36C25018B0815-0002005.pdf
PDF 456 KB Posted
- Solicitation number
- 36C25018B0815
About this file
36C25018B0815 0002 E8-01.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25019C0025-000.docx | DOCX document | |
| 36C25018B0815-0003000.docx | DOCX document | |
| 36C25018B0815-0002007.pdf | ||
| 36C25018B0815-0002004.pdf | ||
| 36C25018B0815-0002002.pdf | ||
| 36C25018B0815-0002006.pdf | ||
| 36C25018B0815-0002003.pdf | ||
| 36C25018B0815-0002000.docx | DOCX document | |
| 36C25018B0815-0002008.pdf | ||
| 36C25018B0815-0002001.pdf | ||
| 36C25018B0815-0002010.pdf | ||
| 36C25018B0815-0002009.pdf | ||
| 36C25018B0815-0001000.docx | DOCX document | |
| 36C25018B0815-003.pdf | ||
| 36C25018B0815-001.docx | DOCX document | |
| 36C25018B0815-004.txt | TXT text file | |
| 36C25018B0815-002.pdf | ||
| 36C25018B0815-000.docx | DOCX document |
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PB
S
793.98 CL Conc
30063
4.3
7.3
0.5
0.8
A.5
METAL TRAILERS
LANDSCAPED AREA
CON
J
J
UPPER
LANDING
1T001C
MID LANDING
1T001B
VESTIBULE
1T001A
11' - 5 3/8"
EXISTING PANEL C1SBEA
MOBILE SPS TRAILER
NEW TEMPORARY CORRIDOR
C1SA
D1SA
E1N3 E1N2 E1N1
E1NA
D1NA
C1E1
C1E1
PLAN NOTES
1.- LOCATION OF EMERGENCY DISTRIBUTION ELECTRICAL ROOM. LOCATION OF
PANEL C1SBEA.
2.- APPROXIMATE PATH FOR ROUTING ELECTRICAL FEEDS FROM DISTRIBUTION
BOARD C1SBEA TO MOBILE SPS LOCATION.
3.- APPROXIMATE PATH FOR ROUTING ELECTRICAL FEEDS FROM DISTRIBUTION
BOARD C1SBEA TO SECOND FLOOR ELECTRICAL CLOSET.
4.- EXISTING LIFE SAFETY PANELBOARD. NEW LIFE SAFETY CIRCUITS ARE TO BE
FED FROM THIS PANEL.
5.- EXISTING LIFE SAFETY PANELBOARD FEEDING EXISTING LIFE SAFETY CIRCUITS
IN LAB AND SPS AREAS. PANELBOARD SHOWN FOR REFERENCE.
6.- EXISTING 480/277V PANELBOARD FOR FEEDING TEMPORARY COOLING UNITS
IN THE TEMPORARY MOBILE SPS CORRIDOR. PROVIDE NEW 25A/1P CIRCUIT
BREAKERS WITHIN EXISTING PANELBOARD.
7.- EXISTING 208/120V PANELBOARD FOR FEEDING TEMPORARY CORRIDOR
RECEPTACLES.
8.- EXISTING 480/277V PANELBOARD THAT IS FEEDING THE LIGHTING IN THE
AREA OF THE TEMPORARY CORRIDOR EXPANSION. PANELBOARD SHOWN FOR
REFERENCE.
9.- PROVIDE 208V, 30A, 1-PHASE CONNECTION TO HEAT TRACE CONTROLLER
AND POWER CONNECTION TO ACTUAL HEAT TRACE CABLING. PROVIDE 30A/2P
CIRCUIT BREAKER WITH 30mA GFCI PROTECTION WITHIN EXISTING PANELBOARD
SHOWN. MAKE ALL FINAL CONNECTIONS. DEMO CIRCUITRY AND CONDUIT BACK
TO SOURCE UPON REMOVAL OF PIPING. LABEL CIRCUIT BREAKER AS A SPARE.
PROVIDE 3-#10 & 1-#10 GROUND IN 3/4" CONDUIT.
10.- PROVIDE NEW 30A/2P CIRCUIT BREAKER IN EXISTING PANELBOARD WITH
30mA GFCI PROTECTION FOR SERVING HEAT TRACE. REFER TO PLAN NOTE #9
FOR FURTHER INFORMATION.
Drawing Title
Approved:
Project Title
Date
Location
Checked By:
Building Number
Project Number
Drawing Number
Drawn By:
Revisions: Date
ARCHITECT/ENGINEERS:
CHALMERS P. WYLIE VA AMBULATORY CARE CENTER
o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
CONSULTANTS:
SCHEMATIC DESIGN REVISIONS - 25% REVIEW SET 2015 10-21
1A
FARID MEHR, PE
CHIEF, ENGINEERING SERVICE
SCHEMATIC DESIGN - 25% REVIEW SET 2015 10-07
DESIGN DEVELOPMENT ONE - 50% REVIEW SET 2015 11-25
DESIGN DEVELOPMENT TWO - 75% REVIEW SET 2016 02-03
CONSTRUCTION DOCUMENTS - 95% REVIEW SET 2016 03-30
BID DOCUMENTS - 100% SET 2016 05-11
BID DOCUMENTS - 100% SET REVISED 2016 11-18
C :\U se rs
\m ba ke r\D oc um en ts
\1
EL
EC
_C en tra l_ m ba ke r.r vt
BID DOCUMENTS - BID
E8.01
CCTS
Electrical Site Plan
2016-05-11
757-16-101EXPAND LAB AND SPS
DEPARTMENTS
1/16" = 1'-0"E8.01
1 ELECTRICAL SITE PLAN
GI