36C25018B0815-0002006.pdf
PDF 219 KB Posted
- Solicitation number
- 36C25018B0815
About this file
36C25018B0815 0002 E8-02.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25019C0025-000.docx | DOCX document | |
| 36C25018B0815-0003000.docx | DOCX document | |
| 36C25018B0815-0002007.pdf | ||
| 36C25018B0815-0002004.pdf | ||
| 36C25018B0815-0002002.pdf | ||
| 36C25018B0815-0002005.pdf | ||
| 36C25018B0815-0002003.pdf | ||
| 36C25018B0815-0002000.docx | DOCX document | |
| 36C25018B0815-0002008.pdf | ||
| 36C25018B0815-0002001.pdf | ||
| 36C25018B0815-0002010.pdf | ||
| 36C25018B0815-0002009.pdf | ||
| 36C25018B0815-0001000.docx | DOCX document | |
| 36C25018B0815-003.pdf | ||
| 36C25018B0815-001.docx | DOCX document | |
| 36C25018B0815-004.txt | TXT text file | |
| 36C25018B0815-002.pdf | ||
| 36C25018B0815-000.docx | DOCX document |
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
J J
J
UPPER
LANDING
1T001C
MID LANDING
1T001B
VESTIBULE
1T001A
11' - 5 3/8"
MOBILE SPS TRAILER LOCATION
EXISTING LOADING DOCK
R3
R3
R3
R3 R3 R3
R3
R3
NL
NL
NL
1 1
E1NA-39
E1NA-41
C1SBEA
C1SBEA
E2E1-40/42
PLAN NOTES
1.- PROVIDE (2) 600V, 400A, 3-POLE, FUSED DISCONNECT SWITCHES IN NEMA
3R ENCLOSURES FOR POWER CONNECTION TO MOBILE TRAILER. TRAILER
PROVIDE LOAD SIDE CABLING FOR EC TO CONNECT.
2.- PROVIDE 240V, 3-POLE, 30A, NON-FUSED DISCONNECT SWITCH IN NEMA
3R ENCLOSURE FOR MOBILE TRAILER AUXILLIARY HEATER. PROVIDE
CONNECTION FROM EXISTING PANEL E2E1 ON SECOND FLOOR. PROVIDE 2-#
10 & 1-#10 GROUND IN 3/4" CONDUIT. PROVIDE NEW 30A/2P CIRCUIT
BREAKER WITHIN EXISTING PANEL. MAKE ALL FINAL CONNECTIONS.
COORDINATE LOCATION OF CONNECTION WITH TRAILER PROVIDER.
3.- PROVIDE RJ-45 CONNECTION TO FIRE ALARM SYSTEM IN MOBILE TRAILER.
THE EXISTING BUILDING SIMPLEX FIRE ALARM SYSTEM IS TO MONITOR THE
TRAILER FIRE ALARM SYSTEM FOR TROUBLE AND ALARM. PROVIDE ALL
NECESSARY FIRE ALARM MONITORING RELAYS TO MONITOR TRAILER DRY
CONTACTS.
4.- CIRCUIT NORMAL POWER LIGHT FIXTURES WITH THE NORMAL POWER
LIGHTING CIRCUIT (D1N1-9) IN THE CORRIDOR TO THE SOUTH. RECONFIGURE
EXISTING LIGHTING CIRCUITRY AS REQUIRED.
5-. CIRCUIT LIFE SAFETY LIGHTING CIRCUIT WITH THE EXISTING LIFE SAFETY
LIGHTING CIRCUIT (D1SA-9) IN THE CORRIDOR TO THE SOUTH. RECONFIGURE
EXISTINGL IGHTING CIRCUITRY AS REQUIRED. LIFE SAFETY LIGHTING SHALL BE
CONNECTED AHEAD OF ALL SWITCHING.
6.- PROVIDE 277V, 1-PHASE, 25A CONNECTION FROM PANELBOARD SHOWN
TO PTAC HVAC UNIT. PROVIDE NEMA 7-25R RECEPTACLE ADJACENT TO UNIT.
COORDINATE MOUNTING LOCATION WITH EQUIPMENT PROVIDER. MAKE ALL
FINAL CONNECTIONS. PROVIDE NEW 25A/1P CIRCUIT BREAKER WITHIN
EXISTING PANELBOARD.
7.- EXTEND EXISTING CORRIDOR GENERAL PURPOSE RECEPTACLE CIRCUIT
(F1N3-1) FROM CORRIDOR TO THE SOUTH TO NEW TEMPORARY CORRIDOR
GENERAL PURPOSE RECEPTACLES. RECONFIGURE EXISTING CIRCUITRY AS
REQUIRED.
GENERAL NOTES
A.- UPON COMPLETION AND OCCUPATION OF THE RENOVATED SPS AREA ON
THE SECOND FLOOR, TEMPORARY CORRIDOR IS TO BE REMOVED. DISCONNECT
AND REMOVE ALL EQUIPMENT AND TURNOVER TO THE GOVERNMENT. DEMO
ALL CIRCUITRY BACK TO SOURCE. CONDUIT RUNS ARE TO REMAIN UP TO
EXISTING CORRIDOR. PROVIDE NEW PULLSTRINGS WITHIN CONDUITS FOR
FUTURE USE. LABEL CONDUITS AS "SPARE FOR MOBILE TRAILERS" AT SOURCE
END AND TERMINATION POINT.
Drawing Title
Approved:
Project Title
Date
Location
Checked By:
Building Number
Project Number
Drawing Number
Drawn By:
Revisions: Date
ARCHITECT/ENGINEERS:
CHALMERS P. WYLIE VA AMBULATORY CARE CENTER
o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
CONSULTANTS:
SCHEMATIC DESIGN REVISIONS - 25% REVIEW SET 2015 10-21
1A
FARID MEHR, PE
CHIEF, ENGINEERING SERVICE
SCHEMATIC DESIGN - 25% REVIEW SET 2015 10-07
DESIGN DEVELOPMENT ONE - 50% REVIEW SET 2015 11-25
DESIGN DEVELOPMENT TWO - 75% REVIEW SET 2016 02-03
CONSTRUCTION DOCUMENTS - 95% REVIEW SET 2016 03-30
BID DOCUMENTS - 100% SET 2016 05-11
BID DOCUMENTS - 100% SET REVISED 2016 11-18
C :\U se rs
\m ba ke r\D oc um en ts
\1
EL
EC
_C en tra l_ m ba ke r.r vt
BID DOCUMENTS - BID
E8.02
CCTS
Enlarged Mobile SPS Electrical Plan
2016-05-11
757-16-101EXPAND LAB AND SPS
DEPARTMENTS
1/4" = 1'-0"E8.02
1 ELECTRICAL MOBILE SPS PLAN
GI
RS
S
R P
F E
O
E E T
L
I G
S
N A O N
RE
E
D
I
R
S
E N
E
HTAT
S
E OF
MACE E-50556
O
OI
MONTGOMERY E-66852
GRIFFIN E-57049
File details come from the government source that posted it.