL BOWL
1/2" NPT
FEMALE INLET
POWDER COATED CAST
ALUMINUM WALL BRACKET
(SEE DETAIL "A")
POWDER COATED CAST
ALUMINUM FLAG HANDLE
(2) GS-PLUS
SPRAY HEADS
6' MAX
CLEVIS HANGER
WITH VAPOR
BARRIER INSULATION
PIPE
NO VAPOR
CLEVIS HANGER
BARRIER INSULATION
NOT TO SCALE
CLEAN OUT DETAIL PIPE SUPPORT DETAIL
NOT TO SCALE
NOTES:
1. REFER TO ARCHITECTURE DRAWINGS FOR EXACT
CONSTRUCTION CONDITIONS AND REQUIREMENTS.
NOTES:
2. THIS DETAIL SHALL BE APPLICABLE TO PLUMBING PIPING
SMALLER THAT 50.
1. ALL HANGERS FOR COPPER PIPING SHALL BE COPPER
COATED.
LOCKING NUT (TYPICAL)
16 GA. SHEET METAL
SADDLE 300 LONG
BLOCK SUPPORT
WHERE REQUIRED TO
ELIMINATE INSULATION
DAMAGE
VAPOR BARRIER
INSULATION
SUPPORT ADJUSTMENT
NUT (TYPICAL)
CONCRETE INSERT
ANCHOR TO
STRUCTURE ABOVE
CONCRETE
HANGER ROD
(TYPICAL)
HEAVY DUTY CLEVIS
HANGER (TYPICAL)
ALL THREAD
ROD (TYPICAL)
CONCRETE INSERT
ANCHOR TO
STRUCTURE
ABOVE
CONCRETE
TO SYSTEM
FLOOR
CLEANOUT WITH
COVER PLATE
3. THIS HANGAR METHOD CAN ONLY BE USED UNDER THE 2ND
FLOOR AS THE ROOF DOES NOT PROVIDE SUPPORT
DEIONIZED WATER FAUCET INSTALLATION
NOT TO SCALE NOT TO SCALE
TRAP PRIMER INSTALLATION
BATHROOM FLOOR DRAIN TRAP PRIMER
NOT TO SCALE
WATER HAMMER ARRESTOR INSTALLATION
NOT TO SCALE
CLEANOUT PLUG
FINISHED
WALL
FINISHED FLOOR
FLOOR DRAIN
PIPING IN WALL
AND UNDER FLOOR
WATER SAVER TRAP PRIMER
J.R. SMITH PRIME-EZE
1'x1' ACCESS DOOR
TRAP PRIMER
DOMESTIC COLD WATER LINE
FLOOR DRAIN
FINISHED FLOOR
TRAP ARM
TRAP
P.D.I. SYMBOLS
FIXTURE UNIT RATING 1-11 12-32 33-60 61-113 114-154 155-330
A B C D E F 5005 5010 5020 5030 5040 5050
WATER HAMMER ARRESTOR SCHEDULE
NOTE:
EXAMPLE:
COLD WATER BRANCH = 26 F.U. = JR. SMITH #5010 HYDROTROL
HOT WATER BRANCH = 6 F.U. = JR. SMITH #5005 HYDROTROL
WHEN HORIZONTAL BRANCH PIPING EXCEEDS 20' IN
LENGTH, AN ADDITIONAL ARRESTOR SHALL BE USED.
PLUG 1 LEG OF TEE WITH BARSTOCK,
DRILL & TAP FOR CONNECTION TO
FAUCET. LENGTH OF NIPPLE BETWEEN
TAPPED BARSTOCK & FAUCET TO BE
AS SHORT AS POSSIBLE.
ENFIELD ENSURE SCH 80
POLYPROPYLENE WITH
FUSION JOINTS.
TEE
SHEETMETAL
PIPE ENCLOSURE.
WALL
BASE
CABINET
FAUCET "WATER SAVER
FAUCET CO." MODEL L7833.
COUNTER
1 1/2"
6 SERRATION POLYPROPYLENE
HOSE END
ROUND NYLON
HANDLE
COMPRESSION CONTROL
DIAPHRAGM VALVE
J.R. SMITH/HYDROTROL #
NOTE:
REMOVE SLAB AND REPLACE AS REQUIRED
NOTE:
REMOVE SLAB AND REPLACE AS REQUIRED
DRAIN TO HANDSINK DETAIL
NTS
WALL MOUNTED EYE WASH
NTS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
WSP USA Buildings Inc.
One Penn Plaza, 2nd Floor New York, NY 10019
(212) 465-5000 www.wsp.com
BI
M
5_
Ft . W ay ne
V
AM
C B as em en t B ld g
1/
5_
W
SP
_P
LB
G
IT
_C en tra l 2
8.
rv t
7/
/2
4:
:1
PM
P600
PLUMBING DETAILS
AE Works
209 SANDUSKY STREET
PITTSBURGH, PA 15212
412-287-7333 AEW Project No. 18025
RENOVATE BASEMENT,
BUILDING 1
2121 LAKE AVE, FORT WAYNE, IN 46805
610A4-19-104
07/15/2020 EG RR
GA
TE
BA
LL
GL
OB
E
FLA
NG
ED
SC
RE
WE
D
REMARKSSTRAINERBODY
LE
SS
G
RA
TE
EX
TE
NS
IO
N
RA
IS
ED
LI
P
DO
ME
FL
AT
T
OP
FU
NN
EL
T
OP
BR
ON
ZE
M
ES
H
SC
RE
EN
TR
AC
TO
R
GR
AT
E
SA
TI
N
FI
NI
SH
PO
LIS
HE
D
FI
NI
SH
SE
CO
ND
AR
Y
ST
RA
IN
ER
SE
DI
ME
NT
B
UC
KE
T
CH
RO
ME
P
LA
TE
D
NI
CK
EL
B
RO
NZ
E
AL
L B
RO
NZ
E
CA
ST
IR
ON
FL
AN
GE
(W
AT
ER
P
RO
OF
IN
G)
SU
MP
R
EC
IE
VE
R
BA
CK
W
AT
ER
V
AL
VE
DE
CK
C
LA
MP
CL
AM
PI
NG
D
EV
IC
E
SE
CO
ND
AR
Y
CL
AM
P
AL
L B
RO
NZ
E
GA
LV
AN
IZ
ED
CA
ST
IR
ON
DE
SI
GN
AT
IO
N
SE
RI
ES
N
O.
JO
SA
M
SM
ITH
W
AD
E
ZU
RN
DRAIN SCHEDULE
PO
LY
PR
OP
YL
EN
E
ST
AI
NL
ES
S
ST
EE
L
ST
AI
NL
ES
S
ST
EE
L
BATHROOM2005FD
DOMESTIC WATER SYSTEM
3" AND LARGER
2½" AND SMALLER
WATER SERVICE
SHUT-OFF VALVES
VALVE SPECIFICATION
FLOOR DRAINS
T.W.
1½" ¾"VALVE
FLUSHOMETER
CARRIER
FIXTURE
1¼"4" 2"
SUPPLIES
2" - -
URINAL
637JR SMITH
0208Y
AMERICAN
STANDARD 6042.001EC.020
SELECTRONIC 6063.013.002
FOUNTAIN
DRINKING ELKAY
P-2
P-3
P-6 --½"1½"1½"
McGUIRE 167
JR SMITHP-TRAP
FAUCET AMERICAN
STANDARD 6114.110.002
0954.004EC
AMERICAN
STANDARDLAVATORY
2" 1½" ½" ½" -
MURRO UNIVERSAL DESIGN
FAUCET FLOW RATE 0.5 GPM
PROVIDE COVER ON SUPPLIES & TRAP.
TEMPERING VALVE POWERS EF-480
P-1/P-1A
JR SMITH
AMERICAN
STANDARD 3351.101
6065.761SELECTRONIC
EXTRA HEAVY DUTY SEATTOILET SEAT
FLUSHOMETER
VALVE
CARRIER
WATER CLOSET
FIXTURES DESIGNATION BASIS OF DESIGN
MANUFACTURER
BASIS OF DESIGN
MODEL #
PLUMBING FIXTURE SERVICE CONNECTION SCHEDULE
S V C.W. H.W. REMARKS
P-1 REGULAR MOUNT HEIGHT
P-1A MOUNT HEIGHT ADA COMPLIANT
HEIGHT, SEE ARCH. DWG FOR
DETAIL DUAL FLUSH 1.6/1.1 GPF
LVRCTL8WSK
FLUSH CYCLE - 0.125 GPF
P-5
P-TRAP
FAUCET
SHOWER
2" 1½" ½" ½" -
P-8A
P-TRAP McGUIRE
SINK
2" 1½" ½" ½" -FAUCET
EYEWASH WATEREW ½"-EW814SAVER
SPILL TO
FLOOR
EMERGENCY THERMOSTATIC MIXING VALVE
WATER SAVER-EW814
WALL MOUNTER, STAINLESS STEE BOWL
¾" ¾"
8902McGUIRE
ALL-IN-ONE MODULAR CASEWORK
UNIT INTEGRATED SINK, MATCH
HERMAN MILLER COMPASS
SYSTEM INSTALLED IN 3E SIDE
COMPASS SYSTEM
COMPASS SYSTEMHERMAN
MILLER
HERMAN
MILLER
FLOW CONTROL ( 1.5 GPM AT 45 PSI ),
METALLIC SHOWER HEAD WITH
TYPE T/P BALANCING VALVE SET.
TU662213.002
TU662213.002
REFER TO ARCH DRAWINGS FOR DETAILS.
AMERICAN
STANDARD
AMERICAN
STANDARD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
WSP USA Buildings Inc.
One Penn Plaza, 2nd Floor New York, NY 10019
(212) 465-5000 www.wsp.com
BI
M
5_
Ft . W ay ne
V
AM
C B as em en t B ld g
1/
5_
W
SP
_P
LB
G
IT
_C en tra l 2
8.
rv t
7/
/2
4:
:1
PM
P700
PLUMBING SCHEDULES
AE Works
209 SANDUSKY STREET
PITTSBURGH, PA 15212
412-287-7333 AEW Project No. 18025
RENOVATE BASEMENT,
BUILDING 1
2121 LAKE AVE, FORT WAYNE, IN 46805
610A4-19-104
07/15/2020 EG RR
CO2
CO
H
HS
NO2
S
TH
TS
T
MS
CD
LPC
P-HWR
P-HWS
G
LPS
(E)
CONDENSATE DRAINAGE
CONDENSATE RETURN
NATURAL GAS
STEAM
RL
RS
REFRIGERANT-LIQUID
REFRIGERANT-SUCTION
2"
REF-HG REFRIGERANT-HOT GAS
HYDRONIC PIPING SYMBOLS
KEYNOTE
CONTINUATION SYMBOL
REVISION NUMBER - SHOWN ON PLANS
GENERAL MECHANICAL SYMBOLS
ROOM NAME AND NUMBER
POINT WHERE NEW CONNECTS TO EXISTING
EXISTING PIPE TAG
ITEM TO BE DEMOLISHED
PIPING BEING DEMOLISHED
ABOVE GROUND PIPING
PIPE SIZE TAG (DIAMETER)
BELOW GROUND PIPING
PIPE INVERT ELEVATION TAG
PIPE SLOPE TAG
* NOTE *
ALL OF GENERAL NOTES ON THIS SHEET ARE TO BE APPLIED TO ALL OTHER DRAWINGS IN THIS SET.THE
SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET MAY OR MAY NOT BE USED IN THIS SET OF
DRAWINGS.
PG PROPANE GAS
Room
INVERT: -10' - 1"
1/8" / 12" SLOPE
16"x8"
16"/8"
(E)
F
S
M
B
D
C
16"Ø
E/A
O/A
T/A
R/A
S/A
EXHAUST AIR
OUTSIDE AIR
RETURN AIR
SUPPLY AIR
TRANSFER AIR
GRILLES, REGISTERS & DIFFUSERS TAG
CFM
EXISTING DUCT TAG
OVAL DUCT SIZE TAG (WIDTH / HEIGHT)
SQUARE DUCT SIZE TAG (WIDTH x HEIGHT)
HVAC SYMBOLS
RECTANGULAR SUPPLY/OUTSIDE AIR DUCT RISE
RECTANGULAR RETURN/TRANSFER AIR DUCT RISE
MECHANICAL EQUIPMENT TAGS
ROUND DUCT SIZE TAG (DIAMETER)
DUCT BEING DEMOLISHED
ROUND SUPPLY/OUTSIDE AIR DUCT RISE
ROUND RETURN/TRANSFER AIR DUCT RISE
RECTANGULAR EXHAUST/RELIEF AIR DUCT RISE
ROUND EXHAUST/RELIEF AIR DUCT RISE
DROP
DROP
DROP
DROP
DROP
DROP
EXISTING EQUIPMENT
TO REMAIN(XR)VAV-XX
Ø ROUND
ABV ABOVE
AC AIR CONDITIONING
AD AREA DRAIN
ADD ADDENDUM
AFF ABOVE FINISHED FLOOR
AFUE ANNUAL FUEL UTILIZATION EFFICIENCY
ALT ALTERNATE
AP ACCESS PANEL
ARCH ARCHITECT/ARCHITECTURAL
BFF BELOW FINISHED FLOOR
BLW BELOW
BTU BRITISH THERMAL UNITS
BTUH BRITISH THERMAL UNITS PER HOUR
CAP CAPACITY
CB CATCH BASIN
CFM CUBIC FEET PER MINUTE
CLG CEILING
CV CONSTANT VOLUME
CW COLD WATER
D DEGREE
DB DRY BULB
DIA DIAMETER
DN DOWN
DW DISTILLED WATER
EA EACH
EAT ENTERING AIR TEMPERATURE
ELEC ELECTRICAL
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EWT ENTERING WATER TEMPERATURE
E/A EXHAUST AIR
EXIST EXISTING
F DEGREES FAHRENHEIT
FCO FLOOR CLEAN OUT
FD FLOOR DRAIN
FD FIRE DAMPER
FDV FIRE DEPARTMENT VALVE
FL FLOOR
FO FUEL OIL
FOV FUEL OIL VENT
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FPM FEET PER MINUTE
FS FLOOR SINK
FT FOOT/FEET
FTR FIN TUBE RADIATION
GAL GALLON
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
GW GREASE WASTE
HB HOSE BIB
HP HORSE POWER
HTG HEATING
HTR HEATER
HW HOT WATER
HYD HYDRANT
ID INDIRECT
IN INCH
INV INVERT
LB POUND
LB/HR POUNDS PER HOUR
LAT LEAVING AIR TEMPERATURE
LP LOW PRESSURE
LPG LIQUEFIED PETROLEUM GAS
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
M/A MIXED AIR
MAX MAXIMUM
MBH ONE THOUSAND BTU PER HOUR
MCF ONE THOUSAND CUBIC FEET
MD MOTORIZED DAMPER
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTR MOTOR
MU/A MAKE-UP/AIR
NC NOISE CRITERIA
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NUMBER
NO NORMALLY OPEN
NTS NOT TO SCALE
O OXYGEN
O/A OUTSIDE AIR
ORD OVERFLOW ROOF DRAIN
PD PRESSURE DROP
PIV POST INDICATOR VALVE
PLBG PLUMBING
PRESS PRESSURE
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAUGE
PWR POWER
R DUCT RISER
R/A RETURN AIR
RCP RADIANT CEILING PANEL
RD ROOF DRAIN
REC RECESSED
RED REDUCER
RH RELATIVE HUMIDITY
RL/A RELIEF AIR
RM ROOM
RPM REVOLUTIONS PER MINUTE
RW RAIN WATER
SF SQUARE FOOT
S/A SUPPLY AIR
SAN SANITARY
SF SQUARE FOOT
SD SMOKE DAMPER
SM SURFACE MOUNT
SP STANDPIPE
SP STATIC PRESSURE
STM STEAM
T THERMOSTAT
TD TEMPERATURE DROP
TDR TRENCH DRAIN
TEMP TEMPERATURE
TYP TYPICAL
UG UNDERGROUND
VAC VACUUM
V VENT
VAV VARIABLE AIR VOLUME
VENT VENTILATION
VTR VENT THROUGH ROOF
W WASTE
WB WET BULB
WCO WALL CLEAN OUT
WH WALL HYDRANT
ABBREVIATIONS
AC AIR CONDITIONING UNIT
ACC AIR COOLED CONDENSER
ACCU AIR COOLING CONDENSING UNIT
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
ATU AIR TERMINAL UNIT
B BOILER
BAS BUILDING AUTOMATION SYSTEM
CH CHILLER
CT COOLING TOWER
CUH CABINET UNIT HEATER
CWP CONDENSER WATER PUMP
CHWP CHILLED WATER PUMP
DBP DOMESTIC WATER BOOSTER PUMP
DC DUCT MOUNTED COIL
DCP DOMESTIC WATER CIRCULATING PUMP
ECC ENGINEERING CONTROL CENTER
EF EXHAUST FAN
EDC ELECTRIC DUCT COIL
ET EXPANSION TANK
EWH ELECTRIC WATER HEATER
FCU FAN COIL UNIT
FP FIRE PUMP
GI GREASE INTERCEPTOR
GRV GRAVITY ROOF VENTILATOR
HWP HEATING WATER PUMP
HX HEAT EXCHANGER
HRU HEAT RECOVERY UNIT
PRV POWER ROOF VENTILATOR
RE RETURN/EXHAUST FAN
RTU ROOFTOP UNIT
SEP SEWAGE EJECTOR PUMP
SF SUPPLY FAN
SP SUMP PUMP
UH UNIT HEATER
WH WATER HEATER
EQUIPMENT ABBREVIATIONS
SD-5
TYPE (SEE SCHEDULE)
SD-1
VAV-XX
VAV BOX
DATA DEVICE TAGS
DAMPER TAGS
VAV-XX
RTU-XX
EQUIPMENT ID
SYMBOL
MANUAL BALANCING DAMPER
BACKDRAFT DAMPER
COMBINATION FIRE/SMOKE
DAMPER
FIRE DAMPER
SMOKE DAMPER
MOTORIZED DAMPER
SENSOR
MANUAL SWITCH
THERMOSTAT
TEMPERATURE SENSOR
TEMPERATURE & HUMIDITY SENSOR
HUMIDITY SENSOR
NITROGEN DIOXIDE SENSOR
CARBON MONOXIDE SENSOR
CARBON DIOXIDE SENSOR
HUMIDISTAT
3-CONE DIFFUSER
ROUND DIFFUSER WITH
ADJUSTABLE PATTERNS
EGGCRATE RETURN/EXHAUST
GRILLE
POINT DISCONNECTION FROM EXISTING HWR
HWS
HEATING HOT WATER RETURN (PERIMETER)
HEATING HOT WATER SUPPLY (PERIMETER)
HEATING HOT WATER RETURN (REHEAT)
HEATING HOT WATER SUPPLY (REHEAT)
EG-2
SIMPLIFIED D/R/G TAG
AIRFLOW
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
B
IM
/1
F t.
W a y n e V
A M
C B a s e m e n t B ld g
/1
M
E P
C e n tr a l
.r v t
/1
/2
:5
:5
P
M
H001
HVAC SYMBOLS, ABBREVIATIONS, AND
GENERAL NOTESAE Works
209 SANDUSKY STREET
PITTSBURGH, PA 15212
412-287-7333
RENOVATE BASEMENT,
BUILDING 1
2121 LAKE AVE, FORT WAYNE, IN 46805
610A4-19-104
07/15/2020 MJC AC
BID DOCUMENTS
HVAC GENERAL NOTES
39 PROVIDE MANUFACTURER'S MATCHING ROOF CURBS FOR ALL ROOF MOUNTING EQUIPMENT.
COORDINATE ACTUAL ROOF PITCH AND CONSTRUCTION DETAILS WITH GENERAL
CONTRACTOR. PROVIDE SLOPED CURBS PER MANUFACTURER'S RECOMMENDATIONS.
GENERAL CONTRACTOR SHALL INSTALL ROOF CURBS AND FLASHING PER ROOFING
MANUFACTURER'S INSTALLATION REQUIREMENTS.
40 UNLESS OTHERWISE NOTED, ALL PIPING AND DUCTWORK IF OVERHEAD, TIGHT TO UNDERSIDE
OF STRUCTURE OR SLAB, WITH SPACE FOR INSULATION.
41 PROVIDE CHAINWHEEL OPERATORS FOR ALL EXPOSED VALVES MOUNTED GREATER THAN
8-FT, 0-IN ABOVE FINISHED FLOOR LEVEL. CHAIN SHALL EXTEND UNOBSTRUCTED TO 7-FT, 0-IN
ABOVE FLOOR LEVEL.
42 ALL PIPING AND DUCTWORK SHALL CLEAR DOORS, WINDOWS, EQUIPMENT CLEARANCES,
MAINTENANCE REQUIREMENTS, CODE SETBACKS, ETC. TO ASSURE PROPER OPERATION,
INSPECTION AND MAINTENANCE.
43 ALL VALVES SHALL BE ADJUSTED FOR SMOOTH AND EASY OPERATION.
44 PROVIDE ALL 90 DEGREE SQUARE ELBOWS WITH DOUBLE RADIUS TURNING VANES UNLESS
OTHERWISE INDICATED OR SPECIFIED. PROVIDE ACCESS DOORS UPSTREAM OF ALL ELBOWS
CONTAINING TURNING VANES.
45 ALL DUCTS SHALL BE BONDED ACROSS FLEXIBLE CONNECTIONS WITH FLEXIBLE COPPER
GROUNDING STRAPS. GROUNDING STRAPS SHALL BE BOLTED OR SOLDERED TO BOTH THE
EQUIPMENT AND THE DUCT.
46 ALL EQUIPMENT SUBMITTALS AND SHOP DRAWINGS REQUIRED BY THE SPECIFICATIONS SHALL
BE APPROVED BY THE ENGINEER PRIOR TO PURCHASE, FABRICATION AND INSTALLATION.
47 ALL HEATING DEVICES AND SURFACES WITH ELEVATED TEMPERATURES WHICH CAN BE
ACCESSED OR COME IN CONTACT WITH OWNER PERSONNEL SHALL BE PROTECTED,
INSULATED, OR CONTROLLED TO REMAIN BELOW 120º F.
48 PROVIDE MANUAL VOLUME DAMPERS IN ALL RUN-OUTS TO DIFFUSERS, BRANCH TAKE-OFFS
FROM MAIN SUPPLY DUCT, AND IN ALL OTHER AREAS REQUIRED TO PROVIDE PROPER SYSTEM
AIRFLOW BALANCING.
HVAC GENERAL NOTES
1 NOT ALL SYMBOLS ARE NECESSARILY USED.
2 COORDINATE FINAL LOCATIONS OF DIFFUSERS AND GRILLES WITH ARCHITECTURAL
REFLECTED CEILING PLANS.
3 CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK ARE DIAGRAMMATIC AND ARE
INTENDED TO CONVEY SCOPE AND GENERAL ARRANGEMENT ONLY. CONTRACTOR TO FIELD
VERIFY DUCT AND PIPE ROUTING AND COORDINATE INTERFERENCE BETWEEN TRADES PRIOR
TO INSTALLATION. CONTRACTOR SHALL BE RESPONSIBLE TO FIELD SURVEY ACTUAL SITE
CONDITIONS AND ACCOMODATE ACTUAL SITE CONDITIONS AS PART OF SCOPE OF WORK AT
NO COST TO OWNER.
4 ROOF OPENINGS, FLASHING, AND COUNTER FLASHING BY GENERAL CONTRACTOR. LOCATION
OF OPENINGS BY HEATING CONTRACTOR.ROOF OPENINGS, FLASHING, AND COUNTER
FLASHING BY GENERAL CONTRACTOR. LOCATION OF OPENINGS BY HEATING CONTRACTOR.
5 DUCTWORK TO BE INSTALLED TIGHT TO UNDERSIDE OF STRUCTURE ABOVE UNLESS NOTED
OTHERWISE.
6 PROVIDE ALL MATERIALS, EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL
COMPLETE AND OPERABLE MECHANICAL SYSTEMS AS INDICATED ON THE DRAWINGS, AS
SPECIFIED AND AS REQUIRED BY CODE.
7 INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN ACCORDANCE WITH
MANUFACTURER'S RECOMMENDATIONS, CONTRACT DOCUMENTS, APPLICABLE BUILDING,
STATE AND LOCAL CODES, SEISMIC REQUIREMENTS, ENERGY CODES AND INSURANCE
UNDERWRITER REQUIREMENTS.
8 COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH ARCHITECTURAL,
STRUCTURAL, CIVIL AND ELECTRICAL WORK, ETC. SHOWN ON OTHER CONTRACT DOCUMENT
DRAWINGS.
9 MAINTAIN A MINIMUM OF 6-FT, 8-IN CLEARANCE TO UNDERSIDE OF PIPES, DUCTS, CONDUITS, SUSPENDED EQUIPMENT, SUPPORTS, ETC., THROUGHOUT ACCESS ROUTES IN MECHANICAL
ROOMS.
10 ALL TESTS SHALL BE COMPLETED AND ACCEPTED BY THE INSPECTOR AND COR BEFORE ANY
MECHANICAL EQUIPMENT OR PIPING INSULATION IS APPLIED.
12 LOCATE ALL TEMPERATURE, PRESSURE AND FLOW MEASURING DEVICES IN ACCESSIBLE
LOCATIONS WITH STRAIGHT SECTION OF PIPE OR DUCT UPSTREAM AND DOWNSTREAM, AS
RECOMMENDED BY THE MANUFACTURER FOR ACCURACY.
13 TESTING ADJUSTING AND BALANCING (TAB) AGENCY SHALL BE A MEMBER OF THE ASSOCIATED
AIR BALANCING COUNCIL (AABC) OR THE NATIONAL ENVIRONMENTAL BALANCING BUREAU
(NEBB). TAB FIRM SHALL HAVE A MINIMUM OF 5 YEARS EXPERIENCE ON SIMILAR PROJECTS.
PERFORM TAB IN ACCORDANCE WITH THE REQUIREMENTS OF THE TAB PROCEDURAL
STANDARD RECOMMENDED BY THE TAB TRADE ASSOCIATION THAT APPROVED THE TAB FIRM'S
QUALIFICATIONS.
14 WHERE TWO OR MORE ITEMS OF THE SAME TYPE OF EQUIPMENT ARE REQUIRED, THE
PRODUCTS OF A SINGLE MANUFACTURER SHALL BE USED.
15 COORDINATE ALL FINAL EQUIPMENT CONNECTIONS WITH THE MANUFACTURERS' CERTIFIED
DRAWINGS. COORDINATE AND PROVIDE ALL DUCTWORK AND PIPING TRANSITIONS REQUIRED
FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT. FIELD VERIFY AND
COORDINATE ALL DUCTWORK AND PIPING DIMENSIONS BEFORE FABRICATION.
16 ALL CONTROL WIRE AND CONDUIT SHALL COMPLY WITH THE NATIONAL ELECTRIC CODE,
DIVISION 26 OF THE SPECIFICATIONS, ALL LOCAL CODES, AND OWNER'S INSURANCE
UNDERWRITER REQUIREMENTS.
17 THE LOCATIONS AND SIZES OF ALL ITEMS SHOWN ON THE DRAWINGS OR CALLED FOR IN THE
SPECIFICATIONS THAT ARE NOT DEFINITELY FIXED BY DIMENSIONS ARE APPROXIMATE ONLY.
THE EXACT LOCATIONS AND SIZES NECESSARY TO SECURE THE BEST CONDITIONS AND
RESULTS SHALL BE DETERMINED BY THE PROJECT SITE CONDITIONS AND SHALL HAVE THE
APPROVAL OF THE ENGINEER BEFORE BEING INSTALLED. DO NOT SCALE DRAWINGS.
18 PLAN DRAWINGS AND SECTIONS CUTS WHICH SPECIFICALLY IDENTIFY SERVICE ROUTE
OFFSETS, ELEVATION CHANGES, OBSTRUCTIONS, ACCESS DOORS, BALANCING DEVICES, ETC.
ARE SHOWN FOR CLARITY WHERE SPECIFIC KNOWN CONDITIONS EXIST. MECHANICAL
CONTRACTOR SHALL COORDINATE EQUIPMENT, DUCTWORK, AND PIPING ROUTINGS WITH ALL
OTHER TRADES. REQUIREMENTS NOT SPECIFICALLY IDENTIFIED SHALL NOT BE INTERPRETED
AS EXCLUSION FROM CONTRACTOR'S SCOPE OF WORK. CONTRACTOR SHALL BE RESPONSIBLE
FOR ACTUAL SITE CONDITIONS AND SHALL INCLUDE SUCH CONDITIONS IN SCOPE OF WORK AT
NO ADDITIONAL COST TO THE OWNER.
19 ALL MISCELLANEOUS STEEL REQUIRED TO ENSURE PROPER INSTALLATION AND SUPPORT OF
MECHANICAL WORK AS SHOWN IN DETAILS FOR PIPING, DUCTWORK AND EQUIPMENT (UNLESS
OTHERWISE NOTED) SHALL BE FURNISHED AND INSTALLED BY THE MECHANICAL CONTRACTOR
AT NO ADDITIONAL COST TO THE OWNER.
20 ALL EQUIPMENT, PIPING, DUCTWORK, ETC., SHALL BE SUPPORTED AS DETAILED, SPECIFIED
AND AS REQUIRED TO PROVIDE A VIBRATION FREE INSTALLATION.
21 ALL OPENINGS IN FIRE RATED WALLS AND SMOKE PARTITIONS DUE TO DUCTWORK, PIPING, CONDUIT, ETC., SHALL BE FIRE STOPPED WITH APPROVED FIRESTOPPING MATERIALS.
22 REFER TO TYPICAL DETAILS FOR DUCTWORK, PIPING AND EQUIPMENT INSTALLATION.
23 UNLESS OTHERWISE SHOWN, LOCATE ALL ROOM THERMOSTATS WITH TOP AT 48-IN ABOVE
FINISHED FLOOR IN ACCORDANCE WITH ADA REQUIREMENTS. NOTIFY THE ENGINEER OF ANY
ROOMS WHERE THE ABOVE LOCATION CAN NOT BE MAINTAINED OR WHERE THERE IS A
QUESTION ON LOCATION. COORDINATE FINAL LOCATIONS WITH OWNER.
24 LOCATE ALL MECHANICAL EQUIPMENT (VAV BOXES, CABINET HEATERS, UNIT HEATERS, ETC.,)
FOR UNOBSTRUCTED ACCESS TO UNIT ACCESS PANELS, FILTERS, CONTROLS AND VALVING.
DO NOT LOCATE FAN POWERED VAV BOXES ABOVE LIGHTING FIXTURES.
25 PROVIDE FLEXIBLE CONNECTIONS IN ALL DUCTWORK SYSTEMS (SUPPLY, RETURN AND
EXHAUST) CONNECTED TO FANS AND OTHER EQUIPMENT WHICH REQUIRE VIBRATION
ISOLATION. FLEXIBLE CONNECTIONS SHALL BE PROVIDED AT THE POINT OF CONNECTION TO
THE EQUIPMENT UNLESS OTHERWISE INDICATED.
26 ALL LOUVERS SHALL BE FURNISHED AND INSTALLED BY THE GENERAL CONTRACTOR (UNLESS
OTHERWISE NOTED). GENERAL CONTRACTOR SHALL COORDINATE SIZES, LOCATIONS, AND
CONNECTIONS WITH MECHANICAL CONTRACTOR. DUCTWORK CONNECTIONS TO LOUVERS
SHALL BE FURNISHED AND INSTALLED BY MECHANICAL CONTRACTOR.
27 PROVIDE AN AIR VENT AT THE HIGH POINT OF EACH DROP IN HYDRONIC WATER PIPING
SYSTEMS. ALL PIPING SHALL SLOPE TO LOW POINTS. PROVIDE HOSE END DRAIN VALVES AT
THE BOTTOM OF ALL RISERS AND LOW POINTS.
28 INSTALL PIPING SO THAT ALL VALVES, STRAINERS, UNIONS, TRAPS, FLANGES AND OTHER
APPURTENANCES REQUIRING ACCESS ARE ACCESSIBLE.
29 ALL ISOLATION VALVES SHALL BE IN LOCATION AND ELEVATION WHICH ALLOWS FOR
EQUIPMENT AND BRANCH PIPING REMOVAL, WHILE MAINTAINING SERVICE UPSTREAM OF THE
ISOLATION VALVE.
30 ALL BALANCING VALVES AND ISOLATION VALVES USED TO ADJUST FLOW RATES SHALL BE
PROVIDED WITH POSITIONS INDICATORS AND MAXIMUM ADJUSTABLE STOPS (MEMORY STOPS).