This is an architectural amendment drawing for door, window, and frame specifications for a cardiac catheterization laboratory remodel project at VA Charleston Health Care System in Charleston, South Carolina. The drawing is submitted as part of the 100% contract documents for bidding phase, dated June 4, 2026 (Addendum #1), with the project number 534-CSI-714.

The document specifies three doors for the project: Door AA205A in the Cardiac Cath Lab (3'-0" wide by 7'-0" tall, 20-minute fire rating, flush solid core wood with lead lining of 1/16" thick lead), Door AA205AA in the Imaging Systems Component Room (3'-0" wide by 7'-0" tall, 20-minute fire rating, flush solid core wood), and Door COR2AA1 in the New Semi-Restricted Corridor (pair of solid core wood doors with narrow lite, 7'-0" wide by 7'-0" tall, 20-minute fire rating). All doors utilize hollow metal frames rated 4 7/8" with painted finish (HM-1/PNT). Hardware sets HW-1, HW-2, and HW-3 are specified with detailed components including hinges, closers, locksets, electronic panic hardware with 24 VDC power supplies, touchless actuators, access control readers, door contacts, and fail-secure operational controls. General notes establish standards for door thickness (1 3/4"), vision panel specifications, fire ratings, closures, and installation details. The architectural team includes Moon Tree, LLC as the architect and structural/civil engineer, and Bowman Foster & Associates, Inc as the MEP/technical engineer and fire protection engineer, with the facility noted as fully sprinklered.

View the file

Other files

File Type Posted
36C24726B0003 0005.docx DOCX document
36C24726B0003 0004.docx DOCX document
36C24726B0003 0003.docx DOCX document
Attachment 20 534-CSI-714 Brand Name J A Takeform Signs.pdf PDF
36C24726B0003 0002.docx DOCX document
Attachment 19 Site Visit Contractor Sign-In sheet.pdf PDF
Attachment 14 1-AD012R1.pdf PDF
Attachment 10 RFI Questions Responses.pdf PDF
Attachment 08 534-CSI-714 Brand Name J A Rauland Nurse Call.pdf PDF
Attachment 18 26-0604-Addendum 1 Narrative.pdf PDF
Attachment 17 283100-R1.pdf PDF
Attachment 16 088000-R1.pdf PDF
Attachment 09 534-CSI-714 Brand Name J A Siemens Desigo.pdf PDF
Attachment 07 534-CSI-714 Brand Name J A Gamewell FCI.pdf PDF
36C24726B0003 0001.docx DOCX document
Attachment 13 takeform signage supplement for CathLab2.pdf PDF
Attachment 12 Siemens Drawings REV 0 2314509R0 534-CSI-714 Cathlab.pdf PDF
Attachment 11 ICRA 534-CSI-714 Cathlab 1 Site Prep TAVRS R1.pdf PDF
Attachment 06 534-CSI-714 Brand Name J A Fire Sprinkler Dampers.pdf PDF
S02 36C24726B0003_1.pdf PDF
Attachment 02 534-CSI-714 Bid Drawings - REV 3-27-26.pdf PDF
Attachment 01 534-CSI-714 Specifications.pdf PDF
Attachment 05 Experience Modification Rate Form.pdf PDF
Attachment 04 Limitations on Subcontracting.pdf PDF
Attachment 03 Wage Determination.pdf PDF
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

HOLLOW METAL

FRAME

2" 3'-0" 2"

B

FLUSH - SOLID

CORE WOOD

(FINISH = WV-1)

F

6" 4" 4"

6"

7' -0

2"

2" 6'-0" 2"

PAIR OF SOLID CORE WOOD,

NARROW LITE

(FINISH = WV-1)

PAIR-NL

2" 4'-8" 2"

3' -6

3'

-8

LEAD LINED VIEW WINDOW

MINIMUM LEAD EQUIVALENCE = 1/16" LEAD

BL-1

HOLLOW METAL

FRAME

HOLLOW METAL

FRAME

AC

HARDWARE SET

HW-1

3 HINGES A8112 4.5" X 4.5" 652

1 LOCKSET F07 45H-7D15H PATD 630AM

1 CLOSER C02211 689

1 KICK PLATE J102 10"X2" LDW B4E CS 630

1 WALL BUMPER L02101 630

1 GASKETING R0Y154

HW-2

6 HINGE 5BB1HW HT 4.5 X 4.5 652

2 POWER TRANSFER EPT10 CON 689

1 ELEC PANIC HARDWARE RX-QEL-9827-EO-LBR-CON 24 VDC 626

1 ELEC PANIC HARDWARE RX-QEL-9827-L-NL-LBR-06-CON 24 VDC 626

1 INTERFACE BOX JB7

1 RIM CYLINDER 1E72 626

1 SFIC CORE TO MATCH EXISTING SYSTEM 626

1 SURF. AUTO OPERATOR 9553 REG2 LESS TRACK AS REQ (120/240 VAC) ANCLR

1 SWITCH 8310-806R

2 EA ACTUATOR, TOUCHLESS 8310-810D 630

2 EA MOUNT BOX 8310-867F

1 EA SAFETY SENSOR 8310-879

2 EA MOP PLATE 8400 6" X 1 1/2" LDW B-CS 630

2 EA ARMOR PLATE 8402 32" X 1" LDW B-CS 630

1 EA GASKETING 488SBK PSA BK

1 EA WEATHERSTRIPPING 8217SBK PSA BK

2 EA WIRE HARNESS CON-P (LENGTH AS REQUIRED)

2 EA WIRE HARNESS CON-6W

1 EA MULTITECH READER BY SECURITY INTEGRATOR BLK

2 EA DOOR CONTACT BY SECURITY INTEGRATOR

"DOOR AND FRAME TO BE PREPPED FOR DOOR CONTACT." BLK

1 POWER SUPPLY PS904 900-4RL-FA KL900 120/240 VAC

1 PROVIDE FACTORY POINT TO POINT WIRING DIAGRAMS

OPERATIONAL DESCRIPTION:

BOTH DOORS NORMALLY CLOSED AND SECURE AT ALL TIME. PULL SIDE WAVE ACTUATOR DISABLAED.

PUSH SIDE WAVE ACTUATOR ALWAYS ENABLED. ACCESS BY KEY OVERRIDE, VALID CREDENTIAL AT READER OR SIGNAL FROM ACCESS CONTROL SYSTEM. PRESENTING VALID CREDENTIAL ENABLES PULL

SIDE WAVE ACTUATOR, BOTH WAVE ACTUATORS INITIATE LATCH RETRACTION AND AUTOMATIC

OPERATION OF BOTH DOOR LEAVES SIMULTANEOUSLY. ENTRY BY PULLING DOOR OPEN OR OUTSIDE WAVE ACTUATOR. FREE EGRESS AT ALL TIMES BY PUSHING DOORS OPEN OR WAVE ACTUATOR. DOORS REMAIN SECURE WITH LOSS OF POWER OR ACTIVATION OF FIRE ALARM. (FAIL SECURE) DOORS

MONITORED BY ACCESS CONTROL

HW-3

2 HINGE 5BB1 HT 4.5 X 4.5 652

1 ELECTRIC HINGE 5BB1 HT 4.5 X 4.5 CON TW8 652

1 FAIL SECURE LOCK 45HW-7-DEU-15-S-IDH 626AM

1 SFIC CORE TO MATCH EXISTING SYSTEM 626

1 SURFACE CLOSER 4040XP 689

1 KICK PLATE 8400 10" X 1" LDW B-CS 630

1 MOP PLATE 8400 6" X 1" LDW B-CS 630

1 WALL STOP WS406/407CCV 630

3 SILENCER SR64/65 AS REQ'D GRY

1 MULTITECH READER BY SECURITY INTEGRATOR BLK

1 DOOR CONTACT BY SECURITY INTEGRATOR

"DOOR AND FRAME TO BE PREPPED FOR DOOR CONTACT." BLK

1 POWER SUPPLY BY SECURITY INTEGRATOR LGR

OPERATIONAL DESCRIPTION:

DOOR NORMALLY CLOSED AND SECURE. ACCESS BY KEY OVERRIDE, VALID CREDENTIAL AT READER OR

SIGNAL FROM ACCESS CONTROL SYSTEM. FREE EGRESS AT ALL TIMES.

DOOR REMAINS SECURE WITH LOSS OF POWER OR ACTIVATION OF FIRE ALARM. (FAIL SECURE)

DOOR MONITORED BY ACCESS CONTROL.

GENERAL DOOR NOTES

1. ALL DOORS SHALL BE 1 3/4" THICK UNLESS NOTED OTHERWISE.

2. REFER TO SPECIFICATIONS MANUAL FOR ADDITIONAL DETAILS ON HARDWARE SETS.

3. ALL DOORS SHALL HAVE NO FIRE RATING UNLESS NOTED OTHERWISE.

4. ALL RATED DOORS SHALL HAVE A FRMAE OF EQUAL RATING UNLESS NOTED OTHERWISE.

5. ALL RATED DOORS SHALL HAVE CLOSURES UNLESS NOTED OTHERWISE.

6. ALL VISION PANELS IN RATED DOORS SHALL BE 5/16" CLEAR CERAMIC FIRE GLASS UNLESS NOTED

OTHERWISE.

7. ALL RATED DOORS WITH VISION PANELS THAT HAVE A RATING OF UNDER 1 HOUR SHALL NOT EXCEED

THE ANUFACTURERS TESTED ASSEMBLY VISION PANELS SIZE.

8. ALL RATED DOORS WITH VISION PANELS THAT HAVE A RATING OF 1 HOUR OF GREATER SHALL NOT

HAVE GLAZING EXCEEDIGN 100 SQUARE INCHES.

9. ALL INTERIOR VISION PANELS SHALL BE 1/4" TEMPERED GLASS UNLESS NOTED OTHERWISE.

10. PROVIDE VINYL REDUCER STRIPS AT ALL CARPET TO LINOLEUM/EPOXY TRANSITIONS UNLESS NOTED

OTHERWISE.

11. ALL DOORS SHALL HAVE A MAXIMUM OF A 3/4" UNDERCUT UNLESS NOTED OTHERWISE. REFER TO

TRANSITION DETAILS FOR ADDITIONAL INFORMATION WHERE APPLICABLE.

12. REFER TO ENTIRE AS700 SERIES FOR ADDITIONAL INFORMATION AND DETAILS FOR DOORS

13. ALL DOUBLE LEAF DOORS TO RECEIEVE EQUAL LEAF SIZES, UNLESS NOTED OTHERWISE.

THE FOLLOWING SETS OF HARDWARE CORRESPOND TO HARDWARE SYMBOLS SHOWN ON DRAWINGS

ONLY THOSE HARDWARE SETS THAT ARE SHOWN ON DRAWINGS WILL BE REQUIRED. DISREGARD

HARDWARE SETS LISTED IN SPECIFICATIONS BUT NOT SHOWN ON DRAWINGS.

THE NUMBERS SHOWN IN THE FOLLOWING SETS COME FROM BHMA STANDARDS.

GYPSUM WALL BOARD

METAL STUD

SEALANT, COLOR TO

MATCH ADJACENT WALL

HOLLOW METAL

DOOR AND FRAME

METAL STUD

SEALANT, COLOR TO

MATCH ADJACENT WALL

LEAD LINES HOLLOW

METAL DOOR AND/OR

FRAME

LEAD LINED GYSPUM WALL BOARD

@ LEAD LINED DOOR HEAD

JAMB (SIM)

@STANDARD DOOR HEAD

JAMB (SIM)

METAL STUD

SEALANT, COLOR TO

MATCH ADJACENT WALL

LEAD LINES HOLLOW

METAL DOOR AND/OR

FRAME

LEAD LINED GYSPUM WALL BOARD

@ LEAD LINED

BORROWED LITE HEAD

JAMB (SIM)

A B C

U.N.O.

4" TYP.

GYPSUM WALL BOARD

METAL STUD

SEALANT, COLOR TO

MATCH ADJACENT WALL

HOLLOW METAL

FRAME

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

VA Health Care System Approval:

Revision: Date:

ARCHITECT:

U.S. Department of Veteran Affairs

MOON TREE, LLC

1808 Deep Creek Rd Oklahoma City, OK 73131

(405) 509-5254

STRUCTURAL / CIVIL

ENGINEER

MOON TREE, LLC

1808 DEEP CREEK ROAD

OKLAHOMA CITY, OK 73131

(405) 509-5254

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

FIRE PROTECTION

ENGINEER

F U

L L

Y S

P R

IN

K

L E

R E

D

BOWMAN FOSTER & ASSOCIATES, INC

6353 CENTER DRIVE, #101

NORFOLK, VA 23502

(757) 466-7400

/4

/2

:1

:3

A

M

1 Addendum #1 6/04/2026 AE105R1

DOOR SCHEDULE, WINDOW SCHEDULE

AND DETAILS

JDA

16 57

DW

PROJECT SUBMISSION PHASE: 100% CONTRACT DOCS FOR BIDDING

CARDIAC CATH LAB REMODEL

03/12/2026

534-CSI-714

VA CHARLESTON HEALTH CARE

109 BEE STREET

CHARLESTON, SC 29401 1-

DOOR SCHEDULE

MARK ROOM NAME

DOOR PANEL WALL

THICKNESS

FRAME HARDWARE

SET

COMMENTS

TYPE MATERIAL WIDTH HEIGHT FIRE RATING TYPE FINISH

AA205A CARDIAC CATH LAB 1 F WD 3'-0" 7'-0" 20 MIN 4 7/8" HM-1 HM-1/PNT HW-1 LEAD LINED = 1/16" THICK LEAD

AA205AA

IMAGING SYSTEMS

COMPONENT ROOM (ICR)

F WD 3'-0" 7'-0" 20 MIN 4 7/8" HM-1 HM-1/PNT HW-3

COR2AA1

NEW SEMI-RESTRICTED

CORRIDOR

PAIR-NL WD 7'-0" 7'-0" 20 MIN 4 7/8" HM-1 HM-1/PNT HW-2

Scale: 1/4" = 1'-0"

DOOR, LITE AND FRAME TYPES

Scale: 3" = 1'-0"

TYP. HM HEAD DETAILS

Scale: 3" = 1'-0"

TYP. HM JAMB DETAIL WITH ADJ. WALL

AMENDMENT DRAWING

Sheets
AE105R1 - DOOR SCHEDULE, WINDOW SCHEDULE AND DETAILS