36C25018B0795-017.pdf
PDF 10 MB Posted
- Attached to
- Construct Clinical and Admin Building 506-329 Federal contract opportunity
- Solicitation number
- 36C25018B0795
About this file
36C25018B0795 506-329 VA Ann Arbor Admin Bldg BID DWGS REVISED_Part7.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25018B0795-0005000.docx | DOCX document | |
| 36C25018B0795-0004000.docx | DOCX document | |
| 36C25018B0795-0003000.docx | DOCX document | |
| 36C25018B0795-0003001.xlsx | XLSX spreadsheet | |
| 36C25018B0795-0002000.docx | DOCX document | |
| 36C25018B0795-0001002.pdf | ||
| 36C25018B0795-0001000.docx | DOCX document | |
| 36C25018B0795-0001001.pdf | ||
| 36C25018B0795-011.pdf | ||
| 36C25018B0795-019.pdf | ||
| 36C25018B0795-021.pdf | ||
| 36C25018B0795-013.pdf | ||
| 36C25018B0795-009.docx | DOCX document | |
| 36C25018B0795-010.pdf | ||
| 36C25018B0795-008.docx | DOCX document | |
| 36C25018B0795-020.pdf | ||
| 36C25018B0795-012.pdf | ||
| 36C25018B0795-007.docx | DOCX document | |
| 36C25018B0795-016.pdf | ||
| 36C25018B0795-015.pdf | ||
| 36C25018B0795-018.pdf | ||
| 36C25018B0795-022.docx | DOCX document | |
| 36C25018B0795-014.pdf | ||
| 36C25018B0795-000.docx | DOCX document |
Show all 24
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1 1/2" HHWS
1 1/2" HHWR
FPB-02-7
FPB-02-5
TU-02-2
TU-02-3
FPB-02-4
FPB-02-3
TU-02-1
FPB-02-2
FPB-02-1
FPB-02-10
FPB-02-9
TU-02-5
FPB-02-8
TU-02-4
MEN'S TOILET
HAC
IT
ELECTRICAL
ASSISTANT CHIEF
CHIEF
UNISEX RR
OPEN OFFICE
AFO
CFO
INTERNAL AUDITOR
STAIRS
S-1
ELEVATOR
E-1
STAIRS
S-2
VESTIBULE
CORRIDOR
OPEN OFFICE
OPEN OFFICE
CORRIDOR
ACCOUNTING
SUPERVISOR
OPEN OFFICE
ELEVATOR LOBBY
BREAK ROOM
CONFERENCE ROOM
WOMEN'S TOILET
PAYROLL SUPERVISOR
MCA PROGRAM OFFICE
COFFEE
A B C D
H
E
4.2
J
2.8
4.8
G
5.4
F K
1" HHWS
1" HHWR
1" HHWR
1" HHWS
1" HHWS
1" HHWR
1/2" HHWR
1/2" HHWS
1" HHWR
1" HHWS
1" HHWR
1" HHWS
1/2" HHWR
1/2" HHWS
1/2" HHWR
1/2" HHWS
1" HHWR
1" HHWS
1" HHWS
1" HHWR
1" HHWR
1" HHWS
1" HHWR
1" HHWS
1" HHWR
1" HHWS
1" HHWR
1" HHWS
1 1/4" HHWS
1 1/4" HHWR
1 1/4" HHWS
1 1/4" HHWR
2" HHWR/S DN
1 1/2" HHWR/S UP
IN CHASE
1/2" HHWR
1/2" HHWS
1" HHWS
1" HHWR
T
T
DDC
CONTROL
PANEL
ACCU-1
REFRIGERANT
PIPING UP/DN
T
1050 Wilshire Drive, Suite 260 Troy, MI 48084 T 248-643-6222
SSOE, Inc.
D A T E
FULLY SPRINKLERED
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
VA ANN ARBOR MEDICAL CENTER CAMPUS
PROJECT #: 015-01361-00
BIDS SUBMISSION_REVISED
C A u to d e s k \R e v it \0 M S S O E .r v t
/9 /2 :5 :3 A M
Scale: 3/16" = 1'-0"
MP120
PIPING SECOND FLOOR PLAN
GOTWALD
506-329CLINICAL & ADMINISTRATIVE
BUILDING
WILSON04-12-18
111 148
N
SCALE: 3/16" = 1'-0"
SECOND FLOOR PIPING PLAN
T
T
T
T
T
T
T
TT
T
GENERAL NOTES:
1. REFRIGERANT PIPING SHOWN AS GENERAL ROUTING. SIZING AND ACCESSORIES PER
MANUFACTURERS INSTALLATION INSTRUCTIONS.
KEY NOTES:
1 NOT USED
2 PROVIDE 3 WAY CONTROL VALVE AT THIS UNIT TO MAINTAIN BRANCH TEMPERATURE.
3 BID DEDUCT ALTERNATE NO. 7: ADD HOT WATER COILS TO INTERIOR TERMINAL UNITS IF
THIRD FLOOR IS A SEMI-HEATED SHELL SPACE.
DESIGN DEVELOPMENT SUBMISSION 1 04-19-16
DESIGN DEVELOPMENT SUBMISSION 2 06-10-16
95% CONSTRUCTION DOCUMENTS
SUBMISSION
11-15-16
BIDS SUBMISSION 01-20-17
BIDS SUBMISSION_REVISED 04-12-18
CONF. ROOM
ASST CHIEF MAS OFF
NON-VA CARE SUPV
WOMEN'S TOILET
VESTIBULE
MEN'S TOILET
HAC
IT
ELECTRICAL
HBU SUPRVISOR
CHIEF MAS OFFICER
327 SCANNING SUPV
RECORD MANAGER
OFFICER
MED RECORDS
SUPERVISOR
CODING SUPERVISOR
OFFICE
ADMINISTRATIVE
OFFICER
ELEVATOR LOBBY
STAIRS
S-1
ELEVATOR
E-1
STAIRS
S-2
COFFEE
OPEN OFFICE
OPEN OFFICE
OPEN OFFICE
CORRIDOR
OPEN OFFICE
CORRIDOR
1 1/2" HHWS
1 1/2" HHWR
A
A
B
B
C
C
D
D
6 6
5 5
3 3
2 2
H
HE
E
4.2
4.2
4 4
J
J
2.8
2.8
4.8
4.8
G
G
5.45.4
F
F
K
K
FPB-03-7
TU-03-4
FPB-03-8
TU-03-5 FPB-03-9
FPB-03-10
FPB-03-3
FPB-03-4
FPB-03-5
TU-03-2
TU-03-3
OPEN OFFICE
OPEN OFFICE
1" HHWS
1" HHWR
1" HHWR
1" HHWS
1" HHWR
1" HHWS
1" HHWS
1" HHWR
1" HHWS
1" HHWR
1" HHWS
1" HHWR
1 1/4" HHWS
1 1/4" HHWR
1 1/4" HHWS
1 1/4" HHWR
1" HHWS
1" HHWR
1" HHWR
1" HHWS
1" HHWS
1" HHWR
1" HHWS
1" HHWR
1/2" HHWR
1/2" HHWS
1" HHWS
1" HHWR
1" HHWS
1" HHWR
1" HHWS
1" HHWR
1" HHWR
1" HHWS
FP-03-1
1 1/2" HHWR/S DN
IN CHASE
T
T
T
T
T
T
T
T
T
T
T
T
DDC
CONTROL
PANEL
TU-03-1
T
FPB-03-2
ACCU-1
REFRIGERANT
PIPING UP
ACCU-1
REFRIGERANT
PIPING DN
T
1050 Wilshire Drive, Suite 260 Troy, MI 48084 T 248-643-6222
SSOE, Inc.
D A
T E
FULLY SPRINKLERED
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
VA ANN ARBOR MEDICAL CENTER CAMPUS
PROJECT #: 015-01361-00
BIDS SUBMISSION_REVISED
C A u to d e s k \R e v it \0
M
S
S O
E .r v t
/9
/2
:5
:4
A
M
Scale: 3/16" = 1'-0"
MP130
PIPING THIRD FLOOR PLAN
GOTWALD
506-329CLINICAL & ADMINISTRATIVE
BUILDING
WILSON04-12-18
112 148
N
SCALE: 3/16" = 1'-0"
THIRD FLOOR PIPING PLAN
GENERAL NOTES:
1. REFRIGERANT PIPING SHOWN AS GENERAL ROUTING. SIZING AND ACCESSORIES PER
MANUFACTURERS INSTALLATION INSTRUCTIONS.
KEY NOTES:
1 BID DEDUCT ALTERNATE NO 6: DELETE REFRIGERANT PIPING AND ACCU-1.
2 PROVIDE 3 WAY CONTROL VALVE AT THIS UNIT TO MAINTAIN BRANCH TEMPERATURE.
DESIGN DEVELOPMENT SUBMISSION 1 04-19-16
DESIGN DEVELOPMENT SUBMISSION 2 06-10-16
95% CONSTRUCTION DOCUMENTS
SUBMISSION
11-15-16
DRAW THRU
BLOW THRU
2" [50mm]
PLUS X
1" [25mm]
MINIMUM
X
2X
UNIT TYPE A B
WHERE X = STATIC PRESSURE IN PAN
NOTE: 1. CPVC PIPE MAY BE USED ONLY IF APPROVED BY LOCAL VA AND
IS INDOORS AND DOES NOT PASS THROUGH RATED BARRIERS.
2. DIELECTRIC FITTING TO BE USED WHEN TWO DISSIMILAR METALS ARE
TO BE CONNECTED.
A B
[2 m m
DRAIN LINE SHALL BE AT LEAST THE SAME
SIZE AS THE NIPPLE ON THE DRAIN PAN.
PIPING SHALL BE RIGID COPPER TYPE L
OR TYPE M UNLESS NOTE BELOW IS MET
PITCH DOWN
TOWARD
DRAIN
CLEAN OUT
FLOOR SINK
DIELECTRIC
FITTING
DRAIN PAN
NOTES:
1. SUPPORT PUMP FROM PIPING ONLY. DO NOT SUPPORT PUMP FROM MOTOR.
BALANCING
DEVICE
PIPE HANGERS - PROVIDE DOUBLE
DEFLECTION NEOPRENE (TYPE HN)
FOR FIRST TWO ON EACH SIDE OF
PUMP (SEE NOTE NO. 1)
PRESSURE GAGE
1/2" [15mm]
STRAINER
BALL OR
BUTTERFLY
(TYP.)
FLEXIBLE
CONNECTION
COIL
WATER RETURN
WATER SUPPLY
MV
UNION
CONNECTIONS (TYP.)
TEST PLUG (TYP.)
MANUAL AIR VENT
DRAIN WITH HOSE
CONNECTION
SHUT OFF VALVE
REDUCER, IF REQUIRED
MODULATION CONTROL VALVE
SINGLE COIL
WATER COIL
WATER COIL
WATER COIL
DOUBLE COIL
NOTES:
1. WHEN COIL IS INCLUDED IN CASING MOUNTED ON VIBRATION ISOLATORS THE FIRST 2 HANGERS FOR EACH PIPE SHALL BE SPRING & NEOPRENE TYPE. TYPE "H" FOR 4" [100mm] PIPE & SMALLER. TYPE "H-P" FOR 5" [125mm] PIPE & LARGER.
2. PIPING SHALL BE INSTALLED IN SUCH MANNER THAT IT WILL NOT BLOCK THE SWING OR USE OF ACCESS DOORS OR
PANELS; NEITHER SHALL IT BLOCK THE SERVICING OF FILTERS, VALES, OR EQUIPMENT.
3. THE FLOW ELEMENT MAY BE INSTALLED IN THE SUPPLY PIPING IF THE REQUIRED MINIMUM UPSTREAM AND DOWNSTREAM
DIMENSIONS CANNOT BE OBTAINED IN THE RETURN PIPING.
FE
MV
MV
MV
MV
MVMV
FE
TI
TI
MV
AIR VENT WHEN
COIL IS NOT
SELF-VENTING
DRAIN WHEN COIL IS
NOT SELF-DRAINING
PIPE HANGER SHALL SUPPORT
PIPING INDEPENDENT OF COIL
AIR VENT WHEN
COIL IS NOT
SELF-VENTING
DRAIN WHEN COIL IS
NOT SELF-DRAINING
DRAIN
REDUCER, IF REQUIRED
TEMPERATURE
INDICATION TO ECC
SEE CONTROL
DIAGRAM
REDUCER, IF REQUIREDPIPE HANGER SHALL SUPPORT
PIPING INDEPENDENT OF COIL
TEST
PLUG
(TYP.
TEST
PLUG
(TYP.)
FLOW ELEMENT
DRAIN
NOTE:
TOP OF CHEMICAL POT FEEDER
TANK SHALL NOT BE MORE THAN
4'-0" [1200mm] ABOVE FINISHED
FLOOR.
F R
O M
P U
M P
D
IS
C H
A R
G E
T O
P U
M P
S U
C T
IO
N
AUTOMATIC FLOW
CONTROL AND BALANCE
DEVICE
FUNNEL
3/4" [20mm]
TO DRAIN
1" [25mm]
CHEMICAL POT FEEDER-
MINIMUM CAPACITY
5 GALLONS [19L]
1" [25mm]
NOTE:
1.
2.
SEE EXPANSION TANK SYSTEM
SCHEDULE FOR COMPONENT
SIZES.
SET PRESSURE REDUCING
VALVE SO PRESSURE AT
HIGHEST POINT IN SYSTEM HAS
A MINIMUM OF 4 PSIG [28kPa].
D
DRAIN
DRAIN
TO PUMP
SUCTION
BLADDER
EXPANSION
TANK
NC
MV
AUTO. AIR VENT TO DRAIN
CONNECTOR PIPE.
HANGER
RODS (TYP)
AIR SEPARATOR
BUTTERFLY
OR BALL
ISOLATION
VALVE
RUN DRAIN LINE TO NEAREST
FD UNLESS INDICATED
OTHERWISE
FROM SYSTEM
6" [150mm]
HOUSEKEEPING PAD
AIR CHARGING
SHRAEDER VALVE
CONNECT TO BFP
SHOWN ON
PLUMBING
DRAWINGS
FLOOR MOUNTING BASE RING WITH
DRAIN ACCESS OPENING SHOWN.
ANGLE IRON LEGS MAY BE USED
AS AN OPTION.
PI
ELEVATION
THREADED PIPING
ELEVATION
WELDED PIPING
NOTES:
1. DRAIN ALL LOW POINTS AS INDICATED ABOVE.
2. WHERE SCALE POCKETS ARE SHOWN ON PIPE RISER DIAGRAMS AND/OR
PLANS LOCATE DRAIN AT BOTTOM OF SCALE POCKET.
REDUCER, IF REQUIRED
3/4" [20mm] BALL VALVE
ADAPTER TO 3/4" [20mm] HOSE
THREAD-PROVIDE HOSE CAP
NUT
TYPICAL WATER PIPING
TYPICAL MANUAL AIR VENT
ELEVATION
NOTES:
1. VENT ALL HIGH POINTS INDICATED ABOVE.
2. IF AUTOMATIC AIR VENTS ARE USED, PIPE DISCHARGE TO DRAIN.
MV
OR
AV
CIRCULATING
WATER
PIPING
1/2" [15mm] x 4" [100mm]
NIPPLE
1/4" [8mm]
COPPER TUBING
1/2" [15mm]
BALL
VALVE
AIR VENT
BOILER
UNION (TYP)
STRAINER (TYP)
PRESSURE GAUGE (TYP)
TEMPERATURE GAUGE (TYP)
LOW POINT DRAIN (TYP)
PUMP
CHECK VALVE (TYP)
TO NEAREST
FLOOR DRAIN
(TYP)
1050 Wilshire Drive, Suite 260 Troy, MI 48084 T 248-643-6222
SSOE, Inc.
D A
T E
FULLY SPRINKLERED
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
VA ANN ARBOR MEDICAL CENTER CAMPUS
PROJECT #: 015-01361-00
BIDS SUBMISSION_REVISED
C A u to d e s k \R e v it \0
M
S
S O
E .r v t
/9
/2
:5
:4
A
M
Scale: 12" = 1'-0"
MP500
MECHANICAL PIPING DETAILS
GOTWALD
506-329CLINICAL & ADMINISTRATIVE
BUILDING
WILSON04-12-18
113 148
SCALE: NOT TO SCALE
1 AIR HANDLING UNIT DRAIN TRAP DETAIL
SCALE: NOT TO SCALE
2 IN-LINE PUMPS - CONNECTIONS
SCALE: NOT TO SCALE
9 TERMINAL UNIT WATER COILS - PIPING CONNECTIONS
SCALE: NOT TO SCALE
4 WATER COILS - PIPING CONNECTIONS
SCALE: NOT TO SCALE
5 WATER TREATMENT - CLOSED SYSTEM
SCALE: NOT TO SCALE
6 FLOOR MOUNTED EXPANSION TANK - PIPING CONNECTIONS
SCALE: NOT TO SCALE
7 TYPICAL DRAIN VALVE CONNECTIONS
SCALE: NOT TO SCALE
8 TYPICAL AIR VENT CONNECTIONS
SCALE: NOT TO SCALE
3 BOILER DETAIL
95% CONSTRUCTION DOCUMENTS
SUBMISSION
11-15-16
D
H
E
4.2
4.2
J
2.8
2.8
4.8
4.8
G
F K
MECHANICAL
SPRINKLERS
IT
ELEV. MAC. RM.
STAIRS
S-1
ELEVATOR
E-1
ELECTRICAL
HAC
CORRIDOR
CORRIDOR
CORRIDOR
ER-4
360 CFM
"x
14"x12"
SR-2
400 CFM
12"x6"
SR-2
270 CFM
2-F/S DPR
SR-1
175 CFM
SR-1
125 CFM
"x
"x
"x
10"x4"
TU-00-3
TU-00-1
10"x10"
TU-00-2
SR-2
200 CFM
CUH-2
8" X 10"
UP WITH 1-F/S DPR
AT FLOOR
10"x6"
B-01 B-02
14" x 12"
SUPPLY UP
14" x 12"
RETURN UP
4-F/S DPR
MH101-BD
1-P1 1-P2
1-AS1
1-P3
1-P4
(BELOW)
2 1/2" HHWS
2 1/2" HHWR
2 1/2"
HHWS/HHWR UP
1 1/4" NG
3/4" NG
3/4" NG
3/4" NG
3/4" NG
1 1/4" DN FROM NEW GAS METER
ABOVE. CONTRACTOR TO PROVIDE
2 PSI OUTLET PRESSURE
1610 CFH
150 FT RUN
3/4" NG UP
TO ROOF
SR-2
285 CFM
SR-2
285 CFM
SR-2
280 CFM
SR-1
150 CFM
RG-4
150 CFM
16"x8"
36"x12"
"x
16"x8"
16"x8"
16"x8"
RG-4
RG-4
425 CFM
RG-4
425 CFM
RG-4
410 CFM
RG-4
400 CFM
1-ET1
1"
1"
1/2" HHWS
1/2" HHWR
3/4" HHWS
3/4" HHWR
KEY NOTES
1 PROVIDE 37 GPM, 400 MBH INPUT, 376 MBH OUTPUT, 94 % EFF, 1.5 FLA, SINGLE PHASE, 120 VOLT
CONDENSING BOILER.
2 4" BOILER FLUE ROUTED TO THE OUTSIDE PER MANUFACTURER'S SIDE VENTING INSTALLTION
INSTRUCTIONS WITH PROPER TERMINATION.
3 4" BOILER AIR INTAKE ROUTED TO THE OUTSIDE PER MANUFACTURER'S SIDE VENTING
INSTALLTION INSTRUCTIONS WITH PROPER TERMINATION.
4 PROVIDE 37 GPM, HEAD - 25 FT, 3/4 HP, SINGLE PHASE, 208 VOLT, ECM MOTOR INLINE PUMP.
5 PROVIDE 3 IN., 55 GPM FULL FLOW TANGENTIAL AIR SEPARATOR.
6 PROVIDE 55 GPM, HEAD - 50 FT, 2 HP, VFD, 3 PHASE, 208 VOLT INLINE PUMP.
ELECTRICAL KEYNOTES
1. REFER TO DRAWING EP100 FOR SCOPE OF BASE BID ELECTRICAL WORK. REMOVE THE
FOLLOWING ELECTRICAL CONNECTIONS AND ASSOCIATED CONTROLS FOR EQUIPMENT BEING
REMOVED AND/OR RELOCATED AS PART OF BID DEDUCT(S).
a.1-SF1 b.1-SF2 c.1-SF3 d.1-EF1 e.1-RF1
f. 1-ERV-1
2. REMOVE ELECTRICAL CONNECTION TO ONE FIRE SMOKE DAMPER AS PART OF BID DEDUCT .
3. PROVIDE UNIFORM LIGHTING LAYOUT IN ROOM WHERE MECHANICAL EQUIPMENT BEING REMOVED
AS PART OF BID DEDUCT NO LONGER INHIBITS LIGHT FIXTURE INSTALLATION.
PLUMBING NOTES
1.) REFER TO DRAWING PL100 AND PL110 FOR SCOPE OF BASE BID PLUMBING WORK. REMOVE THE
FOLLOWING NATURAL GAS CONNECTIONS AND ASSOCIATED ACCCESSORIES FOR EQUIPMENT
BEING REMOVED AND/OR RELOCATED AS PART OF BID DEDUCT(S).
a. B-01
b. B-02
2.) PROVIDE 400 CFH TO B-01 AND 400 CFH TO B-02. REFER TO DETAIL 8/PL400 FOR NATURAL GAS
CONNECTION TO EQUIPMENT.
FIRST FLOOR
816'-0"
SECOND FLOOR
829'-4"
ROOF
856'-0"
THIRD FLOOR
842'-8"
BASEMENT FLOOR
801'-0"
D
T.O.S. LOW POINT
856'-0"
"x
"x
"8
"x
"x
"x
18"x18"
12"x14"
12"x14" 28"x20"
"x
"x
"x
"x
28"x20"
28"x20"
"x
"x
S A
R A
S A
R A
E A
1-RTU-1
52" x 12"
52" x 12"
52" x 12"
1050 Wilshire Drive, Suite 260 Troy, MI 48084 T 248-643-6222
SSOE, Inc.
D A
T E
FULLY SPRINKLERED
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
VA ANN ARBOR MEDICAL CENTER CAMPUS
PROJECT #: 015-01361-00
BIDS SUBMISSION_REVISED
C A u to d e s k \R e v it \0
M
S
S O
E B id D e d u c t_
.r v t
/9
/2
:5
:4
A
M
Scale: As indicated
MH101-BD
HVAC BASEMENT PLAN - BID DEDUCT
ALTERNATE
GOTWALD
506-329CLINICAL & ADMINISTRATIVE
BUILDING
WILSON04-12-18
114 148
N
SCALE: 3/16" = 1'-0"
HVAC BASEMENT PLAN - BID DEDUCT ALTERNATE
SCALE: 1/4" = 1'-0"MH101-BD
1 SECTION - DUCT RISER - BID DEDUCT ALTERNATE
ASST CHIEF MAS OFF
VESTIBULE
MEN'S TOILET
HAC
318 IT
ELECTRICAL
HBU SUPRVISOR
CHIEF MAS OFFICER
MED RECORDS
SUPERVISOR
STAIRS
S-1
ELEVATOR
E-1
STAIRS
S-2
COFFEE
OPEN OFFICE
OPEN OFFICE
CORRIDOR
"x
ER-2
210 CFM
ER-3
330 CFM
ELEVATOR LOBBY
CONF. ROOM
CODING SUPERVISOR
OFFICE
ADMINISTRATIVE
OFFICER
WOMEN'S TOILET
A B C D
H
E
4.2
J
2.8
4.8
G
5.4
F
52"x12"
FPB-03-5
FPB-03-8
FPB-03-3
13-F/S DPR
12-F/S DPR
26"x22"
ER-2
210 CFM
18"x18"
"x
ER-1
50 CFM
11-F/S DPR
18" x 16" DN
FP-03-1
6"x6"
56" x 20" DN 56" x 24" UP
TO 1-RTU-1
44" x 24" DN 54" x 24" UP
TO 1-RTU-1
"x
MH101-BD
SCANNING SUPV
RECORD MANAGER
OFFICER
NON-VA CARE SUPV
OPEN OFFICE
3/4" NG RISER
20" x 20" UP
TO 1-RTU-1
20"x20"
10"x10"
OPEN OFFICE
1 1/2" HHWS/
HHWR DN
1" HHWS
1" HHWR
1 1/4" HHWS
1 1/4" HHWR
1" HHWR
1" HHWS
1" HHWR
1" HHWS
1" HHWS
1" HHWR
1 1/4" HHWS
1 1/4" HHWR
1" HHWS
1" HHWR
GENERAL NOTES
1.) ALL TYPES OF TERMINAL UNITS SHALL BE INSTALLED PER DETAIL 2 ON MH501.
2.) ALL EXHAUST BRANCHES SHALL BE INSTALLED PER DETAIL 1 ON MH501
BID DEDUCT KEY NOTES
1 EQUIPMENT TO PROVIDE HEAT UNDER BID DEDUCT ALT #7
1050 Wilshire Drive, Suite 260 Troy, MI 48084 T 248-643-6222
SSOE, Inc.
D A
T E
FULLY SPRINKLERED
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
VA ANN ARBOR MEDICAL CENTER CAMPUS
PROJECT #: 015-01361-00
BIDS SUBMISSION_REVISED
C A u to d e s k \R e v it \0
M
S
S O
E B id D e d u c t_
.r v t
/9
/2
:5
:5
A
M
Scale: As indicated
MH131-BD
HVAC THIRD FLOOR PLAN - BID DEDUCT
ALTERNATE
GOTWALD
506-329CLINICAL & ADMINISTRATIVE
BUILDING
WILSON04-12-18
115 148
N
SCALE: 3/16" = 1'-0"
THIRD FLOOR HVAC PLAN - BID DEDUCT ALTERNATE
A
B
B
C
C
D
D
6 6
5 5
3 3
2 2
H
HE
E
4.2
4.2
4 4
J
J
2.8
2.8
4.8
4.8
G
G
5.45.4
F
F
K
K
MH101-BD
1-RTU-1
"x
"x
3/4" NG 3/4" NG RISER FROM BELOW
ELECTRICAL KEY NOTES
1.) REFER TO DRAWING EP140 FOR SCOPE OF BASE BID ELECTRICAL WORK. REMOVE THE FOLLOWING ELECTRICAL CONNECTIONS AND ASSOCIATED CONTROLS FOR EQUIPMENT BEING REMOVED AND/OR
RELOCATED AS PART OF BID DEDUCT(S).
a. 1-H1
b. ACCU-01
2.) PROVIDE 200A, 480V, 3P DISCONNECT SWITCH WITH 150A FUSES IN NEMA 3R ENCLOSURE. FEED
FROM NEW 150A, 3P CIRCUIT BREAKER IN PANEL 4-MDP-BA VIA 3#1/0,1#6/G,1-1/2"C.
PLUMBING NOTES
1.) PROVIDE 810 CFH TO RTU-01. REFER TO DETAIL 8/PL400 FOR NATURAL GAS CONNECTION
TO EQUIPMENT.
1050 Wilshire Drive, Suite 260 Troy, MI 48084 T 248-643-6222
SSOE, Inc.
D A T E
FULLY SPRINKLERED
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
VA ANN ARBOR MEDICAL CENTER CAMPUS
PROJECT #: 015-01361-00
BIDS SUBMISSION_REVISED
C A u to d e s k \R e v it \0 M S S O E B id D e d u c t_ .r v t
/9 /2 :5 :0 A M
Scale: As indicated
MH141-BD
HVAC ROOF PLAN - BID DEDUCT
ALTERNATE
GOTWALD
506-329CLINICAL & ADMINISTRATIVE
BUILDING
WILSON04-12-18
116 148
N
SCALE: 3/16" = 1'-0"
ROOF HVAC PLAN - BID DEDUCT ALTERNATE
3. FAN SELECTION TOTAL STATIC PRESSURE TO INCLUDE DIRTY FILTER ALLOWANCE.
2. PROVIDE MERV 13 FILTER UPSTREAM OF COOLING COIL. PRESSURE DROP: 0.35 IN WG CLEAN, 0.75 IN WG DIRTY
1. PROVIDE MERV 8 FILTER UPSTREAM OF HEAT WHEEL. PRESSURE DROP: 0.24 IN WG CLEAN, 0.59 IN WG DIRTY
NOTES
WINTER 3500 0.0 0.0 57.3 48.8 3500 13.9 13.8
RTU-1 ROOF 18000 3500 1.5 2 x 10 18000 1.24 2 x 5
SUMMER 3500 95.0 75.0 78.3 64.8 3500 91.6 72.8
R-410A 75.6 62.6 51.1 50.9 0.43 810 648 2 460/3/60 134 7658
DB (°F) WB (°F) DB (°F) WB (°F) DB (°F) WB (°F) DB (°F) WB (°F) DB (°F) WB (°F)
SEASON
AIRFLOW
(CFM)
EAT LAT AIRFLOW
(CFM)
EAT
TOTAL
AIRFLOW
(CFM)
OUTDOOR
AIRFLOW
MIN/MAX
(CFM)
ESP
(IN WG)
MOTOR
(HP)
MIN/MAX
AIRFLOW
(CFM)
ESP
(IN WG)
MOTOR
(HP)
OUTSIDE AIR EXHAUST
REFRIG
EAT LAT AIR PD
(IN WG)
INPUT
(MBH)
OUTPUT
(MBH)
NAT GAS
PRESSURE
(PSIG)
V/PH/HZ MCA
MARK
LOCATION/
SERVICE
SUPPLY FAN DATA EXHAUST/RELIEF FAN DATA ENERGY RECOVERY COOLING CAPACITY (500 FPM MAX FACE VELOCITY) HEATING CAPACITY ELECTRICAL
WEIGHT
(LBS)
REMARKS
ROOFTOP UNIT SCHEDULE
SEQUENCE OF OPERATION
SYSTEM OPERATING MODES: THE BUILDING AUTOMATION SYSTEM (BAS) SHALL INCLUDE A
USER-ADJUSTABLE TIME-OF-DAY SCHEDULE TO DEFINE WHEN THE VARIOUS AREAS OF THE
FACILITY ARE EXPECTED TO BE OCCUPIED VERSUS UNOCCUPIED. THEN, BASED ON CURRENT
ZONE CONDITIONS, THE BAS DETERMINES THE CURRENT SYSTEM OPERATING MODE.
• OCCUPIED HEAT/COOL
DURING THE OCCUPIED MODE, THE ROOFTOP UNIT (RTU) MODULATES THE SUPPLY FAN TO
DELIVER THE REQUIRED AIRFLOW TO THE ZONES, POSITIONS THE OUTDOOR-AIR DAMPER TO
BRING IN REQUIRED AMOUNT OF VENTILATION, ENABLES THE HEAT WHEEL TO WHEN THE UNIT
IS NOT IN ECONOMIZER, MODULATES THE RELIEF FAN(S) TO MAINTAIN BUILDING PRESSURE AT
THE DESIRED SETPOINT, AND CYCLES THE COMPRESSORS, MODULATES (OR STAGES) THE
SOURCE OF HEAT, AND/OR ENABLES THE AIRSIDE ECONOMIZER TO DISCHARGE AIR AT THE
DESIRED SETPOINT.
• UNOCCUPIED HEAT/COOL
DURING THE UNOCCUPIED MODE, THE RTU SHUTS OFF WITH THE RETURN AIR DAMPER OPEN
AND THE OUTDOOR-AIR DAMPER AND RELIEF DAMPER CLOSED.
• MORNING WARM-UP/PRE-COOL
DURING THE MORNING WARM-UP/PRE-COOL MODE, EACH VAV TERMINAL UNIT VARIES PRIMARY
AIRFLOW, CYCLES A TERMINAL FAN (IF EQUIPPED), AND/OR MODULATES (OR STAGES) A LOCAL
HEAT SOURCE (IF EQUIPPED) TO RAISE/LOWER THE ZONE TEMPERATURE TO THE OCCUPIED
SETPOINT (HEATING OR COOLING), AND THEN CLOSES. MEANWHILE, THE RTU MODULATES THE
SUPPLY FAN TO DELIVER THE REQUIRED AIRFLOW TO THE ZONES, CLOSES THE OUTDOOR-AIR
DAMPER, CLOSES THE CENTRAL RELIEF DAMPER (OR SHUTS OFF THE CENTRAL RELIEF FAN),
AND CYCLES THE COMPRESSORS OR MODULATES (OR STAGES) THE SOURCE OF HEAT TO
DISCHARGE AIR AT THE DESIRED SETPOINT.
FOR A COLD-AIR VAV SYSTEM, IF THE RETURN AIR DEW POINT TEMPERATURE IS HIGHER THAN
55°F (ADJ) DURING MORNING PRE-COOL MODE, THE DISCHARGE-AIR TEMPERATURE SETPOINT
WILL BE RESET EVERY 10 MINUTES SO THAT IT IS ONLY 2°F (ADJ) BELOW THE CURRENT
RETURN AIR DEW POINT TEMPERATURE.
OPTIMIZED SYSTEM-LEVEL CONTROL SEQUENCES: THE BAS SHALL PERFORM THE FOLLOWING
OPTIMIZED SYSTEM-LEVEL CONTROL STRATEGIES:
• OPTIMAL START
THE BAS SHALL INITIATE OPTIMAL START MODE SUCH THAT THE RTU IS STARTED AND VAV
BOXES ARE ENABLED TO ALLOW THE ZONE TEMPERATURE TO REACH THE OCCUPIED HEATING
OR COOLING SETPOINT PRIOR TO SCHEDULED OCCUPANCY. THE SYSTEM SHALL WAIT AS
LONG AS POSSIBLE BEFORE STARTING, SO THAT THE TEMPERATURE IN EACH ZONE REACHES
THE OCCUPIED SETPOINT JUST IN TIME FOR SCHEDULED OCCUPANCY.
• OPTIMAL STOP
THE BAS SHALL INITIATE OPTIMAL STOP MODE SUCH THAT COOLING OR HEATING IS DISABLED
SO THAT THE ZONE TEMPERATURE DOES NOT DRIFT BEYOND THE OCCUPIED STANDBY
SETPOINT BY THE END OF THE SCHEDULED OCCUPANCY PERIOD. THE RTU SUPPLY FAN SHALL
CONTINUE OPERATING, AND VENTILATION CONTROL SHALL CONTINUE, THROUGH THE END OF
THE SCHEDULED OCCUPANCY PERIOD.
• UNOCCUPIED ECONOMIZING (NIGHT PURGE)
BETWEEN 4:00 AM (ADJ.) AND 6:00 AM (ADJ), THE BAS SHALL INITIATE UNOCCUPIED
ECONOMIZING MODE IF THE CURRENT ZONE TEMPERATURE IS AT LEAST 1°F WARMER THAN
THE OCCUPIED COOLING SETPOINT AND THE OUTDOOR DRY-BULB TEMPERATURE IS MORE
THAN 15°F (ADJ) COOLER THAN THE CURRENT ZONE TEMPERATURE. WHEN INITIATED, THE RTU
IS STARTED (OA DAMPER FULLY OPEN, COMPRESSORS OFF) AND VAV BOXES ARE ENABLED TO
ALLOW THE ZONE TEMPERATURE TO COOL TO THE OCCUPIED COOLING SETPOINT.
• OPTIMIZED CONTROL OF SUPPLY DUCT STATIC PRESSURE (FAN-PRESSURE OPTIMIZATION)
AT A FREQUENCY OF ONCE EVERY 10 MINUTES, THE BAS SHALL MONITOR THE DAMPER
POSITION OF ALL VAV TERMINAL UNITS. THE BAS SHALL CALCULATE A NEW SUPPLY FAN DUCT
STATIC PRESSURE SETPOINT BASED ON THE POSITION OF THE FURTHEST-OPEN VAV DAMPER,
AND SEND THIS NEWLY-CALCULATED SETPOINT TO THE RTU CONTROLLER. WHEN ANY VAV
DAMPER IS MORE THAN 75% (ADJ) OPEN, THE SUPPLY FAN DUCT STATIC PRESSURE SETPOINT
SHALL BE RESET UPWARD BY 5% UNTIL NO DAMPER IS MORE THAN 75% (ADJ) OPEN OR THE
STATIC PRESSURE SETPOINT HAS RESET TO THE MAXIMUM SETTING. WHEN ALL VAV DAMPERS
ARE LESS THAN 65% (ADJ) OPEN, THE SUPPLY FAN DUCT STATIC PRESSURE SETPOINT SHALL
BE RESET DOWNWARD BY 5% UNTIL AT LEAST ONE DAMPER IS MORE THAN 65% (ADJ) OPEN OR
THE STATIC PRESSURE SETPOINT HAS RESET TO THE MINIMUM SETTING.
• OPTIMIZED CONTROL OF SUPPLY AIR TEMPERATURE (SAT RESET)
AT A FREQUENCY OF ONCE EVERY 10 MINUTES, THE BAS SHALL MONITOR THE OUTDOOR DRY-
BULB TEMPERATURE, AS WELL AS THE ZONE TEMPERATURE AND DAMPER POSITION OF ALL VAV
TERMINAL UNITS. THE BAS SHALL CALCULATE A NEW SAT SETPOINT BASED ON CURRENT
OUTDOOR AIR (OA) TEMPERATURE, AND SEND THIS NEWLY-CALCULATED SAT SETPOINT TO THE
RTU CONTROLLER. WHEN THE OA TEMPERATURE IS WARMER THAN 65°F (ADJ), THE SAT
SETPOINT SHALL BE 55°F (ADJ). WHEN THE OA TEMPERATURE IS COLDER THAN 55°F (ADJ), THE SAT SETPOINT SHALL BE 60°F (ADJ). WHEN THE OA TEMPERATURE IS BETWEEN 55°F (ADJ) AND 65°F (ADJ), THE SAT SETPOINT SHALL BE RESET PROPORTIONALLY BETWEEN 55°F (ADJ) AND 60° F (ADJ). IF AT LEAST TWO (ADJ) ZONES HAVE BOTH 1) A VAV DAMPER THAT IS MORE THAN 75%
OPEN, AND 2) A CURRENT ZONE TEMPERATURE THAT IS HIGHER THAN THE CURRENT COOLING
SETPOINT, THEN THE SAT SETPOINT SHALL RETURN TO 55°F (ADJ) IF THE OUTDOOR DEW POINT IS HIGHER THAN 60°F (ADJ), THIS SAT RESET SEQUENCE SHALL BE SUSPENDED AND THE SAT
SETPOINT SHALL BE RESET TO 55°F (ADJ) UNTIL OUTDOOR DEW POINT DROPS BELOW 57°F
(ADJ).
• OPTIMIZED CONTROL OF VENTILATION (VENTILATION OPTIMIZATION)
THE ACTUAL OUTDOOR AIRFLOW SHALL BE SENSED AT THE OUTDOOR AIR INTAKE OF THE RTU,
AND CONTROLLED TO AN AIRFLOW SETPOINT DETERMINED ACCORDING TO ASHRAE STANDARD
62.1. WHEN THE BAS TIME-OF-DAY SCHEDULE INDICATES THAT A ZONE IS UNOCCUPIED, THE
REQUIRED OUTDOOR AIRFLOW FOR THAT ZONE SHALL BE ZERO. WHEN THE SCHEDULE
INDICATES THAT A ZONE IS OCCUPIED, THE REQUIRED OUTDOOR AIRFLOW FOR THAT ZONE
SHALL EQUAL THE DESIGN OUTDOOR AIRFLOW, UNLESS THE ZONE IS EQUIPPED WITH
OCCUPANCY SENSOR AND/OR A CARBON DIOXIDE (CO¬2) SENSOR, OR USES A TIME-OF-DAY
VENTILATION SCHEDULE, TO REDUCE THE REQUIRED OUTDOOR AIRFLOW DURING PERIODS
OF PARTIAL OCCUPANCY. THE REQUIRED OUTDOOR-AIR FRACTION (CURRENT REQUIRED
OUTDOOR AIRFLOW DIVIDED BY THE CURRENT PRIMARY AIRFLOW) SHALL BE CONTINUOUSLY
CALCULATED FOR EACH ZONE (VAV TERMINAL UNIT). AT A FREQUENCY OF ONCE EVERY 10
MINUTES, THE BAS SHALL GATHER THIS DATA FROM ALL VAV TERMINAL UNITS, CALCULATE THE
MINIMUM REQUIRED OUTDOOR AIRFLOW FOR THE SYSTEM ACCORDING TO ASHRAE 62.1, AND
SEND THIS NEWLY-CALCULATED OUTDOOR AIRFLOW SETPOINT TO THE RTU CONTROLLER.
R
B
C
A
B
C
D
E
OS
SWITCH, CEILING MOUNTED PULL
SWITCH
BLANK = SINGLE POLE
2 = DOUBLE POLE
3 = THREE-WAY
4 = FOUR-WAY
D = DIMMER
K = KEY OPERATED
LV= LOW VOLTAGE
L = LOCK
LM= LOW VOLTAGE MASTER
P = WITH PILOT LIGHT
PB= PUSH BUTTON STATION
RC= REMOTE CONTROL
T = TIMER OPERATED
WP= WEATHER PROOF
X = EXPLOSION PROOF
OS= STAND ALONE OCCUPANCY SENSOR
RECESSED DOWNLIGHT FIXTURE, LETTER INDICATES TYPE.
LIGHT FIXTURE, RECESSED, 2'x4' [610x1220mm];
LETTER INDICATES TYPE.
LIGHT FIXTURE, RECESSED, 1'x4' [305x1220mm];
LETTER INDICATES TYPE.
ELECTRICAL SYMBOLS - LIGHTING PLAN
LIGHT FIXTURE, RECESSED, 1'x8' [305x2439mm]; LETTER INDICATES TYPE.
LIGHT FIXTURE, SURFACE MOUNTED, 2'x4' [610x1220mm];
LETTER INDICATES TYPE.
LIGHT FIXTURE, SURFACE, 1'x4' [305x1220mm];
LETTER INDICATES TYPE.
LIGHT FIXTURE, SURFACE MOUNTED, 1'x8' [305x2439mm]; LETTER INDICATES TYPE.
LIGHT FIXTURE, EMERGENCY;
LETTER INDICATES TYPE.
LIGHTING, ONE HEAD EMERGENCY BATTERY POWER
STREET LIGHT WITH BRACKET
LIGHT POLE, ONE MAST ARM, ONE LUMINAIRE
LIGHT POLE, POST TOP MOUNT LUMINAIRE
LIGHT POLE, ONE LUMINAIRE
LIGHTING, EXTERIOR BUILDING
LIGHTING, TWO HEAD EMERGENCY BATTERY POWER
EXTERIOR FLOOD LIGHT
EXIT SIGN, WALL MOUNTED WITH DIRECTIONAL ARROWS AND
FACES AS SHOWN AS HATCHED AREA
EXIT SIGN, CEILING MOUNTED WITH DIRECTIONAL ARROWS AND
FACES AS SHOWN AS HATHED AREA
LIGHT FIXTURE, RECESSED, 2'x2' [610x610mm]; LETTER
INDICATES TYPE.
LIGHT FIXTURE, SURFACE MOUNTED, 2'x2' [610x610mm]; LETTER INDICATES TYPE.
LIGHT FIXTURE, STRIP/INDUSTRIAL; LETTER INDICATES TYPE.
LIGHT FIXTURE, WALL MOUNTED
LIGHT FIXTURE, BOLLARD
LIGHT FIXTURE, DIRECTIONAL
LIGHT POLE, TWO LUMINAIRES
TIME CLOCK
RECTIFIER, CATHODIC PROTECTION SANITARY
ELECTRICAL STRIP MOLD (OUTLETS ON 2'-0" [610mm] CENTERS OR AS DESIGNATED ON DRAWINGS), MTD 3'-6" [1067mm] AFF OR AS
INDICATED.
3-GANG COMPARTMENT BOX IN FLOOR FOR TELEPHONE, DATA &
RECEPTACLE.
DISCONNECT SWITCH, FUSED
DISCONNECT SWITCH, UNFUSED
STARTER, COMBINATION WITH DISCONNECT SWITCH
STARTER OR MOTOR CONTROLLER
POTHEAD
STRESS CONE
VENTILATOR OR FAN COIL UNIT OUTLET
CONDUIT TERMINATED 6" [152mm] AFF IN STANDARD BOX FOR
EXTENSION TO EQUIPMENT AS DIRECTED.
CONDUIT TERMINATED W/COUPLING (FLUSH W/FINISHED FLOOR) FOR
EXTENSION TO EQUIPMENT AS DIRECTED.
ELECTRICAL SYMBOLS - POWER PLAN
JUNCTION BOX
TRANSFORMER, PLAN
MOTOR, SINGLE-PHASE
MOTOR, THREE-PHASE
WYE CONNECTION
DUCT, CELL FLOOR HEADER
DUCT, TROLLEY
DUCT, UNDERFLOOR JUNCTION BOX
EARTH GROUND
LADDER CABLE TRAY
BRANCH CIRCUIT HOMERUN. LINES INDICATE NUMBER OF CIRCUITS,
NEUTRAL, AND SWITCH LEG CONDUCTORS. ONE SEPARATE GREEN
GROUNDING CONDUCTOR SHALL BE PROVIDED FOR EACH HOMERUN;
NOT SHOWN
PULL BOX
WIREWAY
RIGID CONDUIT LINE = RC
SUBSTATION
BUSWAY
FLOOR OUTLET, DATA COMMUNICATION
OUTLET, DATA COMMUNICATION
PUSH BUTTON
DISTRIBUTION PANEL
LIGHTING PANEL
PANELBOARD CABINET, FLUSH MOUNTED
PANELBOARD CABINET, SURFACE MOUNTED
RECEPTACLE, CLOCK HANGER
RECEPTACLE, DUPLEX
RECEPTACLE, DUPLEX ON EMERGENCY POWER
RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT INTERRUPTER
RECEPTACLE, QUADRAPLEX
RECEPTACLE, SINGLE
RECEPTACLE, SINGLE WITH SWITCH
RECEPTACLE, SPECIAL PURPOSE
A = 120V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 5-20R.
B = 208V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 6-20R.
C = 120V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 5-30R.
D = 208V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 6-30R.
E = 208V, 60A, 1 PHASE, 3-POLE, 4W, NEMA 14-60R.
F = 208V, 30A, 3 PHASE, 3-POLE 4W, NEMA 15-30R.
G = 208V, 50A, 3 PHASE, 3 POLE, 4W, NEMA 15-30R.
H = 208V, 60A, 3 PHASE, 3 POLE, 4W, NEMA 15-60R.
RECEPTACLE, SWITCHED DUPLEX
DIRECT BURIAL CABLE = DB
POWER DUCT = P
HI VOLTAGE SWITCH ON CONCRETE PAD
LOW VOLTAGE SWITCH ON CONCRETE PAD
DUAL POWER AND TELECOMMUNICATIONS MANHOLE
DROP CORD, SINGLE CONVENIENCE OUTLET, 3-WIRE, GROUNDING
TYPE, 20A, W/#12 CONDUCTORS IN FLEXIBLE CORD (CENTER LINE
OF OUTLET: 6'-6" [1981mm] AFF. MINIMUM).
ELECTRICAL STRIP MOLD (OUTLETS ON 2'-0" [610mm] CENTERS OR AS DESIGNATED ON DRAWINGS), MTD 3'-6" [1067mm] AFF OR AS
INDICATED.
3-GANG COMPARTMENT BOX IN FLOOR FOR TELEPHONE, DATA &
RECEPTACLE.
RELAY; LETTER INDICATES RELAY TYPE
50 = INSTANTANEOUS OVERCURRENT OR RATE-OF-RISE
51 = AC-TIME OVERCURRENT
67 = AC-DIRECTIONAL OVERCURRENT
86 = LOCK OUT
ELECTRICAL SYMBOLS - POWER PLAN
SWITCH
F = FUSED SWITCH K = KEY OPERATED
L = LOCK LM= LOW VOLTAGE MASTER
M = MANUAL MOTOR STARTING MC= MOMENTARY CONTACT
MP= MOTOR SNAP WITH PILOT LIGHT P = WITH PILOT LIGHT
(THERMAL TYPE)
PB= PUSH BUTTON STATION RC= REMOTE CONTROL
WP= WEATHER PROOF X = EXPLOSION PROOF
VARIABLE FREQUENCY DRIVE
1PH SINGLE-PHASE
1P SINGLE POLE
2/C TWO-CONDUCTOR
3/C THREE-CONDUCTOR
3PH THREE-PHASE
4/C FOUR-CONDUCTOR
4W FOUR-WIRE
A/C UNIT AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED CABLE
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
ADO AUTOMATIC DOOR OPENER
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER, AUTOMATIC
FREQUENCY CONTROL, OR AVAILABLE
FAULT CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AH AMPERE HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
AMB OR A AMBIENT
AMP AMPERE
ARCH ARCHITECT
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
BAT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISH FLOOR
BIL BASIC INSULATION LEVEL
BLDG BUILDING
BPIP BOILER PLANT INSTRUMENTATION PANEL
BRKR BREAKER
BYP BY PASS
C CONDUIT
CAB CABINET
CALC CALCULATE
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/CONTRACTOR
INSTALLED
CF/OI CONTRACTOR FURNISHED/OWNER
INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CKT BRKR CIRCUIT BREAKER
CLF CURRENT LIMITING FUSE
CLG CEILING
CMU CONCRETE MASONRY UNIT
COAX COAX CABLE
COMM COMMUNICATION
COMPT COMPARTMENT
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CU FT CUBIC FEET
CUR CURRENT
DB DECIBEL OR DIRECT BURIAL
DC DIRECT CURRENT
DCP DIMMER CONTROL PANEL
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DISTR DISTRIBUTION
DISTR PNL DISTRIBUTION PANEL
DMR SW DIMMER SWITCH
DN DOWN
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
EC EMPTY CONDUIT
EG EQUIPMENT GROUND
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMCP EMERGENCY MONITORING CONTROL
PANEL
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
EPRF EXPLOSION PROOF
ESMT EASEMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST EXISTING
ELECTRICAL ABBREVIATIONS
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FABL FIRE ALARM BELL
FABX FIRE ALARM BOX
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FI FILM ILLUMINATOR
FIXT FIXTURE
FLA FULL LOAD AMPS
FLEX FLEXIBLE METALLIC CONDUIT
FLT FLOODLIGHT
FLUOR FLUORESCENT
FLUOR FIX FLUORESCENT FIXTURE
FOUTT TELEPHONE FLOOR OUTLET
FP FIRE PROTECTION
FT FEET OR FOOT
FU SW FUSED SWITCH
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G OR GND GROUND OR GENERATOR
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GTB GROUND TERMINAL BOX
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
IESNA ILLUMINATION ENGINEERING SOCIETY OF
NORTH AMERICA
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
kV KILOVOLT kVA KILOVOLT AMPERE kVAH KILOVOLT AMPERE PER HOUR kVAR KILOVOLT AMPERE REACTIVE kW KILOWATT kWH KILOWATT HOUR kWHM KILOWATT HOUR METER
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LM LUMEN
LP LIGHT POLE
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LTCP LOCAL TEMPERATURE CONTROL PANEL
LT LIGHT
LTG LIGHTING
LTG PNL LIGHTING PANEL
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
MLO MAIN LUGS ONLY
MT MOUNT
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT MICROWAVE
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NEUT OR N NEUTRAL
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NS NO SCALE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OL OVERLOAD
P POLE
PA PUBLIC ADDRESS
PB PANELBOARD, PULL BOX, OR
PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT UNIT
PCB POLYCHLORINATED BIPHENYL
PEC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PNL PANEL
POD POWER OPERATED DAMPER
PT POTENTIAL TRANSFORMER
PTRV POWER TYPE ROOF VENTILATION
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
RCP REFLECTED CEILING PLAN
REC RECESSED
RECPT RECEPTACLE
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
REQD REQUIRED
SCC SHORT CIRCUIT CAPACITY
SES SERVICE ENTRANCE SECTION
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SURF SURFACE
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TC TIME CLOCK
TEL TELEPHONE
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V VOLT
VA VOLT AMPERE
VAR VOLT AMPERE REACTIVE
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
W WATT
WH WATER HEATER
WP WEATHERPROOF
XFER TRANSFER
XFMR TRANSFORMER
DP#__
LP
TC
T
PB
S
S
S
HVS
LVS
P
T
R
VFD
RC
DB
P
W W
B B
C C
J
T T
POKE THRU
FLOOR BOX
POKE THRU
FLOOR BOX
OSB = LUTRON LOS-CDT-2000-WH
OSA = MS-Z101-WH
LVB = LUTRON QSWS2-2BI-WH
LVA = LUTRON QSWS2-1BI-WH
CL CENTER LINE
(R) NEW LOCATION FOR RELOCATED ITEM
A
P
GROUND ROD
COMBINATION MAGNETIC MOTOR STARTER - FULL VOLTAGE TYPE
WITH FUSIBLE DISCONNECT SWITCH
LIGHT FIXTURE, STRIP/INDUSTRIAL EMERGENCY; LETTER INDICATES TYPE.
CEILING MOUNTED OCCUPANCY SENSOR
1050 Wilshire Drive, Suite 260 Troy, MI 48084 T 248-643-6222
SSOE, Inc.
D A
T E
FULLY SPRINKLERED
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
VA ANN ARBOR MEDICAL CENTER CAMPUS
PROJECT #: 015-01361-00
BIDS SUBMISSION_REVISED
C A u to d e s k \R e v it \0
E
S
S O
E .r v t
/9
/2
:1 :2
P
M
E000
ELECTRICAL SYMBOLS, LEGEND AND
NOTES
PATERSON
506-329CLINICAL & ADMINISTRATIVE
BUILDING
BUTTS11-15-16
117 148
GENERAL NOTES
A THESE DRAWINGS REPRESENT THE GENERAL EXTENT AND ARRANGEMENT OF SYSTEMS, BUT ARE NOT TO BE CONSIDERED FABRICATION DRAWINGS. THESE DRAWINGS ARE SUPPLEMENTARY TO THE PROJECT SPECIFICATIONS. COORDINATE WITH OTHER TRADES, AND PROVIDE EACH SYSTEM COMPLETE, INCLUDING
ALL NECESSARY COMPONENTS, FITTINGS, AND OFFSETS.
B INSTALL SYSTEMS SUCH THAT CODE REQUIRED WORKING CLEARANCE AND DEDICATED EQUIPMENT SPACE ALONG WITH SERVICE ACCESS SPACE IS PROVIDED AROUND ALL MECHANICAL AND ELECTRICAL EQUIPMENT, AND AROUND ANY COMPONENTS WHICH REQUIRE SERVICE ACCESS.
C COORDINATE AND PROVIDE ACCESS DOORS WITHIN INACCESSIBLE CEILING, SHAFT, AND CHASE AREAS FOR ALL COMPONENTS WHICH REQUIRE SERVICE ACCESS. REFER TO ARCHITECTURAL DRAWINGS FOR CEILING TYPES AND PARTITION RATINGS. ACCESS DOORS IN FIRE RATED SURFACES SHALL MAINTAIN THE
FIRE RATING OF THE PARTITION.
D PROVIDE ALL MISCELLANEOUS STEEL AND HARDWARE TO SUPPORT ALL DEVICES AND EQUIPMENT AS INDICATED IN THE SPECIFICATIONS.
E REFER TO MECHANICAL/ELECTRICAL SCHEDULE DRAWING(S) FOR ELECTRICAL REQUIREMENTS FOR MECHANICAL EQUIPMENT. PROVIDE ALL CONNECTIONS, STARTERS, DISCONNECTS, ETC. AS INDICATED ON THE SCHEDULES AND WHERE ELSEWHERE NOTED. PROVIDE THE CIRCUIT OF HIGHER AMPACITY WHERE CIRCUIT SIZES ARE SHOWN ON THE ELECTRICAL DRAWINGS THAT DIFFER FROM WHAT IS INDICATED ON THE MECHANICAL SCHEDULES.
F VERIFY REQUIREMENTS OF ALL MECHANICAL EQUIPMENT WITH EQUIPMENT SHOP DRAWINGS PRIOR TO ORDERING MATERIALS. NOTIFY THE ENGINEER OF ANY DISCREPANCIES BETWEEN THE EQUIPMENT SHOP DRAWINGS AND ELECTRICAL DRAWINGS. OBTAIN DIRECTION FROM THE ENGINEER PRIOR TO ORDERING
MATERIALS WHERE DISCREPANCIES EXIST.
G PROVIDE NEW OVERCURRENT PROTECTIVE DEVICES TO MATCH EXISTING EQUIPMENT WHERE NEW OVERCURRENT PROTECTIVE DEVICES ARE REQUIRED TO
SERVE NEW LOADS FROM EXISTING EQUIPMENT.
H TRANSFORMER CONDUCTORS SHALL BE SIZED IN ACCORDANCE WITH THE NEC UNLESS NOTED OTHERWISE.
I MOTOR CIRCUIT PROTECTION SHALL BE SIZED IN ACCORDANCE WITH THE NEC UNLESS NOTED OTHERWISE.
J TYPICAL HOMERUN CIRCUIT IS 3/4"C., 2#12 & 1#12 GND (CU), UNLESS OTHERWISE NOTED. SHARED NEUTRALS ARE PROHIBITED. REFER TO THE BRANCH CIRCUIT VOLTAGE DROP TABLE ON THIS DRAWING FOR MAXIMUM DISTANCE FOR BRANCH CIRCUIT WIRING.
K WHERE MULTIPLE SWITCHES, RECEPTACLES, AND OTHER OUTLETS (EXCEPT WALL PHONES) ARE INDICATED PROVIDE MULTI-GANG BACK BOXES WITH GANG
BARRIERS AND A COMMON FACEPLATE FOR ALL SIMILAR DEVICES.
L WHERE DIFFERENT RECESSED ELECTRICAL DEVICES WITH THE SAME MOUNTING HEIGHTS ARE INDICATED SIDE-BY-SIDE, MOUNT THE DEVICES SO THAT THERE IS ONE INCH BETWEEN ADJACENT VERTICAL EDGES OF THE FACEPLATES, UNLESS OTHERWISE NOTED.
M WHERE ELECTRICAL DEVICES WITH DIFFERENT MOUNTING HEIGHTS ARE LOCATED IN THE SAME AREA ALIGN DEVICES VERTICALLY THROUGH THEIR
CENTERLINES.
N REFER TO ARCHITECTURAL ELEVATIONS FOR COORDINATED LOCATIONS OF TYPICAL ELECTRICAL DEVICES. VERIFY MOUNTING HEIGHTS OF ALL OUTLETS.
O TYPICAL MOUNTING HEIGHTS ARE INDICATED ON THE ARCHITECTURAL DRAWINGS. COORDINATE THE MOUNTING HEIGHT OF DEVICES AND EQUIPMENT INDICATED ON THESE DRAWINGS THAT ARE INDICATED AT DIFFERENT MOUNTING HEIGHTS THAN THOSE INDICATED ON THE ARCHITECTURAL DRAWINGS WITH
THE ARCHITECT AND/OR ENGINEER PRIOR TO INSTALLATION.
P COORDINATE THE EXACT LOCATION OF ALL FLOOR BOXES WITH THE FINAL FURNITURE LAYOUT DRAWINGS AND ARCHITECTURAL TRADE.
Q WHERE THE NUMBER OF CURRENT-CARRYING CONDUCTORS IN A RACEWAY EXCEEDS THREE, THE ALLOWABLE AMPACITY OF EACH CONDUCTOR SHALL BE REDUCED AS SHOWN IN THE ADJUSTMENT FACTOR TABLE IN THE NATIONAL ELECTRICAL CODE. LOAD DIVERSITY FACTORS SHALL NOT BE USED IN SIZING
BRANCH CIRCUIT CONDUCTORS.
R CONTRACTOR SHALL PROVIDE UPDATED, TYPED PANEL DIRECTORIES FOR ALL PANELBOARDS MODIFIED DURING DEMOLITION AND/OR CONSTRUCTION. ANY CIRCUITS MADE AVAILABLE DURING DEMOLITION AND NOT RE-USED DURING CONSTRUCTION SHALL BE MARKED "SPARE".
S PROVIDE A DISCONNECTING MEANS FOR ALL LIGHTING FIXTURES PER NEC SECTION 410.130.G.1.
T COORDINATE ANY SHUT DOWN OF EXISTING SERVICES AND EQUIPMENT THAT ARE REMAINING IN USE WITH THE OWNER'S REPRESENTATIVE. WHERE EXISTING BUILDING SERVICE IS REQUIRED TO BE SHUT DOWN, INCLUDE ALL ASSOCIATED OVERTIME COST TO PERFORM THIS WORK DURING WEEKENDS AND EVENINGS, INCLUDE ALL COSTS FOR PROVIDING TEMPORARY POWER WHERE SHUT DOWNS MUST OCCUR FOR PERIODS LONGER THAN THESE HOURS. COORDINATE
ELECTRICAL SHUT DOWNS WITH THE OWNER 72 HOURS PRIOR TO SHUT DOWN.
U ALL EXISTING 2'X4' AND 2'X2' LED LUMINAIRES LOCATED IN EXISTING BUILDING #4 BEING DEMOLISHED SHALL BE REMOVED, WRAPPED TO PROVIDE PROTECTION FROM DAMAGE, AND TRANSPORTED TO AN AREA DESIGNATED BY THE VA FOR STORAGE. THESE FIXTURES SHALL BE INSTALLED IN NEW BUILDING #4 AS
INDICATED IN THESE DOCUMENTS FOR FIXTURES DENOTED WITH (R).
BRANCH CIRCUIT VOLTAGE DROP TABLE
AWG
#12
#10
#8
120V, 20A CIRCUIT
65 FEET
105 FEET
160 FEET
277V, 20A CIRCUIT
150 FEET
245 FEET
375 FEET
DESIGN DEVELOPMENT SUBMISSION 1 04-19-16
DESIGN DEVELOPMENT SUBMISSION 2 06-10-16
95% CONSTRUCTION DOCUMENTS
SUBMISSION
11-15-16
1050 Wilshire Drive, Suite 260 Troy, MI 48084 T 248-643-6222
SSOE, Inc.
D A
T E
FULLY SPRINKLERED
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
VA ANN ARBOR MEDICAL CENTER CAMPUS
PROJECT #: 015-01361-00
BIDS SUBMISSION_REVISED
C A u to d e s k \R e v it \0
E
S
S O
E .r v t
/9
/2
:1 :2
P
M
E001
SCHEDULES AND NOTES
PATERSON
506-329CLINICAL & ADMINISTRATIVE
BUILDING
BUTTS11-15-16
118 148
LIGHTING FIXTURE SCHEDULE
TYPE LAMPS DESCRIPTION VOLTAGE MANUFACTURER (BASIS OF DESIGN IS LISTED) APPARENT LOAD
L1 3500K LED 2' x 4' LED LAY-IN TROFFER WITH: 4000 LUMENS; STEEL HOUSING; WHITE POWDER COAT ONE-PIECE LOWER REFLECTOR; T-BAR CLIPS; 0-10V DIMMABLE DRIVER WIRED FOR DIMMING. 120 V CREE LIGHTING CAT. NO. CR24-40L-35K-10V OR
ENGINEER/VA APPROVED EQUIVALENT
40 VA
L1A 3500K LED 2' x 4' LED LAY-IN TROFFER WITH: 5000 LUMENS; STEEL HOUSING; WHITE POWDER COAT ONE-PIECE LOWER REFLECTOR; T-BAR CLIPS; 0-10V DIMMABLE DRIVER WIRED FOR DIMMING. 120 V CREE LIGHTING CAT. NO. CR24-50L-35K-10V OR
ENGINEER/VA APPROVED EQUIVALENT
50 VA
L1AE 3500K LED SAME AS FIXTURE TYPE 'L1A' EXCEPT COMPLETE WITH 1400 LUMENS EMERGENCY BATTERY BACKUP. 120 V CREE LIGHTING CAT. NO. CR24-50L-35K-10V-EB14 OR
ENGINEER/VA APPROVED EQUIVALENT
50 VA
L1E 3500K LED SAME AS FIXTURE TYPE 'L1' EXCEPT COMPLETE WITH 1400 LUMENS EMERGENCY BATTERY BACKUP. 120 V CREE LIGHTING CAT. NO. CR24-40L-35K-10V-EB14 OR
ENGINEER/VA APPROVED EQUIVALENT
40 VA
L2 3500K LED 2' x 2' LED LAY-IN TROFFER WITH: 3200 LUMENS; STEEL HOUSING; WHITE POWDER COAT ONE-PIECE LOWER REFLECTOR; T-BAR CLIPS; 0-10V DIMMABLE DRIVER WIRED FOR DIMMING. 120 V CREE LIGHTING CAT. NO. CR22-32L-35K-10V OR
ENGINEER/VA APPROVED EQUIVALENT
32 VA
L2E 3500K LED SAME AS FIXTURE TYPE 'L2' EXCEPT COMPLETE WITH 1400 LUMENS EMERGENCY BATTERY BACKUP. 120 V CREE LIGHTING CAT. NO. CR22-32L-35K-10V-EB14 OR
ENGINEER/VA APPROVED EQUIVALENT
32 VA
L3E 3500K LED 4' WALL MOUNT LED FIXTURE WITH: 4000 LUMENS MIN.; STEEL HOUSING, IMPACT MODIFIED LINEAR FACETED REFRACTOR; 0-10V DIMMING DRIVER WIRED FOR NON-DIMMING. COMPLETE WITH 1400 LUMENS
EMERGENCY BATTERY BACKUP.
120 V LITHONIA LIGHTING CAT. NO.
WL4-40L-EZ1-LP835-EL14L OR ENGINEER/VA
APPROVED EQUIVALENT
40 VA
L4 3500K LED 11'-3" LONG, 4" (NOMINAL) RECESSED SLOT, LED LIGHTING FIXTURE MOUNTED IN GYP. CEILING WITH: 381 LUMENS PER FOOT MAX; PRECISION CUT EXTRUDED ALUMINUM BODY; HIGH REFLECTANCE STEEL MATTE WHITE REFLECTOR; FROST WHITE SNAP IN LENS; INTEGRALLY FUSED; 0-10V DIMMABLE DRIVER WIRED FOR NON-DIMMING. VERIFY THE EXACT LENGHTS WITH THE ARCHITECT PRIOR TO ORDERING.
120 V FINELIGHT CAT. NO. HP-4 R-11'
3"-S-8-35-F-120V-SC-SF OR ENGINEER/VA APPROVED
EQUIVALENT
106 VA
L5 3500K LED 6" (NOMINAL) ROUND APERTURE, RECESSED 1500 LUMEN LED DOWNLIGHT WITH: SEMI-SPECULAR OPTICAL SYSTEM AND TRIM FLANGE FINISH; 0-10V DIMMABLE ELECTRONIC POWER SUPPLY WITH OVERLOAD AND SHORT CIRCUIT PROTECTION; REGRESSED LENS; LEDS AND POWER SUPPLY SERVICEABLE FROM BELOW; UL LISTED SUITABLE FOR WET LOCATIONS.
120 V GOTHAM CAT. NO.
EVO-35/15-6AR-MD-LSS-120-EZ10-SF OR
ENGINEER/VA APPROVED EQUIVALENT
19 VA
L5E 3500K LED SAME AS FIXTURE TYPE 'L5' EXCEPT COMPLETE WITH EMERGENCY BATTERY PACK WITH INTEGRAL TEST SWITCH. 120 V GOTHAM CAT. NO.
EVO-35/15-6AR-MD-LSS-120-EZ10-SF/EL OR
ENGINEER/VA APPROVED EQUIVALENT
19 VA
L6 3500K LED 4' LED STRIPLIGHT WITH: 5000 LUMENS; COLD-ROLLED STEEL CONSTRUCTION WITH OPTICAL DROP LENS ASSEMBLY; AIRCRAFT CABLE MOUNTING; WHITE PAINTED FINISH; FIXTURE SHALL HAVE INTEGRAL DRIVER
AND SLOW BLOW FUSE.
120 V LITHONIA LIGHTING CAT. NO.
ZL1D-L48-5000LM-FST-120-35K-80CRI-WH-ZACVH OR
ENGINEER/VA APPROVED EQUIVALENT
42 VA
L6AE 3500K LED SAME AS FIXTURE TYPE 'L6' EXCEPT SURFACE MOUNTED HORIZONTALLY ON WALL AND COMPLETE WITH 1400 LUMENS EMERGENCY BATTERY BACKUP. 120 V LITHONIA LIGHTING CAT. NO.
ZL1D-L48-5000LM-FST-120-35K-80CRI-E7W-WH OR
ENGINEER/VA APPROVED EQUIVALENT
40 VA
L6E 3500K LED SAME AS FIXTURE TYPE 'L6' EXCEPT COMPLETE WITH 1400 LUMENS EMERGENCY BATTERY BACKUP. 120 V LITHONIA LIGHTING CAT. NO.
ZL1D-L48-5000LM-FST-120-35K-80CRI-E7W-WH-ZACVH
OR ENGINEER/VA APPROVED EQUIVALENT
42 VA
L7 3500K LED 4'X4' LED SUSPENDED FIXTURE WITH: 7000 LUMENS; EXTRUDED ALUMINUM RAILS; DIE-CAST CORNERS; FROSTED ACRYLIC OPTICAL DIRECT/INDIRECT DIFFUSER; POWER PROVIDED THROUGH SUSPENSION
SYSTEM;
120 V FOCAL POINT CAT. NO.
FNRP-44-FL50-7000L-35K-1C-UNV-LD1-G-CLV48
33 VA
L8 3000K LED LED DECORATIVE LED CEILING/PENDANT LUMINAIRE WITH: 500LUMEN OUTPUT; SATIN NICKEL FINISH; LATTE CYLINDRICAL GLASS SHADE; DIMMABLE; 59" CABLE LENGTH; 4" ROUND FLUSH CANOPY; SHORT CIRCUIT
PROTECTION.
120 V TECH LIGHTING CAT. NO. 700-MP-MHUD-L-S-LEDS830
OR ENGINEER/VA APPROVED EQUIVALENT
8 VA
L9 3000K LED 25.8"W X 4.8"H DECORATIVE LED WALL SCONCE: 900 LUMENS; HORIZONTAL MOUNT; FROSTED LENS; SATIN NICKEL BODY. 120 V TECH LIGHTING CAT. NO. 700BCMET-S-LED OR
ENGINEER/VA APPROVED EQUIVALENT
20 VA
L10E 3500K LED 4' WALL MOUNT LED FIXTURE WITH: 4000 LUMENS MIN.; STEEL HOUSING, IMPACT MODIFIED LINEAR FACETED REFRACTOR; 0-10V DIMMING DRIVER WIRED FOR DIMMING; INTEGRAL OCCUPANCY SENSOR; WITH 1400
LUMENS EMERGENCY BATTERY BACKUP.
120 V FOCAL POINT CAT. NO.
FDALW-MG-875LF-35K-1C-UNV-SD5-WM-EM-WH-4' OR
ENGINEER/VA APPROVED EQUIVALENT
39 VA
L11 3000K LED 2'-0" LONG, SUREFACE MOUNTED LED UNDERCABINET LIGHT: 504 LUMENS; LOW PROFILE DESIGN; ALUMINUM HOUSING; END CAPS; DIRECT WIRED; SWIVEL HEAD ALLOWS FOR LIGHT TO BE DIRECTED; WHITE
FINISH; PROVIDE ROW CONNECTORS FOR LINEAR RUNS.
120 V LITHONIA LIGHTING CAT. NO. UCLD24-WH OR
ENGINEER/VA APPROVED EQUIVALENT
12 VA
L12E 4000K LED WALL MOUNT WALL PACK WITH: 1959 LUMENS; SINGLE-PIECE DIE-CAST ALUMINUM HOUSING, DIE-CAST DOOR FRAME IS FULLY GASKETED WITH A ONE-PIECE SILICONE GASKET; DARK BRONZE POWDERCOAT FINISH; PRECISION-MOLDED ACRYLIC LENS; WITH EMERGENCY BATTERY BACKUP RATED FOR -20 DEG. OPERATING TEMPERATURE.
120 V LITHONIA LIGHTING CAT. NO.
WST-LED-1-10A700/40K-SR4-120-SF/ELCW-DDBXD OR
ENGINEER/VA APPROVED EQUIVALENT
24 VA
L13 4100K LED LED FLOOD LIGHT FIXTURE WITH: 1300 LUMENS; DIE-CAST ALUMINUM HOUSING; ARCHITECTURAL JUNCTION BOX WITH DARK BRONZE FINISH; FROSTED FILTER; VERY WIDE FLOOD DISTRIBUTION; DARK BRONZE
POWDER COAT FINISH; DIMMING DRIVER;
120 V HYDREL CAT. NO.
TPS1-18LED-WHT41K-MVOLT-VWFL-YM-ARTL-FRF-LDI
M-LP-DDB OR ENGINEER/VA APPROVED EQUIVALENT
34 VA
L14 4100K LED LED FLOODLIGHT FIXTURE WITH: 1600 LUMENS; DIE-CAST ALUMINUM HOUSING; ARCHITECTURAL JUNCTION BOX WITH DARK BRONZE FINISH; FROSTED FILTER; WIDE FLOOD DISTRIBUTION; DARK BRONZE POWDER
COAT FINISH; DIMMING DRIVER;
120 V HYDREL CAT. NO.
TPS1-18LED-WHT41K-MVOLT-WFL-YM-ARTL-FRF-LDIM
-LP-DDB OR ENGINEER/VA APPROVED EQUIVALENT
34 VA
L15 4000K LED LED BOLLARD FIXTURE WITH; 1500 LUMENS; ALUMINUM HOUSING; FROSTED BOROSILICATE GLASS LENS; FORWARD THROW OPTICS; DARK BRONZE POWDER COAT FINISH; DIMMING DRIVER; 120 V HYDREL CAT. NO.
3110C-H42-8C0B-40K-120-FT-LDIM-DDB OR
ENGINEER/VA APPROVED EQUIVALENT
74 VA
X1 LED RECESSED MOUNTED L.E.D. EXIT SIGN WITH: BRUSHED ALUMINUM FINISH; CLEAR ACRYLIC PANEL; SINGLE FACE; RED LETTERING; L.E.D.'S MOUNTED ON A PRINTED CIRCUIT BOARD; NICKEL CADMIUM BATTERY
PACK; SELF-DIAGNOSTICS; *PROVIDE WM OPTION WHERE WALL MOUNTED.
120 V LITHONIA CAT. NO. EDGR-1-R-EL/SD-WM* OR
ENGINEER/VA APPROVED EQUIVALENT
3 VA
X2 LED RECESSED MOUNTED L.E.D. EXIT SIGN WITH: BRUSHED ALUMINUM FINISH; MIRRORED ACRYLIC PANEL; DOUBLE FACE; RED LETTERING; L.E.D.'S MOUNTED ON A PRINTED CIRCUIT BOARD; NICKEL CADMIUM
BATTERY PACK; SELF-DIAGNOSTICS.
120 V LITHONIA CAT. NO. EDGR-2-RMR-EL/SD OR
ENGINEER/VA APPROVED EQUIVALENT
6 VA
FLOOD LIGHTS PHOTOCELL DIMMABLE DUSK DAWN ALL 100%
BOLLARDS PHOTOCELL DIMMABLE DUSK DAWN ALL 100%
REAR EXIT PHOTOCELL DIMMABLE DUSK DAWN ALL 100%
FRONT CANOPY PHOTOCELL DIMMABLE DUSK DAWN ALL 100%
EXTERIOR
S-2 OCCUPANCY SENSOR STEP DIMMING ALWAYS - ALL 100%/50% DIM TO 50% WHEN NO OCCUPANCY
S-1 OCCUPANCY SENSOR STEP DIMMING ALWAYS - ALL 100%/50% DIM TO 50% WHEN NO OCCUPANCY
STAIRS
CONFERENCE ROOM OCCUPANCY SENSOR DIMMABLE - - - LAST LOCAL DIMMABLE OVERRIDE SWITCH WITH TIME-OUT, WARNING FLASH
ELEVATOR LOBBY TIME CLOCK DIMMABLE 7AM 7PM MON-FRI 100% LOCAL ON/OFF OVERRIDE SWITCH WITH TIME-OUT, WARNING FLASH
RECEPTION PENDANTS TIME CLOCK DIMMABLE 7AM 7PM MON-FRI 100% LOCAL ON/OFF OVERRIDE SWITCH WITH TIME-OUT, WARNING FLASH; DIMMER CONTROL IN ELECTRICAL CLOSET
CORRIDORS TIME CLOCK DIMMABLE 7AM 7PM MON-FRI 100% LOCAL ON/OFF OVERRIDE SWITCH WITH TIME-OUT, WARNING FLASH
OPEN OFFICE AREAS TIME CLOCK DIMMABLE 7AM 7PM MON-FRI 100% LOCAL ON/OFF OVERRIDE SWITCH WITH TIME-OUT, WARNING FLASH
THIRD FLOOR
CONFERENCE ROOM OCCUPANCY SENSOR DIMMABLE - - - LAST LOCAL DIMMABLE OVERRIDE SWITCH WITH TIME-OUT, WARNING FLASH
ELEVATOR LOBBY TIME CLOCK DIMMABLE 7AM 7PM MON-FRI 100% LOCAL OVERRIDE SWITCH WITH TIME-OUT, WARNING FLASH
RECEPTION PENDANTS TIME CLOCK DIMMABLE 7AM 7PM MON-FRI 100% LOCAL OVERRIDE SWITCH WITH TIME-OUT, WARNING FLASH; DIMMER CONTROL IN ELECTRICAL CLOSET
CORRIDORS TIME CLOCK DIMMABLE 7AM 7PM MON-FRI 100% LOCAL OVERRIDE SWITCH WITH TIME-OUT, WARNING FLASH
OPEN OFFICE AREAS TIME CLOCK DIMMABLE 7AM 7PM MON-FRI 100% LOCAL OVERRIDE SWITCH WITH TIME-OUT, WARNING FLASH
SECOND FLOOR
VESTIBULE TIME CLOCK DIMMABLE 7AM 7PM MON-FRI 100% LOCAL ON/OFF OVERRIDE SWITCH WITH TIME-OUT, WARNING FLASH
WAITING TIME CLOCK DIMMABLE 7AM 7PM MON-FRI 100% LOCAL DIMMABLE OVERRIDE SWITCH WITH TIME-OUT, WARNING FLASH
ELEVATOR LOBBY TIME CLOCK DIMMABLE 7AM 7PM MON-FRI 100% LOCAL ON/OFF OVERRIDE SWITCH WITH TIME-OUT, WARNING FLASH
RECEPTION PENDANTS TIME CLOCK DIMMABLE 7AM 7PM MON-FRI 100% LOCAL ON/OFF OVERRIDE SWITCH WITH TIME-OUT, WARNING FLASH; DIMMER CONTROL IN ELECTRICAL CLOSET
CORRIDORS TIME CLOCK DIMMABLE 7AM 7PM MON-FRI 100% LOCAL ON/OFF OVERRIDE SWITCH WITH TIME-OUT, WARNING FLASH
OPEN OFFICE AREAS TIME CLOCK…