36C25018B0815-003.pdf

PDF 6 MB Posted

Attached to
Remodel Pharmacy IV Prep Room - FCA Project 757-19-101
Solicitation number
36C25018B0815
Issued by

About this file

36C25018B0815 Project Drawings.pdf

View the file

Other files

File Type Posted
36C25019C0025-000.docx DOCX document
36C25018B0815-0003000.docx DOCX document
36C25018B0815-0002007.pdf PDF
36C25018B0815-0002004.pdf PDF
36C25018B0815-0002002.pdf PDF
36C25018B0815-0002006.pdf PDF
36C25018B0815-0002005.pdf PDF
36C25018B0815-0002003.pdf PDF
36C25018B0815-0002000.docx DOCX document
36C25018B0815-0002008.pdf PDF
36C25018B0815-0002001.pdf PDF
36C25018B0815-0002010.pdf PDF
36C25018B0815-0002009.pdf PDF
36C25018B0815-0001000.docx DOCX document
36C25018B0815-001.docx DOCX document
36C25018B0815-004.txt TXT text file
36C25018B0815-002.pdf PDF
36C25018B0815-000.docx DOCX document
Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ST

ATE OF OHIO

DELLOS

D

MORRISON

R E

G I S

T

ER ED A RC

H

I T E

C T

PROJECT SITE

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

VA Project No.

Drawing Number

Dwg. of on e-ei gh th in ch on e fo ot on e-qu ar te r in ch on e fo ot th re e-ei gh th s in ch on e fo ot on e-ha lf in ch on e fo ot th re e-qu ar te rs in ch on e fo ot on e in ch on e fo ot on e an d on e-ha lf in ch es on e fo ot th re e in ch es on e fo ot

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

ARCHITECT/ENGINEERS:CONSULTANTS:

CDL Project No.

Department of Veterans Affairs Ambulatory Care Center

ARCHITECT

2727 TULLER PARKWAY, SUITE 200

DUBLIN, OHIO 43017

614.798.1515 P

COLLABORATIVE DESIGN

MEP ENGINEER

3073 N. HIGH STREET

COLUMBUS, OHIO 43202

614.267.4928 P

W.E. MONKS & CO.

Collaborative Design,Ltd.

2727 Tuller Parkway, Suite 200

Dublin, Ohio 43017

Tel 614.798.1515 Fax 614.798.5105

COLUMBUS, OH

757-19-201

1A

Chalmers P. Wylie Ambulatory Care Center

757-19-201 REMODEL

PHARMACY IV PREP ROOM

05/18/18

COVER SHEET

G-001

17029

Chalmers P. Wylie Ambulatory Care Center

757-19-201 REMODEL PHARMACY IV PREP ROOM

420 NORTH JAMES ROAD, COLUMBUS, OHIO 43219-1834

DM DM MB

INDEX OF DRAWINGS

G-001 COVER SHEET 1

G-002 GENERAL INFORMATION 2

G-003 OVERALL FIRST FLOOR PLAN 3

G-004 OVERALL SECOND FLOOR PLAN 4

AS-100 ENLARGED PLANS - DEMOLITION & NEW CONSTRUCTION 5

AS-101 ENLARGED PLANS - EQUIPMENT & REFLECTED CEILING PLANS 6

AS-102 ROOF PLAN 7

AS-300 SCHEDULES & WALL TYPES & DETAILS 8

FP-001 FIRE PROTECTION GENERAL NOTES 9

FP-100 FIRE PROTECTION SECOND FLOOR PLAN 10

P-001 PLUMBING ABBREVIATIONS / SYMBOLS 11

P-100 PLUMBING FLOOR PLANS 12

P-200 TEMPORARY TRAILER PLUMBING PLAN 13

M-001 HVAC ABBREVIATIONS / SYMBOLS 14

M-100 HVAC SECOND FLOOR DEMOLITION PLAN 15

M-101 HVAC SECOND FLOOR PLAN 16

M-102 HVAC PIPING SECOND FLOOR PLAN 17

M-103 HVAC THIRD FLOOR / ROOF PLANS 18

M-500 HVAC DETAILS & DIAGRAMS 19

M-600 HVAC SCHEDULES 20

E-001 ELECTRICAL ABBREVIATIONS / SYMBOLS 21

E-100 ELECTRICAL SECOND FLOOR DEMOLITION PLAN 22

E-101 ELECTRICAL SECOND FLOOR LIGHTING & POWER PLANS 23

E-102 ELECTRICAL THIRD FLOOR / ROOF PLAN 24

E-200 TEMPORARY TRAILER ELECTRICAL PLAN 25

E-500 ELECTRICAL SCHEDULES AND DETAILS 26

N.T.S.Scale:

LOCATION MAP

Revisions Date

BID SET 5/18/18

DELLOS

D

MORRISON

R E

G I S

T

ER ED A RC

H

I T E

C T

CG-1

PP

CR

PBL

MD

HO

000'-0"

DATUM

CONCRETE

GYP. BD.

PLYWOOD

INSUL.

RIGID INSUL.

EARTH

GRAVEL

SAND

BLOCK

DATUM MARKER

DOOR NUMBER

COLUMN LINE BUBBLE

CODED NOTE (NUMBER)

DETAIL MARKER

ELEVATION MARKERS

SECTION CUT

SECTION TITLE

DETAIL TITLE

PLAN TITLE

NORTH ARROW

1. PERFORM WORK AS REQUIRED FOR PROPER COMPLETION OF THE WORK. DRAWINGS MAY NOT SHOW ALL EXISTING ITEMS OR CONDITIONS. CONTRACTOR SHALL NOT RECEIVE EXTRA PAYMENT FOR REQUIREMENTS WHICH CAN BE INFERRED THROUGH OBSERVATION OF EXISTING CONDITIONS AT THE SITE.

2. THE CONTRACTOR IS RECOMMENDED TO VISIT THE SITE AND BECOME FAMILIAR WITH EXISTING CONDITIONS PRIOR TO SUBMITTING A BID. SEE SOLICITATION FOR DATE AND TIME OF SITE

VISIT.

3. PROVIDE TEMPORARY DUST PARTITIONS AND PROVIDE TEMPORARY EXIT CORRIDORS AND ROUTING SAFETY DEVICES. COORDINATE WITH COR AND THE VA'S SAFETY PLAN.

4. COORDINATE BUILDING ACCESS AND CONSTRUCTION SCHEDULING WITH VA.

5. COMPLY WITH ALL VA RULES AND REGULATIONS, ALSO SEE SPECIFICATIONS FOR REFERENCE STANDARDS THAT GOVERN THIS PROJECT.

6. UNDER NO CIRCUMSTANCES SHALL CONSTRUCTION ACTIVITIES INTERFERE WITH SAFETY OF THE PUBLIC, OWNER'S EMPLOYEES, OR CONSTRUCTION PERSONNEL. ADHERE STRICTLY TO CONFINES OF AREAS OF WORK; DO NOT INTERRUPT HOSPITAL FUNCTIONS AT ANY TIME. REMAINING AREAS OF THE BUILDING OUTSIDE THE LIMITS OF CONSTRUCTION SHALL REMAIN

OPERATIONAL AND NOT BE DISRUPTED BY THE SCOPE OF THIS WORK.

7. DRAWINGS ARE DIAGRAMMATIC IN NATURE. THE DRAWINGS REPRESENT THE INTENT OF THE PROJECT WORK. ALL FIELD CONDITIONS, OFFSETS, TRANSITIONS, ETC. ARE NOT REPRESENTED.

ALL EXISTING CONDITIONS AND DIMENSIONS ARE BASED ON EXISTING DRAWINGS. DUE TO THE POSSIBILITY OF DISCREPANCIES THE CONTRACTOR SHOULD VERIFY EXISTING CONDITIONS BEFORE BEGINNING CONSTRUCTION AND NOTIFY THE COR IMMEDIATELY OF ANY DISCREPANCIES. ALL BUILDING FLOOR LEVELS ARE ESTABLISHED FROM EXISTING DRAWINGS AND SHALL BE

FIELD VERIFIED.

8. WHERE WORK IS DONE IN EXISTING AREAS, THE EXISTING FINISHED CONDITIONS ARE TO BE REPAIRED OR REPLACED. THESE FINISHED CONDITIONS ARE TO MATCH EXISTING UNLESS OTHERWISE NOTED. WHERE NEW FINISHED CONDITIONS ARE TO BE INSTALLED, EXISTING FINISHED CONDITIONS ARE TO BE REMOVED BY THE CONTRACTOR.

9. WHERE DISCREPANCIES OCCUR BETWEEN FLOOR PLANS AND DETAILS AND LARGE SCALE DRAWINGS, CONSULT COR FOR CLARIFICATIONS. WHERE CONFLICTS OCCUR BETWEEN

ARCHITECTURAL DRAWINGS AND ENGINEERING DRAWINGS, CONSULT COR FOR INTERPRETATION.

10. ALL ROOM DIMENSIONS ARE FACE TO FACE OF PARTITION FOR METAL STUD PARTITIONS AND TO FACE OF MASONRY FOR ALL MASONRY PARTITIONS.

11. PROVIDE DOUBLE STUDS FOR AND BLOCKING AS REQUIRED TO SUPPORT EQUIPMENT, WALL GUARDS, ETC. AT DRYWALL PARTITIONS. PROVIDE FIRE RETARDANT WOOD OR METAL BLOCKING IN WALLS AS REQUIRED FOR WALL-MOUNTED EQUIPMENT AND HARDWARE, INCLUDING ITEMS IDENTIFIED AS BEING PROVIDED BY VA. VERIFY ALL MOUNTING REQUIREMENTS WITH COR, MANUFACTURER, OR EQUIPMENT SUPPLIER.

12. ALL INTERIOR FIRE-RATED PARTITIONS SHALL EXTEND ABOVE THE FINISHED CEILING AND SHALL TERMINATE AT ASSEMBLIES OF GREATER RATING. NON FIRE-RATED PARTITIONS SHALL NOT PENETRATE RATED PARTITIONS. ALL FULL-HEIGHT PARTITIONS TO HAVE ACOUSTIC SEALANT AT BOTTOM PLATE AND TOP PLATE.

13. CONTROL JOINTS IN GYPSUM BOARD PARTITIONS SHALL BE LOCATED WHERE:

A. A PARTITION OR FURRING ABUTS A STRUCTURAL ELEMENT OR DISSIMILAR WALL OR CEILING.

B. A CEILING ABUTS A STRUCTURAL ELEMENT, DISSIMILAR WALL OR PARTITION OR OTHER VERTICAL PENETRATION.

C. A PARTITION OR FURRING RUN EXCEEDING 30'-0". IF THERE IS A DOOR OPENING IN THE 30'-0" RUN, LOCATE THE CONTROL JOINT AT BOTH SIDES OF THE JAMB FROM

HEAD OF DOOR TO TOP OF PARTITION.

14. ELECTRICAL PANELS, FIRE EXTINGUISHER CABINETS, AND OTHER WALL RECESSED OBJECTS OVER 16 SQUARE INCHES, ARE TO BE WRAPPED IN GYPSUM BOARD TO MAINTAIN THE

APPROPRIATE WALL RATING, IF REQUIRED.

15. PROVIDE FIRE AND/OR SMOKE DAMPERS AT ALL LOCATIONS WHERE MECHANICAL DUCTS PENETRATE FIRE AND/OR SMOKE WALLS.

16. WHERE ITEMS ARE DEEPER THAN THE PARTITION WALLS ARE TO BE FURRED OUT TO CONCEAL PIPING, ELECTRICAL PANELS, FIRE EXTINGUISHER CABINETS, AND RECESSED OBJECTS.

NO FURRING SHALL OCCUR ON THE CORRIDOR SIDE OF THE PARTITION.

17. GYPSUM BOARD ABUTTING OTHER MATERIALS OR EXISTING FINISHES IS TO BE FINISHED WITH METAL CORNER BEAD.

18. GYPSUM BOARD AT METAL STUD FURR-OUTS IN AREAS WITH FINISH CEILING SHOULD EXTEND TO 6" ABOVE FINISH CEILING AND BE BRACED WITH VERTICAL MEMBERS SECURED AT A

45 DEGREE ANGLE TO STRUCTURE ABOVE AT 8'-0"O.C.

19. PROVIDE PROPER SUPPORT FOR NEW WORK. IF HANGERS, BACKERS, OR OTHER SUPPORTS ARE NOT DETAILED, NOTED, OR SPECIFIED, CONTRACTOR SHALL SUBMIT A VIABLE SUPPORT

DETAIL TO THE COR FOR APPROVAL.

20. ALL MATERIALS AND INFORMATION NOTED ON ANY OF THE WALL SECTIONS OR DETAILS ON DRAWINGS APPLY TO ALL OTHER SECTIONS AND DETAILS ON THOSE SHEETS WHERE SHOWN OR

WHERE SIMILAR CONDITIONS OCCUR WHETHER NOTED OR NOT.

21. PROVIDE ALL TRANSITION STRIPS AND TERMINATION STRIPS AS REQUIRED AT CHANGE IN FLOOR MATERIAL TO ASSURE SMOOTH TRANSITION OF FINISHES. PROVIDE FOR TRANSITION AT

CENTERLINE OF DOORS WHENEVER POSSIBLE.

22. REMOVE UTILITIES SERVING ITEMS/FIXTURES. DEVICES SHOWN TO BE DEMOLISHED. REMOVE UTILITIES BACK TO ACTIVE LINE OR BRANCH OR TO THE SOURCE.

23. MEDICAL EQUIPMENT SHOWN AS DASHED OR NOTED IN PLAN IS PROVIDED BY VA. SEE VA PROVIDED EQUIPMENT SCHEDULE OR DRAWINGS. CONTRACTOR TO COORDINATE INSTALLATION REQUIREMENTS WITH VA PROVIDED EQUIPMENT. CONTRACTOR TO PROVIDE BLOCKING FOR MISCELLANEOUS VA PROVIDED EQUIPMENT AND FURNISHINGS. CONTRACTOR TO REVIEW PRIOR TO INSTALLATION OF GYP BOARD ANY ADDITIONAL BLOCKING OR SERVICES REQUIRE BY VA NOT SHOWN ON DRAWINGS COORDINATE WITH COR.

24. PRODUCTS LISTED BY MANUFACTURER AND/OR MODEL NUMBER WERE USED AS A DESIGN BASIS, OTHER MANUFACTURERS MAY BE USED AS APPROVED BY VA AND/OR ARCHITECT.

25. BEFORE FABRICATION OR INSTALLATION OF ANY NEW WORK INSIDE THE BUILDING, CONTRACTOR SHALL PREPARE COORDINATION DRAWINGS AT 1/4" SCALE MINIMUM. COORDINATION DRAWINGS SHALL INCLUDE ALL NEW WORK SUCH AS FIRE PROTECTION PIPING AND HEADS, PLUMBING PIPING, MEDICAL GAS PIPING, HVAC DUCTWORK, HVAC PIPING, LIGHTS, CABLE TRAY, ELECTRICAL FEEDER CONDUITS, CEILING GRID, ETC. ALL WORK SHALL BE COORDINATED WITH NEW AND EXISTING STRUCTURE AND WALLS. CONTRACTOR SHALL INCLUDE MINOR RELOCATIONS OF NEW WORK AS REQUIRED TO FIT THE WORK INTO THE EXISTING BUILDING AND THE NEW ADDITION. ANY CONFLICTS CAUSED BY WORK INSTALLED BEFORE APPROVAL OF THE COORDINATION DRAWINGS BY THE COR SHALL BE REMOVED AND RE-INSTALLED IN ACCORDANCE WITH THE COORDINATION DRAWINGS.

26. ALL SHUT DOWNS SHALL BE PERFORMED DURING OFF HOURS, HOURS OF OPERATION ARE 7AM-5PM MON-FRI & 7AM-4:30PM SAT -SUN.

WPT

WD

WO

WM

WG

WIN

W/

WHB

WWF

WS

WP

WC

WH

WTW

VB

VCT

VIN

VERT

VRM

VB

LINTELLTL

CUBIC YARD

CUBIC FOOT

COURSE(S)

COUNTERSUNK SCREW

COUNTERSINK

COUNTERFLASHING

COUNTER

CORRUGATED

CORNER GUARD

CONTROL JOINT

CONTRACT(OR)

CY

CF

CRS

CTSK

CS

CONTR

CFL

CTR

CORR

CG

CJ

CLEANOUT

CENTER TO CENTER

CONTINUOUS

CONSTRUCTION

CONNECTION

CONCRETE

COMPARTMENT

COMBINATION

COLUMN

CLOSURE

CLEAR(ANCE)

CONST

C-C

CONT

CX

CMU

CONC

COMPT

COMB

CO

COL

CLS

CLR

FUTURE

FURRED(ING)

FURNISHED BY OTHERS

FULL SIZE

FIRE RETARDANT TREATED

FOUNDATION

FOOTING

FLUSH JOINT

FLUORESCENT

FLOOR PLATE

FUT

FUR

FBO

FS

FRT

FND

FLUR

FPL

FTG

FJT

PROPERTY LINE

PREFORMED

PREFINISHED

PREFABRICATE(D)

PRECAST CONCRETE

POUNDS PER SQUARE INCH

POUNDS PER SQUARE FOOT

POUNDS PER LINEAL FOOT

POUNDS PER CUBIC FOOT

POLYVINYL CHLORIDE

POINT

PLYWOOD

PLATE GLASS

PLATE

PLASTIC LAMINATE

LOUVER

LIVE LOAD

LVR

LL

PFB

PL

PRF

PFN

PVC

PCC

PSI

PSF

PLF

PCF

PT

PWD

PG

PL

PLAM

UNF

TYP

TOW TOP OF WALL

TYPICAL

FLATHEAD MACHINE SCREW

FIRE EXTINGUISHER CABINET

ANOD ANODIZED

CARP CARPET(ED)

CENTER LINE

CIRCUMFERENCE

CIRCLE

CHAMFER

CERAMIC TILE

CENTIMETER(S)

CEILING HEIGHT

CEILING

CATCH BASIN

CAST-IN-PLACE

CAST IRON

CL

CIRC

CIR

CHAM

CT

CM

CHT

CLG

CB

CIP

CI

BUILDING

BRONZE

BOTTOM

BOTH WAYS

BOTTOM AND TOP

BLDG

BRK

BOT

BW

B&T

FIRE EXTINGUISHERFE

FLOOR DRAIN

FLOOR CLEANOUT

FLOORING

FLEXIBLE

FLATHEAD WOOD SCREW

FLASHING

FIRE-RESISTANT COATING

FIREPROOF

FIRE HOSE STATION

FHMS

FHWS

FD

CO

FLR

FLX

FRC

FHS

FEC

FLG

FP

FOOT

FIRE ALARM

FINISHED FLOOR

FINISH(ED)

FIBERGLASS

FENCE

FASTEN, FASTENER

FACE OF STUDS

FACE OF MASONRY

FACE OF FINISH

FACE OF CONCRETE

FN

FGL

FT

FA

FF

FIN

FOS

FOM

FOF

FOC

FAS

BOTH SIDES

BLOCKING

BITUMINOUS

BEVELED

BETWEEN

BENCH MARK

BED JOINT

BEARING PLATE

BEARING

BS

BD

BLKG

BLK

BIT

BVL

BOARD

BLOCK

BTWN

BEL

BM

BJT

BPL

BRG

BELOW

BACK PLASTER(ED)

AUTOMATIC

ASPHALT

AREA DRAIN

ARCHITECT(URAL)

APPROXIMATE

BP

AUTO

ASPH

AD

ARCH

APX

EXTERIOR

EXPOSED

EXPANSION BOLT

EXPANSION JOINT

EXISTING

EXHAUST

EXCAVATE

EACHWAY

EXP

EXT

EXG

EXH

EXCA

EB

EJ

EW

EACH

EQUIPMENT

EQUAL

ENCLOSE(URE)

EMERGENCY

EMBANKMENT

ELEVATION

ELECTRIC WATER COOLER

ELECTRICAL PANELBOARD

ELECTRIC(AL)

EACH FACE

EQP

ENC

EMER

EMB

EQ

EL

EWC

ELEC

EA

EP

EF

ACP

ANCHOR BOLT

ANCHOR, ANCHORAGE

ALUMINUM

ALTERNATE

AIR CONDITIONING

AGGREGATE

ADJUSTABLE

ADJACENT

ADHESIVE

ADDENDUM

ACOUSTICAL TILE

AGG

AB

ANCH

ALUM

ALT

A/C

ADJT

ADJ

ADH

ADD

ACT

ACOUSTICAL

ACCESS PANEL

ACCESS

ABV ABOVE

ACOUS

AP

ACC

AFF

DIAMETERDIA

DRAWING

DRAWER

DRAIN TILE

DRAINBOARD

DRAIN

DOWNSPOUT

DOOR

DIVISION

DISPENSER

DIMENSION

D

DWG

DWR

DRB

DT

DPR

DS

DR

DIV

DIM

DIAGONAL

DETAIL

DEPRESSED

DEMOLISH

DEAD LOAD

DAMPERDPR

DIAG

DET

DEP

DEM

DL

RISERR

MISCELLANEOUSMISC

PERIMETER

PERFORATE(D)

PEDESTAL

PAVEMENT

PAVE(D), (ING)

PARTITION

PARTICLE BOARD

PARKING

PARALLEL

PAPER TOWEL RECEPTOR

PAPER TOWEL DISPENSER

PANIC BAR

PANEL

PAINT(ED)

OVERHEAD

OVERALL

OUTSIDE FACE

OUTSIDE DIAMETER

OPPOSITE SURFACE

OPPOSITE HAND

OPPOSITE

OPEN-WEBB JOIST

OPENING

OPAQUE

ON CENTER(S)

OBSCURE

NOT TO SCALE

NOT IN CONTRACT

NORTH

NEAR FACE

NONMETALLIC

NOMINAL

NOISE REDUCTION

NICKEL

NATURAL

MULLION

MOVABLE

MOUNT(ED), (ING)

MOLDING, MOULDING

MODULAR

OJ

LIGHTPROOF

LIGHT CONTROL

LIGHT

LENGTH

LAVATORY

LAMINATE(D)

LAG BOLT

LADDER

LABORATORY

LABEL

LAM

LP

LC

LT

L

LAV

LB

LAD

LAB

LBL

JOIST

KNOCKOUT

KICKPLATE

JOINT

JOINT FILLER

JOINT

JANITOR'S CLOSET

JST

KO

KPL

J

JF

JT

JC

PERI

PERF

PED

PVMT

PV

PTN

PBD

PK

PAR

PTR

PTD

PB

OA

PNL

PNT

OH

OF

OD

OPS

OPH

OPP

INCH

INSIDE FACE

INVERT

INTERMEDIATE

INTERLOCK

INTERIOR

INSULATION

INSIDE DIAMETER

INCLUDE(D), (ING)

INT

IN

IF

INV

INTM

ILK

INSUL

ID

INCL

HOT WATER HEATER

HOSE BIBB

HORIZONTAL

HOLLOW METAL

HOLLOW CORE

HEXAGONAL

HEIGHT

HEAVY DUTY

HEADER

HEAD JOINT

HWH

HB

HOR

HM

HC

HX

HT

HD

HVAC

HDR

HJT

OPG

OP

OC

OBS

NTS

NIC

NF

NMT

NOM

NR

NI

NAT

MULL

MOV

MT

MLD

MOD

SQUARESQ

T&B

TOM

TOC

TOS

TSL

TPD

TPTN

THR

THK

TEL

SD

SYS

SYN

SYM

SUSP

STRUCT

STOR

STL

STA

STD

SS

TOILET PAPER DISPENSER

TOP AND BOTTOM

TOP OF MASONRY

TOP OF CONCRETE

TOP OF STEEL

TOP OF SLAB

TOILET PARTITION

THRESHOLD

THICK(NESS)

TELEPHONE

STORM DRAIN

SYNTHETIC

SYMMETRY(ICAL)

SUSPENDED

STRUCTURAL

SYSTEM

STANDARD

STAINLESS STEEL

STORAGE

STEEL

STATION

SPA

SPEC

SPL

SPC

SP

SC

SL

SIM

SH

SG

SHT

SHTH

SSK

SEC

SNT

SCN

SCH

SFGL

RVT

SPECIFICATION(S)

SOUNDPROOF

SPACES

SPECIAL

SPACER

SOLID CORE

SHELF, SHELVING

SHEET GLASS

SLEEVE

SIMILAR

SHEET

SHEATHING

SERVICE SINK

SCHEDULE

SECTION

SEALANT

SCREEN

SAFETY GLASS

RIVET

MIRROR

MINIMUM

MILLIMETER(S)

METER(S)

METAL THRESHOLD

METAL ROOF DECKING

METAL FURRING

METAL FLOOR DECKING

METAL

MEMBER

MEDIUM

MECHANIC(AL)

MAXIMUM

MATERIAL(S)

MASONRY OPENING

MASONRY

MANUFACTURE(ER)

MANHOLE

GALVANIZED STEEL SHEET

GLASS, GLAZINGGL

HANDICAP

HARDWARE

GYPSUM

GROUT

GRAVEL

GRADE, GRADING

GRAB BAR

GLASS FIBER

GLASS BLOCK

GT

GYP

HDCP

HDW

GVL

GD

GB

GLF

GLBK

GASKET(ED)

GALVANIZED PIPE

GALVANIZED IRON

GALVANIZED

GAGE, GAUGEGA

GKT

GSS

GP

GI

GALV

MECH

MRD

MIR

MIN

MM

MTHR

MTFR

MFD

MET

MBR

MED

MH

MAX

MTL

MO

MAS

MFR

RCP

REV

ROW

RH

RO

RM

RFG

RVS

RA

RET

RES

REM

RAD

RE

FRL

REF

RWC

RL

REINFORCED CONCRETE PIPE

REVISION(S), REVISED

RIGHT OF WAY

RIGHT HAND

ROUGH OPENING

ROOM

ROOFING

REVERSE(SIDE)

RETURN AIR

RESILIENT

RETURN

REMOVE

REINFORCE(D), (ING)

REFLECT(ED), (IVE), (OR)

RAINWATER CONDUCTOR

RADIUS

REFERENCE

RAIL(ING)

WOOD

WITHOUT

WIRE MESH

WIRED GLASS

WHEEL BUMPER

WELDED WIRE FABRIC

WATERPROOFING

WATER CLOSET

WALL TO WALL

WATERSTOP

WINDOW

WITH

WALL HUNG

VAPOR BARRIER

VINYL BASE

VINYL

VERTICAL

VERMICULITE

UNFINISHED

M

N

WORKING

POINT

HEATING/VENTILATION/

AIR CONDITIONING

CONCRETE

MASONRY UNIT

ACOUSTICAL CEILING

PANEL

ABOVE FINISHED

FLOOR

VINYL COMPOSITION

TILE

ARCHITECTURAL SYMBOLS

ARCHITECTURAL HATCH GENERAL NOTES

ARCHITECTURAL ABBREVIATIONS

ROOM NUMBER & NAME

ENLARGED DETAILS OR PLANS

WALL TYPE

WINDOW INDICATOR (LETTER)

CARD READER

PUSH BUTTON COMBINATION LOCK

PUSH PLATE WALL SWITCH FOR AUTO DOORS

FERROMAGNETIC DETECTORS

CORNER GUARD (NUMBER INDICATES

DIFFERANT STYLES AND SIZES. SEE

DETAILS SHEET 3/AS501 AND

SPECIFICATIONS.

HOLD OPEN

VIEW NAME

SCALE

X

SCALE

VIEW NAME

X

SCALE

VIEW NAME

X

X

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

VA Project No.

Drawing Number

Dwg. of on e-ei gh th in ch on e fo ot on e-qu ar te r in ch on e fo ot th re e-ei gh th s in ch on e fo ot on e-ha lf in ch on e fo ot th re e-qu ar te rs in ch on e fo ot on e in ch on e fo ot on e an d on e-ha lf in ch es on e fo ot th re e in ch es on e fo ot

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

ARCHITECT/ENGINEERS:CONSULTANTS:

CDL Project No.

Collaborative Design,Ltd.

2727 Tuller Parkway, Suite 200

Dublin, Ohio 43017

Tel 614.798.1515 Fax 614.798.5105

COLUMBUS, OH

757-19-201

1A

Chalmers P. Wylie Ambulatory Care Center

757-19-201 REMODEL

PHARMACY IV PREP ROOM

05/18/18

GENERAL INFORMATION

G-002

17029

Approver DM MB

DELLOS

D

MORRISON

R E

G I S

T

ER ED A RC

H

I T E

C T

UP

UP

UP

UP

UP

I

EXISTING

DUMPSTER

CEILING WORK FOR

PLUMBING LOCATION OF TEMPORARY

IV PREP CENTER

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

VA Project No.

Drawing Number

Dwg. of on e-ei gh th in ch on e fo ot on e-qu ar te r in ch on e fo ot th re e-ei gh th s in ch on e fo ot on e-ha lf in ch on e fo ot th re e-qu ar te rs in ch on e fo ot on e in ch on e fo ot on e an d on e-ha lf in ch es on e fo ot th re e in ch es on e fo ot

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

ARCHITECT/ENGINEERS:CONSULTANTS:

CDL Project No.

Collaborative Design,Ltd.

2727 Tuller Parkway, Suite 200

Dublin, Ohio 43017

Tel 614.798.1515 Fax 614.798.5105

COLUMBUS, OH

757-19-201

1A

Chalmers P. Wylie Ambulatory Care Center

757-19-201 REMODEL

PHARMACY IV PREP ROOM

05/18/18

OVERALL FIRST FLOOR PLAN

G-003

17029

Approver DM MB

N Scale: 1" = 20'-0"

OVERALL FIRST FLOOR PLAN

DELLOS

D

MORRISON

R E

G I S

T

ER ED A RC

H

I T E

C T

O S

G F

C I

O S

J

JJ

M

J

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

VA Project No.

Drawing Number

Dwg. of on e-ei gh th in ch on e fo ot on e-qu ar te r in ch on e fo ot th re e-ei gh th s in ch on e fo ot on e-ha lf in ch on e fo ot th re e-qu ar te rs in ch on e fo ot on e in ch on e fo ot on e an d on e-ha lf in ch es on e fo ot th re e in ch es on e fo ot

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

ARCHITECT/ENGINEERS:CONSULTANTS:

CDL Project No.

Collaborative Design,Ltd.

2727 Tuller Parkway, Suite 200

Dublin, Ohio 43017

Tel 614.798.1515 Fax 614.798.5105

COLUMBUS, OH

757-19-201

1A

Chalmers P. Wylie Ambulatory Care Center

757-19-201 REMODEL

PHARMACY IV PREP ROOM

05/18/18

OVERALL SECOND FLOOR PLAN

G-004

17029

? DM MB

N Scale: 1/16" = 1'-0"

OVERALL SECOND FLOOR PLAN

AREA OF WORK

DELLOS

D

MORRISON

R E

G I S

T

ER ED A RC

H

I T E

C T

I

EXISTING

DUMPSTER

EXIST.

ISO

HOOD

EXIST.

ISO

HOOD

EXIST. TABLE

30x60

EXIST.

STORAGE

CABINET

26x40

EXIST.

STORAGE

CABINET

26x40

EXIST.

CART

23x44

EXIST.

CART

23x44

EXIST.

2 UNIT

REF.

EXIST.

STORAGE

CABINET

26x40

EXIST.

GOWN

CABINET

26x40

EXIST.

CART

19x24

ISO IV PREP

2A213

ANTE PREP

2A212

CONTROL

SUBSTANCE

2A211

SATELITE

PHARMACY

2A210

D2

D1

D4

D1

D1

D5

D7

D6

D7

D6

D6

D6

D6

D6

D7

D7

D7

D9

D9

D9

D8

D8

D8

D8

D9

D7

D10

EXIST. 3 UNIT REF.

EXIST.

REF.

D7

D3

EXIST.

HOOD

D2

D12

D12

D13

D13

D14

D16 D15

D15

D10

D10

D10

IV PREP

2A211

ANTE ROOM

2A212

SATELITE

PHARMACY

2A210

ISO IV PREP

2A213

JANITOR

CLOSET

2A212A

DEMARCATION LINE

5' - 4 1/4"

/8 "5

/4

/8

AREA OF WORK

3' - 7 1/16"

4' - 11"

4' - 11"

2A211

2A212

2A212A

2B

2A213

/4

9' - 10"

8 5/8"

1' - 0"

1' - 6 5/8"

4' - 10 1/2"

5' - 4 1/4"

/2

/2

2A

6 3/4"

/8

/8

/4

15' - 0"

FOOD

SERVICE

1A075

KITCHEN

1A076

KITCHEN

STORAGE

1A077

HAC

1A020

KITCHEN

STORAGE

1A077A

D11

EXISTING WALL OR ITEM TO BE

DEMOLISHED

NEW WALL PER WALL TYPES

DEMO/NEW WORK PLAN LEGEND

S1

S2

S3

S4

S5

S6 S7

S8

S9

S10

S11

S11

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

VA Project No.

Drawing Number

Dwg. of on e-ei gh th in ch on e fo ot on e-qu ar te r in ch on e fo ot th re e-ei gh th s in ch on e fo ot on e-ha lf in ch on e fo ot th re e-qu ar te rs in ch on e fo ot on e in ch on e fo ot on e an d on e-ha lf in ch es on e fo ot th re e in ch es on e fo ot

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

ARCHITECT/ENGINEERS:CONSULTANTS:

CDL Project No.

Collaborative Design,Ltd.

2727 Tuller Parkway, Suite 200

Dublin, Ohio 43017

Tel 614.798.1515 Fax 614.798.5105

COLUMBUS, OH

757-19-201

1A

Chalmers P. Wylie Ambulatory Care Center

757-19-201 REMODEL

PHARMACY IV PREP ROOM

05/18/18

ENLARGED PLANS - DEMOLITION

& NEW CONSTRUCTION

AS-100

17029

DM DM MB

N Scale: 1/4" = 1'-0"

SECOND FLOOR PLAN - DEMOLITION N

Scale: 1/4" = 1'-0"

SECOND FLOOR PLAN - NEW CONSTRUCTION

DEMO PLAN CODED NOTES

D1 EXISTING DOOR, FRAME, AND HARDWARE TO BE DEMOLISHED. DOOR HARDWARE TO

BE TURNED OVER TO OWNER.

D2 WALL TO BE DEMOLISHED FULL HEIGHT. ALL ITEMS MOUNTED IN/ON WALL SHALL BE

REMOVED OR DEMOLISHED BACK TO NEAREST SOURCE. SEE ALSO

MECHANICAL/ELECTRICAL/PLUMBING DRAWINGS.

D3 WALL TO BE DEMOLISHED AS NECESSARY FOR NEW OPENING. ALL ITEMS MOUNTED

IN/ON WALL IN THE AREA OF WORK SHALL BE REMOVED OR DEMOLISHED BACK TO

NEAREST SOURCE. SEE ALSO MECHANICAL/ELECTRICAL/PLUMBING DRAWINGS.

D4 WALL MOUNTED SINK TO BE REMOVED SEE PLUMBING DRAWINGS FOR ADDITIONAL

INFORMATION. REPAIR FLOOR PENETRATIONS. SET ASIDE SINK FOR

REINSTALLATION IN NEW LOCATION PER NEW WORK PLAN AND PLUMBING

DRAWINGS.

D5 EXISTING HOOD TO BE TEMPORARILY RELOCATED BY OWNER. EXISTING HOOD TO

BE REINSTALLED IN NEW LOCATION WHEN CONSTRUCTION IS COMPLETE BY OWNER.

SEE NEW WORK PLAN AND MECHANICAL DRAWINGS."

D6 EXISTING EQUIPMENT/FURINITURE TO BE TEMPORARILY RELOCATED BY OWNER.

EXISTING EQUIPMENT/FURNITURE TO REINSTALLED IN CURRENT LOCATION WHEN

CONSTRUCTION IS COMPLETE BY OWNER. SEE EQUIPMENT PLAN.

D7 EXISTING EQUIPMENT/FURINITURE TO BE TEMPORARILY RELOCATED BY OWNER.

OWNER TO REINSTALL EXISTING EQUIPMENT/FURNITURE IN NEW LOCATION WHEN

CONSTRUCTION IS COMPLETE BY OWNER. SEE EQUIPMENT PLAN.

D8 DEMOLISH EXISTING FLOORING AND WALL BASE IN THIS AREA.

D9 DEMOLISH EXISTING CEILING SYSTEM IN THIS AREA. ALL CEILING MOUNTED ITEMS

TO BE REMOVED/DEMOLISHED PER MECHANICAL/ELECTRICAL/PLUMBING DRAWINGS.

D10 REMOVE GYPSOM BOARD FROM ONE SIDE OF EXISTING STUD WALL, METAL STUDS

TO REMAIN

D11 REMOVE EXISTING LAY IN CEILING IN THIS AREA AS NECESSARY FOR ABOVE CEILING

WORK ASSOCIATED WITH MECH/ELEC/PLUM. REINSTALL LAY IN CEILING SYSTEM

AFTER MEP WORK IS COMPLETED.

D12 REMOVE EXISTING PAPER TOWEL DISPENSOR, FRAMED MIRROR AND SOAP

DISENSOR AND RETAIN FOR REINSTALLATION.

D13 REMOVE EXISTING HAND SANITIZER DISPENSOR AND RETAIN FOR REINSTALLATION.

D14 REMOVE AND RETAIN EXISTING ROOM SIGN FOR RELOCATION.

D15 INSTALL TEMPORARY ICRA/PCRA CLASS IV DUST BARRIER UNTIL PASS THROUGH

AND PERMINANT JANITOR CLOSET WALLS HAVE BEEN INSTALLED.

D16 EXISTING CASEWORK TO BE TEMPORARILY RELOCATED BY CONTRACTOR. EXISTING

CASEWORK TO REINSTALLED IN CURRENT LOCATION WHEN CONSTRUCTION IS

COMPLETE BY CONTRACTOR. SEE EQUIPMENT PLAN.

NEW CONSTRUCTION PLAN CODED NOTES

1 RELOCATED SINK, SEE PLUMBING DRAWINGS

2A NEW 18x18 HEPA FILTERED PASS THROUGH CHAMBER.

2B NEW 12x12 PASS THROUGH CHAMBER.

3 NEW MOP SINK PER PLUMBING DRAWINGS

4 TEMPORARY ICRA/PCRA CLASS IV DUST BARRIER STUD AND GYP BD WALL TO DECK

ABOVE DURING CONSTRUCTION.

5 ALIGN NEW WALL FINISHD FACE WITH EXISTING WALL FINISHED FACE.

6 NEW TAPE DEMARKATION LINE. TAPE TO BE "ULINE" HEAVY DUTY 8 MIL (2") ITEM

NUMBER S-383. TURN EXCESS TAPE OVER TO OWNER.

7 NEW DYSON AIRBLADE DB, MOUNTED PER DYSON GUIDELINES.

8 REINSTALL FRAMED MIRROR, BOTTOM EDGE AT MAX. 40" A.F.F.

9 REINSTALL SOAP DISPENSOR, CONTROLS AT 48" A.F.F.

10 REINSTALL HAND SANITIZER, CONTROLS AT 48" A.F.F.

11 REINSTALL ROOM SIGN, MATCH EXISTING HEIGHT.

12 SEAL AROUND ALL PENATRATIONS, I.E. JUNCTION BOXES, LIGHTS, DIFFUSERS, DUCTS,

DOORS, PASS THROUGH CHAMBERS, ETC. LOCATED IN GYPSUM BOARD WALLS AND

CEILINGS TO INSURE AN AIR-TIGHT SEAL.

13 COORDINATE DOOR OPERATOR SENSOR WITH ELECTRICAL DRAWINGS. TOP OF

SENSOR AT 48" A.F.F.

14 CORNER GUARD.

15 SEAL AROUND ALL OPENINGS, OUTLETS, SWITCHES, LIGHT FIXTURES, HVAC

DIFFUSERS, WALL OPENINGS, DOOR FRAMES, ETC. EVERYTHING MUST BE SEALED

TIGHT FOR AIR BALANCE.

16 PROVIDE NEW ROOM SIGN, MATCH EXISTING SIGN DESIGN & MOUNTING HEIGHT FROM

CODED NOTE 11.

N Scale: 1/4" = 1'-0"

FIRST FLOOR PLAN - DEMOLITION

N Scale: 1/16" = 1'-0"

TEMPORARY IV PREP TRAILER SITE PLAN

SITE PLAN CODED NOTES - TEMPORARY TRAILER

S1 EXISTING RAMP ENCLOSURE TO REMAIN FOR MOBILE IV PREP CENTER DURING

REMODEL PHARMACY IV PREP ROOM PROJECT. REMOVE RAMP ENCLOSURE

INCLUDING FOUNDATION AT END OF PROJECT AND RESTORE SITE TO GRASS

COVERED LAWN.

S2 EXISTING CONCRETE PAD FOR MOBILE IV PREP CENTER LOCATION. CONCRETE

PAD TO REMAIN AT END OF PROJECT.

S3 EXISTING ELECTRICAL PANELS FOR MOBILE IV PREP CENTER. ALL ELECTRICAL FOR

IV PREP CENTER TO REMOVED BACK TO A POINT INSIDE MAIN BUILDING AT END OF

PROJECT, SEE ELECTRICAL DRAWINGS.

S4 EXISTING FIRE, HOT & COLD WATER SOURCE FOR MOBILE IV PREP CENTER. ALL

FIRE, HOT & COLD WATER LINES FOR IV PREP CENTER TO BE REMOVED BACK TO A

POINT INSIDE MAIN BUILDING AT END OF PROJECT, SEE MEP DRAWINGS.

S5 EXISTING SANITARY CONNECTION FOR MOBILE IV PREP CENTER. SAW-CUT

EXISTING CONCRETE PAD AS NECESSARY FOR INSTALLATION OF SANITARY LINES

FOR IV PREP CENTER. ALL SANITARY LINES FOR IV PREP CENTER TO BE REMOVED

AT END OF PROJECT AND PATCH AND REPAIR CONCRETE PAD, SEE MEP

DRAWINGS.

S6 TERMINATE TEMPORARY UTILITIES JUST INSIDE MAIN BUILDING AT END OF

PROJECT. EXISTING WALL PANEL MODIFIED FOR IV PREP CENTER UTILITIES TO BE

REPAIRED TO ADD GALVANIZED WEATHER TIGHT ACCESS PANEL AT END OF

PROJECT, PAINT TO MATCH PANEL. PANEL MANUFACTURER IS "TESCO

ENTERPRISES", COLOR IS "ALLOY 110 SATIN COPPER & LACQUER"

S7 RENTAL OF TEMPORARY IV PREP CENTER BY CONTRACTOR. CONTRACTOR TO

KEEP MOBILE CENTER ON SITE UNTIL RENOVATED PHARMACY IS CERTIFIED. SEE

SPECIFICATIONS FOR ADDITIONAL INFORMATION. TEMPORARY CENTER TO BE

RETURNED AT END OF PROJECT.

S8 INSTALL 4" THICK CONCRETE WALK TO ALIGN WITH IV PREP CENTER DOOR AND

ADJACET CONCRETE SLAB. CONCRETE WALK TO BE REMOVED AT END OF

PROJECT.

S9 INSTALL CANOPY FROM TEMPORARY IV PREP CENTER DOOR TO ENTRY FOR MAIN

BUILDING. CANOPY TO BE REMOVED AT END OF PROJECT.

S10 EXISTING ENTRY DOOR INTO MAIN BUILDING AND CARD READER TO REMAIN AT END

OF PROJECT.

S11 EXISTING SAFETY BARRIERS TO BE REMOVED AT END OF PROJECT AND DISPOSED

OF OFF SITE.

DELLOS

D

MORRISON

R E

G I S

T

ER ED A RC

H

I T E

C T

O S

G F

C I

O S

J

J J

M

J

EXIST.

ISO

HOOD

EXIST.

ISO

HOOD

EXIST. TABLE

30x60

EXIST.

STORAGE

CABINET

26x40

EXIST.

STORAGE

CABINET

26x40

EXIST.

CART

23x44

RELOCATED

CART

23x44

RELOCATED

2 UNIT

REFRIG.

RELOCATED

STORAGE

CABINET

26x40

RELOCATED

GOWN

CABINET

26x40

RELOCATED

CART

19x24

RELOCATED

HOOD

ISO IV PREP

2A213

ANTE ROOM

2A212

IV PREP

2A211

SATELITE

PHARMACY

2A210

RELOCATED

REFRIG.

RELOCATED

3 UNIT

REFRIG.

ISO IV PREP

2A213

ANTE ROOM

2A212

IV PREP

2A211

SATELITE

PHARMACY

2A210

C2

C2

C2

C1

C3

C3

C4

C4

C1

C1

C1

C1

C5

C5

C5

C5

C5

C6

C6

C6

C6

C6

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

VA Project No.

Drawing Number

Dwg. of on e-ei gh th in ch on e fo ot on e-qu ar te r in ch on e fo ot th re e-ei gh th s in ch on e fo ot on e-ha lf in ch on e fo ot th re e-qu ar te rs in ch on e fo ot on e in ch on e fo ot on e an d on e-ha lf in ch es on e fo ot th re e in ch es on e fo ot

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

ARCHITECT/ENGINEERS:CONSULTANTS:

CDL Project No.

Collaborative Design,Ltd.

2727 Tuller Parkway, Suite 200

Dublin, Ohio 43017

Tel 614.798.1515 Fax 614.798.5105

COLUMBUS, OH

757-19-201

1A

Chalmers P. Wylie Ambulatory Care Center

757-19-201 REMODEL

PHARMACY IV PREP ROOM

05/18/18

ENLARGED PLANS - EQUIPMENT

& REFLECTED CEILING PLANS

AS-101

17029

Approver DM MB

N Scale: 1/4" = 1'-0"

ENLARGED PLAN - NEW EQUIPMENT LAYOUT N

Scale: 1/4" = 1'-0"

ENLARGED PLAN - REFLECTED CEILING

REFLECTED CEILING PLAN CODED NOTES

C1 EXISTING CEILING SYSTEM TO REMAIN

C2 NEW GYPSUM BOARD CEILING SYSTEM, PROVIDE ACCESS

PANEL AS REQUIRED FOR ABOVE CEILING MECHANICAL

EQUIPMENT, MINIMUM OF (1) PER ROOM.

C3 REWORK EXISTING CEILING SYSTEM AT NEW WALL

LOCATION.

C4 EXISTING GYPSUM BOARD SOFFIT TO REMAIN

C5 PROVIDE ICRA/PCRA CLASS IV DUST BARRRIER ABOVE AND

IN LINE WITH WALL BELOW DURING CONSTRUCTION.

C6 PROVIDE ACCESS PANEL IN CEILING FOR ACCESS TO

MECHANICAL EQUIPMENT. COORDINATE EXACT LOCATION

WITH MECHANICAL EQUIPMENT.

DELLOS

D

MORRISON

R E

G I S

T

ER ED A RC

H

I T E

C T

J

V A R I E S

3/4"=1'-0"

ANCHOR DETAIL

EXIST. ROOF

MEMBRANE

TPO

SEALANT

S.S.CLAMPING RING

RIGID INSULATION

EXIST.

CONCRETE DECK

TPO FLASHING PER

MANUFACTURERS

RECOMMENDATION

NOTE:

ASSEMBLY TO BE SHOP

FABRICATED AND HOT DIPPED

GALVANIZED

TPO SEALANT

3/8" PLATE

3/8" DIA.

GALV. STEEL

CABLE

3/16"

3/16"

3/16"

3" ∅ SCH 40

PIPE

3/8" x 3" x 3"

PLATE

WITH 4

1 1/2"=1'-0"

MECH. CURB DETAIL

EXIST. ROOF MEMBRANE

EXIST. CONCRETE DECK

RIGID INSUL.

WELDED SPLICE

TPO SEALANT

2x4 TREATED WOOD

BLOCKING

MECH. FASTENER

TPO FLASHING PER MANUFACTURERS

RECOMMENDATION

ROOFTOP MECHANICAL

EQUIPMENT BY HVAC CONTR.

V A R I E S

P E R

M A N U F A C T U R E R

R E C O M M M E N D A T I O N

1 1/2"=1'-0"

MECH. RAIL DETAIL

EXIST. ROOF MEMBRANE

EXIST. CONCRETE DECK

RIGID INSUL.

WELDED SPLICE

TPO SEALANT

2x4 TREATED WOOD

BLOCKING

TPO FLASHING PER MANUFACTURERS

RECOMMENDATION

ROOFTOP MECHANICAL

EQUIPMENT RAIL BY HVAC CONTR.

GALVANIZED STEEL

COUNTERFLASHING

R1

R2

R3

R4

R2

R4

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

VA Project No.

Drawing Number

Dwg. of on e-ei gh th in ch on e fo ot on e-qu ar te r in ch on e fo ot th re e-ei gh th s in ch on e fo ot on e-ha lf in ch on e fo ot th re e-qu ar te rs in ch on e fo ot on e in ch on e fo ot on e an d on e-ha lf in ch es on e fo ot th re e in ch es on e fo ot

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

ARCHITECT/ENGINEERS:CONSULTANTS:

CDL Project No.

Collaborative Design,Ltd.

2727 Tuller Parkway, Suite 200

Dublin, Ohio 43017

Tel 614.798.1515 Fax 614.798.5105

COLUMBUS, OH

757-19-201

1A

Chalmers P. Wylie Ambulatory Care Center

757-19-201 REMODEL

PHARMACY IV PREP ROOM

05/18/18

ROOF PLAN

AS-102

17029

Approver Checker Designer

N Scale: 1/8" = 1'-0"

THIRD FLOOR / ROOF PLAN

ROOF PLAN CODED NOTES

R2 NEW ROOF TOP EQUIPMENT PER

MECHANICAL/ELECTRICAL DRAWINGS. NEW 14" x

14" ROOF OPENING IN EXISTING CONCRETE

COMPOSITE DECK, (6 1/2" THICK). "DO NOT" OVER

CUT 14" x 14" OPENING. COORDINATE OPENING

WITH LOCATION OF EXISTING STEEL FRAMING.

OPENING REINFORCING IS NOT REQUIRED FOR 14"

x 14" OPENING. IF OVERCUT, NOTIFY COR

IMMEDIATELY.

R3 PATCH AND REPAIR EXISTING TPO ROOFING AT

NEW ROOF TOP EQUIMENT. REPLACE INSULATION,

THICKNESS TO MATCH EXISTING & PROVIDE

POSITIVE SLOPE TOWARDS ROOF DRAIN.

R4 NEW GUY WIRE SUPPORT PER DETAILS 1 &

2/1A-AS-102

DELLOS

D

MORRISON

R E

G I S

T

ER ED A RC

H

I T E

C T

6"8" 2'-6"

A B

GLAZING

AS

SCHEDULED

2"SEE DOOR

S E

E D

O O

R S

C H

E D

2"

SCHED

S.S.

WELDED

FRAME

REFER TO

PLANS

REFER TO

PLANS

WALL THICKNESS NOTED

AS 5" [127 mm] ON

PLANS

3-5/8" [92 mm]

METAL STUDS @

16" [406 mm] O.C.

ROOF OR

FLOOR ABOVE

PROVIDE SLIP

CONNECTION WITH

DEEP LEG TRACK

5/8" [16 mm]

GYP. BD. EACH SIDE

FINISH CEILING -

SEE REFLECTED

CEILING PLAN FOR

LOCATION

WALL THICKNESS

NOTED ON PLANS

EXISTING METAL

STUD WALL TO

REMAIN

WALL THICKNESS

NOTED ON PLANS

3-5/8" METAL

STUDS @ 16"

O.C.

ROOF OR

FLOOR ABOVE

REMOVE GYP.

BOARD THIS SIDE

OF EXIST. WALL

5/8" GYP.

BD.

BRACE WALL @

4'-0" O.C.

MAX.

WALL THICKNESS NOTED

AS 5" [127 mm] ON

PLANS

3-5/8" [92 mm]

METAL STUDS @

16" [406 mm] O.C.

ROOF OR

FLOOR ABOVE

PROVIDE SLIP

CONNECTION WITH

DEEP LEG TRACK

5/8" [16 mm]

GYP. BD. EACH SIDE

BATT INSULATION

FINISH CEILING -

SEE REFLECTED

CEILING PLAN FOR

LOCATION

BRACE WALL @

4'-0" O.C.

MAX.

BATT INSULATION

BATT

INSULATION

FINISH CEILING -

SEE REFLECTED

CEILING PLAN FOR

LOCATION

EXISTING METAL

STUD WALL TO

REMAIN

6" METAL STUDS

@ 16" O.C.

ROOF OR

FLOOR ABOVE

REMOVE GYP.

BOARD THIS SIDE

OF EXIST. WALL

5/8" GYP.

BD.

BATT

INSULATION

FINISH CEILING -

SEE REFLECTED

CEILING PLAN FOR

LOCATION

EXISTING METAL

STUD WALL &

GYP. BOARD @

CORRIDOR TO

REMAIN

NOTE: ALL METAL STUDS ARE 20 GAUGE UNLESS NOTED OTHERWISE. SEE BELOW FOR TYPICAL CONTROL JOINT LOCATIONS AND INSTALLATION.

1A 41B 3

7_

7 _ 8

2"

NOTE 1:

OMIT BRACE WHEN "D" DIMENSION IS LESS THAN 2'-0"

FOR GYP. WALLBD. OR 16" FOR PLASTER PARTITION.

SECTION B

VERTICAL STUDS @ 2'-0" MAX. W/GYPSUM WALL BD.

1'-4" W/GYPSUM LATH & PLASTER DOUBLE STUDS

FOR SUPPORTING CONC. BACKER BOARD.

PROVIDE CONTINUOUS BRACING WHEN STUDS

EXCEED 10'-0" & ARE FINISHED BOTH SIDES

JAMB ANCHOR CLIPS 3 PER SIDE - COORDINATE

W/HINGE REINFORCEMENT.

DETAIL D

SEE NOTE

1/2"

CONST.

JOINT

RUNNER

BET.

STUDS

SEE

DOOR

SCHEDULE

SHIM AS

REQ'D.

SEC. B

ELEVATION AT DOOR FRAME

DETAIL D

PROVIDE

SOUND

DEADENING

WHERE

REQ'D.

SANITARY STOP

METAL DOOR FRAME

METAL

ANCHOR

CLIP

SHIM AS

REQ'D.

DETAIL C

JAMB ANCHOR

SECTION A

DOUBLE STUDS

DETAIL C

1/ 2"

JAMB ANCHORS

(FURNISHED WITH FRAME)

EQ

EQ

VA

RI

ES

VARIES

MET.

DOOR

FRAME

M A X

1/2"

A A

D

EQ

EQ

M

IN

WIDTH

STUD

MINUS 3/16"

[5mm]

JAMB DEPTH

M

IN

M

IN

. WIDTH

STUD

FR

AM

E

FA

CE

MI

NU

S 3/

MI

NU

S 3/

FR

AM

E

FA

CE

"M

IN.

5/ 8"

MA

X.

NOT TO SCALE

TYPICAL PARTITION FRAMING FOR DOORS

1-1/2"=1'-0"

DOOR HEAD DETAIL

1-1/2"=1'-0"

DOOR JAMB DETAIL

DOOR - SEE

SCHEDULE

3 5/8"

MTL. STUDS

5/8" GYPSUM

BOARD EACH SIDE

S.S. DOOR

FRAME

SEALANT

CONTINUOUS

EACH SIDE

INSULATION PER

WALL TYPES INSULATION PER

WALL TYPES

3 5/8"

MTL. STUDS

S.S. FRAME WITH 3

ANCHORS PER JAMB

SEALANT

CONTINUOUS EACH

SIDE

5/8" GYPSUM

BOARD

EACH SIDE

DOOR - SEE

SCHEDULE

SEE TYPICAL DOOR FRAMING DETAIL 3/AS-300

SEE TYPICAL DOOR FRAMING DETAIL 3/AS-300

CONTROL JOINT DETAIL

1/4"=1'-0"

CONTROL JOINT

ON HINGE SIDE

OF DOOR LINE OF CEILING

LINE OF ROOM BASE

CONTROL JOINT DETAIL

1/4"=1'-0"

CONTROL JOINT

ON HINGE SIDE

OF DOOR LINE OF CEILING

LINE OF ROOM BASE

GYPSUM BOARD CONSTRUCTION NOTES FOR CONTROL JOINT INSTALLATION

INSTALL CONTROL JOINTS CONSISTENT WITH LINES OF BUILDING SPACES IN LOCATIONS SUCH AS THE FOLLOWING:

1. WHERE EXPANSION OR CONTROL JOINTS OCCUR IN SUBSTRATE;

2. WHERE CEILING FRAMING OR FURRING CHANGES DIRECTION;

3. WHERE WINGS OF "L," "U," AND "T"-SHAPED CEILING AREAS ARE JOINED;

4. WHERE GYPSUM BOARD ABUTS STRUCTURAL ELEMENTS, SUCH AS COLUMNS, BEAMS AND LOAD BEARING WALL;

5. WHERE GYPSUM BOARD ABUTS DISSIMILAR WALL, CEILING OR SOFFIT FINISHES BY EDGE TRIM.

6. AT BOTH CORNERS OF DOOR JAMBS, EXTENDING FROM DOOR HEAD TO CEILING.

7. AT BOTH CORNERS OF WINDOW JAMBS, EXTENDING FROM WINDOW HEAD TO CEILING.

B. FULL HEIGHT DOOR FRAMES SHALL BE CONSIDERED EQUIVALENT TO A CONTROL JOINT.

C. PROVIDE CONTROL JOINTS IN FIRE-RESISTANT CONSTRUCTION ACCORDING TO GA 234.

8. LOCATE CONTROL JOINTS ACCORDING TO THE FOLLOWING CHART:

CONSTRUCTION AND LOCATION MAX. SINGLE DIMENSION MAX. SINGLE AREA

CEILING INTERIOR

WITH PERIMETER RELIEF 50-0" 2500 SQ. FT.

WITHOUT PERIMETER RELIEF 30'-0" 900 SQ. FT.

CEILING - EXTERIOR GYPSUM BOARD 30'-0" 900 SQ. FT.

PARTITION - INTERIOR 30-0"

NOT TO SCALE

TYPICAL CORNER GUARD DETAIL

CORNER

GUARD

FINISHED WALL

1 _ 2

T Y P

EXIST. CONCRETE DECK

SHEET VINYL FLOOR

4" INTEGRAL ROOM BASE

TERMINATION

STRIP

SEALANT

PARTITION WALL

J-BEAD

FRT WOOD BLOCKING

3/8 " GYP. BD.

PROVIDE CANOPY SIMILAR TO IMAGE

FROM TEMPORARY IV PREP CENTER TO MAIN BUILDING ENTRY.

PROVIDE CANOPY WITH CLEAR PLASTIC SIDES.

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

VA Project No.

Drawing Number

Dwg. of on e-ei gh th in ch on e fo ot on e-qu ar te r in ch on e fo ot th re e-ei gh th s in ch on e fo ot on e-ha lf in ch on e fo ot th re e-qu ar te rs in ch on e fo ot on e in ch on e fo ot on e an d on e-ha lf in ch es on e fo ot th re e in ch es on e fo ot

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

ARCHITECT/ENGINEERS:CONSULTANTS:

CDL Project No.

Collaborative Design,Ltd.

2727 Tuller Parkway, Suite 200

Dublin, Ohio 43017

Tel 614.798.1515 Fax 614.798.5105

COLUMBUS, OH

757-19-201

1A

Chalmers P. Wylie Ambulatory Care Center

757-19-201 REMODEL

PHARMACY IV PREP ROOM

05/18/18

SCHEDULES & WALL TYPES &

DETAILS

AS-300

17029

Approver Checker Designer

DOOR SCHEDULE

Mark Panel Width Panel Height Thickness Panel Type

Panel Material Glazing Frame Type

Frame Material Head Detail Jamb Detail Sill Detail Fire Rating

Hardware Set Remarks

2A212 3' - 8" 7' - 6" 1 3/4" B SS CLR/TEMP 1 SS 1/AS-3OO 2/AS-300 -- - 1F

2A212A 3' - 0" 7' - 0" 1 3/4" A SS - 1 SS 1/AS-3OO 2/AS-300 -- - 5D

2A211 3' - 8" 7' - 6" 1 3/4" B SS CLR/TEMP 1 SS 1/AS-3OO 2/AS-300 -- - 1

2A213 3' - 9" 7' - 6" 1 3/4" B SS CLR/TEMP 1 SS 1/AS-3OO 2/AS-300 X/AS-300 - 1

ROOM FINISH SCHEDULE

Number Name

WALL

BASE

FLOOR

FINISH

WALL

MATERIAL

WALL

FINISH

CEILING

MATERIAL

CEILING

FINISH

CEILING

HEIGHT REMARKS

2A211 IV PREP NOTE 2 RSF GYP BD EPOXY PAINT GYP BD EPOXY PAINT 8'-6"

2A212 ANTE ROOM NOTE 2 RSF GYP BD EPOXY PAINT GYP BD EPOXY PAINT 9'-0"

2A213 ISO IV PREP NOTE 2 RSF GYP BD EPOXY PAINT GYP BD EPOXY PAINT 9'-0"

2A210 SATELITE PHARMACY NOTE 2 RSF GYP BD EPOXY PAINT GYP BD EPOXY PAINT 9'-0" NOTE 1

2A212A JANITOR CLOSET NOTE 2 RSF GYP BD EPOXY PAINT GYP BD EPOXY PAINT 9'-0"

Scale: 1/4" = 1'-0"4

DOOR TYPES

Scale: 1/4" = 1'-0"5

FRAME TYPES

N.T.S.Scale:

WALL TYPES

REMARKS:

1. NEW FINISHES TO MATCH EXISTING FOR ROOM 2A210

2. INTEGRAL RSF COVED BASE.

N.T.S.Scale:

Temporary Canopy

Revisions Date

BID SET 5/18/18

Scale: 3" = 1'-0"7

INTEGRAL RSF COVED BASE DETAIL

FIRE PROTECTION GENERAL NOTES:

1. FIRE PROTECTION SYSTEM TO COMPLY WITH NFPA 13, 14, 20, 24

AND ALL APPLICABLE STATE CODES.

2. FINAL INSPECTION AND APPROVAL BY CONTRACTION OFFICER'S

REPRESENTATIVE (COR).

3. SPRINKLER SHOP DRAWINGS AND MATERIAL SUBMITTALS SHALL

BE SUBMITTED TO THE COR AND SHALL BE APPROVED PRIOR TO

ANY INSTALLATION.

4. PIPE ROUTING IS NOT SHOWN. IT IS THE RESPONSIBILITY OF THIS

CONTRACTOR TO PROVIDE PIPING MODIFICATIONS AND OFFSETS

REQUIRED FOR PROPER INSTALLATION AND COORDINATION WITH

OTHER TRADES.

5. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR

CEILING DESCRIPTIONS AND HEIGHTS.

6. SPRINKLERS ARE TO BE COORDINATED WITH ALL DIFFUSERS,

SPEAKERS, LIGHTING FIXTURES AND CEILING SYSTEMS. SPACING

OF SPRINKLERS SHALL BE IN ACCORDANCE WITH NFPA 13 AND THE

LISTING OF THE SPRINKLER.

7. BEFORE FABRICATION OF INSTALLATION OF ANY NEW WORK INSIDE

THE BUILDING, CONTRACTOR SHALL PREPARE COORDINATION

DRAWINGS AT 1/4" SCALE MINIMUM. COORDINATION DRAWINGS

SHALL INCLUDE ALL NEW WORK SUCH AS FIRE PROTECTION PIPING

AND HEADS, PLUMBING PIPING, MEDICAL GAS PIPING, HVAC

DUCTWORK, HVAC PIPING, LIGHTS, CABLE TRAY, ELECTRICAL

FEEDER CONDUITS, CEILING GRID, ETC. ALL WORK SHALL BE

COORDINATED WITH NEW AND EXISTING STRUCTURE AND WALLS.

CONTRACTOR SHALL INCLUDE MINOR RELOCATIONS OF NEW

WORK AS REQUIRED TO FIT THE WORK INTO THE EXISTING

BUILDING AN THE NEW ADDITION. ANY CONFLICTS CAUSED BY

WORK INSTALLED BEFORE APPROVAL OF THE COORDINATION

DRAWINGS BY THE COR SHALL BE REMOVED AND RE-INSTALLED IN

ACCORDANCE WITH THE COORDINATION DRAWINGS.

8. SPRINKLER LOCATIONS SHALL BE CENTERED IN THE TILE. PROVIDE

ARM-OVER OR SWING JOINT AS REQUIRED. SUPPORT ANDY

ARM-OVER 18" OR LONGER.

9. SLEEVE AND FIRESTOP ALL PENETRATIONS THROUGH RATED

WALLS, CEILINGS, AND FLOORS WITH U/L LISTED ASSEMBLIES.

FIRESTOP ASSEMBLIES SHALL BE EQUAL OR EXCEED THE RATING

OF THE WALL, CEILING OR FLOOR. SEE ARCHITECTURAL DRAWINGS

FOR FINAL FINISHES.

10. PROVIDE ACCESS PANELS TO ALL VALVES ABOVE

NON-ACCESSIBLE CEILINGS AND CHASES.

11. COORDINATE PIPING WITH ALL ELECTRICAL EQUIPMENT (PANELS,

TRANSFORMERS, ETC.) PRIOR TO ANY INSTALLATION. DO NOT

ROUTE ANY PIPING OVER ANY ELECTRICAL PANELS UNDER ANY

CIRCUMSTANCES. ANY PIPING RUN OVER ELECTRICAL SHALL BE

REROUTED AT NO ADDITIONAL COST.

12. THE FIRE PROTECTION SYSTEMS AND INFORMATION SHOWN

WITHIN THESE DRAWINGS AND THE SPECIFICATIONS, REPRESENT

THE DESIGN INTENT OF THE ENGINEER OF RECORD. IT IS THE

RESPONSIBILITY OF THE CONTRACTOR TO SUBMIT LAYOUT

DRAWINGS TO THE AUTHORITY HAVING JURISDICTION FOR

PERMITTING AND REVIEW. THE LAYOUT DRAWINGS SHALL BE IN

COMPLIANCE WITH NFPA 13, 8-1, WORKING PLANS.

13. FINAL INSPECTION AND APPROVAL BY LOCAL FIRE MARSHAL AND

ARCHITECT/ENGINEER.

14. ROLL GROOVE AND CUT GROOVED COUPLINGS AND FITTINGS

SHALL BE PROVIDED BY A SINGLE MANUFACTURER, NO EXCEPTION.

15. WITHIN THE AREA OF WORK, PROVIDE TEMPORARY UPRIGHT

SPRINKLER HEADS FOR COMPLETE COVERAGE PER NFPA 13 IN ALL

AREAS WHERE EXISTING CEILINGS WILL BE REMOVED FOR MORE

THAN 10 HOURS. REMOVE TEMPORARY HEADS AND INSTALL

PERMANENT PENDANT HEADS WHEN CEILING IS RE-INSTALLED.

FIRE PROTECTION LEGEND

RESPONSETEMP MFG.PLATESTYLEMODELFINISHK-FACSYMBOL

FIRE SPRINKLER LEGEND

SYMBOL DESCRIPTION

1" DROP

SPRINKLER HEAD

1" 90° ELL 1" 90° ELL

1x\ REDUCER

BRANCH LINE

CEILING

RETURN BEND DETAIL

FIRE PROTECTION DESIGN DATA

QUICK RESPONSE175° 5.6 CHROME F1FR 56 INSTITUTIONAL CHROME RELIABLE

NOTES

NOTE:

SPECIFIED SPRINKLER IS BASIS OF DESIGN ONLY. CONTRACTOR SHALL MATCH EXISTING SPRINKLER HEAD TYPE, TEMPERATURE RATING, K-FACTOR, ETC. CONTRACTOR SHALL PROVIDE ADDITIONAL SPRINKLERS AS

REQUIRED TO BE INSTALLED IN SPARE SPRINKLER HEAD CABINET

F

F

F

SYMBOL DESCRIPTION

QUICK RESPONSE175° 5.6 CHROME F1FR 56 INSTITUTIONAL CHROME RELIABLE

- NEW UPRIGHT SPRINKLER

- NEW PENDENT SPRINKLER

- EXISTING PENDENT SPRINKLER

- DEMOLITION PENDENT SPRINKLER

- NEW SPRINKLER PIPING

- EXISTING SPRINKLER PIPING

- DEMOLITION SPRINKLER PIPING

W/FP

ESCUTCHEON

W/FP

ESCUTCHEON

DESIGN CRITERIA:

THE FOLLOWING PUBLICATIONS SHALL BE USED AS A REFERENCE FOR DESIGN OF

THE FIRE SUPPRESSION SYSTEM ON THIS PROJECT.

1. DEPT. OF VETERAN'S AFFAIRS FIRE PROTECTION DESIGN GUIDELINES

2. NFPA 1, UNIFORM FIRE CODE - 2007 EDITION

3. NFPA 13, INSTALLATION OF SPRINKLER SYSTEMS - 2010 EDITION

4. EXISTING FIRE PUMP CRITERIA: OBTAIN LATEST FLOW TEST DATA FROM COTR.

NOT TO SCALE

ENTIRE AREA OF CONSTRUCTION (EXCEPT AS NOTED):

OCCUPANCY CLASSIFICATION: LIGHT HAZARD

SYSTEM TYPE: WET PIPE

DESIGN DENSITY: .10 GPM/SQ. FT.

HYDRAULIC REMOTE AREA: 1,500 SQ. FT.

SPRINKLER ORIFICE SIZE: 1/2"

DURATION OF SUPPLY: 30 MINUTES

MAXIMUM COVERAGE/SPRINKLER HEAD: 225 SQ. FT.

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

VA Project No.

Drawing Number

Dwg. of on e-ei gh th i nc h o ne f oo t on e-qu ar te r in ch o ne f oo t th re e-ei gh th s in ch o ne f oo t on e-ha lf in ch o ne f oo t th re e-qu ar te rs i nc h o ne fo ot on e in ch o ne f oo t on e an d on e-ha lf in ch es o ne f oo t th re e in ch es o ne f oo t

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

ARCHITECT/ENGINEERS:CONSULTANTS:

Collaborative Design,Ltd.

2727 Tuller Parkway, Suite 200

Dublin, Ohio 43017

Tel 614.798.1515 Fax 614.798.5105

COLUMBUS, OH

757-19-201

1A

Chalmers P. Wylie Ambulatory Care Center

REMODEL PHARMACY IV

PREP ROOM

1 BID SET 05/18/18 05/18/18

FIRE PROTECTION GENERAL

NOTES

FP-001

Approver TWM JCRevisions Date

J

K

K

L

L

4.9

4.9

3.83.8

J

J

K

K

L

L

4.9

4.9

3.83.8

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

VA Project No.

Drawing Number

Dwg. of on e-ei gh th i nc h o ne f oo t on e-qu ar te r in ch o ne f oo t th re e-ei gh th s in ch o ne f oo t on e-ha lf in ch o ne f oo t th re e-qu ar te rs i nc h o ne fo ot on e in ch o ne f oo t on e an d on e-ha lf in ch es o ne f oo t th re e in ch es o ne f oo t

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

ARCHITECT/ENGINEERS:CONSULTANTS:

Collaborative Design,Ltd.

2727 Tuller Parkway, Suite 200

Dublin, Ohio 43017

Tel 614.798.1515 Fax 614.798.5105

COLUMBUS, OH

757-19-201

1A

Chalmers P. Wylie Ambulatory Care Center

REMODEL PHARMACY IV

PREP ROOM

1 BID SET 05/18/18 05/18/18

FIRE PROTECTION SECOND

FLOOR PLAN

FP-100

Approver TWM JC

1/4" = 1'-0"

SECOND FLOOR FIRE PROTECTION PLAN - NEW CONSTRUCTION

1/4" = 1'-0"

SECOND FLOOR FIRE PROTECTION PLAN - DEMOLITION

DEMOLITION PLAN NOTES FOR AFFECTED ROOMS (BOXED AREA):

PREPARE FIRE SPRINKLER PIPING SYSTEM FOR DEMOLITION OF

WALLS AND CEILINGS BY REMOVING EXISTING FIRE SPRINKLER

HEADS IN THE AFFECTED AREAS, OR BY PROTECTIONG HEADS IN

PLACE.

REWORK EXISTING BRANCH ARM-OVERS FROM OLD LOCATIONS TO

NEW LOCATIONS OF NEW HEADS IN ACCORDANCE WITH THE NEW

ROOM WALL AND CEILING LAYOUTS.

PROVIDE NEW TEE CONNECTION IN EXISTING FIRE SPRINKLER PIPING

AND EXTEND BRANCH ARMOVER TO NEW SPRINKLER HEAD

LOCATION TO ACCOMMODATE NEW WALL AND CEILING LAYOUT

FOR ROOMS.

NEW CONSTRUCTION PLAN NOTES FOR AFFECTED ROOMS (BOXED AREA):

PROVIDE NEW FIRE SPRINKER HEADS FOR ALL REMOVED HEADS, AND FOR

ADDITIONAL HEAD LOCATIONS.

NORTH

NORTH2

1 2 3

EX SAN

SAN

PLUMBING PIPE LINE TYPES

EX VENT

PLUMBING AND FIRE PROTECTION SUPPRESSION GENERAL NOTES

(APPLY TO ALL PLUMBING DRAWINGS)

A. THE PIPING SYSTEMS SHOWN ARE SCHEMATIC. THE INSTALLING

CONTRACTOR SHALL COORDINATE PIPING INSTALLATIONS WITH

THE PIPING, AIR DUCT, AND CONDUIT INSTALLATIONS OF THE FIRE

PROTECTION, HVAC, AND ELECTRICAL CONTRACTORS. VERIFY ALL

PIPE CLEARANCES BEFORE INSTALLATION OF PIPING.

B. THE INSTALLING CONTRACTOR SHALL VERIFY ALL PIPE

CLEARANCES WITH THE BUILDING STRUCTURE BEFORE

INSTALLATION. ALL CONFLICTS SHALL BE REPORTED TO THE

OWNER BEFORE FABRICATION AND INSTALLATION.

C. ALL INTERIOR SANITARY DRAINS 2-1/2" AND SMALLER SHALL BE

SLOPED AT 1/4" PER FOOT MINIMUM. SANITARY AND STORM DRAINS

3" AND LARGER SHALL SLOPE AT 1/8" PER FOOT MINIMUM.

D. INSTALLING CONTRACTOR SHALL BEAR THE RESPONSIBILITY OF

CORRECTLY CONNECTING NEW SANITARY PIPING TO EXISTING

SANITARY PIPING, NEW DOMESTIC WATER PIPING TO EXISTING

DOMESTIC WATER PIPING, AND NEW STORM PIPING TO EXISTING

STORM PIPING.

E. REFER TO ARCHITECTURAL DRAWINGS FOR IDENTIFICATION AND

LOCATIONS OF NEW WALLS. COORDINATE EXACT DIMENSIONS OF

ROUGH-INS WITH CONTRACTOR INSTALLING NEW WALLS.

F. INSTALLING CONTRACTOR SHALL PROVIDE A CLEAN SET OF

AS-BUILT CONTRACT DRAWING PRINTS MARKED IN RED PENCIL,

SHOWING ALL DEVIATIONS FROM CONTRACT DRAWINGS. RECORD

DRAWINGS SHALL SHOW ALL UNDERGROUND PIPING BY DIMENSION

FROM BUILDING WALLS OR STUCTURAL COLUMNS, AND DEPTH

BELOW GRADE OR SLAB. KEEP PRINTS CURRENT WITH EVERYDAY

JOB PROGRESS.

G. PIPING WILL NOT BE ALLOWED TO BE INSTALLED ABOVE ANY

ELECTRICAL EQUIPMENT OR SWITCHGEAR, OR WITHIN THREE(3)

FEET IN FRONT OF SUCH SWITCHGEAR/EQUIPMENT.

H. ALL PLUMBING PIPING SHALL BE INSTALLED AS COORDINATED WITH

HVAC SHOP DRAWINGS THAT SHOW COORDINATION OF ALL PME

TRADES. INSTALL ALL PLUMBING SHUT-OFF VALVES IN AN

ACCESSIBLE LOCATION. COORDINATE WITH HVAC, ELECTRICAL,

AND F.P.C.

I. CONTRACTOR TO FOLLOW THE SPECIFICATIONS FOR ALL

NECESSARY PERMITS AND INSPECTIONS, AND COMPLY WITH ALL

CODE REQUIREMENTS.

PLUMBING ABBREVIATIONS

AFF ABOVE FINISH FLOOR

AHJ AUTHORITY HAVING JURISDICTION

ASSE AMERICAN SOCIETY OF SANITARY ENGINEERS

CA COMPRESSED AIR

CISPI CAST IRON SOIL PIPE INSTITUTE

CO CLEANOUT

DCW DOMESTIC COLD WATER

DHW DOMESTIC HOT WATER

EA EACH

E.C. ELECTRICAL CONTRACTOR

EX. OR EXISTING

EXIST.

FT FEET OR FOOT

F.P. FIRE PROTECTION (CONTRACTOR)

G.C. GENERAL CONTRACTOR

GPM GALLONS PER MINUTE

HVAC HEATING, VENTILATION, AIR CONDITIONING

OPC OHIO PLUMBING CODE

NFPA NATIONAL FIRE PROTECTION ASSOC.

NHCI NO-HUB CAST IRON

N.T.S. NOT TO SCALE

PDI PLUMBING AND DRAIN INSTITUTE

P.C. PLUMBING CONTRACTOR

PSI POUNDS PER SQUARE INCH

SANU SANITARY UNDERGROUND

SAN SANITARY

SK SINK

SS STAINLESS STEEL

TYP. TYPICAL

V VENT

PLUMBING SYMBOLS

CONNECT TO EXISTING

LIMIT OF DEMOLITION

FLOOR DRAIN

CLEAN OUT

BALL VALVE

PIPE DOWN

PIPE UP

TEE

90 ELBOW

PIPE DOWN

TRAP PRIMER

EXSAN

SAN

SAN VENTV

EXV

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

VA Project No.

Drawing Number

Dwg. of on e-ei gh th i nc h o ne f oo t on e-qu ar te r in ch o ne f oo t th re e-ei gh th s in ch o ne f oo t on e-ha lf in ch o ne f oo t th re e-qu ar te rs i nc h o ne fo ot on e in ch o ne f oo t on e an d on e-ha lf in ch es o ne f oo t th re e in ch es o ne f oo t

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

ARCHITECT/ENGINEERS:CONSULTANTS:

Collaborative Design,Ltd.

2727 Tuller Parkway, Suite 200

Dublin, Ohio 43017

Tel 614.798.1515 Fax 614.798.5105

COLUMBUS, OH

757-19-201

1A

Chalmers P. Wylie Ambulatory Care Center

REMODEL PHARMACY IV

PREP ROOM

1 BID SET 05/18/18 05/18/18

PLUMBING ABBREVIATIONS /

SYMBOLS

P-001 Approver TWM JCRevisions Date

K

K

L

L

4.9

4.9

3.83.8

J

J

K

K

L

L

4.9

4.9

3.83.8

J

J

K

K

L

L

4.9

4.9

3.83.8

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

VA Project No.

Drawing Number

Dwg. of on e-ei gh th i nc h o ne f oo t on e-qu ar te r in ch o ne f oo t th re e-ei gh th s in ch o ne f oo t on e-ha lf in ch o ne f oo t th re e-qu ar te rs i nc h o ne fo ot on e in ch o ne f oo t on e an d on e-ha lf in ch es o ne f oo t th re e in ch es o ne f oo t

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

ARCHITECT/ENGINEERS:CONSULTANTS:

Collaborative Design,Ltd.

2727 Tuller Parkway, Suite 200

Dublin, Ohio 43017

Tel 614.798.1515 Fax 614.798.5105

COLUMBUS, OH

757-19-201

1A

Chalmers P. Wylie Ambulatory Care Center

REMODEL PHARMACY IV

PREP ROOM

1 BID SET 05/18/18 05/18/18

PLUMBING FLOOR PLANS

P-100 Approver TWM JC

NORTH

DEMOLITION PLUMBING PLAN NOTES:

DISCONNECT DOMESTIC WATER AND DRAIN PIPING FROM EXISTING SCRUB SINK AND ASSOCIATED

EYEWASH DRENCH HOSE ASSEMBLY. REMOVE FIXTURE AND ACCESSORIES FOR FUTURE RE-

INSTALLATION AT LATER TIME IN PROJECT.

COORDINATE STORAGE OF FIXTURE UNITS WITH VAACC.

REMOVE SCRUB SINK CARRIER AND RE-INSTALL FOR NEW FIXTURE LOCATION. COORDINATE WITH

NEW WALL LAYOUTS AND OTHER TRADES.

NEW CONSTRUCTION PLUMBING PLAN NOTES:

EXTEND EXISTING DRAIN, DCW, AND DHW PIPING FROM EXISTING SCRUB SINK

LOCATION TO NEW SCRUB SINK LOCATION IN WALL CAVITY. PROVIDE REQUIRED

SUPPORTS FOR HORIZONTAL PIPING. INSULATE DOMESTIC WATER PIPING TO MATCH

EXISTING.

PROVIDE BACKING SUPPORT FOR PIPING, DEVICES, APPURTENANCES, AND FIXTURE

ACCESSORIES.

CONFIRM SCRUB SINK CARRIER IS SECURELY ANCHORED AND READY FOR SCRUB

SINK BRACKET SUPPORTS BEFORE WALL COVERING IS APPLIED.

INSTALL SCRUB SINK, INCLUDING EYEWASH DRENCH HOSE ASSEMBLY, AND MAKE

ALL FINAL CONNECTIONS.

CONNECT NEW 2" SANITARY VENT PIPING INTO EXISTING 2" VENT PIPING ABOVE

CEILING. PROVIDE CLEANOUT FITTING FOR TESTING NEW PIPING SYSTEM. SEE FIRST

FLOOR PLAN FOR CONTINUATION.

NEW 2" VENT SERVING NEW MOP SINK.

CONNECT NEW 3/4" DCW AND DHW BRANCH PIPING INTO EXISTING 3/4" DCW AND DHW

PIPING WITH ISOLATION VALVE. EXTEND TO NEW MOP SINK. PROVIDE WATER

HAMMER ARRESTORS AND NON-SLAM CHECK VALVES. PROVIDE PIPING INSULATION

AND PIPE IDENTIFICATION PER SPECIFICATIONS.

PROVIDE NEW MOP SINK BASE AND FAUCET WITH ACCESSORIES. MAKE ALL FINAL

CONNECTIONS.

CONNECT NEW 2" SANITARY BRANCH DRAIN (WITH TEST FITTING) INTO EXISTING 2"

SANITARY DRAIN ABOVE FIRST FLOOR CEILING. EXTEND 2" DRAIN TO NEW MOP SINK

LOCATION AND PROVIDE TRAP AND VENT PIPING TO ABOVE THE SECOND FLOOR.

SEE SECOND FLOOR PLAN FOR CONTINUATION.

NORTH

2 3

MOP SINK

EXISTING 2" SAN. ABOVE

1st FLOOR CEILING

NEW 2" VENT

EXISTING 2" VENT ABOVE

2nd FLOOR CEILING

NEW 2" SAN. ABOVE

1st FLOOR CEILING

STACK DIAGRAM

1AP100

A

N.T.S.

1 3

1 2

1/8" = 1'-0"

SECOND FLOOR PLUMBING PLAN - DEMOLITION

1/8" = 1'-0"

SECOND FLOOR PLUMBING PLAN - NEW CONSTRUCTION

1/8" = 1'-0"

FIRST FLOOR PLUMBING PLAN

NORTH

I

1"ø 1 1/4"ø

2"ø

HW

CW

FIRE

S A

N

4" EXISTING UNDERGROUND

SANITARY

1B012

L

L

M

M

B

B

1B012

1B103A

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

VA Project No.

Drawing Number

Dwg. of on e-ei gh th i nc h o ne f oo t on e-qu ar te r in ch o ne f oo t th re e-ei gh th s in ch o ne f oo t on e-ha lf in ch o ne f oo t th re e-qu ar te rs i nc h o ne fo ot on e in ch o ne f oo t on e an d on e-ha lf in ch es o ne f oo t th re e in ch es o ne f oo t

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

ARCHITECT/ENGINEERS:CONSULTANTS:

Collaborative Design,Ltd.

2727 Tuller Parkway, Suite 200

Dublin, Ohio 43017

Tel 614.798.1515 Fax 614.798.5105

COLUMBUS, OH

757-19-201

1A

Chalmers P. Wylie Ambulatory Care Center

REMODEL PHARMACY IV

PREP ROOM

1 BID SET 05/18/18 05/18/18

TEMPORARY TRAILER PLUMBING

PLAN

P-200 Approver TWM PDC

1/4" = 1'-0"

TEMPORARY TRAILER PLUMBING PLAN

NORTH

1/8" = 1'-0"

TRAILER HOT WATER SHUT OFF RM 1A350

1/8" = 1'-0"

TRAILER COLD WATER REMOVAL CORRIDOR 1B012

PLAN NOTES NEW WORK:

EXTEND EXISTING 1" HOT WATER TO NEW TEMPORARY

PHARMACY AND MAKE FINAL CONNECTION WITH VALVE.

EXTEND EXISTING 1-1/4" COLD WATER TO NEW

TEMPORARY PHARMACY AND MAKE FINAL CONNECTION

WITH VALVE.

EXTEND EXISTING 4" SANITARY AND CONNECT TO NEW

TEMPORARY PHARMACY.

EXTEND EXISTING 2" FIRE PROTECTION TO NEW

TEMPORARY PHARMACY AND MAKE FINAL CONNECTION.

MAINTAIN EXISTING 140°F HOT WATER TEMPERATURE

CABLE ON HOT WATER LINE COMPLETE TO CONNECTION

TO TEMPORARY PHARMACY.

PROVIDE SELF-REGULATING UL LISTED COMMERCIAL

GRADE FREEZE PROTECTION CABLE TO PROTECT

EXPOSED SANITARY PIPING FROM FREEZING. SYSTEM

SHALL BE COMPLETE WITH POWER CONNECTIONS, END

CAPS, AND GROUNDING LUG. CABLES SHALL BE

PERFORMANCE BASED AT -21°F @ 6W/FT. INSULATE PER

MANUFACTURER'S REQUIREMENTS.

EXISTING 1" HOT WATER, 1 1/4" COLD

WATER, & 2" FIRE PROTECTION.

PLAN NOTES DEMOLITION WORK:

AFTER VA HAS MOVED OUT OF TEMPORARY

PHARMACY, REMOVE FIRE PROTECTION PIPING

FROM TEMPORARY PHARMACY BACK TO THIS

POINT AND CAP.

AFTER VA HAS MOVED OUT OF TEMPORARY

PHARMACY, REMOVE COLD WATER LINE BACK TO

MAIN IN CORRIDOR 1B012 (APPROXIMATELY 180')

AND CAP AT MAIN.

AFTER VA HAS MOVED OUT OF TEMPORARY

PHARMACY, SHUTOFF 1" DHW SERVING

TEMPORARY PHARMACY AT 2-1/2" MAIN. DRAIN

PIPING DOWN STREAM OF CLOSED VALVE.

AFTER VA HAS MOVED OUT OF TEMPORARY

PHARMACY, REMOVE…