This pre-solicitation notice is for the renovation of Laboratory Building 310 at the Dayton Veterans Affairs Medical Center in Dayton, Ohio. The contractor will provide all labor, supervision, materials and equipment for phased removal of the existing boiler system and installation of upgraded boilers with associated controls. The work must be completed within 925 calendar days of receiving the notice to proceed. The solicitation will be posted on August 21, 2020 on SAM.gov, with proposals due approximately 30 days later. This is a 100% set-aside for service-disabled veteran-owned small businesses, with a minimum of 15% of the construction work required to be performed by the prime contractor or subcontractor. Bonds will be required. The project value is between $5-10 million under NAICS code 236220. Questions can be emailed to the point of contact by the specified deadline.

View the file

Other files

Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DATE: 05/20/2021

Addendum No. 2

PROJECT NAME: Dayton Renovate Laboratory B310

DVAMC, 4100 West Third Street Dayton, Ohio 45428

This Addendum supplements and amends the original Drawings and Specifications for the above referenced project. This Addendum shall be forwarded to all Prime Bidders.

This Addendum shall be taken into account in the preparation of bids and shall become a part of the Contract Documents.

Receipt of this Addendum must be acknowledged on the Form of Proposal.

This addendum consists of xx revised drawing sheets and xx Specification sections.

General

1. N/A

Specifications

1. 12 34 23 01: Pre-Engineered and Prefabricated relocatable Building Unit

a. 2.2.B.10.g: Building will required a concrete slab. Contractor is required to provide foundation and slab design. State of Ohio registered engineer sealed drawings and calculations will be required in the submittal.

b. Soil borings are not available at the site. A building has been recently demolished in that location.

1. 13 24 23.01

a. Paragraph 2.2 B 9 b: add the following text at the end of the paragraph: “Refer to temporary building new work plan on sheet E100 and single line diagram on sheet E701 for circuiting information, panel sizes, AIC ratings, etc.”

Drawings

2. Sheet AS101: Signage Plan- Sheet reissued

a. Signage locations/types have been marked.

3. Sheet M101 (revised drawing attached)

a. Clarified duct removal requirements.

4. Sheet M102 (revised drawing attached)

a. Added TAB requirements.

b. Tagged Airflow Control Valves.

c. Moved Airflow Control Valve to Phase 2.

d. Clarified lab exhaust requirements.

5. Sheet M106 (revised drawing attached)

a. Tagged Airflow Control Valves.

b. Moved Airflow Control Valve to Phase 2.

c. Clarified lab exhaust requirements.

d. Added requirement to remove duct run.

6. Sheet M116 (revised drawing attached)

a. Added requirement for fire barrier duct wrap.

7. Sheet M119 (revised drawing attached)

a. Added requirement for fire barrier duct wrap.

b. Added requirement for straight run of ductwork at fan.

8. Sheet M602 (revised drawing attached)

a. Added Airflow Control Valves for temporary labs to schedule.

9. E Series Drawings (revised drawings attached)

a. Reprinted E Series drawings to include floor plan backgrounds due to printing issue on previously issued set.

10. Sheet E100 (revised drawing attached)

a. Revised note to clarify division of responsibility between Modular Building and

Division 26 contractors.

11. Sheet E102 (revised drawing attached)

a. Revised note and added detail to clarify drop cord receptacle requirements.

12. Sheet E701 (revised drawing attached)

a. Revised note to clarify division of responsibility between Modular Building and

Division 26 contractors.

End of Addendum No. 2

PUBLIC

TOILET

2E126

STORAGE

2E128

BSL 3 LAB

2E133

BSL 3

VESTIBULE

2E134

MICROBIOLOGY

2E137

OFFICE

ANITA

2E144

IT CLOSET

2E143

HISTOLOGY

& TISSUE

PROCESSING

2E146

OFFICE

DANA

2E136

OFFICE

DAWN

2E130

FLUORO

MICRO

2E129

ELECTRICAL

2E124

DI WATER

2E123

OFFICE

TECH

2E121

DRAW 1

2E120

DRAW 2

2E117

STAFF

DRUG

SCREEN

2E112

STAFF

TOILET

2E108

OFFICE DR.

WOOTEN

2E107

TOILET

2E106

TOILET

2E109

DRAW 3

2E119

DRAW 4

2E110

DRAW 5

2E105

DRAW 6

STRETCHER

2E104

WAITING

C2-2

BIO-MED

WORKROOM

2E127

FAMILY

VIEWING

2E138

MORGUE

VAULT

2E141

OFFICE JILL

+ 1

2E148

CONFERENCE

ROOM

2E152

STAFF

TOILET

2E150

CHIEF

OFFICE

2E156

OFFICE

2E151OFFICE

2E149

CLERICAL

AREA

2E157

OFFICE

2E154

OFFICE

2E155

OFFICE

2E153

CONFERENCE

ROOM

2E158

2ND & 3RD

SHIFT

SUPERVISOR

2E161

FORMALIN

RECYCLE

2E160

FILE

STORAGE

2E165

STORAGE

2E166

STAFF

TOILET

2E167

STAFF

TOILET

2E168

LOCKERS

2E169STAFF

LOUNGE

2E170

LOGISTICS

STORAGE

2E171

NON-LAB

STORAGE

2E172HOUSEKEEPING

2E173

HOUSEKEEPING

2E175

STORAGE

2E176

EQUIPMENT

CLOSET

2E140

VESTIBULE

2E139

SPECIMEN

DROP-OFF

2E101

RECEPTION

2E122

MECHANICAL

2E174

CORRIDOR

C2-3

CORRIDOR

C2-5

CORRIDOR

C2-1

CORRIDOR

2E118

VESTIBULE

2E111

REFRIGERATOR

2E135

INCUBATOR

2E131

EQUIPMENT

CLOSET

2E132

COMM

CLOSET

2E164

CLOSET

2E163

PUBLIC

TOILET

2E125

STAIR

SWB-2

STAIR

SWC-2

STAIR

SWD-2

STAIR

SWA-2

BIOLOGICAL

SPECIMEN

2E130A

OFFICE

2E171A

TISSUE

STORAGE

2E159

2ND & 3RD

SHIFT

SUPERVISORS

2E162

H

H

H

H

H

H

H

H

HH

H.B2

H

H

G

I

I

I

G

I

I

H.B2

G

G

G

G

G

G

G

G

J.2

G

H

G

E E.2

E.2

B

E

G

G

G

G

G G

E.2 E.2 G

J.2

E.2

G

G

E

G

G

G

E.2

G

G

H.B2

H

G

G

G

E

E.2

E.2

G

G

M.3 M.3

M.3

G

G

M.3

G

J.2

D

D D

E.2

I

M.3

M.3

M.3 M.3

M.3

M.3

M.3

M.3

M

M

M

M

M

M M

M

N

N

N

N

G

G

G

G

G

G

G G

G

G G

F

F

G

F F

G

F

F

F

F

F

F

F

B

B.3

B

B

ELECTRICAL

2E177

STORAGE

2E178

CTU

2E145

BLOOD

BANK

2E145A

CTU

2E145

ELECTRICAL

2E113

IT CLOSET

2E114

EQUIPMENT

CLOSET

2E115

WALK-IN

COOLER

2E116

CTU

2E145

CTU

2E145

COPY

2E151A

OFFICE

MONICA

2E142

BLOCK &

SLIDE

2E147

JOHN

A.

POE

IO

HO

FOET

A T

S

R E G I S

E T

R

ED RA

C H

TI

E C T

VA Project No.

JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

/1

/2

:1

:3

A

M

Renovate Laboratory

02/19/2021

SIGNAGE PLAN

AS101

NHKR

17006.00

552-18-101

Dayton, OH

310STATION

PHILIP KIRK, PE

BID SET

N Scale: 1/8" = 1'-0"

SECOND FLOOR SIGNAGE PLAN

GENERAL FINISH PLAN NOTES

A. All walls to be painted P-1, unless otherwise noted. See Finish Legend and Finish Schedule.

B. All metal door frames to be painted P-6 in Gloss Level 5, unless otherwise noted. See Finish Legend.

C. Provide appropriate flooring transition pieces at all unlike flooring material intersections. All schluter trim to be anodized aluminum finish. All johnsonite/tarkett transitions to match RB-1 finish color.

D. All exposed gyp. ceilings as well as underside and faces of bulkheads/ soffits to be painted.

Underside of bulkhead/soffit to be painted P-5; unless noted otherwise. Refer to finish legend and reflected ceiling plans for extents and finish requirements.

E. Refer to door schedule for clarification of door materials.

F. All exposed gyp. walls to be painted unless noted otherwise.

G. All diffusers to be painted to match adjacent wall finish.

H. All new and existing window sills to be soild surface, SS-3.

J. Refer to interior elevations for casework finish locations.

K. Where new finishes would match existing finishes, or new finishes are not required, maintain existing finishes where possible during demolition and construction phase for reuse. Patch and paint existing finishes where disturbed by construction.

L. Refer to wall protection plan for locations and extents ( I.E corner guards, handrails, crash rails, rigid wall protection).

M. All flooring to be installed continuous under all casework.

N. All restroom countertops to be (SS-2).

O. Products of other manufacturer's equivalent to colors, finishes, textures and patterns of manufacturers listed that meet requirements of technical specifications shall be acceptable upon approval in writing by contracting officer for finish requirements.

SIGNAGE SCHEDULE

MARK MOUNTING HEIGHT

B 54" A.F.F. TO TOP

B.3 54" A.F.F. TO TOP

D 54" A.F.F. TO TOP

E 54" A.F.F. TO TOP

E.2 54" A.F.F. TO TOP

F 54" A.F.F. TO TOP

G 54" A.F.F. TO TOP

H 54" A.F.F. TO TOP

H.B2 54" A.F.F. TO TOP

I 54" A.F.F. TO TOP

J.2 54" A.F.F. TO TOP

M 84" A.F.F. TO TOP

M.3 MOUNTED TO CEILING

N 54" A.F.F. TO TOP

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290

DEDUCT ALT #3

DEDUCT ALT #2

Revisions Date

6 Addendum #2 05.20.2021

IB

T

T

T

T

T

T

T

T

T T

T

T

T

T

T

T

T

T

T

T

T

T T

T

E.1 G H J K L

M P

EF8

AH8

AH5

AH6

EF6

AH5

x1 x1 x1 x8 x81"

H

W S

2"

H W

R x1 x1 ø

1.

H W

S 2"

H

W R x7 x7

1 3

7 7 x8 x8

1.5" - MPC

1.5" - MPS

7 7 7

7 7

7 7

12ø

12ø

32x12 - EA

EF13

EF12

EF13

EF11

EF13

x1 x1 ø

(5)

(30)

CTU

2E145

BLOOD BANK

2E145A

CAPPED

1400 W Dorothy Lane, Dayton, OH 45409

P: 937-224-0861 www.heapy.com

VA Project No.

JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

HEAPY PROJECT No.: 2018-05007 OHIO COA FIRM No.: 05128

/1

/2

:1

:5

P M

Renovate Laboratory

02/19/2021

2ND FLR PLAN - PH1 - REMOVALS

M101

W JSBGA

17006.00

552-18-101

Dayton, Ohio

310STATION

PHILIP KIRK, PE

BID SET

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290

N Scale:

PLAN

1/8" = 1'-0"1

SECOND FLOOR PLAN PHASE 1 - REMOVALS

GENERAL NOTES

A. REFER TO SHEET M001 FOR LEGEND, KEY PLAN, ABBREVIATIONS, AND GENERAL NOTES.

NOTES

1. EXISTING DUCTW ORK TO REMAIN.

2. EXISTING PIPING TO REMAIN.

3. EXISTING AIR TERMINAL UNIT TO REMAIN.

4. EXISTING EXHAUST HOOD TO REMAIN.

5. PHASE AS DEPICTED ON ARCHITECTURAL PLANS. ALL W ORK OUTSIDE OF BOUNDARY

SHALL TAKE PLACE DURING OFF HO URS (9PM-5AM)

6. EXISTING FAN COIL UNIT TO REMAIN.

7. EXISTING AIR DEVICE TO REMAIN.

8. EXISTING EXHAUST DUCTS UP TO 4TH FLOOR TO REMAIN.

9. EXISTING TRANSFER DUCT AND AIR DEVICES TO REMAIN.

10. EXISTING THERMOSTAT TO REMAIN.

11. REMOVE EXISTING DUCTW ORK AND ASSOCIATED SUPPORTS, ETC.

12. REMOVE DUCTW ORK TO THIS POINT AND CAP.

13. REMOVE DUCT TO THIS POINT FOR RECONNECTION IN NEW W ORK.

14. REMOVE EXISTING AIR DEVICE FOR RELOCATION IN NEW W ORK TO ACCOMMODATE

NEW W ALL.

15. REMOVE SECTION OF DUCTW ORK AS REQUIRED FOR CONNECTION IN NEW W ORK.

16. REMOVE DUCTW ORK FROM FUME HOOD BACK TO POINT INDICATED FOR RECONNECTION

IN NEW W ORK. DECOMMISSIONED HOOD TO REMAIN UNTIL PHASE 3.

Revisions Date

1 ADDENDUM 2 05/20/21

T

T

T

T

T

T

T

T T

T

T

T

T

T

T

T

T

T

T

T

T T

T

E.1 G H J K L

M P

STAIR

SW B-2 STAIR

SW C-2

STAIR

SW D-2

STAIR

SW A-2

x1 x1 x1 x1 x1 ø x1

22x12 x1 x7 9x x8

14x5 - EA

32x12

R

7 7 7

7 7 x8 x8 x8 x8

1 .5" - MPS

1.5" - MPC

12ø

12ø

AH5

AH6

EF6

AH5

EF8

AH8

2E116FT

HISTOLOGY

TEMP

2E116FT

HISTOLOGY

TEMP

2E116B

TOXICOLOGY

2E116GT

MICROBIOLOGY

TEMP

10x5

10x6 10x5

13 30 x1

12ø

8ø

6ø

10ø ø

AV-1

ø

10x5 10x514x6

1 1

AV-2

AV-3

12ø12ø 12ø12ø

12ø

1 12 ø

1400 W Dorothy Lane, Dayton, OH 45409

P: 937-224-0861 www.heapy.com

VA Project No.

JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

FULLY SPRINKLERED

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

HEAPY PROJECT No.: 2018-05007 OHIO COA FIRM No.: 05128

/1

/2

:5

:3

P M

Renovate Laboratory

02/19/2021

2ND FLR PLAN - PH1 - DUCTWORK

M102

W JSJPR

17006.00

552-18-101

Dayton, Ohio

310STATION

PHILIP KIRK, PE

BID SET

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290

N Scale:

PLAN

1/8" = 1'-0"1

SECOND FLOOR PLAN PHASE 1 - DUCTWORK

GENERAL NOTES

NOTES

1. EXISTING DUCTW ORK TO REMAIN.

2. EXISTING EXHAUST DUCTS UP TO 4TH FLOOR.

3. EXISTING AIR TERMINAL UNIT TO REMAIN.

4. EXISTING THERMOSTAT TO REMAIN.

5. PHASE AS DEPICTED ON ARCHITECTURAL PLANS. ALL W ORK OUTSIDE OF BOUNDARY

SHALL TAKE PLACE DURING OFF HO URS (9PM-5AM)

6. EXISTING FAN COIL UNIT TO REMAIN. BALANCE TO INDICATED CFM.

7. EXISTING AIR DEVICE TO REMAIN. BALANCE TO INDICATED CFM.

8. EXISTING EXHAUST HOOD TO REMAIN.

9. EXISTING TRANSFER DUCT AND AIR DEVICES TO REMAIN.

10. CONNECT EXHAUST TO HOOD/EQUIPMENT PER MANUFACTURERS RECOMMENDATIONS.

TRANSITION AS REQUIRED. APPROXIMATE CFM SHOW N. COORDINATE EXACT AIR FLOW

W ITH COR. BASED ON PURCHASED EQUIPMENT.

11. RELOCATE AIR DEVICES AS REQUIRED TO ACCOMMODATE NEW W ALL. EXTEND

DUCTW ORK ACCORDINGLY. BALANCE TO INDICATED CFM.

12. BALANCE EXISTING ATU TO INDICATED CFM.

13. PROVIDE DUCT FOR FUTURE PHASE.

14. CAP DUCT FOR EXTENSION IN FUTURE PHASE.

A. REFER TO SHEET M001 FOR LEGEND, KEY PLAN, ABBREVIATIONS, AND GENERAL NOTES.

Revisions Date

1 ADDENDUM 2 05/20/21

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T T

T

T

T

T

T

T

T

T

T

T

T

T T

T

E.1 G H J K L

M P x9

S

A x7

S A

44x20 - SA 30x26 - SA x1

S A

44x24 - SA x1

S A

44x18 - SA

16x14 x1

S A x1

32x16 - SA 30x16 - SA x1

S A x1 x8 x1

24x10 - RA x6

R

A

18x6 - RA x6

R

A x1

E A x1

E A x1

E A x1

E A x2

30x22 - EA

22x8 - EA

10x6 - EA

26x18 - SA x1

S A

30x24 - EA

36x30 - EA x2

E A

28x25 - RA x2

R A x2

E A x2

E A x1

E A x5

E

A

33x33 - RA

5-211

5-211

8ø

CD1

160 CFM

5-212

6ø

CD1

100 CFM

6ø

CD1

100 CFM

8ø

CD1

170 CFM

5-214

6ø

CD1

100 CFM

6ø

CD1

130 CFM

6ø

CD1

50 CFM

6ø

CD1

120 CFM

5-204

8ø

CD1

200 CFM

5-215

6-203

6-202

6-203

6-202

8ø

CD1

200 CFM

6-201 6-201

6ø

CD1

100 CFM

8ø

CD1

155 CFM

6ø

CD1

85 CFM

6ø

CD1

100 CFM

8ø

CD4

285 CFM

6-207

6-207

8ø

CD4

195 CFM

8ø

CD4

195 CFM

5-235

5-235

6-210

6-209

6-208

6-208

5-234

8-202

5-233

8-201

8-202

5-213

5-213

8ø

CD1

200 CFM

5-2045-203

5-203

8ø

CD1

220 CFM8ø

CD1

180 CFM

6ø

CD1

100 CFM

24x12

275 CFM

CG1

8ø

CD3CD3

225 CFM

8ø

CD1

150 CFM

D

20x18 - SA x1

20x18 - SA

8x6 - SA x1

S A

20x18 - SA

10ø

(5)CD1

320 CFM

10ø

(4)CD1

260 CFM

x4

E

A

8x6 - SA

10ø

CD1

310 CFM

x1

S A

10ø

(6)CD1

285 CFM

20x18 - SA

12ø

(6)CD1

395 CFM

6x

6x8

6x10 - SA

8ø

(2)CD1

140 CFM 8x10

5-214

5-227

5-234

5-223

5-228

AH-6

8x8

24x12

180 CFM

CG1

24x12

200 CFM

CG1

24x12

120 CFM

CG1

24x12

100 CFM

CG1

24x12

100 CFM

CG1

24x12

100 CFM

CG1

24x12

100 CFM

CG1

24x12

390 CFM

CG1

8ø

CG1

150 CFM

24x10 - RA

AH5

EF6

AH5

EF8

AH8

EF13

EF12

EF13

EF11

EF13

44x20 - SA

5-227

12x24

70 CFM

CG1

24x12

255 CFM

CG1

x1

S A x1

E A

30x16 - SA

24x12

310 CFM

CG1

5-215

5-229

5-229

5-226

5-226 10x8

220 CFM

TR1

2E166

STORAGE

2E162

2ND & 3RD

SHIFT

SUPERVISORS

2E165

FILE

STORAGE

2E161

2ND & 3RD

SHIFT

SUPERVISOR

2E160

FO RMALIN

RECYCLE

2E146

HISTOLOGY

& TISSUE

PROCESSING

C2-10

BLOCK &

SLIDE

2E143

IT CLOSET

2E144

OFFICE

ANITA

C2-9

OFFICE

MONICA

2E141

MORGUE

VAULT

2E139

VESTIBULE

2E140

EQUIPMENT

CLOSET2E137

MICROBIOLOGY

2E136

OFFICE

DANA

2E130A

BIOLOGICAL

SPECIMEN

2E133

BSL 3 LAB

2E134

BSL 3

VESTIBULE

2E128

STORAGE

2E126

PUBLIC

TOILET

2E125

PUBLIC

TOILET

2E127

BIO-MED

WORKROOM

2E129

FLUORO

MICRO

2E131

INCUBATOR

2E172

NON-LAB

STORAGE

2E170

STAFF

LO UNGE

2E171A

OFFICE

2E169

LOCKERS

2E167

STAFF

TOILET

C2-5-3

CORRIDOR-3

6ø

CD1

105 CFM

5-212 ø

S

A

8ø

CD3CD3

105 CFM

8ø

CD3CD3

105 CFM

6-209 x1

S A x3

5-223

2E130

OFFICE

DAWN

8ø

CD1

230 CFM

10x10

8x10 x1

S A

12x8

12x10 12 x8

12x12

24x12

100 CFM

CG1

24x12

160 CFM

CG1

24x12

100 CFM

CG1

10x8

220 CFM

TR2TR2

2E138

FAMILY

VIEWING

10x8 - RA x8

12ø

CG1

520 CFM

24x12

85 CFM

CG1

24x12

90 CFM

CG1

6x

12x12

150 CFM

TR2

6-210 x1

S A

24x12

50 CFM

CG1

V-01

V-02

8ø

CD1

275 CFM8x

10'-2"

2E168

STAFF

TOILET

10x8 - SA

12x24

70 CFM

CGI

x1

E A

10x8

10x12

12x12

AC-2E141

AC-2E143

CU-2E135

R

8x6

50 CFM

TR2

12ø x1

E A

10x8

10x810x8 x1

E A

12x8

12x8

12x8 - RA

26x18 - SA

24x16

5-230

8x6

150 CFM

TR1

24x12

150 CFM

CG1

10x10

8ø

CD3CD3

105 CFM

8ø

CD1

185 CFM

18x1012ø

8-201

14x12 12ø

12ø

30x14 x1 x1

V-03 1 24x24

2345 CFM

(2) CG1

V-04

V-05

12ø

12ø

V-12

V-13

V-11

V-10

12ø

12ø

1400 W Dorothy Lane, Dayton, OH 45409

P: 937-224-0861 www.heapy.com

VA Project No.

JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

FULLY SPRINKLERED

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

HEAPY PROJECT No.: 2018-05007 OHIO COA FIRM No.: 05128

/1

/2

:0

:0

P M

Renovate Laboratory

02/19/2021

2ND FLR PLAN - PH2 - DUCTWORK

M106

W JSBGA

17006.00

552-18-101

Dayton, Ohio

310STATION

PHILIP KIRK, PE

BID SET

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290

N Scale:

PLAN

1/8" = 1'-0"1

SECOND FLOOR PLAN PHASE 2 - DUCTWORK

GENERAL NOTES

NOTES

1. EXISTING DUCTW ORK TO REMAIN.

2. CAP DUCT FOR EXTENSION IN FUTURE PHASE.

3. PHASE AS DEPICTED ON ARCHITECTURAL PLANS. ALL W ORK OUTSIDE OF BOUNDARY

SHALL TAKE PLACE DURING OFF HO URS (9PM-5AM).

4. CONTINUE DUCT OVER AND UP THRU THE ROOF. REFER TO SHEET M120.

5. CONNECT EXHAUST TO HOOD/EQUIPMENT PER MANUFACTURERS RECOMMENDATIONS.

TRANSITION AS REQUIRED. PROVIDE MANUAL DAMPER AND BALANCE ACCORDINGLY.

APPROXIMATE CFM SHOW N. COORDINATE EXACT AIRFLOW W ITH COR BASED ON

PURCHASED EQUIPMENT.

6. CONNECT EXHAUST TO HOOD/EQUIPMENT PER MANUFACTURERS RECOMMENDATIONS.

TRANSITION AS REQUIRED. APPROXIMATE CFM SHOW N. COORDINATE EXACT AIRFLOW

W ITH COR BASED ON PURCHASED EQUIPMENT.

7. UPON COMPLETION OF PHASE 2 AND AFTER PHASE 1 IS NO LONGER BEING UTILIZED BY

VA STAFF ( MOVE-IN PERIOD FOR PHASE 2), REMOVE SECTION OF DUCTW ORK AS

REQUIRED AND CONNECT NEW EXHAUST DUCTW ORK TO RISER.

8. UPON COMPLETION OF PHASE 2 AND AFTER PHASE 1 IS NO LONGER BEING UTILIZED BY

VA STAFF ( MOVE-IN PERIOD FOR PHASE 2), REMOVE SECTION OF DUCTW ORK.

A. REFER TO SHEET M001 FOR LEGEND, KEY PLAN, ABBREVIATIONS, AND GENERAL NOTES.

Revisions Date

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

E.1 G H J K L

M P x9

S

A x7

S A x6

S

A x2

S A x2

S A x1

S A x1

S A

24x10 - RA x1

R A x1

E A x1

E A x1

E A

15x10 - EA x6

E

A x5

E A

14x5 - EA x1

E

A

12x3 - EA x1

E A

32x12 - EA x5

E

A

5-212

5-205

8ø

CD1

170 CFM

5-215

10ø

CD1

225 CFM

10ø

CD1

225 CFM

10ø

CD1

320 CFM

6-206

6-205

6-209

5-203

6ø

CD1

100 CFM

6-204

10ø

CD1

320 CFM

10ø

CD1

285 CFM

10ø

CD1

285 CFM

10ø

CD1

285 CFM

10ø

CD1

285 CFM

10ø

CD1

400 CFM

6ø

CD1

60 CFM

10ø

CD1

335 CFM

10ø

CD1

335 CFM

10ø

CD1

335 CFM

10ø

CD1

335 CFM

10ø

CD1

335 CFM

10ø

CD1

335 CFM

10ø

CD1

275 CFM10ø

CD1

275 CFM

10ø

CD1

270 CFM

10ø

CD1

390 CFM

10ø

CD1

395 CFM

10ø

CD1

395 CFM

10ø

CD1

390 CFM

10ø

CD1

395 CFM

10ø

CD1

395 CFM

12x10 - SA x1

S A

8x

S

A

12x8 - SA

8ø

CD1

320 CFM

x8

S

A

10ø

CD1

285 CFM

5-231

5-207

5-208 x8

S

A x6

R

A

AH5

AH6

EF6

AH5

EF8

AH8

ø

S

A

24x24

1130 CFM

(2)CG1

24x24

990 CFM

CG1

24x12

75 CFM

CG1

x1

S

A

14x12 - SA x1

S A x1

S A

6ø - EA

8-205

8-204

8-205

2E145

CTU

2E113

ELECTRICAL

2E116

WALK-IN

REFRIGERATOR

2E115

EQUIPMENT

CLOSET

2E114

IT CLOSET

2E145A

BLOOD

BANK

2E178

STORAGE

OFFICE TECH

2E121

10ø

CD1

395 CFM

10ø

CD1

390 CFM

10ø

CD1

395 CFM

x1

S A

14x14 x1

S A x1

S A x1

S A

8ø - SA x1

S A

8x6 - RA

8x6

70 CFM

H1

6x6

40 CFM

H1

6x6

40 CFM

F1

6x6

70 CFM

F1

V-01

V-02

V-03

V-04

V-05

V-06

V-07

20x16

V-08

V-09

V-10

V-12

V-14

V-15

4ø 4ø

6ø

AC-2E116

V-11

24x24

550 CFM

CG1

24x24

1000 CFM

CG1

10ø

CD1

400 CFM

x1 x1

S A x1

S A

12x8 - RA

10ø

CD1

320 CFM24x12

200 CFM

CG1

20x16 x1

1400 W Dorothy Lane, Dayton, OH 45409

P: 937-224-0861 www.heapy.com

VA Project No.

JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

FULLY SPRINKLERED

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

HEAPY PROJECT No.: 2018-05007 OHIO COA FIRM No.: 05128

/1

/2

:5

:5

P M

Renovate Laboratory

02/19/2021

2ND FLR PLAN - PH5 - DUCTWORK

M116

W JSBGA

17006.00

552-18-101

Dayton, Ohio

310STATION

PHILIP KIRK, PE

BID SET

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290

GENERAL NOTES

NOTES

1. EXISTING DUCTW ORK TO REMAIN.

2. PHASE AS DEPICTED ON ARCHITECTURAL PLANS. ALL W ORK OUTSIDE OF BOUNDARY

SHALL TAKE PLACE DURING OFF HO URS (9PM-5AM).

3. EXTEND 4" DUCT DOW N W ALL NEAR EQUIPMENT #90 AND TERMINATE 3'-0" AFF. PROVIDE

CONNECTION FOR 1/2" ID TUBING FROM EQUIPMENT #90. TUBING DISTANCE NOT TO

EXCEED 15'-0" IN LENGTH. PROVIDE MANUAL DAMPER IN DUCT BELOW CEILING.

4. PROVIDE 2 HOUR RATED FIRE BARRIER DUCT W RAP ON DUCTW ORK AND HANGERS

W ITHIN 10 FEET OF FIRE BARRIER.

N Scale:

PLAN

1/8" = 1'-0"1

SECOND FLOOR PLAN PHASE 5 - DUCTWORK

A. REFER TO SHEET M001 FOR LEGEND, KEY PLAN, ABBREVIATIONS, AND GENERAL NOTES.

Revisions Date

1 ADDENDUM 2 05/20/21

AFM S

AFM S

AFM S

G H J K L

M P

310-HRC2

310-RF5

310-AHU6

AH5

AH8

EF-8

310-HRC3

36x30 - EA

60x28 - EA x2

E A

32x22 - EA

28x25 - RA

38x60 - RA x3

R A

42x32 - RA

46x24 - R A

28x25 - EA

25x18 - SA

20x24 - EA x2

E A

2"

301"

1" COND. DN

INTERSTITIAL

SPACE ABOVE

O.R. SUITE

AF-6

C H

R

C H

S

C H

R

C H

S

6"

6"

CHR

CHS

310-SF6

PF-6

PF-5

AF-5

310-EF14

310-EF6

AH5

AH6

EF6

AH5

EF8

AH8

EF13

EF12

EF13

EF11

EF13

AF-6

AH5

310-EF6

AH8

AF-8

PF-8 10

AF-10

36x30 - EA

UP

1400 W Dorothy Lane, Dayton, OH 45409

P: 937-224-0861 www.heapy.com

VA Project No.

JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

HEAPY PROJECT No.: 2018-05007 OHIO COA FIRM No.: 05128

/1

/2

:2

:5

P M

Renovate Laboratory

02/19/2021

4TH FLR PLAN - PH5 - NEW WORK

M119

W JSBGA

17006.00

552-18-101

Dayton, Ohio

310STATION

PHILIP KIRK, PE

BID SET

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290

GENERAL NOTES

NOTES

1. EXISTING DUCTW ORK TO REMAIN.

2. EXISTING PIPING TO REMAIN.

3. EXISTING AIR HANDLING UNIT TO REMAIN .

4. DUCT DOW N TO SECOND FLOOR. REFER TO SHEET MD102 FOR CONTINUATION.

5. REPLACE EXISTING AFTERFILTERS [(6) 24x24x36] UPON COMPLETION OF PHASE 5 NEW

W ORK. CHANGE FILTERS AFTER NORMAL W ORK HOURS SO FILTERS ARE NOT BEING

CLEANED DURING DEMOLITION W ORK.

6. REPLACE EXISTING PREFILTERS [(6) 24x24x15] UPON COMPLETION OF PHASE 5 NEW

W ORK. CHANGE FILTERS AFTER NORMAL W ORK HOURS SO FILTERS ARE NOT BEING

CLEANED DURING DEMOLITION W ORK.

7. REPLACE EXISTING AFTERFILTERS [(8) 24x24x36] UPON COMPLETION OF PHASE 5 NEW

W ORK. CHANGE FILTERS AFTER NORMAL W ORK HOURS SO FILTERS ARE NOT BEING

CLEANED DURING DEMOLITION W ORK.

8. REPLACE EXISTING PREFILTERS [(8) 24x24x15] UPON COMPLETION OF PHASE 5 NEW

W ORK. CHANGE FILTERS AFTER NORMAL W ORK HOURS SO FILTERS ARE NOT BEING

CLEANED DURING DEMOLITION W ORK.

9. REPLACE EXISTING AFTERFILTERS [(2) 24x24x36] UPON COMPLETION OF PHASE 5 NEW

W ORK. CHANGE FILTERS AFTER NORMAL W ORK HOURS SO FILTERS ARE NOT BEING

CLEANED DURING DEMOLITION W ORK.

10. REPLACE EXISTING PREFILTERS [(2) 24x24x15] UPON COMPLETION OF PHASE 5 NEW

W ORK. CHANGE FILTERS AFTER NORMAL W ORK HOURS SO FILTERS ARE NOT BEING

CLEANED DURING DEMOLITION W ORK.

11. PROVIDE 2 HOUR RATED FIRE BARRIER DUCT W RAP ON DUCTW ORK AND HANGERS

W ITHIN 10 FEET OF FIRE BARRIER.

12. PROVIDE MINIMUM 3 DUCT DIAMETERS STRAIGHT RUN AT INLET AND OUTLET OF FAN.

PROVIDE CHEMICAL RATED FLEXIBLE DUCT CONNECTORS.

N Scale:

PLAN

1/8" = 1'-0"1

FOURTH FLOOR PLAN PHASE 5

A. REFER TO SHEET M001 FOR LEGEND, KEY PLAN, ABBREVIATIONS, AND GENERAL NOTES.

Revisions Date

3 PROVIDE HOSPITAL GRADE SOUND ATTENUATOR WHERE REQUIRED TO CONFORM TO THE MAXIMUM NC35 REQUIREMENT.

5 HEATING COIL CAPACITY BASED ON WINTER MINIMUM CFM.

ABSORPTION COFFICIENT (REFERENCE 10 [-12] WATTS) WITH 3" S.P. DIFFERENTIAL ACROSS UNIT AT MAXIMUM CFM SETTING.

1 PROVIDE DUCT TRANSITION AT UNIT INLET WHERE UNIT INLET SIZE AND DUCT RUNOUT SIZE ARE DIFFERENT.

THE MINIMUM PRESSURE REQUIRED AT THE UNIT INLET TO OBTAIN THE RATED CFM.

6 CONTROL TYPES: V.V.R.: VARIABLE VOLUME REHEAT TERMINAL; C.V.R.: CONSTANT VOLUME REHEAT TERMINAL

2 THE UNIT MAXIMUM SP IS THE PRESSURE DIFFERENCE BETWEEN THE UNIT INLET AND DISCHARGE INCLUDING REHEAT COIL AND SOUND ATTENUATOR. IT IS ALSO

4 UNIT NOISE LEVEL SELECTION SHALL NOT EXCEED A ROOM NC OF 35 FROM BOTH AIRBORNE AND RADIATED NOISE, BASED ON A 10 DB ROOM

NOTES :

7 AIR TERMINAL UNIT WITH LISTED CFM SHALL BE CONTROLLED THRU ECC WITH PROGRAMMABLE OCCUPIED/UNOCCUPIED TIMES AND/OR BE CONNECTED TO OCCUPANCY SENSOR(S). PROVIDE OCCUPANCY SENSORS AND ASSOCIATED WIRING WHERE NOT PROVIDED BY DIV. 26.

REFER TO DIV. 26 SPECIFICATIONS FOR PRODUCT REQUIREMENTS. REFER TO "HVAC DESIGN DATA" SCHEDULE ON SHEET M601 FOR UNOCCUPIED TEMPERATURES.

AIR TERMINAL UNIT SCHEDULEAIR VALVE SCHEDULE

1400 W Dorothy Lane, Dayton, OH 45409

P: 937-224-0861 www.heapy.com

VA Project No.

JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

HEAPY PROJECT No.: 2018-05007 OHIO COA FIRM No.: 05128

/1

/2

:2

:2

P M

Renovate Laboratory

02/19/2021

SCHEDULES

M602

W JSBGA

17006.00

552-18-101

Dayton, Ohio

310STATION

PHILIP KIRK, PE

BID SET

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290

FIRE ALARM SYMBOLSELECTRICAL SYMBOLS

EXISTING OUTLET OR DEVICE TO REMAIN. MAINTAIN EXISTING CIRCUITING.

DASH SYMBOL INDICATES PARTICULAR OUTLET OR DEVICE TO BE REMOVED AND CIRCUITRY MADE CONTINUOUS WHERE

REQUIRED.

ELECTRICAL CONNECTION.

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERWISE). WHEN SHOWN, RECEPTACLE TO HAVE

"CONTROLLED" MARKINGS.

20A-125V SINGLE RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERWISE).

SPECIAL PURPOSE RECEPTACLE. REFER TO NOTE ON PLAN.

20A-125V DOUBLE DUPLEX RECEPTACLE. NEMA 5-20R, (18" MH UNLESS NOTED OTHERWISE) TWO GANG ASSEMBLY.

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R WITH BOTTOM OUTLET CONTROLLED BY WALL SWITCH. (18" MH UNLESS

NOTED OTHERWISE).

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R, WITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH UNLESS NOTED

OTHERWISE).

20A-125V WEATHERPROOF DUPLEX RECEPTACLE, NEMA 5-20R (HORIZONTAL 18" MH UNLESS NOTED OTHERWISE) WITH

STANDARD COVER, VERTICAL MOUNT.

20A-125V WEATHERPROOF DUPLEX RECEPTACLE, NEMA 5-20R WITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH

UNLESS NOTED OTHERWISE), WITH STANDARD COVER, VERTICAL MOUNT.

20A-125V POWERLOCK GROUNDING TYPE RECEPTACLE, HOSPITAL USE (66" MH UNLESS NOTED OTHERWISE).

20A-125V DUPLEX TOMBSTONE TYPE RECEPTACLE, NEMA 5-20R WITH COVERPLATE AND HOUSING. MOUNTED ON LAB

TABLE. COORDINATE INSTALLATION WITH FURNITURE PROVIDER.

20-125V DUPLEX RECEPTACLE, NEMA 5-20R, WITH ISOLATED GROUND (18" MH UNLESS NOTED OTHERWISE).

20A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-20R (18" MH UNLESS NOTED OTHERWISE).

30A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-30R (18" MH UNLESS NOTED OTHERWISE).

50A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-50R (18" MH UNLESS NOTED OTHERWISE).

20A-250V-3PH-4W SINGLE RECEPTACLE, NEMA 15-20R (18" MH UNLESS NOTED OTHERWISE).

30A-250V-3PH-4W SINGLE RECEPTACLE, NEMA 15-30R (18" MH UNLESS NOTED OTHERWISE).

50A-250V-3PH-4W SINGLE RECEPTACLE, NEMA 15-50R (18" MH UNLESS NOTED OTHERWISE).

JUNCTION BOX. SQUARE DEVICE INDICATES A CONNECTION TO CRITICAL POWER.

MULTI-OUTLET RECEPTACLES ASSEMBLY, NEMA 5-15R (SINGLE OUTLETS ON 18" CENTERS) (46" MH UNLESS NOTED

OTHERWISE).

CLOCK HANGER OUTLET, SINGLE NEMA 5-15R RECESSED IN COVER PLATE (84" MH UNLESS NOTED OTHERWISE).

SINGLE POLE SWITCH (46" MH UNLESS NOTED OTHERWISE).

TWO POLE WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).

MULTI-WAY WALL SWITCH, # INDICATES NUMBER OF WAYS (46" MH UNLESS NOTED OTHERWISE).

SWITCH WITH NEON PILOT LIGHT. ONE-GANG ASSEMBLY (46" MH UNLESS NOTED OTHERWISE).

KEY OPERATED WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).

LIGHTING DIMMER SWITCH (46" MH UNLESS NOTED OTHERWISE) 0-10V UNLESS OTHERWISE INDICATED.

SWITCH WITH INTEGRAL OCCUPANCY SENSOR AND ON/OFF OVERRIDE (46" MH UNLESS NOTED OTHERWISE).

FLUSH FRACTIONAL HORSEPOWER MOTOR STARTER WITH NEON PILOT LIGHT. ONE-GANG ASSEMBLY (46" MH UNLESS

NOTED OTHERWISE).

HP RATED WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).

DISCONNECT SWITCH.

MOTOR STARTER.

COMBINATION MOTOR STARTER AND DISCONNECT SWITCH.

ELECTRIC MOTOR.

ELECTRICAL PANEL OR SWITCHBOARD PER DRAWINGS.

PULL BOX.

LINE VOLTAGE THERMOSTAT.

UNIT HEATER.

FAN COIL.

ELECTRIC BASEBOARD HEATER.

AIR CONDITIONER.

CONDENSING UNIT.

UNIT VENTILATOR.

CORD REEL.

DUAL SERVICE, POWER AND COMMUNICATIONS POWER POLE.

PHOTOELECTRIC SENSOR.

LIGHTING CONTRACTOR.

CEILING MOUNTED OCCUPANCY SENSOR.

WALL MOUNTED OCCUPANCY SENSOR.

CEILING MOUNTED DAYLIGHT SENSOR.

OCCUPANCY SENSOR POWER PACK.

FIRE ALARM SPEAKER & SIGNAL LIGHT (80" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN TOILET ROOMS AND 75 CANDELA FOR ALL OTHER LOCATIONS.

FIRE ALARM SIGNAL LIGHT (80" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN TOILET ROOMS AND 75 CANDELA FOR ALL OTHER LOCATIONS.

PUSHBUTTON (46" MH UNLESS NOTED OTHERWISE) EDWARDS 852 (120 VOLT).

BUZZER (90" MH UNLESS NOTED OTHERWISE) EDWARDS 340-A (120 VOLT).

4" DIAMETER (90" MH UNLESS NOTED OTHERWISE) EDWARDS "ADAPTABEL" (120 VOLT).

NURSE CALL SYMBOLS

NURSE CALL DESK MOUNTED MASTER CONTROL STATION (OUTLET AT 18" MH UNLESS NOTED OTHERWISE). SUBSCRIPT

"W" INDICATES WALL MOUNT (46" MH UNLESS NOTED OTHERWISE).

NURSE CALL CONTROL PANEL.

NURSE CALL STAFF STATION (46" MH UNLESS NOTED OTHERWISE).

NURSE CALL DUTY STATION (46" MH UNLESS NOTED OTHERWISE).

EMERGENCY NURSE CALL STATION WITH PULL CORD FOR PATIENT USE (46” MH AND TO SIDE AND WITHIN 12” FROM FRONT OF TOILET BOWL IN TOILET ROOMS, 66” MH IN SHOWERS AND WET AREAS, 46” MH UNLESS NOTED OTHERWISE IN

ALL OTHER AREAS).

PATIENT NURSE CALL UTILITY CONSOLE (46" MH UNLESS NOTED OTHERWISE).

PATIENT NURSE CALL STATION (ONE OR TWO CORDS AS INDICATED, 46" MH UNLESS NOTED OTHERWISE).

CEILING MOUNTED NURSE CALL DOME LIGHT.

WALL MOUNTED NURSE CALL DOME LIGHT (90" MH UNLESS NOTED OTHERWISE).

CEILING MOUNTED COMBINATION DOME LIGHT AND BUZZER.

CEILING MOUNTED NURSE CALL ZONE LIGHT.

NURSE CALL EMERGENCY BUTTON (46" MH UNLESS NOTED OTHERWISE).

EMERGENCY CODE BLUE BUTTON (46" MH UNLESS NOTED OTHERWISE).

GF

WP

WP/GF

T

IG

20A

30A

50A

20A

50A

30A

J

P

K

DM

OS

H

UH

FC

AC

CU

UV

PP

OS

M

OS

M

DS

OP

PC

T

F

F

S F

CEILING MOUNTED FIRE ALARM SPEAKER.

B

FIRE ALARM CONTROL PANEL.

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R (46" MH UNLESS NOTED OTHERWISE).

C

M

CR

LC

N

N

N B

N Z

NC

NS

ND

N

W

NM

N T

N E

N B

P/B

ELAPSED TIME INDICATOR CLOCK (90" MH UNLESS NOTED OTHERWISE) WITH RESET SWITCH (46" MH UNLESS NOTED

OTHERWISE).

INTERCOM SYSTEM DESK MOUNTED MASTER CONTROL STATION. SUBSCRIPT "W" INDICATES WALL MOUNT (46" MH

UNLESS NOTED OTHERWISE).

INTERCOM STAFF STATION (46" MH UNLESS NOTED OTHERWISE).

INTERCOM HORN TYPE SPEAKER (84" MH UNLESS NOTED OTHERWISE).

INTERCOM SPEAKER FLUSH MOUNT IN CEILING.

I

M

H

S

FACP

NCCP

AV SYMBOL

S H

SURFACE MOUNTED PAGING/INTERCOM SPEAKER (90" MH UNLESS NOTED OTHERWISE). SUBSCRIPT "H" INDICATES HANGING CEILING SPEAKER. 1-GANG BOX WITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. SPEAKER, INSTALLATION

AND CABLING PER DIV 27.

S HORN TYPE PAGING/INTERCOM SYSTEM SPEAKER (90" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. GROMMETED FACEPLATE, SPEAKER, INSTALLATION AND WIRING PER DIV 27.

V PAGING/INTERCOM SYSTEM WALL MOUNTED SPEAKER VOLUME CONTROLLER (46" MH UNLESS NOTED OTHERWISE). 1-GANG BOX AND 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. VOLUME CONTROLLER WITH FACEPLATE, INSTALLATION

AND WIRING PER DIV 27.

DUCT HEATER.H

DH

H

EB

LOW-VOLTAGE MOMENTARY WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).L

SECURITY SYMBOL

CC

CCTV SYSTEM WALL MOUNTED CAMERA (REFER TO CAMERA SCHEDULE FOR MOUNTING HEIGHT AND CAMERA SPECIFICATIONS). SUBSCRIPT "X" INDICATES ENTRY IN CAMERA SCHEDULE. 1-GANG BOX WITH 0.75" CONDUIT TO ABOVE

ACCESSIBLE CEILING PER DIV 26. CAMERA AND CABLING PER DIV 28.

EDC

ELECTRONIC DOOR CONTROL/MONITORING. REFER TO DOOR CONTROL SCHEDULE FOR ADDITIONAL INFORMATION. LOCK AND INSTALLATION BY OTHERS. LOW VOLTAGE WIRING PER DIV 28. CONDUIT PATHWAYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. REFER TO SECURITY ROUGH-IN DETAILS.

HD

HANDICAP DOOR OPERATOR MOTOR ASSEMBLY BY OTHERS. 120V POWER CONNECTION AND CONDUIT FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. LOW VOLTAGE WIRING AND INTERFACE WITH SMS

AND DOOR ACTUATOR BUTTONS PER DIV 28. REFER TO SECURITY ROUGH-IN DETAILS.

HA

WALL/PEDESTAL MOUNT HANDICAP DOOR ACTUATOR BUTTON, FURNISHED BY OTHERS. BOX AS REQUIRED BY SYSTEM MANUFACTURER WITH INSTALLATION AND CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV

26. ALL LOW VOLTAGE WIRING AND INTERFACE WITH SMS AND DOOR MOTOR PER DIV 28. REFER TO SECURITY ROUGH-IN

DETAILS.

CR EL

WALL MOUNTED PROXIMITY CARD READER (46" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. CARD READER AND CABLING PER DIV 28. REFER TO SECURITY

ROUGH-IN DETAILS.

KC

WALL MOUNTED COMBINATION KEYPAD/CARDREADER (46" MH UNLESS NOTED OTHERWISE). 2-GANG BOX WITH 0.75" CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. DEVICE AND CABLING PER DIV 28.

X

JB M

SECURITY SYSTEM JUNCTION BOX TO BE LOCATED ABOVE ACCESSIBLE CEILING (MIN 6"X6"X4"). ROUTE LOCAL DOOR SECURITY WIRING CONDUITS/RACEWAYS TO JUNCTION BOX. EXTEND 1" CONDUIT WITH DOOR SECURITY WIRING TO LOCAL 2-DOOR CONTROL PANEL/REMOTE DOOR CONTROL PANEL AS INDICATED ON DRAWINGS. REFER TO SECURITY ROUGH-IN

DETAILS.

TECHNOLOGY SYMBOLS

P WALL MOUNTED PHONE OUTLET (46" MH UNLESS NOTED OTHERWISE). BOX WITH CONDUIT TO ABOVE ACCESSIBLE CEILING

PER DIV 26. JACKS, FACEPLATE AND CABLE PER DIV 27. REFER TO FACEPLATE DETAILS.

XR

WALL MOUNTED AV OUTLET (84" MH UNLESS NOTED OTHERWISE). BOX WITH CONDUIT PER DIV 26. REFER TO FACEPLATE DETAILS. JACKS, FACEPLATE AND CABLING PER DIV 27. SUBSCRIPT "X" INDICATES ALTERNATE CONFIGURATION.

XV

WALL MOUNTED AV OUTLET (44" MH UNLESS NOTED OTHERWISE). BOX WITH CONDUIT PER DIV 26. REFER TO FACEPLATE DETAILS. JACKS, FACEPLATE AND CABLING PER DIV 27. SUBSCRIPT "X" INDICATES ALTERNATE

CONFIGURATION.

CONDUIT SLEEVE / FIRE RATED SLEEVE ASSEMBLY THRU WALL (1-2" SLEEVE UNLESS NOTED OTHERWISE) PER DIV 26.

J TELECOM BOX AND CONDUIT PER DIV 26, REFER TO PLANS.

D WALL MOUNTED VOICE/DATA OUTLET (18" MH UNLESS NOTED OTHERWISE). BOX WITH CONDUIT(S) TO ABOVE CORRIDOR CEILING PER DIV 26. JACKS, FACEPLATE AND CABLE PER DIV 27. REFER TO FACEPLATE DETAILS.

X I

WALL MOUNTED AV OUTLET (18" MH UNLESS NOTED OTHERWISE). BOX WITH CONDUITS TO ABOVE ACCESSIBLE CEILING PER DIV 26. REFER TO FACEPLATE DETAILS. JACKS, FACEPLATE AND CABLING PER DIV 27. SUBSCRIPT "X" INDICATES

ALTERNATE CONFIGURATION.

AP

0 CEILING MOUNTED WIRELESS ACCESS POINT. WAP FURNISHED BY VA, INSTALLED BY CONTRACTOR, AND DATA DROP

PER DIV 27.

ABBREVIATIONS

AAP - AREA ALARM PANEL - MEDICAL GAS

ACC - ACCESS

ADJ - ADJUSTABLE

AF - ARC FAULT CIRCUIT INTERRUPTER

AFCI - ARC FAULT CIRCUIT INTERRUPTER

AFF - ABOVE FINISHED FLOOR TO BOTTOM OF ITEM

AFG - ABOVE FINISHED GRADE TO BOTTOM OF ITEM

ALT - ALTERNATE

AP - ACCESS PANEL

APPROX - APPROXIMATE

ARCH - ARCHITECT OR ARCHITECTURAL

ASSY - ASSEMBLY

ATS - AUTOMATIC TRANSFER SWITCH

BLDG - BUILDING

BOE - BOTTOM OF EQUIPMENT

BOT - BOTTOM

BTWN - BETWEEN

CFCI - CONTRACTOR FURNISHED CONTRACTOR INSTALLED

CKT - CIRCUIT

CLG - CEILING

CMU - CONCRETE MASONRY UNIT

CONN - CONNECT OR CONNECTION

CONTR - CONTRACTOR

COR - CONTRACTING OFFICER'S REPRESENTATIVE

CORR - CORRIDOR

CTR - CENTER

CY -CRYOSTAT

D - DEPTH

DET - DETAIL

DIA - DIAMETER

DIM - DIMENSION

DIV - DIVISION

DN - DOWN

DWG - DRAWING

EA - EACH

EC - ELECTRICAL (DIVISION 26)

EJ - EXPANSION JOINT

ELEC - ELECTRICAL

ELEV - ELEVATION OR ELEVATOR

EM - EMERGENCY

EQ - EQUAL

EQS - EQUIPMENT SUPPLIER

EQUIP - EQUIPMENT

ETR - EXISTING TO REMAIN

EX - EXISTING

EXP - EXPANSION

EXT - EXTERIOR

FCE - FIRE CONTROL EQUIPMENT

FF - FINISHED FLOOR ELEVATION

FLR - FLOOR

FSC - FIRE SUPPRESSION (DIVISION 21)

FT - FEET

FTG - FOOTING

FRZ - FREEZER

GC - GENERAL CONTRACTOR

GF - GROUND FAULT CIRCUIT INTERRUPTER

GFB - GROUNF FAULT CIRCUIT INTERUPTER BREAKER

GFCI - GROUND FAULT CIRCUIT INTERRUPTER OR

GOVERNMENT FURNISHED CONTRACTOR INSTALLED

GFFT - GROUND FAULT FEED THRU

HC - HVAC (DIVISION 23)

HP - HORSE POWER OR HIGH POINT

HVAC - HEATING, VENTILATING, AND AIR CONDITIONING

ID - INSIDE DIAMETER

IN - INCHES

KEC - KITCHEN EQUIPMENT

L - LENGTH

LBS - POUNDS

MAP - MASTER ALARM PANEL (MEDICAL GAS)

MAX - MAXIMUM

MEZZ - MEZZANINE

MFR - MANUFACTURER

MH - MANHOLE OR MOUNTING HEIGHT TO CENTER LINE OF ITEM

MIN - MINIMUM OR MINUTE

MISC - MISCELLANEOUS

MTD - MOUNTED

MTG - MOUNTING

MW - MICROWAVE

NIC - NOT IN CONTRACT

NOM - NOMINAL

NTS - NOT TO SCALE

OD - OUTSIDE DIAMETER

OFCI - OWNER FURNISHED CONTRACTOR INSTALLED

OFOI - OWNER FURNISHED OWNER INSTALLED

PC - PLUMBING (DIVISION 22)

PLBG - PLUMBING

PR - PRINTER

RAD - RADIUS

REC - RECESSED

REQD - REQUIRED

RF - REFRIGERATOR

RI - ROUGH-IN

S - SURFACE MOUNTED

SC - SECURITY

SCH - SCHEDULE

SHT - SHEET

SMS - SECURITY MANAGEMENT SYSTEM

SPEC - SPECIFICATIONS

SQ - SQUARE

SS - STAINLESS STEEL

STD - STANDARD

STRUC - STRUCTURAL OR STRUCTURE

SUC - SITE UTILITY

TC - TECHNOLOGY

TEMP - TEMPERATURE

TOE - TOP OF EQUIPMENT

TR - TAMPER RESISTANT

TYP - TYPICAL

UNO - UNLESS NOTED OTHERWISE

VFD - VARIABLE FREQUENCY DRIVE

VOL - VOLUME

W/ - WITH

W/0 - WITHOUT

WP - WEATHERPROOF

ZVC - ZONE VALVE CABINET

E2

B

E2

DETAIL: B = DETAIL DESIGNATION

E2 = SHEET WHERE DETAIL IS LOCATED

SECTION: 1 = SECTION DESIGNATION

E2 = SHEET WHERE SECTION IS LOCATED

PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH IT IS SHOWN.

DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.

GENERAL FLOOR PLAN NOTES

WIRE & CONDUIT IN WALL OR ABOVE CEILING.

WIRE & CONDUIT IN OR BELOW SLAB OR GRADE.

EACH ARROWHEAD REPRESENTS ONE COMPLETE CIRCUIT; "X" DENOTES PANEL

NAME; NUMBER(S) DENOTES CIRCUIT(S).

LADDER TRAY, 12" x 4" DEEP UNLESS NOTED OTHERWISE.

CONDUIT FOR DATA CIRCUITRY.DAT

WIRE & CONDUIT FOR FIRE ALARM CIRCUITRY.FA

WIRE & CONDUIT FOR NURSE CALL CIRCUITRY.NC

EXISTING WIRE & CONDUIT TO REMAIN.EX

CONDUIT TO BE REMOVED.

WIRE & CONDUIT FOR NIGHT LIGHT CIRCUITRY.NL

CONDUIT FOR PHONE CIRCUITRY.PHO

WIRE & CONDUIT FOR SECURITY SYSTEM CIRCUITRY.SEC

WIRE RUN IN SURFACE WIREWAY.W

CABLE MANAGEMENT SYSTEM PATHWAY.CM

X - 1,2

WIRE & CONDUIT FOR EMERGENCY CIRCUITRY.EM

WIRE & CONDUIT FOR SOUND SYSTEM CIRCUITRY.S

WIRE & CONDUIT FOR INTERCOM SYSTEM CIRCUITRY.I

WIRE & CONDUIT FOR TELEVISION SYSTEM CIRCUITRY.TV

LUMINAIRE SYMBOLS

LIGHTING FIXTURE. CAPITAL LETTER DENOTES FIXTURE TYPE, LOWER CASE LETTER DENOTES

SWITCHING ARRANGEMENT.

LIGHTING FIXTURE ON NIGHT LIGHT OR EMERGENCY CIRCUIT.

EXIT LIGHTING FIXTURE, ARROWS AS INDICATED.

A a

WIREMOLD RACEWAY, AS NOTED ON PLANS.

CABLE TRAY, 12" x 4" DEEP UNLESS NOTED OTHERWISE.

4"

4"

4"

NURSE CALL MULTI-PIN CATV JACK (84" AFF UNLESS NOTED OTHERWISE).

NURSE CALL STAFF PRESENCE STATION (60" AFF UNLESS NOTED OTHERWISE).

C

NS

P

NS

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R WITH 2 INTEGRAL USB CHARGERS (18" MH UNLESS NOTED OTHERWISE).

NOTE:

ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT

TO MODIFICATIONS ON OTHER DRAWINGS.

ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT

NECESSARILY BE USED ON THIS PROJECT.

LIGHTING FIXTURE ON CRITICAL CIRCUIT.

SQUARE DEVICE INDICATES A CONNECTION TO CRITICAL POWER. SPECIFICATION IS SAME AS RESPECTIVE ROUND DEVICE.

J

FLOOR BOX, # INDICATES TYPE, REFER TO FLOOR BOX (FB) SCHEDULE. IF NO #, PROVIDE FLUSH FLOOR BOX WITH ROUND

COVERPLATE AND ONE 20A-125V DUPLEX RECEPTACLE. PROVIDE CARPET FLANGE WHERE REQD.

X

POKE-THRU PER DIV 26. # INDICATES TYPE, REFER TO POKE-THRU (PT) SCHEDULE. SUBSCRIPT "X" INDICATES

TECHNOLOGY DEVICE(S), REFER TO TECHNOLOGY DETAILS.

X

CEILING MOUNTED FIRE ALARM SPEAKER & SIGNAL LIGHT. # WHEN SHOWN INDICATES CANDELA RATING OF STROBE.

WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN TOILET ROOMS AND 75 CANDELA FOR ALL OTHER

LOCATIONS.

FIRE ALARM MANUAL STATION (46" MH UNLESS NOTED OTHERWISE). SUBSCRIPT "K" INDICATES KEY OPERATED.

CEILING MOUNTED SMOKE DETECTOR.

CEILING MOUNTED HEAT DETECTOR.

DUCT MOUNTED SMOKE DETECTOR. SUBSCRIPT "S" INDICATES SUPPLY. SUBSCRIPT "R" INDICATES RETURN.

DUCT MOUNTED HEAT DETECTOR. SUBSCRIPT "S" INDICATES SUPPLY. SUBSCRIPT "R" INDICATES RETURN.

ELECTRIC RELEASE DOOR CLOSER.

ELECTRO-MAGNETIC DOOR HOLDER.

WATER FLOW SWITCH.

VALVE SUPERVISORY SWITCH.

CEILING MOUNTED REMOTE TEST STATION AND ALARM INDICATOR LIGHT FOR DUCT DETECTOR. SUBSCRIPT "W" INDICATES

WALL MOUNTED.

SMOKE DAMPER.

FIRE FIGHTER'S TELEPHONE (60" MH UNLESS NOTED OTHERWISE).

KF

S M

H

C

D

FS

V

R W

SD

FT

PRESSURE SWITCH.

ADDRESSABLE MODULE. SUBSCRIPT "I" INDICATES INPUT. SUBSCRIPT "C" INDICATES CONTROL.

POST INDICATOR VALVE.

KNOX BOX (46" MH UNLESS NOTED OTHERWISE). SUBSCRIPT "S" INDICATES SUPERVISED UNIT.

PS

AM

C/I

PIV

K S

H

S S/R

S/R

S F

BEAM DETECTOR. SUBSCRIPT "T" INDICATES TRANSMITTER FUNCTION. SUBSCRIPT "R" INDICATES RECEIVER FUNCTION.B T/R

AIR SAMPLING SMOKE DETECTOR SAMPLING PORT.A

REMOTE ANNUNCIATOR PANEL.

NOTIFICATION APPLIANCE CIRCUIT EXTENDER PANEL.

AIR SAMPLING SMOKE DETECTOR BASE UNIT.

RAP

NAC

ASSD

SURFACE MOUNTED FIRE ALARM SPEAKER (80" AFF). SUBSCRIPT "R" INDICATES RECESSED MOUNTING.S R

T2 1 ELEVATION: 1 = ELEVATION DESIGNATION

T2 = SHEET WHERE ELEVATION IS LOCATED

FLOOR BOX PER DIV 26. # INDICATES TYPE, REFER TO FLOOR BOX (FB) SCHEDULE. SUBSCRIPT "X" INDICATES

TECHNOLOGY DEVICE(S), REFER TO TECHNOLOGY DETAILS.

X

CUSTOM OUTLET IN SURFACE RACEWAY. SURFACE RACEWAY PER DIV 26. OUTLET JACKS, FACEPLATE AND CABLING PER

DIV 27.

W

FIRE RATED POKE-THRU, # INDICATES TYPE, REFER TO POKE-THRU (PT) SCHEDULE E501. IF NO #, PROVIDE 6 INCH RECESSED ACCESS POKE-THRU WITH TWO 20A-125V DUPLEX RECEPTACLES. PROVIDE CARPET FLANGE WHERE REQD.

X

F

CEILING MOUNTED FIRE ALARM SIGNAL LIGHT. # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN TOILET ROOMS AND 75 CANDELA FOR ALL OTHER LOCATIONS.

EM

SC

X

Z VALCOM RECESSED 2X2 CEILING PAGING SPEAKER WITH CABLING PER DIV 27.

Q Q-MATIC SYSTEM CEILING MOUNTED LED DISPLAYS, FURNISHED BY SYSTEM VENDOR, INSTALLED BY CONTRACTOR, CABLED PER DIV 27.

SF Q-MATIC SYSTEM RECESSED CEILING SPEAKER, FUIRNISHED BY SYSTEM VENDOR, INSTALLED BY CONTRACTOR, WITH

CABLING PER DIV 27.

WALL MOUNTED FLAT PANEL DISPLAY, NUMERAL INDICATES NOMINAL SCREEN SIZE.

AP

B

0 AT&T GUEST WiFi CEILING MOUNTED WIRELESS ACCESS POINT. REMOVE AND RE-INSTALL IN NEW LOCATION, PROVIDE

NEW DATA DROP PER DIV 27 TO EQUIPMENT ROOM 2E114.

AP

X

0 CELLUALR DAS ANTENNA. MAINTAIN.

1. THESE NOTES APPLY EQUALLY TO THE FULL SET OF DOCUMENTS.

2. INCLUDE ALL WORK NECESSARY TO ACCOMMODATE PHASING. REFER TO

ARCHITECTURAL DRAWINGS AND GENERAL REQUIREMENTS SECTION 01 00 00.

3. INSULATE DUCTWORK AND PIPING WHERE EXISTING INSULATION HAS BEEN

DAMAGED AND/OR REMOVED IN THE PERFORMANCE OF WORK IN THIS

PROJECT.

4. PROVIDE ALL ROOFING PENETRATION, REPAIR & REINFORCEMENT IN THE

EXISTING BUILDING FOR WORK INDICATED. ENGAGE A ROOFING

SUBCONTRACTOR TO PERFORM THE ROOFING WORK. WHERE ROOFING WORK

IS REQUIRED, THE EXISTING ROOFING MEMBRANE AND INSULATION SHALL BE

CUT, REMOVED AND RESTORED AS REQUIRED TO ATTAIN A WATERTIGHT

CONDITION. THE ROOFING SUB-CONTRACTOR SHALL BE A CERTIFIED

INSTALLER FOR SUCH INSTALLATION TO MAINTAIN THE EXISTING WARRANTY

ON THE ROOF.

5. THE CONTRACTOR SHALL REFER TO ALL SPECIFICATION SECTIONS AND THESE

DRAWINGS FOR DETAILS OF BUILDING CONSTRUCTION TO ENSURE SPACE AND

SATISFACTORY ARRANGEMENT FOR THEIR WORK. THE VARIOUS DRAWINGS

COMPRISING THE SET ARE INTERDEPENDENT AND MUST BE USED JOINTLY AT

ALL TIMES. THE CONTRACTOR SHALL REFER TO THE GENERAL REQUIREMENTS

OF THE CONTRACT. THE NOTES AND SYMBOLS INDICATED ON THE DRAWINGS

ARE FOR THE GUIDANCE OF ALL TRADES INVOLVED IN THE PROJECT AND MUST

BE FOLLOWED TO EXECUTE THE WORK AS INTENDED. IF DISCREPANCIES

OCCUR, CONTACT THE COR THRU THE CONTRACTING OFFICER FOR

CLARIFICATION BEFORE PROCEEDING.

6. IN ACCORDANCE WITH GENERALLY ACCEPTED CONSTRUCTION PRACTICES,

THE CONTRACTOR WILL BE SOLELY AND COMPLETELY RESPONSIBLE FOR THE

CONDITIONS ON THE JOB SITE, INCLUDING SAFETY OF ALL PERSONS AND

PROPERTY DURING PERFORMANCE OF THE WORK. THIS WILL APPLY

CONTINUOUSLY AND NOT BE LIMITED TO NORMAL WORKING HOURS. SEE

SPECIFICATIONS FOR MORE SPECIFIC DETAILS ON RESPONSIBILITIES.

7. ALL WORK MUST BE COORDINATED WITH THE CONTRACTING OFFICER AND

COR TO MAINTAIN OPERATION OF THE EXISTING FACILITY.

8. THE CONTRACTOR SHALL COORDINATE HIS WORK WITH THE WORK OF

OTHERS. HE SHALL KEEP HIMSELF INFORMED OF THE PROGRESS AND DETAIL

DEVELOPMENT OF THE WORK OF OTHERS AND SHALL BE RESPONSIBLE FOR

COORDINATING AND EXPEDITING HIS WORK WITH OTHERS SO THAT THE

PROGRESS OF THE TOTAL WORK SHALL BE KEPT ON SCHEDULE.

9. ALL WORK SHALL BE PERFORMED IN COMPLETE COMPLIANCE WITH ALL

GOVERNING CODES AND STANDARDS.

10. EXISTING CONDITIONS SHOWN HAVE BEEN BASED UPON AVAILABLE DRAWING

INFORMATION, AND MAY BE AT VARIANCE WITH ACTUAL WORK IN PLACE. THE

CONTRACTOR SHALL TAKE ALL NECESSARY FIELD MEASUREMENTS AND FIELD

VERIFY ALL CONDITIONS AFFECTING THE EXECUTION OF THE WORK. ANY

DISCREPANCIES BETWEEN EXISTING CONDITIONS AND THE WORK SHOWN ON

THE CONTRACT DOCUMENTS WHICH MAY IMPACT THE PROGRESS OF THE

WORK SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTING

OFFICER IN WRITING FOR RESOLUTION BEFORE PROCEEDING WITH THE WORK.

11. THE CONTRACTOR AND/OR TRADE, FITTING OR PLACING HIS WORK INTO OR

ON THE WORK OF OTHERS DOES SO WITH THE UNDERSTANDING THAT THE

INSTALLATION OF HIS WORK CONSTITUTES HIS ACCEPTANCE OF THE

SUITABILITY OF THE WORK IN PLACE. IF THE WORK OF OTHERS IS NOT

ACCEPTABLE, HE SHALL NOTIFY THE COR AND SUCH WORK SHALL BE

CORRECTED. ANY NEW WORK INSTALLED IN UNSUITABLE EXISTING WORK

SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR OR TRADE INSTALLING

THE NEW WORK. NO CLAIMS FOR ADDITIONAL COMPENSATION FOR

CORRECTING WORK INSTALLED IN UNSUITABLE EXISTING CONDITIONS WILL BE

CONSIDERED.

12. IF, IN THE PERFORMANCE OF THIS WORK, MATERIALS ARE OBSERVED WHICH

ARE SUSPECTED TO CONTAIN ASBESTOS, THE CONTRACTOR SHALL

IMMEDIATELY INFORM THE COR. WORK THAT WOULD EXPOSE WORKERS TO

THE INHALATION OF ASBESTOS PARTICLES SHALL BE TERMINATED. WORK MAY

BE RESUMED ONLY AFTER A DETERMINATION HAS BEEN MADE AND UNSAFE

MATERIALS HAVE BEEN REMOVED OR ENCAPSULATED AND THE AREA

DECLARED SAFE.

13. CONTRACTOR SHALL TAKE SPECIAL CARE WHILE WORKING ADJACENT TO

ASBESTOS MATERIALS AND MUST BE PROPERLY PROTECTED WITH CLOTHING,

BREATHING APPARATUS, ETC. VERIFY REQUIREMENTS OF VAMC'S INFECTION

CONTROL RISK ASSESSMENT TEAM (ICRA).

14. ALL CUTTING AND PATCHING REQUIRED FOR THIS PROJECT SHALL BE

INCLUDED IN THE CONTRACT. REFINISH ANY SURFACE DISTURBED UNDER

THIS WORK TO MATCH EXISTING.

15. FIELD VERIFY EXISTING CONDITIONS, PRIOR TO PERFORMING WORK.

16. REFER TO SPECIFICATIONS SECTION 01 00 00 GENERAL REQUIREMENTS AND

THESE DRAWINGS FOR DESCRIPTIONS OF THE BID ITEMS INCLUDING

DESCRIPTIONS OF THE BASE BID AND DEDUCT ALTERNATES. ADDITIONAL

INFORMATION NOTED THROUGHOUT THE

DRAWINGS.

17. SYSTEMS SERVING AREAS OUTSIDE THE CONSTRUCTION ZONE SHALL REMAIN

OPERATIONAL DURING CONSTRUCTION. ANY OUTAGES SHALL BE PERFORMED

ON WEEKENDS OR WEEK NIGHTS. DOWNTIME SHALL BE KEPT TO A MINIMUM,

AND SHALL BE COORDINATED AND SCHEDULED 4 WEEKS (30 CALENDAR DAYS)

IN ADVANCE WITH THE COR.

18. REFER TO NEW WORK FLOOR PLANS FOR WORK THAT MAY BE REQUIRED

PRIOR TO ANY REMOVAL WORK.

19. READ ALL NOTES THOROUGHLY PRIOR TO STARTING CONSTRUCTION.

20. FOR EXISTING EQUIPMENT, SUCH AS LIGHTING FIXTURES, WIRING DEVICES,

CONDUITS, ETC., SHOWN ON PLANS TO BE REMOVED, COMPLETELY CUT/CAP

CONDUITS AT THE AREA OF WORK PERIMETER AND REMOVE CONDUIT WITHIN

THE WORK AREA, DISCONNECT WIRING AT THE OVERCURRENT PROTECTIVE

DEVICE AND REMOVE WIRING COMPLETELY FROM THE ABANDONED CONDUITS.

21. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE OVERCURRENT

PROTECTIVE DEVICE. COMPLETELY REMOVE ALL ABANDONED WIRING.

GENERAL NOTES

1400 W Dorothy Lane, Dayton, OH 45409

P: 937-224-0861 www.heapy.com

VA Project No.

JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

HEAPY PROJECT No.: 2018-05007 OHIO COA FIRM No.: 05128

/1

/2

:1

:4

A

M

Renovate Laboratory

02/19/2021

LEGEND, ABBREVIATIONS & INDEX

OF DRAWINGS

E001

JHSMSG

17006.00

552-18-101

Dayton, Ohio

310STATION

PHILIP KIRK, PE

BID SET

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290

INDEX OF DRAWINGS

Sheet Number Sheet Name

E001 LEGEND, ABBREVIATIONS & INDEX OF DRAWINGS

E100 1ST FLR PLAN - PH0 - NEW WORK & 2ND FLR PLAN - PH1 - REMOVALS

E101 2ND FLR PLAN - PH1 - LIGHTING

E102 2ND FLR PLAN - PH1 - POWER

E103 2ND FLR PLAN - PH1 - SYSTEMS

E104 2ND FLR PLAN - PH1 - TECHNOLOGY

E105 2ND FLR PLAN - PH2 - REMOVALS

E106 2ND FLR PLAN - PH2 - LIGHTING

E107 2ND FLR PLAN - PH2 - POWER

E108 2ND FLR PLAN - PH2 - SYSTEMS

E109 1ST FLR PLAN - PH2 - TECHNOLOGY

E110 2ND FLR PLAN - PH2 - TECHNOLOGY

E111 9TH FLR PLAN - PH2 - TECHNOLOGY

E112 2ND FLR PLAN - PH3 - REMOVALS

E113 2ND FLR PLAN - PH3 - LIGHTING

E114 2ND FLR PLAN - PH3 - POWER

E115 2ND FLR PLAN - PH3 - SYSTEMS

E116 2ND FLR PLAN - PH3 - TECHNOLOGY

E117 2ND FLR PLAN - PH4 - REMOVALS

E118 2ND FLR PLAN - PH4 - LIGHTING

E119 2ND FLR PLAN - PH4 - POWER

E120 2ND FLR PLAN - PH4 - SYSTEMS

E121 2ND FLR PLAN - PH4 - TECHNOLOGY

E122 2ND FLR PLAN - PH5 - REMOVALS

E123 2ND FLR PLAN - PH5 - LIGHTING

E124 2ND FLR PLAN - PH5 - POWER

E125 2ND FLR PLAN - PH5 - SYSTEMS

E126 1ST FLR PLAN - PH5 - TECHNOLOGY

E127 2ND FLR PLAN - PH5 - TECHNOLOGY

E128 1ST FLR PLAN - PH6 - REMOVALS

E129 4TH FLR PLAN - MECHANICAL PLAN

E401 ENLARGED PLANS - TELECOMMUNICATIONS

E402 ENLARGED PLANS - TELECOMMUNICATIONS

E403 ENLARGED PLANS - TELECOMMUNICATIONS

E501 DETAILS

E502 DETAILS

E503 DETAILS - LIGHTING FIXTURES

E601 PANEL SCHEDULES

E602 PANEL SCHEDULES

E701 SINGLE-LINE DIAGRAM

1 ADDENDUM 2 5/20/2021

F R

Z

FRZ

GF

RF

46"

F R

Z

R F

R F

R F

46"

GF

GF

46"/GF

GF

GF

G F

G F

G F

G F

G F

F R

Z

GF46"

46"/GF

GF

GF

D

24" MH

D

D

D

DD

D D

D

54" MH

D

D

DD

D

D

D

D

D

D

D

D

D

D

AP

AP

SC

SC

SC

SC

SC

CR

CR

EDC

EDC

D D

GF

G F

GF

IM

IM

IM

IC

D

D

F

F

F

F

F F

F

F

F

46" J

CC

CC

SC

AP

AP

X

D

48" MH

AP SC

HA

HD

48" MH

D

CC CC

SC

48" MH

D

48" MH

4D/2V

D

48" MH

D

48" MH

D

AP

SC

AP SC

D

SC

D

P

D 4 8" M

H

D 4 8" M

H4 D

P

D 4 8" M

H

4 D /2 V

D

48" MH

SCAP

SC 48" MH

4D

D

V

AP

D

D

P

AP

X

SC

D

D

P

D

48" MH

P

D

48" MH

AP

D

48" MH

4D D

D

SC

D

48" MH

4D

D

D

D

1D D D

SC

SC

D 1D

DD

AP

HA

CC

P

D

AP D

1DAP

B

SC

CC

CC

D

D

D SC

AP

X

R

D 4D

D 1D

D 1D

DD

HA

HD AP

SC

D 4 D

AP

D

4D

D

4DSC

D 4D

D 4D

D D

RD

6D

J

SC

D 4 8" M

H

D 4 8" M

H

2 D /1 V

D

D

D

D

D

D

D

D D

2D/2V

D

1D D

D

CC

CC

SC

P D

M

H

D 4 8" M

H4 D

D

48" MH

4D

D 4D

DD

SC

SC

CR

CR

HA

GF

GF

F

GF

F

F

F

JJ

J

P-TUBE

J J

J

R F

F R

Z

J J

J

J

J

S

J J J

FRZ

RF

JJJ

J

J

J J

J J

J

RF

J J

RF

FRZ

FRZ

J J

J

GF

GF

J

S

D A T A

S T A T I O N

X Y

D A T A

S T A T I O N

X Y K

DATA STATION X-Y DATA STATION X-Y DATA STATION X-Y DATA STATION X-Y

J

PP

PP

PP

PP

PP

PP

E.1 G H

1E-100

E403

CTU - TEMP

1E101

OFFICE, STAFF

1E102 OFFICE, STAFF

1E103

1E104

BREAK

ROOM

MECHANICAL

1E105

E.1 G H J K L

M N

P

E401

E402

E401

13 13 13 13

MICROBIOLOGY TEMP

2E116GT

HISTOLOGY TEMP

2E116FT

TOXICOLOGY

2E116B

2E114

2E164

2E163

ATS-EDPL ATS-EDPC ATS-EDPM

GPG

EDPL EDPC EDPM

GLLP4 T9 GLRP4

TEMP ATS

GERP1

T16

T15

DPN1

T12

T2

DUPLEX

MAIN

A/J

US1 XFMR

NORTH

DUPLEX

MAIN

A/J

D R

A W

O U

T B

R E

A K

E R

S

US1 XFMR

SOUTH

310MDP

EMCS

SERVER

500KW

GENERATOR

G-1

500KW

GENERATOR

G-2

LOCATION OF MAIN

ELECTRICAL ROOMS

LOCATION OF TEMPORARY LAB BUILDING

1400 W Dorothy Lane, Dayton, OH 45409

P: 937-224-0861 www.heapy.com

VA Project No.

JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

HEAPY PROJECT No.: 2018-05007 OHIO COA FIRM No.: 05128

/1

/2

:1

:4

A

M

Renovate Laboratory

02/19/2021

1ST FLR PLAN - PH0 - NEW WORK &

2ND FLR PLAN - PH1 - REMOVALS

E100

JHSMSG

17006.00

552-18-101

Dayton, Ohio

310STATION

PHILIP KIRK, PE

BID SET

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290

N Scale:

PROJECT

1/8" = 1'-0"

1ST FLR PLAN - PH0 - NEW WORK

N Scale:

PROJECT

1/8" = 1'-0"

2ND FLOOR PLAN - PH1 - REMOVALS

GENERAL NOTES

A. FOR EXISTING EQUIPMENT, SUCH AS LIGHTING FIXTURES, WIRING DEVICES, CONDUITS, ETC., SHOWN ON PLAN TO BE REMOVED, COMPLETELY CUT/CAP CONDUITS AT THE AREA OF WORK

PERIMETER AND REMOVE CONDUIT WITHIN THE WORK AREA, DISCONNECT WIRING COMPLETELY

FROM THE ABANDONED CONDUITS.

B. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE OVERCURRENT PROTECTIVE

DEVICE. COMPLETELY REMOVE ALL ABANDONED WIRING.

C. MAINTAIN AND RESTORE IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS PASSING THROUGH

RENOVATED AREAS AND SERVICING UNDISTURBED AREAS.

D. FOR PLUMBING, HVAC EQUIPMENT TO BE REMOVED, DEMOLISH ALL CONDUIT, CONDUCTORS AND

ANY ASSOCIATED ELECTRICAL EQUIPMENT. REFER TO DIVISION 22, 23 DRAWINGS FOR

LOCATIONS.

E. PROVIDE A FULLY FUNCTIONAL VIDEO INTERCOM SYSTEM TO INCLUDE ALL BACK-BOXES,

ACCESSORIES, MOUNTS, CABLING, POWER SUPPLIES AND DOOR RELEASE RELAY.

PLAN NOTES

1. EXISTING SIGNALS CLOSET TO SERVE TEMPORARY MODULAR BUILDING. REFER TO SHEET E403.

2. 4" EZ-PATH FIRE RATED SLEEVE ASSEMBLY THROUGH WALL.

3. FLUSH MOUNTED STAINLESS STEEL DOOR STATION.

4. DESKTOP MOUNTED VIDEO MASTER STATION WITH PICTURE MEMORY.

5. DESKTOP MOUNTED VIDEO…