36C24919R0012 0008 15-584-Electrical Sheet - T-601 - TECHNOLOGY RISERS.pdf
View the file
Other files
Show 40 more
Latest 50 of 67 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BUILDING 202
OIT ROOM 127EXISTING
BUILDING
17 IT ROOM
GRADE
BUILDING 201
OIT ROOM 129
HH-11HH-10HH-9MH-8MH-1
EXISTING FIRE
ALARM PANEL
VERIFY
LOCATION
EXISTING B#1
TELECOM
ROOM 31
(TEL. DATA
INTERCOM)
MH-2
HH-3,4,5,7
AND MH-6
4-12 STRAND
FIBER
300 PR TEL.1 1/4" INNER
DUCT
4-12 STRAND
FIBER
300 PR TEL.1 1/4" INNER
DUCT
300 PR TEL.
4-12 STRAND
FIBER
300 PR TEL.
4-12 STRAND
FIBER
300 PR TEL.
4-12 STRAND
FIBER
300 PR TEL.
4-12 STRAND
FIBER
3-12 STRAND
FIBER
50 PR TEL.1 1/4" INNER
DUCT
1 1
3 4
18 18 18
10 10
8 8
10 6
12 - 16/2 SHIELDED
(IN CONDUIT)
12 - 16/2 SHIELDED
(IN CONDUIT)
1-14/2 SHIELDED
2-14/2 SHIELDED
2-14/2 SHIELDED2-14/2 SHIELDED2-14/2 SHIELDED2-14/2 SHIELDED2-14/2 SHIELDED
1 - 14/2 SHIELDED
(IN CONDUIT)
1 - 14/2 SHIELDED
(IN CONDUIT)
BAS IN ATTIC
(IN INNERDUCT)
BAS
MECH.
RM 135
1 PR FIBER
(IN INNERDUCT)
BAS
MECH.
RM 134
1 PR FIBER
(IN INNERDUCT)
1 1
PATCH PNL
W.M.
2-WAY AMP
END OF LINE
DEVICES
UPS
S S S
TO B#1, RM 31
EQUIP. SEE SITE
& RISER BELOW.
14/2 SHIELDED
120V
DATA SWITCH
SEE SITE
PLAN.
14/2 SHIELDED
120V
END OF LINE
DEVICE
AMP 1
S S S
N.T.S.T-601
1 PARTIAL LOCAL/WIDE AREA RISER DIAGRAM
1 EXISTING MH-1 AND MH-2 TO REMAIN.
2 EXISTING 3-4" CONDUITS.
3 NEW 2-4" CONDUIT, BORE FROM MH-8 TO NEW
HH-9. SEE TS102 FOR MORE INFO.
4 NEW 2-4" CONDUIT, BORE FROM NEW HH-9 TO
NEW HH-10. SEE TS101 AND TS102 FOR MORE
INFO.
5 EXISTING 2-4" CONDUIT.
6 NEW 2-4" CONDUIT WITH INNER DUCT.
7 NEW 2-3" STUB UPS FROM BUILDING TO
PROPERTY LINE FOR FUTURE SERVICE. SEE
TS101 FOR MORE INFO.
8 NEW HANDHOLES (HH-9, 10, AND 11).
9 PROVIDE NEW 300 PR 22AWG CAT3 OUTDOOR
TELEPHONE CABLE WITH SERVICE ENTRANCE
PROTECTION AT BOTH ENDS, RUN CABLE IN
EXISTING 4" CONDUIT ABOVE CEILING IN B#1,
B#2, B#3, AND CONNECTION CORRIDOR TO
B#17 IT ROOM. COORDINATE LOCATION WITH
COR. TERMINATE TO 110 BLOCK. LABEL ALL
PORTS FOR CLC.
10 PROVIDE THE FOLLOWING:
a. 2-12 STRAND OUTDOOR/INDOOR TIGHT
BUFFERED ARMORED INTERLOCKED SINGLE
MODE FIBER (DATA-OS2).
b. 300 PR 22 AWG CAT3 TELEPHONE CABLE
WITH SERVICE ENTRANCE PROTECTION AT
EACH END.
c. 12 STRAND 62.5 MULTI MODE FIBER FOR
FIRE ALARM (OM1).
d. PROVIDE 2-14/2 SHIELDED INTERCOM/
PAGING OUTDOOR CABLE WITH S.E.P.
e. INSTALL CABLES ABOVE IN THE 4" CONDUITS
WITH INNERDUCT. SEE SHEET T-601 FOR MORE
INFO.
11 PROVIDE THE FOLLOWING:
a. 1-12 STRAND OUTDOOR/INDOOR TIGHT
BUFFERED ARMORED INTERLOCKED SINGLE
MODE FIBER (DATA-OS2).
b. 50 PR 22 AWG CAT5 TELEPHONE CABLE
WITH SERVICE ENTRANCE PROTECTION AT
EACH END.
c. 12 STRAND 62.5 MULTI MODE FIBER FOR
FIRE ALARM (OM1).
d. INSTALL CABLES ABOVE IN THE 4" CONDUITS
WITH INNERDUCT. SEE SHEET T-601 FOR MORE
INFO.
e. 12 - 16/2 SHIELDED OUTDOOR CABLE FOR
MEDICAL GAS ALARM. TERMINATE ON 110
BLOCK WITH SERVICE ENTRANCE
PROTECTION IN THE IT ROOM AND EXTEND
CABLES TO MEDICAL GAS ALARM PANEL. SEE
MECHANICAL/PLUMBING DRAWINGS FOR
EXACT LOCATIONS SEE T-601 FOR MORE INFO.
f. PROVIDE 1-14/2 SHIELDED INTERCOM/
PAGING OUTDOOR CABLE WITH S.E.P. AT BOTH
ENDS.
g. 12 STRAND 62-5 MULTI MODE FIBER FOR
BAS (OM1).
12 MEDICAL GAS ALARM PANEL.
13 PROVIDE 2-4" STUB UP (CAP FOR FUTURE
BUILDINGS).
14 PROVIDE 1-2" CONDUIT FOR FUTURE FIRE
ALARM.
15 PROVIDE 12 STRAND FIBER TO EXISTING FIRE
ALARM PANEL. VERIFY EXACT LOCATION.
16 PROVIDE 12 - 16/2 SHIELDED MEDICAL GAS
ALARM CABLES WITH SERVICE ENTRANCE
PROTECTION AT EACH END.
17 REMOVE EXISTING FIBER, COPPER, AND
CABLING FROM EXISTING 4" CONDUIT ALL THE
WAY BACK TO THE SOURCE. THIS CONDUIT IS
GOING TO BE USED FOR NEW CABLING SEE
NOTE 10.
18 10' CABLE LOOP FOR EACH CABLE ENTERING
AND EXISTING THE MANHOLES AND
HANDHOLES.
19 INTERCOM/PAGING (PAMN) EQUIPMENT.
20 PROVIDE 2-14/2 SHIELDED INTERCOM/PAGING
OUTDOOR CABLE WITH S.E.P. FOR CLC 201
AND CLC 202.
21 PROVIDE 12 STRAND 62.5 MULTI MODE FIBER
FOR BAC (OM1) AND TERMINATE IN
MECHANICAL ROOM (BUILDING 201 ROOM 135,
BUILDING 202 ROOM 134) ON FIBER OPTIC
WALL PATCH PANEL WITH ST CONNECTORS,
COORDINATE LOCATIONS WITH COR.
22 PROVIDE 12 STRAND FIBER TO NEW BAS
PATCH IN THE ATTACH OF BUILDING 17.
VERIFY EXACT LOCATION.
# SHEET KEY NOTES:
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
VA FORM 08-6231
on e ei gh th in ch o ne fo ot on e qu ar te r i nc h on e fo ot th re e ei gh th s in ch o ne fo ot on e ha lf in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot 6" on e in ch o ne fo ot 6" on e an d on e ha lf in ch es o ne fo ot 6" th re e in ch es o ne fo ot
6"
LEXINGTON VAMC, LEESTOWN DIVISION
2250 LEESTOWN ROAD
LEXINGTON, KY 40511
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER: Project Number Scale 15-584
A/E CONSTRUCT CONTINUING
CARE FACILITES, PHASE 1
596-332
SHEET NOTES:
WALL RATING LEGEND
1 HR FIRE RATED (FIRE BARRIER)
1 HR FIRE RATED (FIRE AND SMOKE
RESISTANT)
SMOKE COMPARTMENT (SMOKE
BARRIER, 1 HR FIRE RESISTANT)
AS INDICATED
FULLY SPRINKLERED
BID DOCUMENTS
E D
C B
A
2 3 4 5 6 7
E D
C B
A
1 2 3 4 5 6 7
Date Checked Drawn
# 201 & 202
10/22/18
3/
/2
:2 7:
A
M
T-601
TECHNOLOGY RISERS
9 9JKM JWB
A.
B.
C.
D.
SEE SHEET T-001 FOR ALTERNATE NOTES.
PROVIDE MINIMUM OF 25' OF CABLE IN EACH
COMMUNICATION MANHOLE AND HANDHOLE.
SUPPORT CABLE ON SUPPORT RACK.
ALL CABLE SPLICING SHALL BE WATER TIGHT.
CONDUIT (DUCT BANK) SHALL NOT BE
ENCASED IN CONCRETE.
3/16" = 1'-0"T-601
2 INTERCOM/ PAGING (PAMN) RACK LAYOUT
3/16" = 1'-0"T-601
3 TYPICAL INTERCOM/ PAGING (PAMN) WIRING DIAGRAM
ADDENDUM 4 03/06/19