08 - Drawings Plumbing.pdf

PDF 8 MB Posted

Attached to
Y1DA--9th Floor MH Renovation WBVAMC
Solicitation number
36C24425B0018
Issued by

About this file

The provided file is a set of detailed plumbing engineering drawings for the renovation of the 9th Floor Mental Health unit at the Wilkes-Barre VA Medical Center. The comprehensive drawing set includes demolition plans, domestic water plans, drain-waste-vent plans, and enlarged detailed plans for the 9th floor, 8th floor, and warehouse areas. The drawings cover multiple technical aspects including plumbing fixtures, piping systems, risers, water connections, drainage routes, and specific technical details for domestic cold water, hot water, sanitary sewer, and vent systems.

The drawings specify precise technical requirements for plumbing infrastructure, including pipe sizes, fixture locations, riser configurations, and installation notes. Key technical specifications include overhead and underground piping routes, connections to existing systems, trap primer requirements, water management controls, and specific installation guidelines. The documents are part of a 100% Construction Documents set dated 04/18/2023, prepared for the VA Medical Center's renovation project with the project number 693-19-106, and are designed to provide comprehensive technical guidance for the plumbing renovation of the mental health floor.

View the file

Other files

File Type Posted
36C24425B0018 0001.docx DOCX document
19a - RFI Responses 2.pdf PDF
19b - RFI Responses 3.pdf PDF
16 - Wilkes Barre PA Campus Site Plan Crane Locations.pdf PDF
21 - WD PA20250095 M4 03-21-2025.pdf PDF
19 - RFI Responses.pdf PDF
18a - Safety Health During Construction Policy 18S-15-346.pdf PDF
20 - Brand Name JA 9F MHU 20241804.pdf PDF
18 - Safety VA Directive 7715 Rev 092023.pdf PDF
22 - 852.219-75 MUST SIGN AND RETURN WITH BID.pdf PDF
36C24425B0018_4.docx DOCX document
17 - Noise and Vibration Control.pdf PDF
12a - ICRA Introductory Information and Instructions.pdf PDF
36C24425B0018_3.docx DOCX document
15 - M P Cut Sheets 693 19 106.pdf PDF
12b - G-009 ICRA.pdf PDF
13 - Structural Calcs 693 19 106 .pdf PDF
14 - Estimate - 693 19 106 M P Calcs.pdf PDF
11 - Drawing Revisions.pdf PDF
12c - 17-H4 ICRA.pdf PDF
12e - 01-A4 ICRA.pdf PDF
12d - 01-A3 ICRA.pdf PDF
12 - ICRA Memo.pdf PDF
36C24425B0018_2.docx DOCX document
09 - Drawings Mechanical.pdf PDF
07 - Drawings General V2.pdf PDF
10 - Drawings Electrical.pdf PDF
06 - Drawings Fire Alarm and Protection.pdf PDF
10a - 17-E43 Revisions 2024-05-30.pdf PDF
03 - Drawings Hazardous Materials.pdf PDF
36C24425B0018 IFB Solicitation.pdf PDF
05a - Drawings Architectural 2.pdf PDF
01c - 107316 Aluminum Canopy System.pdf PDF
01d - 220523 Gen Duty Valves Plumb Piping.pdf PDF
36C24425B0018_1.docx DOCX document
05b - Drawings Architectural 3.pdf PDF
02 - Drawings General V1.pdf PDF
05c - A15 Revisions 2024-05-30.pdf PDF
05 - Drawings Architectural 1.pdf PDF
04 - Drawings Structural.pdf PDF
01 - Specifications Project 693-19-106 .pdf PDF
01b - 087100 Door Hardware.pdf PDF
01a - 066116 Solid Surfacing Fabrication.pdf PDF
01e - 221100 Fac Water Distr.pdf PDF
36C24425B0018.docx DOCX document
Show all 45

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AREA OF WORK

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

C :\R ev it

\1 9.

_A

R C

H _R

_z m ill er 4N

R T

Z .r vt 4/

/2

4:

:4

P M

01-12

COVER - VOLUME 2 RENOVATE 9TH FLOOR MENTAL

HEALTH

1111 EAST END BLVD, WILKES-BARRE, PA 18711

693-19-106

01 & 17

04/18/2023 DR ZAM

100% CONSTRUCTION

DOCUMENTS

VEG 19.25

WILKES-BARRE VA MEDICAL CENTER

1111 EAST END BLVD, WILKES-BARRE, PA 18711

VAMC PROJECT #: 693-19-106

RENOVATE 9TH FLOOR MENTAL HEALTH

DWG 01 of 01 F

IN

A L

D R

A W

IN

G

S S

U B

M

IT

T A

L

SHEET

NUMBER SHEET NAME

GENERAL

01-12 COVER - VOLUME 2

PLUMBING

01-P1 PLUMBING ABBREVIATIONS, SYMBOLS, & LEGENDS

01-P2 EQUIPMENT & FIXTURE SCHEDULES

01-P3 DEMOLITION PLAN - 8TH FLOOR WEST

01-P4 DEMOLITION PLAN - 8TH FLOOR CENTER

01-P5 DEMOLITION PLAN - 8TH FLOOR EAST

01-P6 DEMOLITION PLAN - 9TH FLOOR WEST

01-P7 DEMOLITION PLAN - 9TH FLOOR CENTER

01-P8 DEMOLITION PLAN - 9TH FLOOR EAST

17-P9 DEMOLITION PLAN - WAREHOUSE

01-P10 DOMESTIC WATER PLAN - 9TH FLOOR WEST

01-P11 DOMESTIC WATER PLAN - 9TH FLOOR CENTER

01-P12 DOMESTIC WATER PLAN - 9TH FLOOR EAST

17-P13 DOMESTIC WATER PLAN - WAREHOUSE

01-P14 DOMESTIC WATER ISOMETRIC

01-P15 DRAIN-WASTE-VENT PLAN - 8TH FLOOR WEST

01-P16 DRAIN-WASTE-VENT PLAN - 8TH FLOOR CENTER

01-P17 DRAIN-WASTE-VENT PLAN - 8TH FLOOR EAST

01-P18 DRAIN-WASTE-VENT PLAN - 9TH FLOOR WEST

01-P19 DRAIN-WASTE-VENT PLAN - 9TH FLOOR CENTER

01-P20 DRAIN-WASTE-VENT PLAN - 9TH FLOOR EAST

17-P21 DRAIN-WASTE-VENT PLAN - WAREHOUSE

01-P22 DRAIN-WASTE-VENT ISOMETRIC

01-P23 ENLARGED DOMESTIC PLANS

01-P24 ENLARGED DOMESTIC PLANS

MECHANICAL

01-M1 MECHANICAL ABBREVIATIONS & NOTES

01-M2 MECHANICAL SYMBOLS

17-M3 EQUIPMENT SCHEDULES - WAREHOUSE

01-M4 EQUIPMENT SCHEDULES - 9TH FLOOR

01-M5 EQUIPMENT SCHEDULES - 9TH FLOOR

01-M6 DEMOLITION PLAN - 9TH FLOOR WEST

01-M7 DEMOLITION PLAN - 9TH FLOOR CENTER

01-M8 DEMOLITION PLAN - 9TH FLOOR EAST

17-M9 DEMOLITION PLAN - WAREHOUSE

01-M10 HVAC PLAN - 9TH FLOOR WEST

01-M11 HVAC PLAN - 9TH FLOOR CENTER

01-M12 HVAC PLAN - 9TH FLOOR EAST

17-M13 HVAC PLAN - WAREHOUSE

17-M14 HVAC PLAN - WAREHOUSE ROOF

01-M15 PIPING PLAN - 9TH FLOOR WEST

01-M16 PIPING PLAN - 9TH FLOOR CENTER

01-M17 PIPING PLAN - 9TH FLOOR EAST

17-M18 PIPING PLAN - WAREHOUSE

17-M19 PIPING PLAN - WAREHOUSE ROOF

01-M20 CONTROLS & INSTRUMENTATION PLAN - 9TH FLOOR WEST

01-M21 CONTROLS & INSTRUMENTATION PLAN - 9TH FLOOR CENTER

01-M22 CONTROLS & INSTRUMENTATION PLAN - 9TH FLOOR EAST

17-M23 CONTROLS & INSTRUMENTATION PLAN - WAREHOUSE

17-M24 CONTROLS & INSTRUMENTATION PLAN - WAREHOUSE ROOF

01-M25 CONTROLS & INSTRUMENTATION DETAILS

01-M26 CONTROLS & INSTRUMENTATION DETAILS

01-M27 CONTROLS & INSTRUMENTATION DETAILS

01-M28 ENLARGED SECTIONS - 9TH FLOOR

01-M29 TYPICAL PATIENT ROOM - 9TH FLOOR

01-M30 ENLARGED PLANS - 9TH FLOOR

01-M31 ENLARGED PLANS - 9TH FLOOR ROOF

01-M32 TYPICAL DETAILS

01-M33 TYPICAL DETAILS

01-M34 TYPICAL DETAILS

SHEET INDEX - VOLUME 2 OF 2RENDERED IMAGEAREA OF WORK

N o rt h

9TH FLOOR

WAREHOUSE

SHEET

NUMBER SHEET NAME

ELECTRICAL

01-E1 ELECTRICAL ABBREVIATIONS AND GENERAL NOTES

01-E2 ELECTRICAL SYMBOLS

01-E3 DEMOLITION PLAN - 9TH FLOOR WEST

01-E4 DEMOLITION PLAN - 9TH FLOOR CENTER

01-E5 DEMOLITION PLAN - 9TH FLOOR EAST

17-E6 DEMOLITION PLAN - WAREHOUSE

01-E7 DEMOLITION RCP - 9TH FLOOR WEST

01-E8 DEMOLITION RCP - 9TH FLOOR CENTER

01-E9 DEMOLITION RCP - 9TH FLOOR EAST

17-E10 DEMOLITION RCP - WAREHOUSE

01-E11 LIGHTING RCP - 9TH FLOOR WEST

01-E12 LIGHTING RCP - 9TH FLOOR CENTER

01-E13 LIGHTING RCP - 9TH FLOOR EAST

17-E14 LIGHTING RCP - WAREHOUSE

01-E15 LIGHTING CONTROL RCP - 9TH FLOOR WEST

01-E16 LIGHTING CONTROL RCP - 9TH FLOOR CENTER

01-E17 LIGHTING CONTROL RCP - 9TH FLOOR EAST

17-E18 LIGHTING CONTROL RCP - WAREHOUSE

01-E19 LIGHTING FIXTURE SCHEDULES

01-E20 LIGHTING CONTROL SCHEDULES

01-E21 LIGHTING CONTROL PANEL SCHEDULES

01-E22 DIGITAL LOW VOLTAGE LIGHTING CONTROL WIRING DIAGRAMS

01-E23 ANALOG LINE VOLTAGE LIGHTING CONTROL WIRING DIAGRAMS

01-E24 NETWORKED LIGHTING CONTROL DETAILS

01-E25 POWER PLAN - 9TH FLOOR WEST

01-E26 POWER PLAN - 9TH FLOOR CENTER

01-E27 POWER PLAN - 9TH FLOOR EAST

17-E28 POWER PLAN - WAREHOUSE

17-E29 POWER PLAN - WAREHOUSE ROOF

01-E30 EQUIPMENT SCHEDULE

01-E31 PANEL SCHEDULES - 9TH FLOOR

01-E32 PANEL SCHEDULES - 9TH FLOOR

01-E33 PANEL SCHEDULES - 9TH FLOOR

17-E34 PANEL SCHEDULES - WAREHOUSE

01-E35 SINGLE LINE DIAGRAM EMERGENCY

01-E36 SINGLE LINE DIAGRAM NORMAL

01-E37 ELECTRICAL RISER DIAGRAM

01-E38 SINGLE LINE DIAGRAM

01-E39 ONE-LINE DIAGRAM

01-E40 TELECOM PLAN - 9TH FLOOR WEST

01-E41 TELECOM PLAN - 9TH FLOOR CENTER

01-E42 TELECOM PLAN - 9TH FLOOR EAST

17-E43 TELECOM PLAN - WAREHOUSE

01-E44 NURSE CALL PLAN - 9TH FLOOR WEST

01-E45 NURSE CALL PLAN - 9TH FLOOR CENTER

01-E46 NURSE CALL PLAN - 9TH FLOOR EAST

01-E47 SECURITY PLAN - 9TH FLOOR WEST

01-E48 SECURITY PLAN - 9TH FLOOR CENTER

01-E49 SECURITY PLAN - 9TH FLOOR EAST

17-E50 SECURITY PLAN - WAREHOUSE

01-E51 ENLARGED TELECOM TR ROOM

17-E52 ENLARGED TELECOM TR ROOM - WAREHOUSE

01-E53 TELECOM DETAILS

01-E54 TYPICAL DETAILS

01-E55 TYPICAL DETAILS

0 100% CONSTRUCTION DOCUMENTS 04/18/2023

ZMiller Image

GENERAL PLUMBING SYMBOLS

DIRECTION OF PIPE PITCH (DOWN)

DIRECTION OF FLOW

GUIDE

ANCHOR

REDUCER OR INCREASER

ECCENTRIC REDUCER

TOP CONNECTION, 45° OR 90°

BOTTOM CONNECTION, 45° OR 90°

SIDE CONNECTION

CAPPED OUTLET

RISE OR DROP IN PIPE

UNION

PIPE UP

PIPE DOWN

POINT OF CONNECTION BETWEEN NEW

AND EXISTING WORK

LIMIT OF DEMOLITION

INVERTED BUCKET TRAP SET INCLUDING

PIPING ACCESSORIES

FLOAT & THERMOSTATIC TRAP SET

INCLUDING PIPING ACCESSORIES

STRAINER

THERMOMETER

PRESSURE GAGE

FLOW ELEMENT

WALL CLEAN OUT

CLEAN OUT

HOSE BIBB, FAUCET HEAD, SHOWER HEAD

WATER HAMMER ARRESTOR (PLAN VIEW)

FE

CO

MA

MV

LA

LV

OA

IA

D

SS

SD

SD

TWR

DWS

DWR

TWS

SS

SCW

FCW

NO

O

N

NG

NG

FOD

FOS

FOR

FOV

PLUMBING PIPING SYMBOLS

DOMESTIC COLD WATER, COLD WATER

DOMESTIC HOT WATER, HOT WATER

DOMESTIC HOT WATER RETURN

MEDICAL AIR

MEDICAL VACUUM

LABORATORY AIR

LABORATORY VACUUM

ORAL EVACUATION

INDUSTRIAL AIR

DRAIN

VENT (SANITARY)

SOIL, WASTE, OR SANITARY SEWER

SANITARY SEWER, BELOW GRADE

STORM WATER

STORM WATER, BELOW GRADE

SOFTEN COLD WATER

FILTERED COLD WATER

DRINKING WATER SUPPLY

DRINKING WATER RETURN

TEMPERED WATER RETURN

TEMPERED WATER SUPPLY

NITROUS OXIDE

OXYGEN

NITROGEN

NATURAL GAS

NATURAL GAS, BELOW GRADE

FUEL OIL DISCHARGE

FUEL OIL SUPPLY

FUEL OIL VENT

FUEL OIL RETURN

REAGENT WATER

REAGENT WATER RETURN

CORROSION RESISTANT SANITARY SEWER

CORROSION RESISTANT VENT (SANITARY)

GREASE WASTE

NEW PIPING

EXISTING PIPING

PIPE TO BE DEMOLISHED

FIXTURE OR EQUIPMENT TO BE DEMOLISHED

AV

PLUMBING VALVE SYMBOLS

GENERIC VALVE (REF SPEC FOR TYPE)

GENERIC VALVE WITH 3/4" HOSE ADAPTER

CHECK VALVE

ANGLE GLOBE VALVE

BUTTERFLY VALVE

BALL VALVE

CONTROL VALVE

THREE-WAY CONTROL VALVE

PRESSURE REGULATING VALVE

AUTOMATIC FLOW CONTROL VALVE

PRESSURE RELIEF VALVE

MANUAL AIR VENT

TEST PLUG (PRESSURE/TEMPERATURE)

AUTOMATIC AIR VENT

THERMOSTATIC MIXING VALVE

IN LINE FILTER

RWR

RW

V CRP

SS CRP

GW

P-###

H4

H7

A

DETAIL NUMBER

DRAWING NUMBER WHERE SHOWN

SECTION LETTER

TYPICAL FIXTURE NUMBER

DRAWING NUMBER WHERE DRAWN

DRAWING SYMBOLS

NEW FIXTURE/EQUIPMENT (SHAPE VARIES, REF: SYMBOLS,

TAGS, & NOTES. SCHEDULED ITEMS ARE NEW UNO)

(E) EXISTING COMPONENT

(X) DEMOLISHED COMPONENT

26-SF 3

TYPICAL EQUIPMENT NUMBER

## GENERAL EQUIPMENT FURNISHED BY OTHERS; REF SHEET

01-P2 FOR CONNECTION SCHEDULE

DOUBLE-LINED VALVE

(REFER TO SPECS FOR TYPE)

PLUMBING GENERAL NOTES

A. PIPING IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN A FURRED

CHASE OR ABOVE THE CEILING. REF SPECIFICATION SECTION 22 05 11.

B. REFER TO ARCHITECTURAL CEILING PLANS FOR CEILING TYPES IN EACH

SPACE. MINIMUM 18"X18" ACCESS PANELS ARE REQUIRED IN HARD CEILINGS

FOR VALVES, TRAPS, DAMPERS, CLEANOUTS, CONTROLS, AND SO FORTH.

COORDINATE FINAL LOCATIONS IN THE FIELD FOR BEST ACCESS. REF

SPECIFICATION 08 31 13.

C. PROVIDE ACOUSTICAL SEALANT PER SPECIFICATION SECTION 07 92 00 AT

PIPE PENETRATIONS THROUGH SOUND RATED PARTITIONS.

D. SUBMIT COMPLETE CONSOLIDATED AND COORDINATED SHOP DRAWINGS

FOR NEW SYSTEMS, AND FOR EXISTING SYSTEMS THAT ARE IN THE SAME

AREAS. DO NOT INSTALL EQUIPMENT FOUNDATIONS, EQUIPMENT, OR PIPING

UNTIL COORDINATION/SHOP DRAWINGS HAVE BEEN APPROVED. REF

SPECIFICATION SECTIONS 01 33 23 AND 22 05 11.

PLUMBING ASCE 7-16 NONSTRUCTURAL SEISMIC

RESTRAINT AND ANCHORAGE NOTES

PROVIDE AND DESIGN SEISMIC BRACING FOR PLUMBING EQUIPMENT, PIPING

AND DUCTWORK IN ACCORDANCE WITH SPECIFICATION SECTION 13 05 41

SEISMIC RESTRAINT REQUIREMENTS FOR NONSTRUCTURAL COMPONENTS.

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

C :\U se rs

\J D ez m an \D oc um en ts

\1 9.

_M

E C

H -P

LU

M

_R

_J D ez m an .rv t 4/

/2

1:

:3

P M

01-P1

PLUMBING ABBREVIATIONS,

SYMBOLS, & LEGENDS

RENOVATE 9TH FLOOR MENTAL

HEALTH

1111 EAST END BLVD, WILKES-BARRE, PA 18711

693-19-106

01 & 17

04/18/2023 MB RT

100% CONSTRUCTION

DOCUMENTS

VEG 19.25 DWG 1 of 24 F

IN

A L

D R

A W

IN

G

S U

B M

IT

T

A L

A

A/E ARCHITECT/ENGINEER

AD AREA DRAIN/ACCESS DOOR

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AG AIR GAP

AS AUTOMATIC SPRINKLER

ASD ADJUSTABLE SPEED DRIVES

ASD AUTOMATIC SPRINKLER DRAIN

ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATION,

AND AIR CONDITIONING ENGINEERS

ASME AMERICAN SOCIETY OF MECHANCIAL ENGINEERS

ASPE AMERICAN SOCIETY OF PLUMBING ENGINEERS

AV ACID VENT

AW ACID WASTE

B

BAS BUILDING AUTOMATION SYSTEM

BFP REDUCED PRESSURE BACKFLOW PREVENTER

BHP BREAK HORSEPOWER

BOD BASIS OF DESIGN

BSP BLACK STEEL PIPE

BT BATHTUB

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

C

CA COMPRESSED AIR

CFM CUBIC FEET PER MINUTE

CGA COMPRESSED GAS ASSOCATION

CI CAST IRON

CO CLEANOUT

CRP CORROSION RESISTANT PIPE

CS CLINICAL SINK

CV CONTROL VALVE

D

DCW DOMESTIC COLD WATER

DEMO DEMOLISH

DFU DRAINAGE FIXTURE UNITS

DHW DOMESTIC HOT WATER

DHWR DOMESTIC HOT WATER RETURN

DI DEIONIZED WATER

DIV DIVISION

DN DOWN

DOE DEPARTMENT OF ENERGY

DS DOWNSPOUT

DW DISHWASHER

DWG DRAWING

DWH DOMESTIC WATER HEATER

DWR DRINKING WATER RETURN

DWS DRINKING WATER SUPPLY

DWV DRAIN WASTE VENT

E

EL ELEVATION

EMCS ENERGY MANAGEMENT CONTROL SYSTEM

EPA ENVIRONMENTAL PROTECTION AGENCY

EPACT ENERGY POLICY ACT

ESC ESCUTCHEON

ESH EMERGENCY SHOWER

ET EXPANSION TANK

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EWS EYE WASH STATION

EWS/SH EYE WASH/DRENCH SHOWER

EX EXISTING

F

F FARENHEIT

FCO FLOOR CLEANOUT

FCW FILTERED COLD WATER

FD FLOOR DRAIN

FDC FIRE DEPARTMENT (HOSE) CONNECTION

FM FLOW METER

FOP FUEL OIL PUMP

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

FOV FUEL OIL VENT

FS FLOOR SINK

FS FLOW SWITCH

FU FIXTURE UNITS

G

GAL GALLON

GCO GRADE CLEANOUT

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GPR GAS PRESSURE REGULATOR

GRS GAS REGULATOR STATION

GT GREASE TRAP

GVTR GAS VENT THROUGH ROOF

GWB GYPSUM WALL BOARD

GWH GAS FIRED WATER HEATER

PLUMBING ABBREVIATIONS

H

HB HOSE BIB

HD HUB DRAIN

HP HORSEPOWER

HR HR

HS HAND SINK

HST HOT WATER STORAGE TANK (DOMESTIC)

HWB HOT WATER BOILER

HWCP HOT WATER CIRCULATING PUMP

HWP HOT WATER PUMP

HX HEAT EXCHANGER

HYD HYDRANT

I

ICW INDUSTRIAL COLD WATER

ID INSIDE DIAMETER

IE INVERT ELEVATION

IHW INDUSTRIAL HOT WATER

INV INVERT

IPC INTERNATIONAL PLUMBING CODE

IRW IRRIGATION WATER

IW INDIRECT WASTE

IWH INSTANTANEOUS WATER HEATER

IWR INDUSTRIAL WATER RETURN

IWS INDUSTRIAL WATER SUPPLY

K

KW KILOWATT

KWH KILOWATT-HOUR

L

LA LABORATORY AIR

LAV LAVATORY

LB POUND

LCW LABORATORY COLD WATER

LHW LABORATORY HOT WATER

LNG LIQUID NATURAL GAS

LOX LIQUID OXYGEN

LV LABORATORY VACUUM

LW LOW WATER

M

M METER

MA MEDICAL AIR

MAV MANUAL AIR VENT

MBH 1000 BTUH

MED MEDICAL

MER MECHANICAL EQUIPMENT ROOM

MFR MANUFACTURER

MH MANHOLE

MOU MEMORANDUM OF UNDERSTANDING

MSB MOP SERVICE BASIN

MV MEDICAL VACUUM

N

N2 NITROGEN

N2O NITROUS OXIDE

NC NORMALLY CLOSED

NG NATURAL GAS

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NOM NOMINAL

NPS NOMINAL PIPE SIZE

NPW NON POTABLE WATER

NTS NOT TO SCALE

O

O2 OXYGEN

OC ON CENTER

OD OUTSIDE DIAMETER

OFD OVERFLOW DRAIN

OH OVER HEAD

OR OPERATING ROOM

OVFL OVERFLOW

P

P&ID PROCESS & INSTRUMENTATION DIAGRAM

PB PUSH BUTTON

PD PRESSURE DROP OR DIFFERENCE

PDI PLUMBING AND DRAINAGE INSTITUTE

PG PRESSURE GAUGE

PH PHASE

PLBG PLUMBING

PLUM PLUMBING

PP PLUMBING PUMP

PPM PARTS PER MILLION

PRS PRESSURE REDUCING STATION

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH ABSOLUTE

PSIG POUNDS PER SQUARE INCH GAGE

PTRV PRESSURE TEMPERATURE RELIEF VALVE

PW POTABLE WATER

R

RD ROOF DRAIN

RDL ROOF DRAIN LEADER

REF REFERENCE OR REFER TO

RH ROOF HYDRANT

RL ROOF LEADER

RO REVERSE OSMOSIS WATER

RP RECIRCULATION PUMP

RPZA REDUCED PRESSURE BACKFLOW PREVENTION

ASSEMBLY

RW REAGENT WATER

RWL RAIN WATER LEADER

RWR REAGENT WATER RETURN

S

SAN SANITARY SEWER

SCFM STANDARD CUBIC FEET PER MINUTE

SCW SOFTENED COLD WATER

SDMH STORM DRAIN MANHOLE

SIM SIMILAR

SMACNA SHEET METAL AND AIR CONDITIONING

CONTRACTORS NATIONAL ASSOCATION

SMH SANITARY MANHOLE

SP SUMP PUMP

SPR SPRINKLER LINE

SQFT/SF SQUARE FEET

SS SANITARY SEWER

SST STAINLESS STEEL

ST STORAGE TANK

SW STORM WATER

T

TCV TEMPERATURE CONTROL VALVE

TD TEMPERATURE DIFFERENCE

TD TRENCH DRAIN

TDH TOTAL DYNAMIC HEAD

TEMP TEMPERATURE

TMV THERMOSTATIC MIXING VALVE

TP TRAP PRIMER

TSTAT THERMOSTAT

TWR TEMPERED WATER RETURN

TWS TEMPERED WATER SUPPLY

TYP TYPICAL

U

UF UNDER FLOOR

UNO UNLESS NOTED OTHERWISE

UR URINAL

V

V VENT

VAC VACUUM OR VOLTAGE (AC)

VB VACUUM BREAKER

VCO VACUUM CLEANER OUTLET

VP VACUUM PUMP

VS VENT STACK

VSD VARIABLE SPEED DRIVE

VTR VENT THROUGH ROOF

W

W WASTE

WC WATER CLOSET

WCO WALL CLEANOUT

WG WATER GAGE

WH WALL HYDRANT

WH WATER HEATER

WHA WATER HAMMER ARRESTER

WL WATER LINE

WM WATER METER

WPD WATER PRESSURE DROP

WS WASTE STACK

WSFU WATER SUPPLY FIXTURE UNITS

X

XP EXPLOSION PROOF

Y

YCO YARD CLEANOUT

YH YARD HYDRANT

0 100% CONSTRUCTION DOCUMENTS 04/18/2023

04/20/2023

A. FOR ALL SCHEDULED EQUIPMENT, PROVIDE BASIS OF DESIGN OR APPROVED

EQUAL. REFER TO SPECIFICATIONS SECTIONS 01 33 23 AND 22 05 11 FOR

FURTHER REQUIREMENTS.

REMARKS:

1. REFER ALSO TO SPECIFICATION

SECTIONS 22 40 00 AND 22 13 00.

2. FIXTURES SHALL BE ACCESSIBLE

UNO. REFER TO GENERAL AND

ARCH PLANS FOR REQUIREMENTS.

3. PROVIDE AN IN-LINE LEGIONELLA

FILTER.

REMARKS:

1. REFER ALSO TO SPECIFICATIONS

SECTIONS:

A. 22 11 23 FOR DCW & DHW

PUMPS.

B. 22 13 29 FOR SW PUMPS.

C. 22 14 29 FOR SUMP PUMPS.

REMARKS:

1. REFER ALSO TO SPECIFICATION

SECTION 22 33 00.

2. SET TO STAGE 2.

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

C :\U se rs

\J D ez m an \D oc um en ts

\1 9.

_M

E C

H -P

LU

M

_R

_J D ez m an .rv t 4/

/2

1:

:3

P M

01-P2

EQUIPMENT & FIXTURE

SCHEDULES

RENOVATE 9TH FLOOR MENTAL

HEALTH

1111 EAST END BLVD, WILKES-BARRE, PA 18711

693-19-106

01 & 17

04/18/2023 MB RT

100% CONSTRUCTION

DOCUMENTS

VEG 19.25 DWG 2 of 24 F

IN

A L

D R

A W

IN

G

S U

B M

IT

T

A L

PLUMBING FIXTURE SCHEDULE

MARK DESCRIPTION

DCW

CONNECTION

(NPS)

DHW

CONNECTION

(NPS)

SS

CONNECTION

(NPS)

VENT

CONNECTION

(NPS) REMARKS

FD-B3 FLOOR DRAIN, 7" WITH SECONDARY STRAINER - - 3 1 1/2 1,2

FD-C3 FLOOR DRAIN, 6" FOR TILE FLOOR - - 3 1 1/2 1,2

FD-D3 FLOOR DRAIN, 6" FOR MEMBRANE FLOOR - - 3 1 1/2 1,2

FD-E4 FLOOR DRAIN, 12" WITH SEDIMENT BUCKET - - 4 2 1,2

FD-S3 FLOOR SINK, 12" SST WITH DOME STRAINER - - 3 2 1,2

P-101 WC, FLOOR MOUNT, FLUSH VALVE 1 - 4 2 1,2

P-103 WC, WALL MOUNT, FLUSH VALVE 1 - 4 2 1,2

P-408 LAV, SMALL WALL MOUNT, WRIST CONTROL, 4" CENTERS 1/2 1/2 1 1/2 1 1/2 1,2

P-417 LAVATORY 1/2 1/2 1 1/2 1 1/2 1,2

P-501 SERVICE SINK 1/2 1/2 1 1/2 1 1/2 1,2

P-502 MOP SERVICE SINK, FLOOR MOUNT 1/2 1/2 3 1 1/2 1,2

P-528 SINK, COUNTER MOUNT 1/2 1/2 1 1/2 1 1/2 1,2

P-808 WASHING MACHINE SUPPLY AND DRAIN UNIT 1/2 1/2 2 1.5 1,2

P-910

WC, LIGATURE RESISTANT, FLOOR MOUNT REAR OUTLET, REAR SPUD

CONCEALED SENSOR FLUSH VALVE

1 - 4 2 1,2

P-912

WC, LIGATURE RESISTANT, WALL MOUNT, BARIATRIC, REAR OUTLET,

REAR SPUD CONCEALED SENSOR FLUSH VALVE

1 - 4 2 1,2

P-930 LAV, LIGATURE RESISTANT, NON-ACCESSIBLE 1/2 1/2 1 1/2 1 1/2 1,2

P-935 1 COMPARTMENT, ANTI-LIGATURE, WHEELCHAIR 1/2 1/2 1 1/2 1 1/2 1,2

P-940 LIGATURE RESISTANT SHOWER BATH MIXING VALVE 3/4 3/4 3 1 1/2 1,2,3

P-941 BARIATRIC LIGATURE RESISTANT SHOWER BATH MIXING VALVE 3/4 3/4 3 1 1/2 1,2,3

PLUMBING PUMP (PP) SCHEDULE

MARK LOCATION

AREA AND/OR BLDG

SERVED SYSTEM PUMP TYPE FLUID GPM

HEAD

(FT WG)

FLUID

TEMP

(°F)

MIN %

EFF

ELECTRICAL/MOTOR DATA

BASIS OF DESIGN REMARKSHP VAC PH CONTROL

1-BP-1 C9-36 MECH 9TH FLOOR DCW END SUCTION

DOMESTIC

WATER

85 69.3 68 52.2 2 208 3 VARIABLE GRUNDFOS HYDRO MULTI-E 3 CRE 5-6 1

1-PP-1 C9-36 MECH 9TH FLOOR DCWR CANNED ROTOR

DOMESTIC

WATER

5 15.5 68 0 1/4 115 1 CONSTANT GRUNDFOS UPS 26-99 SFC 1

1-PP-2 C9-36 MECH 9TH FLOOR DHWR CANNED ROTOR

DOMESTIC

WATER

5 15.5 140 0 1/4 115 1 CONSTANT GRUNDFOS UPS 26-99 SFC 1

ELECTRIC WATER HEATER (EWH) SCHEDULE

MARK LOCATION TYPE

TOTAL

KW

CONNECTION

SIZE (IN)

DESIGN DHW

TEMP

(°F)

ELECTRICAL DATA

BASIS OF DESIGN OR

APPROVED EQUAL REMARKSVAC PH MCA MOCP

17-WH-1 BLDG 17 - UNDER SINK

POINT OF

USE

7.2 1/2 90 208 1 26 35 STIEBEL ELTRON DHC-E8 1,2

17-WH-2 BLDG 17 - UNDER SINK

POINT OF

USE

7.2 1/2 100 208 1 26 35 STIEBEL ELTRON DHC-E8 1

17-WH-3 BLDG 17 - UNDER SINK

POINT OF

USE

9 1/2 100 208 1 44 50 STIEBEL ELTRON DHC-E12 1,2

17-WH-4 BLDG 17 - UNDER SINK

POINT OF

USE

7.2 1/2 100 208 1 26 35 STIEBEL ELTRON DHC-E8 1,2

A. REFER TO 01-P1 FOR PLUMBING SYMBOLS, ABBREVIATIONS, AND GENERAL

NOTES.

B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE

VHA COR BEFORE PROCEEDING WITH WORK.

C. REFER TO I SHEET SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED

LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP

PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE

SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL

PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN

SHALL GOVERN.

D. REFER TO SPECIFICATIONS SECTIONS 01 00 00 AND 23 05 11 FOR SELECTIVE

DEMOLITION AND REPAIR REQUIREMENTS. PATCH OPENINGS REMAINING IN

EXISTING CONSTRUCTION FOLLOWING DEMOLITION OF PENETRATIONS NOT

REPLACED IN KIND. MATCH AESTHETICS AND LIFE SAFETY RATINGS OF THE

SURROUNDING CONSTRUCTION. ENGAGE LICENSED AND SITE-APPROVED

ROOFING CONTRACTOR TO PATCH AND SEAL WHERE ITEMS ARE REMOVED

THROUGH THE EXISTING ROOF. MAINTAIN EXISTING WARRANTIES.

E. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT

PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING

HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN

ACCORDANCE WITH THE SPECIFICATIONS.

F. REFER TO I SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.

G. PROVIDE SERVICE VALVES AT LIMITS OF DEMOLITION. CAP ENDS WHERE

NOT RECONNECTED IN NEW WORK. EXISTING SYSTEMS SHALL REMAIN IN

SERVICE FOLLOWING DEMOLITION. REFER TO 22 05 11 FOR DEAD END

REQUIREMENTS.

H. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:

a. DOMESTIC WATER

b. MED GAS

c. STORM DRAINAGE

d. VENTS

I. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:

a. SANITARY SEWER

A B C D E F G

F

-P

F

-P

4"ø SS OH

4" ø

S S

O H

4" ø S

S O H

4"ø SS OH

4" ø

S S

O H

4"ø SS OH

4" ø

S S

O H

2"ø SS OH

4" ø

S S

O H

4"ø SS OH

4"ø SS OH

4" ø

S S

O H

4"ø SS OH

4" ø

S S

O H4" ø S S O

H

2" ø

S S

O H

4"ø SS4"ø SS

2"ø SS

4"ø SS

2"ø SS OH 4"ø SS OH

4"ø SS OH

4" ø S

S O H

4" ø

S S

O H

4"ø SS

4" ø

S S

2 1/2"ø DHW

2 1/2"ø DCW

E-9

ELEVATOR

E-8

ELEVATOR

E-7

ELEVATOR

C8-81

OFFICE

C8-82

OFFICE

C8-83

OFFICE

C8-84

OFFICE

C8-72

OFFICE

C8-71

WAITINGC8-13A

RECEPTION

C8-69

SOILED UTILITY

C8-68

CLEAN STORAGE

C8-61

PATIENT EDUCATION

ST-1

STAIR

C8-14

ELEC

C8-15

MECH

C8-02

CLEAN STORAGE

C8-03

TECHNICIAN ROOM

C8-04

SOILED UTILITY

C8-05

SLEEP ROOM

C8-05A

BATH

C8-06A

BATH

C8-06

SLEEP ROOM

C8-07

BARIATRIC SLEEP

ROOM

C8-07A

BARIATRIC BATH

C8-08A

BATH

C8-08

SLEEP ROOM

C8-09

SLEEP LAB MGR

OFFICE

C8-100

CORRIDOR

C8-70

CORRIDOR

C8-12

NUTRITION

C8-16

JANITOR CLOSET

C8-17

ELECTRICAL

C8-11

TOILET

ST-5

STAIR

C8-21A

UTILITY

C8-21

UTILITY CORRIDOR

C8-24

TEMP NUTREATION

OFFICE

C8-24B

COPY

C8-23

CORRIDOR

C8-20

ELEVATOR LOBBY

C8-23A

KITCHENETTE

C8-23B

BREAK LOCKER

ROOM

C8-70D

ELECTRICAL

C8-18

TOILET

C8-19

TOILET

C8-10

CORRIDOR

C8-101

CORRIDOR

4" ø

S S

O H

C5

01-P23

2"ø DHW3"ø DCW

P la n N o rt h

T ru e N o rt h

BLDG 01

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

00KEYNOTES

KEY PLAN

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

C :\U se rs

\J D ez m an \D oc um en ts

\1 9.

_M

E C

H -P

LU

M

_R

_J D ez m an .rv t 4/

/2

1:

:4

P M

01-P3

DEMOLITION PLAN - 8TH FLOOR

WEST

RENOVATE 9TH FLOOR MENTAL

HEALTH

1111 EAST END BLVD, WILKES-BARRE, PA 18711

693-19-106

04/18/2023 MB RT

100% CONSTRUCTION

DOCUMENTS

VEG 19.25 DWG 3 of 24 F

IN

A L

D R

A W

IN

G

S U

B M

IT

T

A L3/16" = 1'-0"

DEMOLITION PLAN - 8TH FLOOR WEST

F6

B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE

VHA COR BEFORE PROCEEDING WITH WORK.

C. REFER TO I SHEET SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED

LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP

PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE

SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL

PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN

SHALL GOVERN.

D. REFER TO SPECIFICATIONS SECTIONS 01 00 00 AND 23 05 11 FOR SELECTIVE

DEMOLITION AND REPAIR REQUIREMENTS. PATCH OPENINGS REMAINING IN

EXISTING CONSTRUCTION FOLLOWING DEMOLITION OF PENETRATIONS NOT

REPLACED IN KIND. MATCH AESTHETICS AND LIFE SAFETY RATINGS OF THE

SURROUNDING CONSTRUCTION. ENGAGE LICENSED AND SITE-APPROVED

ROOFING CONTRACTOR TO PATCH AND SEAL WHERE ITEMS ARE REMOVED

THROUGH THE EXISTING ROOF. MAINTAIN EXISTING WARRANTIES.

E. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT

PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING

HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN

ACCORDANCE WITH THE SPECIFICATIONS.

F. REFER TO I SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.

G. PROVIDE SERVICE VALVES AT LIMITS OF DEMOLITION. CAP ENDS WHERE

NOT RECONNECTED IN NEW WORK. EXISTING SYSTEMS SHALL REMAIN IN

SERVICE FOLLOWING DEMOLITION. REFER TO 22 05 11 FOR DEAD END

REQUIREMENTS.

H. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:

a. DOMESTIC WATER

b. MED GAS

c. STORM DRAINAGE

d. VENTS

I. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:

a. SANITARY SEWER

H J K L M N O P

F

-P

/F6 01-P3

F

-P

F

-P

2"ø SS OH

2"ø SS OH

4"ø SS OH

4"ø SS OH

4"ø SS OH

4" ø

S S

O H

4"ø SS OH

4" ø

S S

O H

4"ø SS OH

4"ø SS OH

4" ø

S S

O H

2" ø S

S O H

4" ø

S S

O H

4" ø

S S

O H

4"ø SS OH

4"ø SS OH 4"ø SS OH

4"ø SS OH

1 1/2"ø SS OH

1 1/2"ø SS OH

1 1/2"ø SS OH

3"ø DCW 2 1/2"ø DHW

E-5

ELEVATOR

E-6

ELEVATOR

E-4

ELEVATOR

E-3

ELEVATOR

E-2

ELEVATOR

E-1

ELEVATOR

C8-29

C8-51

GROUP ROOM

C8-30

VOLUNTARY

SERVICE STORAGE

C8-52

STORAGE

C8-28

C8-28A

TOILET

C8-27

OFFICE

C8-26

OFFICE

C8-25

OFFICE

C8-51A

TELEPHONE

C8-53

CORRIDOR

C8-26A

TOILET

C8-77

SOCIAL WORK ROOM

C8-54

CORRIDOR

C8-56

MECHANICAL ROOM

ST-3

STAIR

C8-55A C8-55

ELEC

C8-52B

CORRIDOR

C8-57

ASSOC CHIEF

C8-58

SECY

C8-59A

TOILET

C8-59B

TOILET

C8-59

WAITING ROOM

C8-54B

C8-54A

MECHANICAL ROOM

C8-78

CONFERENCE

C8-79

OFFICE

C8-80

OFFICE

C8-76

OFFICE

C8-75

OFFICE

C8-74

OFFICE

C8-73

OFFICE

C8-101

CORRIDOR

C8-52A

CORRIDOR

P la n N o rt h

T ru e N o rt h

BLDG 01

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

00KEYNOTES

KEY PLAN

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

C :\U se rs

\J D ez m an \D oc um en ts

\1 9.

_M

E C

H -P

LU

M

_R

_J D ez m an .rv t 4/

/2

1:

:4

P M

01-P4

DEMOLITION PLAN - 8TH FLOOR

CENTER

RENOVATE 9TH FLOOR MENTAL

HEALTH

1111 EAST END BLVD, WILKES-BARRE, PA 18711

693-19-106

04/18/2023 MB RT

100% CONSTRUCTION

DOCUMENTS

VEG 19.25 DWG 4 of 24 F

IN

A L

D R

A W

IN

G

S U

B M

IT

T

A L3/16" = 1'-0"

DEMOLITION PLAN - 8TH FLOOR CENTER

F6

B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE

VHA COR BEFORE PROCEEDING WITH WORK.

C. REFER TO I SHEET SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED

LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP

PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE

SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL

PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN

SHALL GOVERN.

D. REFER TO SPECIFICATIONS SECTIONS 01 00 00 AND 23 05 11 FOR SELECTIVE

DEMOLITION AND REPAIR REQUIREMENTS. PATCH OPENINGS REMAINING IN

EXISTING CONSTRUCTION FOLLOWING DEMOLITION OF PENETRATIONS NOT

REPLACED IN KIND. MATCH AESTHETICS AND LIFE SAFETY RATINGS OF THE

SURROUNDING CONSTRUCTION. ENGAGE LICENSED AND SITE-APPROVED

ROOFING CONTRACTOR TO PATCH AND SEAL WHERE ITEMS ARE REMOVED

THROUGH THE EXISTING ROOF. MAINTAIN EXISTING WARRANTIES.

E. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT

PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING

HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN

ACCORDANCE WITH THE SPECIFICATIONS.

F. REFER TO I SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.

G. PROVIDE SERVICE VALVES AT LIMITS OF DEMOLITION. CAP ENDS WHERE

NOT RECONNECTED IN NEW WORK. EXISTING SYSTEMS SHALL REMAIN IN

SERVICE FOLLOWING DEMOLITION. REFER TO 22 05 11 FOR DEAD END

REQUIREMENTS.

H. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:

a. DOMESTIC WATER

b. MED GAS

c. STORM DRAINAGE

d. VENTS

I. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:

a. SANITARY SEWER

Q R S T U V

F

-P

F

-P

1 1/2"ø SS OH

1 1/2"ø SS OH

4" ø

S S

O H

C8-43B

TOILET

C8-43A

TOILET

C8-35

ST-2

STAIR

C8-42A

MECH

C8-42

ELEC

C8-40

GROUP ROOM C8-37A

OFFICE

C8-37

C8-38

EMPLOYEE FITNESS

C8-39

CORRIDOR

C8-36A

STORAGE

C8-38A

TOILET

C8-36

OFFICE

C8-45

TOILET

C8-41

CORRIDOR

C8-46

CORRIDOR

C8-49

OFFICE

C8-47A

HAC

C8-47

ELECTRICAL

C8-33

STORAGE

C8-32

STORAGE

C8-50A

TOILET

C8-50

C8-34

STORAGE

C8-30

VOLUNTARY

SERVICE STORAGE

C8-49A

OFFICE

C8-49B

MECHANICAL

C8-49C

ELECTRICAL

P la n N o rt h

T ru e N o rt h

BLDG 01

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

00KEYNOTES

KEY PLAN

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

C :\U se rs

\J D ez m an \D oc um en ts

\1 9.

_M

E C

H -P

LU

M

_R

_J D ez m an .rv t 4/

/2

1:

:4

P M

01-P5

DEMOLITION PLAN - 8TH FLOOR

EAST

RENOVATE 9TH FLOOR MENTAL

HEALTH

1111 EAST END BLVD, WILKES-BARRE, PA 18711

693-19-106

04/18/2023 MB RT

100% CONSTRUCTION

DOCUMENTS

VEG 19.25 DWG 5 of 24 F

IN

A L

D R

A W

IN

G

S U

B M

IT

T

A L3/16" = 1'-0"

DEMOLITION PLAN - 8TH FLOOR EAST

F6

4" RWC

FD "B"

2"

3/4" H & CW DN.

3/4"

4" S & VENT UP

4" S & VTR

2" HW

4" CW

1/2" H & CW

2" SD "C"

2" SD "C"

2" SD "C"

4"

2"

1 1/2"

4" CW

2" HW

1 1/2"

2"

2" (RAC)

2" VENT UP

2" VENT UP

2"

2"

2"

3/4"

3/4"

1/2" RECIRC

1" CW

3/4"

3/4"

1/2"

1/2"

3/4"

2" SD "C"

3/4"1 1/2"

1/2"

1/2"

2" 1"

2" SD "C"

1/2"

2" SD "C"

2" SD "C"

1/2" HW & CW DN.

1 1/2" CW DN.

3/4" HW DN.

1 1/2"1"

1 1/2" CW &

1/2" HW DN.

SA-"B"

3/4" HW DN.

1 1/2" CW DN.

1 1/2"

1" 2"

1 1/2"

3/4" 1 1/2"

2"

1 1/2" 2"

1" 1"

1/2" H & CW

1 1/4"

1/2"

1/2" CW & HW DN.

1 1/4" CW

1/2" HW

1 1/4"

1/2" CW & HW DN.

1 1/4" CW DN.

3/4"

1 1/2"

SA-"B"

3/4" CW & HW DN.

1/2" CW & HW

DN.

1/2" CW & HW

DN.

2 1/2" H & CW UP FROM BELOW. CAP LINES

BELOW FLOOR IN CHASE.

2" STANDPIPE AND 2" WASTE BELOW

FLOOR

3/4" CW & HW

DN.

1 1/2" VENT UP

2" STAND PIPE 2" WASTE BELOW

FLOOR

3/4" CW & HW

DN.

1 1/4" CW & 1/2" HW

DN.

1/2" CW & HW DN.

1 1/4" CW & 1/2"

HW DN.

4" SAN DN. 2"

VENT UP

1 1/4" CW & 1/2" HW

DN.

1 1/4" CW & 1/2"

HW DN.

1 1/2" CW & 1/2" HW DN.

TO WC & LAV

3/4" CW TO HB

3/4" CW UP

2" W DN. 2" V UP

1 1/4" CW & 1/2"

HW DN.

1 1/2" CW & 1/2"

HW DN.

3/4" CW & HW DN.

A. REFER TO 01-P1 FOR PLUMBING SYMBOLS, ABBREVIATIONS, AND GENERAL

NOTES.

B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE

VHA COR BEFORE PROCEEDING WITH WORK.

C. REFER TO I SHEET SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED

LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP

PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE

SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL

PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN

SHALL GOVERN.

D. REFER TO SPECIFICATIONS SECTIONS 01 00 00 AND 23 05 11 FOR SELECTIVE

DEMOLITION AND REPAIR REQUIREMENTS. PATCH OPENINGS REMAINING IN

EXISTING CONSTRUCTION FOLLOWING DEMOLITION OF PENETRATIONS NOT

REPLACED IN KIND. MATCH AESTHETICS AND LIFE SAFETY RATINGS OF THE

SURROUNDING CONSTRUCTION. ENGAGE LICENSED AND SITE-APPROVED

ROOFING CONTRACTOR TO PATCH AND SEAL WHERE ITEMS ARE REMOVED

THROUGH THE EXISTING ROOF. MAINTAIN EXISTING WARRANTIES.

E. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT

PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING

HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN

ACCORDANCE WITH THE SPECIFICATIONS.

F. REFER TO I SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.

G. PROVIDE SERVICE VALVES AT LIMITS OF DEMOLITION. CAP ENDS WHERE

NOT RECONNECTED IN NEW WORK. EXISTING SYSTEMS SHALL REMAIN IN

SERVICE FOLLOWING DEMOLITION. REFER TO 22 05 11 FOR DEAD END

REQUIREMENTS.

H. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:

a. DOMESTIC WATER

b. MED GAS

c. STORM DRAINAGE

d. VENTS

I. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:

a. SANITARY SEWER

1 S&V 1

S&V 2 S&V 3 S&V 4

S&V 6

S&V 5

S&V 7

S&V 8

S&V 37

S&V 33

1 1

1 1

A B C D E F G

F

-P

F

-P

TYP

P la n N o rt h

T ru e N o rt h

BLDG 01

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

00KEYNOTES

KEY PLAN

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

C :\U se rs

\J D ez m an \D oc um en ts

\1 9.

_M

E C

H -P

LU

M

_R

_J D ez m an .rv t 4/

/2

1:

:4

P M

01-P6

DEMOLITION PLAN - 9TH FLOOR

WEST

RENOVATE 9TH FLOOR MENTAL

HEALTH

1111 EAST END BLVD, WILKES-BARRE, PA 18711

693-19-106

04/18/2023 MB RT

100% CONSTRUCTION

DOCUMENTS

VEG 19.25 DWG 6 of 24 F

IN

A L

D R

A W

IN

G

S U

B M

IT

T

A L

1. RISER S+V NUMBERS REFER TO EXISTING SEWER AND VENT RISER TO

REMAIN.

2. EXISTING DOMESTIC HOT & COLD WATER RISER LOCATION TO REMAIN.

3. INTENT IS TO DEMOLISH PLUMBING SERVING THE 9TH FLOOR BACK TO

EXISTING RISERS.

3/16" = 1'-0"

DEMOLITION PLAN - 9TH FLOOR WEST

F6

2" SD "C"

2" SD "C"

1 1/2"

1 1/2"

2"

1"

1 1/2"

1 1/4"

1"

1/2"

3/4"

2"

3/4"

1 1/2"

2" 3/4"

SA-"B"

1"

1 1/2"

3/4"1 1/2"

2" SD "C"

3/4" HW & CW DN.

1 1/4" CW DN.

2" SD "C"

1 1/2"

1/2" H & CW DN.

1"3/4"

1 1/2"

1/2" H & CW DN.

1 1/2"

1 1/2"

4" LEADER NO. 1"

DN. 3088∅

3" CW & 2 1/2"

HW RISER

1 1/2" CW DN. 1 1/4" CW TP WC

1/2" HW DN. TO LAV

1 1/4" CW & 1/2" HW

DN.

1/2" HW & CW DN.

1" CW & 1/2" HW RISERS

1 1/2" CW & 3/4" HW

DN.

1 1/2" CW & 2" HW

RISERS

1/2" CW & HW DN.

1/2" CW & HW

DN.

1/2" CW & HW DN.

1 1/4" CW & 1/2" HW

DN.

3" CW & 2 1/2" HW RISER

5" MAIN HOT WATER

RISER

6" COLD WATER RISER

2" DRINKING WATER

RISER

6" COLD WATER TO HOT WATER

GENERATOR

S&V 10

S&V 9

S&V 11

S&V 12 S&V 16

S&V 17

S&V 20

1 1

2 2 2

H J K L M N O P

/F6 01-P6

F

-P

F

-P

F

-P

TYP

(E) 4"ø SS

(E) 2"ø V

S 231 V 23 1

A. REFER TO 01-P1 FOR PLUMBING SYMBOLS, ABBREVIATIONS, AND GENERAL

NOTES.

B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE

VHA COR BEFORE PROCEEDING WITH WORK.

C. REFER TO I SHEET SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED

LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP

PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE

SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL

PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN

SHALL GOVERN.

D. REFER TO SPECIFICATIONS SECTIONS 01 00 00 AND 23 05 11 FOR SELECTIVE

DEMOLITION AND REPAIR REQUIREMENTS. PATCH OPENINGS REMAINING IN

EXISTING CONSTRUCTION FOLLOWING DEMOLITION OF PENETRATIONS NOT

REPLACED IN KIND. MATCH AESTHETICS AND LIFE SAFETY RATINGS OF THE

SURROUNDING CONSTRUCTION. ENGAGE LICENSED AND SITE-APPROVED

ROOFING CONTRACTOR TO PATCH AND SEAL WHERE ITEMS ARE REMOVED

THROUGH THE EXISTING ROOF. MAINTAIN EXISTING WARRANTIES.

E. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT

PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING

HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN

ACCORDANCE WITH THE SPECIFICATIONS.

F. REFER TO I SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.

G. PROVIDE SERVICE VALVES AT LIMITS OF DEMOLITION. CAP ENDS WHERE

NOT RECONNECTED IN NEW WORK. EXISTING SYSTEMS SHALL REMAIN IN

SERVICE FOLLOWING DEMOLITION. REFER TO 22 05 11 FOR DEAD END

REQUIREMENTS.

H. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:

a. DOMESTIC WATER

b. MED GAS

c. STORM DRAINAGE

d. VENTS

I. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:

a. SANITARY SEWER

P la n N o rt h

T ru e N o rt h

BLDG 01

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

00KEYNOTES

KEY PLAN

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

C :\U se rs

\J D ez m an \D oc um en ts

\1 9.

_M

E C

H -P

LU

M

_R

_J D ez m an .rv t 4/

/2

1:

:5

P M

01-P7

DEMOLITION PLAN - 9TH FLOOR

CENTER

RENOVATE 9TH FLOOR MENTAL

HEALTH

1111 EAST END BLVD, WILKES-BARRE, PA 18711

693-19-106

04/18/2023 MB RT

100% CONSTRUCTION

DOCUMENTS

VEG 19.25 DWG 7 of 24 F

IN

A L

D R

A W

IN

G

S U

B M

IT

T

A L3/16" = 1'-0"

DEMOLITION PLAN - 9TH FLOOR CENTER

F6

1. RISER S+V NUMBERS REFER TO EXISTING SEWER AND VENT RISER TO

REMAIN.

2. EXISTING DOMESTIC HOT & COLD WATER RISER LOCATION TO REMAIN.

3. DEMO (E) PLUMBING PIPES FROM MIXING STATION TO RISER TO ALLOW

FOR NEW PLUMBING INSTALLATION. CAP PIPES AT RISER

4. (E) HOT WATER MIXING STATION SHALL REMAIN FOR FUTURE USE.

5. INTENT IS TO DEMOLISH PLUMBING SERVING THE 9TH FLOOR BACK TO

EXISTING RISERS.

1"

1/2" H & CW DN.

1 1/2"1"

1 1/2"

FD-"B"

4" RD (700∅)

4" RD (440∅)

1/2" H & CW DN.

2" HW

3" CW

3/4" @ CLG. BELOW

4" RD (440∅)

3/4" CW TO HB

3/4" CW UP

3" CW & 2 1/2"

HW RISER

3" HW 4"

CW

S&V 18

S&V 29 S&V 27

S&V 26

S&V 31

1 1

Q R S T U V

F

-P

F

-P

TYP

S&V 25 1

A. REFER TO 01-P1 FOR PLUMBING SYMBOLS, ABBREVIATIONS, AND GENERAL

NOTES.

B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE

VHA COR BEFORE PROCEEDING WITH WORK.

C. REFER TO I SHEET SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED

LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP

PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE

SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL

PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN

SHALL GOVERN.

D. REFER TO SPECIFICATIONS SECTIONS 01 00 00 AND 23 05 11 FOR SELECTIVE

DEMOLITION AND REPAIR REQUIREMENTS. PATCH OPENINGS REMAINING IN

EXISTING CONSTRUCTION FOLLOWING DEMOLITION OF PENETRATIONS NOT

REPLACED IN KIND. MATCH AESTHETICS AND LIFE SAFETY RATINGS OF THE

SURROUNDING CONSTRUCTION. ENGAGE LICENSED AND SITE-APPROVED

ROOFING CONTRACTOR TO PATCH AND SEAL WHERE ITEMS ARE REMOVED

THROUGH THE EXISTING ROOF. MAINTAIN EXISTING WARRANTIES.

E. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT

PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING

HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN

ACCORDANCE WITH THE SPECIFICATIONS.

F. REFER TO I SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.

G. PROVIDE SERVICE VALVES AT LIMITS OF DEMOLITION. CAP ENDS WHERE

NOT RECONNECTED IN NEW WORK. EXISTING SYSTEMS SHALL REMAIN IN

SERVICE FOLLOWING DEMOLITION. REFER TO 22 05 11 FOR DEAD END

REQUIREMENTS.

H. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:

a. DOMESTIC WATER

b. MED GAS

c. STORM DRAINAGE

d. VENTS

I. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:

a. SANITARY SEWER

P la n N o rt h

T ru e N o rt h

BLDG 01

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

00KEYNOTES

KEY PLAN

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

C :\U se rs

\J D ez m an \D oc um en ts

\1 9.

_M

E C

H -P

LU

M

_R

_J D ez m an .rv t 4/

/2

1:

:5

P M

01-P8

DEMOLITION PLAN - 9TH FLOOR

EAST

RENOVATE 9TH FLOOR MENTAL

HEALTH

1111 EAST END BLVD, WILKES-BARRE, PA 18711

693-19-106

04/18/2023 MB RT

100% CONSTRUCTION

DOCUMENTS

VEG 19.25 DWG 8 of 24 F

IN

A L

D R

A W

IN

G

S U

B M

IT

T

A L3/16" = 1'-0"

DEMOLITION PLAN - 9TH FLOOR EAST

F6

1. RISER S+V NUMBERS REFER TO EXISTING SEWER AND VENT RISER TO

REMAIN.

2. EXISTING DOMESTIC HOT & COLD WATER RISER LOCATION TO REMAIN.

3. DEMO (E) ROOF DRAINS AND STORM PIPES BACK TO RISER.

4. INTENT IS TO DEMOLISH PLUMBING SERVING THE 9TH FLOOR BACK TO

EXISTING RISERS.

W X Y Z

(E) 4"ø SS

(E

1/

2" ø

D C

W

(X)

17-DWH-E

(X) P-89

(X) P-1

(X) P-66

A. REFER TO 01-P1 FOR PLUMBING SYMBOLS, ABBREVIATIONS, AND GENERAL

NOTES.

B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE

VHA COR BEFORE PROCEEDING WITH WORK.

C. REFER TO I SHEET SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED

LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP

PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE

SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL

PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN

SHALL GOVERN.

D. REFER TO SPECIFICATIONS SECTIONS 01 00 00 AND 23 05 11 FOR SELECTIVE

DEMOLITION AND REPAIR REQUIREMENTS. PATCH OPENINGS REMAINING IN

EXISTING CONSTRUCTION FOLLOWING DEMOLITION OF PENETRATIONS NOT

REPLACED IN KIND. MATCH AESTHETICS AND LIFE SAFETY RATINGS OF THE

SURROUNDING CONSTRUCTION. ENGAGE LICENSED AND SITE-APPROVED

ROOFING CONTRACTOR TO PATCH AND SEAL WHERE ITEMS ARE REMOVED

THROUGH THE EXISTING ROOF. MAINTAIN EXISTING WARRANTIES.

E. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT

PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING

HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN

ACCORDANCE WITH THE SPECIFICATIONS.

F. REFER TO I SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.

G. PROVIDE SERVICE VALVES AT LIMITS OF DEMOLITION. CAP ENDS WHERE

NOT RECONNECTED IN NEW WORK. EXISTING SYSTEMS SHALL REMAIN IN

SERVICE FOLLOWING DEMOLITION. REFER TO 22 05 11 FOR DEAD END

REQUIREMENTS.

H. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:

a. DOMESTIC WATER

b. MED GAS

c. STORM DRAINAGE

d. VENTS

I. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:

a. SANITARY SEWER

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

00KEYNOTES

KEY PLAN

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

C :\U se rs

\J D ez m an \D oc um en ts

\1 9.

_M

E C

H -P

LU

M

_R

_J D ez m an .rv t 4/

/2

1:

:5

P M

17-P9

DEMOLITION PLAN - WAREHOUSE RENOVATE 9TH FLOOR MENTAL

HEALTH

1111 EAST END BLVD, WILKES-BARRE, PA 18711

693-19-106

04/18/2023 MB RT

100% CONSTRUCTION

DOCUMENTS

VEG 19.25 DWG 9 of 24 F

IN

A L

D R

A W

IN

G

S U

B M

IT

T

A L3/16" = 1'-0"

DEMOLITION PLAN - WAREHOUSE

F6

1. DEMO PLUMBING VENT THRU ROOF. PROTECT AND REUSE OPENING FOR

NEW VENT.

2. DEMO PLUMBING FIXTURES, DRAINS, PIPING AND VENT IN HATCHED AREA

3. DEMO FLOOR CLEAN OUT.

4. TO EXISTING DOMESTIC COLD WATER SUPPLY.

P-912

P-912

P-910

P-502

P-912

P-910

2 1/2"ø DCW2 1/2"ø DCW

2"ø DHW

2 1/2"ø DCW

2"ø DHW

2 1/2"ø DCW

2"ø DHW

2" ø

D H

W

1/

2" ø

D C

W

2"ø DHW

2 1/2"ø DCW

2"ø DHW

2 1/2"ø DCW

2 1/2"ø DCW

2"ø DHW

2"ø DHW

2 1/2"ø DCW

3/ 4" ø D

C W

P-501

P-930

P-935

P-935

P-935 P-417

P-528

P-408

P-930

P-930

P-930

P-912

P-910

P-940P-940

P-941

P-941

P-940

P-101

A B C D E F G

F

-P

F

-P

2 1/2"ø DCW

2 1/2"ø DHW

P-941

P-941

C9-62

ELEC

C9-53

ELEC

C9-58

ELECTRICAL

E-7

ELEVATOR

E-8

ELEVATOR

E-9

ELEVATOR

C9-46

LINEN

C9-44A

TOILET

C9-52

SALLY PORT

C9-51

HAC

C9-41A

TOILET

C9-66A

TOILET

C9-68A

TOILET

C9-68

BARIATRIC

GERIATRIC

C9-69

OFFICE

C9-66

GERIATRIC

ST-5

STAIR

ST-1

STAIR

C9-63

ELEC

C9-71

GROUP THERAPY

C9-50

MEETING

C9-45

PATIENT STORAGE

C9-C07

CORRIDOR

C9-70

CLEAN UTILITY

C9-41

WOMEN'S

C9-49

WOMEN'S BARIATRIC

C9-49A

TOILET

C9-54

ELEVATOR LOBBY

C9-67A

TOILET

C9-65

MED

C9-47

OFFICE/ GROUP

ROOM

C9-47A

STORAGE

C9-44

WOMEN'S

C9-56

CLEAN STORAGE

C9-55

MECHANICAL

C9-60

CONFERENCE

C9-57

HAC

C9-59

PREFUNCTION/

COLLABORATION

C9-61

WORKSTATIONS

C9-43

WOMEN'S

C9-C06

CORRIDOR

C9-43A

TOILET

C9-42

STAFF TOILET

C9-40

MED

C9-C09

CORRIDOR

C9-C08

CORRIDOR

S3

LINEN CHUTE

C9-48

LAUNDRY

C9-64

NURSE'S STATION

C9-67

BARIATRIC

GERIATRIC

C9-72

DAY/TV

C9-72A

GERIATRIC DINING

C5

01-P23

SIM

4 1/2"ø DCW

A. REFER TO 01-P1 FOR PLUMBING SYMBOLS, ABBREVIATIONS, AND GENERAL

NOTES.

B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE

VHA COR BEFORE PROCEEDING WITH WORK.

C. REFER TO I-SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED

LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP

PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE

SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL

PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN

SHALL GOVERN.

D. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT

PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING

HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN

ACCORDANCE WITH THE SPECIFICATIONS.

E. REFER TO I SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.

F. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:

a. DOMESTIC WATER

b. MED GAS

c. STORM DRAINAGE

d. VENTS

G. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:

a. SANITARY SEWER

P la n N o rt h

T ru e N o rt h

BLDG 01

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

00KEYNOTES

KEY PLAN

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

C :\U se rs

\J D ez m an \D oc um en ts

\1 9.

_M

E C

H -P

LU

M

_R

_J D ez m an .rv t 4/

/2

1:

:5

P M

01-P10

DOMESTIC WATER PLAN - 9TH

FLOOR WEST

RENOVATE 9TH FLOOR MENTAL

HEALTH

1111 EAST END BLVD, WILKES-BARRE, PA 18711

693-19-106

04/18/2023 MB RT

100% CONSTRUCTION

DOCUMENTS

VEG 19.25 DWG 10 of 24 F

IN

A L

D R

A W

IN

G

S U

B M

IT

T

A L3/16" = 1'-0"

DOMESTIC WATER PLAN - 9TH FLOOR WEST

F6

1. DCW TO NEW HUMIDIFIER. COORDINATE WITH MECHANICAL.

2. OFFSET DOMESTIC WATER RISERS TO WALL ABOVE 8TH FLOOR CEILING

AND RECONNECT TO EXISTING RISER.

3. PROVIDE CONTROLS COMPATIBLE WITH WATER MANAGEMENT

CONTROLLER.

4. PROVIDE AND CONNECT TO TRAP PRIMER CONTROLLER.

2"ø DHW

2 1/2"ø DCW

1/

2" ø

D C

W

2" ø

D H

W

2" ø

D H

W

3" ø

D C

W

2"ø DHW

3"ø DCW

1" ø

D C

W

1" ø

D H

W R

2" ø

D H

W

1/

2" ø

D C

W

1" ø

D C

W

1" ø

D H

W R

2 1/2"ø DCW

2"ø DHW

2 1/2"ø DCW

2"ø DHW

1" ø

D C

W

3/ 4" ø D

H W

2"ø DHW

2 1/2"ø DCW

2 1/2"ø DCW2 1/2"ø DCW

2"ø DHW

2 1/2"ø DCW

2"ø DHW

2 1/2"ø DCW

2"ø DHW

1" ø

D H

W

1" ø

D C

W

1" ø

D H

W R

P-910

P-912

P-528

P-910

P-910

P-528

P-417

P-930

P-930

P-408

P-930

P-930

P-101

P-940 P-940

H J K L M N O P

F

-P

/F6 01-P10

F

-P

F

-P

01-P23

F5

01-P23

F1

C9-35

NURSE'S LOUNGE

C9-35A

LOCKERS

ST-3

STAIR

C9-34

ELEC C9-34A

ELEC

E-4

ELEVATOR

C9-23

ELEVATOR LOBBY

E-5

ELEVATOR

E-6

ELEVATOR

C9-21

SALLY PORT

E-2

ELEVATOR

E-3

ELEVATORC9-30

ELEVATOR LOBBY

C9-28

SALLY PORT

C9-33

STAFF TOILET

C9-29

INTERVIEW

C9-31

TELECOM ROOM

C9-C04

CORRIDOR

C9-37

TEAMING/

COUNSELING

C9-32

MECHANICAL

C9-22

SERVING KITCHEN

C9-16

DINING/ ACTIVITIES

C9-19

ELEC

C9-38

EXAM/ INTAKE

C9-26

LOBBY

C9-39

HEAD NURSE

OFFICE

C9-27

NURSE'S STATION

C9-27A

NURSE'S

WORKROOM

C9-C05

CORRIDOR

C9-25

ANTE ROOM

C9-24

MEN'S

C9-C03

CORRIDOR

E-1

ELEVATOR

C9-20

MEN'S

C9-18

MEN'S

C9-17

GROUP THERAPY

C9-20A

TOILET

C9-18A

TOILET

C9-25B

SECLUSION ROOM

C9-24A

TOILET

C9-25A

TOILET

P-528

P-941

A. REFER TO 01-P1 FOR PLUMBING SYMBOLS, ABBREVIATIONS, AND GENERAL

NOTES.

B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE

VHA COR BEFORE PROCEEDING WITH WORK.

C. REFER TO I-SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED

LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP

PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE

SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL

PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN

SHALL GOVERN.

D. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT

PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING

HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN

ACCORDANCE WITH THE SPECIFICATIONS.

E. REFER TO I SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.

F. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:

a. DOMESTIC WATER

b. MED GAS

c. STORM DRAINAGE

d. VENTS

G. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:

a. SANITARY SEWER

P la n N o rt h

T ru e N o rt h

BLDG 01

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

00KEYNOTES

KEY PLAN

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

C :\U se rs

\J D ez m an \D oc um en ts

\1 9.

_M

E C

H -P

LU

M

_R

_J D ez m an .rv t 4/

/2

1:

:0

P M

01-P11

DOMESTIC WATER PLAN - 9TH

FLOOR CENTER

RENOVATE 9TH FLOOR MENTAL

HEALTH

1111 EAST END BLVD, WILKES-BARRE, PA 18711

693-19-106

04/18/2023 MB RT

100% CONSTRUCTION

DOCUMENTS

VEG 19.25 DWG 11 of 24 F

IN

A L

D R

A W

IN

G

S U

B M

IT

T

A L3/16" = 1'-0"

DOMESTIC WATER PLAN - 9TH FLOOR CENTER

F6

1. OFFSET DOMESTIC WATER RISERS TO WALL ABOVE 8TH FLOOR CEILING

AND RECONNECT TO EXISTING RISER.

2. PROVIDE CONOTROLS COMPATIBLE WITH WATER MANAGEMENT

CONTROLLER.

3. PROVIDE DOMESTIC COLD WATER CONNECTIONS ABOVE COUNTER TOP

FOR COFFEE MAKER AND ICE MACHINE.

2"ø DHW

2 1/2"ø DCW

2"ø DHW

2 1/2"ø DCW

2"ø DHW

2 1/2"ø DCW

P-912 P-910

P-910

2 1/2"ø DCW

2"ø DHW

3/ 4" ø D

C W

1/

2" ø

D C

W

2" ø

D H

W

2 1/2"ø DCW

2"ø DHW

2 1/2"ø DCW

2"ø DHW

2 1/2"ø DCW

2"ø DHW

2 1/2"ø DCW

3"ø DCW

2"ø DHW

P-502

P-910

P-930

P-930

P-910

P-501

P-912

P-935 P-930

P-930

P-935

P-940P-940

P-941

P-940

P-941

Q R S T U V

F

-P

F

-P

C9-02

HAC

C9-04A

TOILET

C9-04

MEN'S

ST-2

STAIR

C9-09

ELEC

C9-11

QUIET ROOM

C9-C01

CORRIDOR

C9-13

SOILED UTILITY

C9-15A

TOILET

C9-15

MEN'S BARIATRIC

C9-14

MEN'S

C9-14A

TOILET

C9-12A

TOILET

C9-12

MEN'S

C9-08

MEN'S BARIATRIC

C9-08A

TOILET

C9-07

OFFICE

C9-05

TOILET

C9-03

GROUP

COUNSELING ROOM

C9-C02

CORRIDOR

C9-06

MECHANICAL

C9-06A

ELEC

C9-01

EAST SUNROOM

C9-10

LAUNDRY

C9-00

COURTYARD

S1

SHAFT

S2

SOILED LINEN

CHUTE

P-808 P-808

3/ 4" ø D

C W

1/2"ø DCW

A. REFER TO 01-P1 FOR PLUMBING SYMBOLS, ABBREVIATIONS, AND GENERAL

NOTES.

B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE

VHA COR BEFORE PROCEEDING WITH WORK.

C. REFER TO I-SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED

LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP

PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE

SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL

PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN

SHALL GOVERN.

D. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT

PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING

HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN

ACCORDANCE WITH THE SPECIFICATIONS.

E. REFER TO I SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.

F. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:

a. DOMESTIC WATER

b. MED GAS

c. STORM DRAINAGE

d. VENTS

G. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:

a. SANITARY SEWER

P la n N o rt h

T ru e N o rt h

BLDG 01

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

00KEYNOTES

KEY PLAN

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

C :\U se rs

\J D ez m an \D oc um en ts

\1 9.

_M

E C

H -P

LU

M

_R

_J D ez m an .rv t 4/

/2

1:

:0

P M

01-P12

DOMESTIC WATER PLAN - 9TH

FLOOR EAST

RENOVATE 9TH FLOOR MENTAL

HEALTH

1111 EAST END BLVD, WILKES-BARRE, PA 18711

693-19-106

04/18/2023 MB RT

100% CONSTRUCTION

DOCUMENTS

VEG 19.25 DWG 12 of 24 F

IN

A L

D R

A W

IN

G

S U

B M

IT

T

A L3/16" = 1'-0"

DOMESTIC WATER PLAN - 9TH FLOOR EAST

F6

1. DCW TO NEW HUMIDIFIER.

2. OFFSET DOMESTIC WATER RISERS TO WALL ABOVE 8TH FLOOR CEILING

AND RECONNECT TO EXISTING RISER.

3. PROVIDE CONTROLS COMPATIBLE WITH WATER MANAGEMENT

CONTROLLER.

4. PROVIDE AND CONNECT TO TRAP PRIMER CONTROLLER.

1"ø DCW

3/ 4" ø D

C W

1 1/2"ø DCW

1/

2" ø

D C

W

P-103

P-103

P-103

W X Y Z

P-408 P-408

P-408

1"ø DCW

P-528

3/4"ø DCW

(E

1/

2" ø

D C

W

(E) 1 1/2"ø DCW

17-WH-1

17-WH-3

17-WH-217-WH-4

1/

2" ø

D C

W

L1-110

OFFICE

L1-109

OFFICE

L1-108

OFFICE

L1-107

OFFICE

L1-105

TOILET

L1-104

COPY/LOCKERS

L1-103

OPEN OFFICE

L1-102

SECRETARY

L1-111

CONFERENCE

L1-112

MECH

L1-100

STORAGE

L1-100H

OFFICE

L1-100G

TOILET

L1-100A

ELEC

L1-100J

LOADING DOCK

L1-102A

CLOSET

L1-100F

LOCKERS

L1-100E

TELECOM ROOM

L1-106

TOILET

L1-001

OXYGEN STORAGE

3/ 4" ø D

C W

A. REFER TO 01-P1 FOR PLUMBING SYMBOLS, ABBREVIATIONS, AND GENERAL

NOTES.

B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE

VHA COR BEFORE PROCEEDING WITH WORK.

C. REFER TO I-SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED

LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP

PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE

SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL

PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN

SHALL…

This is the start of the file's text. The full file is on GovTribe.