08 - Drawings Plumbing.pdf
PDF 8 MB Posted
- Attached to
- Y1DA--9th Floor MH Renovation WBVAMC
- Solicitation number
- 36C24425B0018
About this file
The provided file is a set of detailed plumbing engineering drawings for the renovation of the 9th Floor Mental Health unit at the Wilkes-Barre VA Medical Center. The comprehensive drawing set includes demolition plans, domestic water plans, drain-waste-vent plans, and enlarged detailed plans for the 9th floor, 8th floor, and warehouse areas. The drawings cover multiple technical aspects including plumbing fixtures, piping systems, risers, water connections, drainage routes, and specific technical details for domestic cold water, hot water, sanitary sewer, and vent systems.
The drawings specify precise technical requirements for plumbing infrastructure, including pipe sizes, fixture locations, riser configurations, and installation notes. Key technical specifications include overhead and underground piping routes, connections to existing systems, trap primer requirements, water management controls, and specific installation guidelines. The documents are part of a 100% Construction Documents set dated 04/18/2023, prepared for the VA Medical Center's renovation project with the project number 693-19-106, and are designed to provide comprehensive technical guidance for the plumbing renovation of the mental health floor.
View the file
Other files
Show all 45
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AREA OF WORK
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\R ev it
\1 9.
_A
R C
H _R
_z m ill er 4N
R T
Z .r vt 4/
/2
4:
:4
P M
01-12
COVER - VOLUME 2 RENOVATE 9TH FLOOR MENTAL
HEALTH
1111 EAST END BLVD, WILKES-BARRE, PA 18711
693-19-106
01 & 17
04/18/2023 DR ZAM
100% CONSTRUCTION
DOCUMENTS
VEG 19.25
WILKES-BARRE VA MEDICAL CENTER
1111 EAST END BLVD, WILKES-BARRE, PA 18711
VAMC PROJECT #: 693-19-106
RENOVATE 9TH FLOOR MENTAL HEALTH
DWG 01 of 01 F
IN
A L
D R
A W
IN
G
S S
U B
M
IT
T A
L
SHEET
NUMBER SHEET NAME
GENERAL
01-12 COVER - VOLUME 2
PLUMBING
01-P1 PLUMBING ABBREVIATIONS, SYMBOLS, & LEGENDS
01-P2 EQUIPMENT & FIXTURE SCHEDULES
01-P3 DEMOLITION PLAN - 8TH FLOOR WEST
01-P4 DEMOLITION PLAN - 8TH FLOOR CENTER
01-P5 DEMOLITION PLAN - 8TH FLOOR EAST
01-P6 DEMOLITION PLAN - 9TH FLOOR WEST
01-P7 DEMOLITION PLAN - 9TH FLOOR CENTER
01-P8 DEMOLITION PLAN - 9TH FLOOR EAST
17-P9 DEMOLITION PLAN - WAREHOUSE
01-P10 DOMESTIC WATER PLAN - 9TH FLOOR WEST
01-P11 DOMESTIC WATER PLAN - 9TH FLOOR CENTER
01-P12 DOMESTIC WATER PLAN - 9TH FLOOR EAST
17-P13 DOMESTIC WATER PLAN - WAREHOUSE
01-P14 DOMESTIC WATER ISOMETRIC
01-P15 DRAIN-WASTE-VENT PLAN - 8TH FLOOR WEST
01-P16 DRAIN-WASTE-VENT PLAN - 8TH FLOOR CENTER
01-P17 DRAIN-WASTE-VENT PLAN - 8TH FLOOR EAST
01-P18 DRAIN-WASTE-VENT PLAN - 9TH FLOOR WEST
01-P19 DRAIN-WASTE-VENT PLAN - 9TH FLOOR CENTER
01-P20 DRAIN-WASTE-VENT PLAN - 9TH FLOOR EAST
17-P21 DRAIN-WASTE-VENT PLAN - WAREHOUSE
01-P22 DRAIN-WASTE-VENT ISOMETRIC
01-P23 ENLARGED DOMESTIC PLANS
01-P24 ENLARGED DOMESTIC PLANS
MECHANICAL
01-M1 MECHANICAL ABBREVIATIONS & NOTES
01-M2 MECHANICAL SYMBOLS
17-M3 EQUIPMENT SCHEDULES - WAREHOUSE
01-M4 EQUIPMENT SCHEDULES - 9TH FLOOR
01-M5 EQUIPMENT SCHEDULES - 9TH FLOOR
01-M6 DEMOLITION PLAN - 9TH FLOOR WEST
01-M7 DEMOLITION PLAN - 9TH FLOOR CENTER
01-M8 DEMOLITION PLAN - 9TH FLOOR EAST
17-M9 DEMOLITION PLAN - WAREHOUSE
01-M10 HVAC PLAN - 9TH FLOOR WEST
01-M11 HVAC PLAN - 9TH FLOOR CENTER
01-M12 HVAC PLAN - 9TH FLOOR EAST
17-M13 HVAC PLAN - WAREHOUSE
17-M14 HVAC PLAN - WAREHOUSE ROOF
01-M15 PIPING PLAN - 9TH FLOOR WEST
01-M16 PIPING PLAN - 9TH FLOOR CENTER
01-M17 PIPING PLAN - 9TH FLOOR EAST
17-M18 PIPING PLAN - WAREHOUSE
17-M19 PIPING PLAN - WAREHOUSE ROOF
01-M20 CONTROLS & INSTRUMENTATION PLAN - 9TH FLOOR WEST
01-M21 CONTROLS & INSTRUMENTATION PLAN - 9TH FLOOR CENTER
01-M22 CONTROLS & INSTRUMENTATION PLAN - 9TH FLOOR EAST
17-M23 CONTROLS & INSTRUMENTATION PLAN - WAREHOUSE
17-M24 CONTROLS & INSTRUMENTATION PLAN - WAREHOUSE ROOF
01-M25 CONTROLS & INSTRUMENTATION DETAILS
01-M26 CONTROLS & INSTRUMENTATION DETAILS
01-M27 CONTROLS & INSTRUMENTATION DETAILS
01-M28 ENLARGED SECTIONS - 9TH FLOOR
01-M29 TYPICAL PATIENT ROOM - 9TH FLOOR
01-M30 ENLARGED PLANS - 9TH FLOOR
01-M31 ENLARGED PLANS - 9TH FLOOR ROOF
01-M32 TYPICAL DETAILS
01-M33 TYPICAL DETAILS
01-M34 TYPICAL DETAILS
SHEET INDEX - VOLUME 2 OF 2RENDERED IMAGEAREA OF WORK
N o rt h
9TH FLOOR
WAREHOUSE
SHEET
NUMBER SHEET NAME
ELECTRICAL
01-E1 ELECTRICAL ABBREVIATIONS AND GENERAL NOTES
01-E2 ELECTRICAL SYMBOLS
01-E3 DEMOLITION PLAN - 9TH FLOOR WEST
01-E4 DEMOLITION PLAN - 9TH FLOOR CENTER
01-E5 DEMOLITION PLAN - 9TH FLOOR EAST
17-E6 DEMOLITION PLAN - WAREHOUSE
01-E7 DEMOLITION RCP - 9TH FLOOR WEST
01-E8 DEMOLITION RCP - 9TH FLOOR CENTER
01-E9 DEMOLITION RCP - 9TH FLOOR EAST
17-E10 DEMOLITION RCP - WAREHOUSE
01-E11 LIGHTING RCP - 9TH FLOOR WEST
01-E12 LIGHTING RCP - 9TH FLOOR CENTER
01-E13 LIGHTING RCP - 9TH FLOOR EAST
17-E14 LIGHTING RCP - WAREHOUSE
01-E15 LIGHTING CONTROL RCP - 9TH FLOOR WEST
01-E16 LIGHTING CONTROL RCP - 9TH FLOOR CENTER
01-E17 LIGHTING CONTROL RCP - 9TH FLOOR EAST
17-E18 LIGHTING CONTROL RCP - WAREHOUSE
01-E19 LIGHTING FIXTURE SCHEDULES
01-E20 LIGHTING CONTROL SCHEDULES
01-E21 LIGHTING CONTROL PANEL SCHEDULES
01-E22 DIGITAL LOW VOLTAGE LIGHTING CONTROL WIRING DIAGRAMS
01-E23 ANALOG LINE VOLTAGE LIGHTING CONTROL WIRING DIAGRAMS
01-E24 NETWORKED LIGHTING CONTROL DETAILS
01-E25 POWER PLAN - 9TH FLOOR WEST
01-E26 POWER PLAN - 9TH FLOOR CENTER
01-E27 POWER PLAN - 9TH FLOOR EAST
17-E28 POWER PLAN - WAREHOUSE
17-E29 POWER PLAN - WAREHOUSE ROOF
01-E30 EQUIPMENT SCHEDULE
01-E31 PANEL SCHEDULES - 9TH FLOOR
01-E32 PANEL SCHEDULES - 9TH FLOOR
01-E33 PANEL SCHEDULES - 9TH FLOOR
17-E34 PANEL SCHEDULES - WAREHOUSE
01-E35 SINGLE LINE DIAGRAM EMERGENCY
01-E36 SINGLE LINE DIAGRAM NORMAL
01-E37 ELECTRICAL RISER DIAGRAM
01-E38 SINGLE LINE DIAGRAM
01-E39 ONE-LINE DIAGRAM
01-E40 TELECOM PLAN - 9TH FLOOR WEST
01-E41 TELECOM PLAN - 9TH FLOOR CENTER
01-E42 TELECOM PLAN - 9TH FLOOR EAST
17-E43 TELECOM PLAN - WAREHOUSE
01-E44 NURSE CALL PLAN - 9TH FLOOR WEST
01-E45 NURSE CALL PLAN - 9TH FLOOR CENTER
01-E46 NURSE CALL PLAN - 9TH FLOOR EAST
01-E47 SECURITY PLAN - 9TH FLOOR WEST
01-E48 SECURITY PLAN - 9TH FLOOR CENTER
01-E49 SECURITY PLAN - 9TH FLOOR EAST
17-E50 SECURITY PLAN - WAREHOUSE
01-E51 ENLARGED TELECOM TR ROOM
17-E52 ENLARGED TELECOM TR ROOM - WAREHOUSE
01-E53 TELECOM DETAILS
01-E54 TYPICAL DETAILS
01-E55 TYPICAL DETAILS
0 100% CONSTRUCTION DOCUMENTS 04/18/2023
ZMiller Image
GENERAL PLUMBING SYMBOLS
DIRECTION OF PIPE PITCH (DOWN)
DIRECTION OF FLOW
GUIDE
ANCHOR
REDUCER OR INCREASER
ECCENTRIC REDUCER
TOP CONNECTION, 45° OR 90°
BOTTOM CONNECTION, 45° OR 90°
SIDE CONNECTION
CAPPED OUTLET
RISE OR DROP IN PIPE
UNION
PIPE UP
PIPE DOWN
POINT OF CONNECTION BETWEEN NEW
AND EXISTING WORK
LIMIT OF DEMOLITION
INVERTED BUCKET TRAP SET INCLUDING
PIPING ACCESSORIES
FLOAT & THERMOSTATIC TRAP SET
INCLUDING PIPING ACCESSORIES
STRAINER
THERMOMETER
PRESSURE GAGE
FLOW ELEMENT
WALL CLEAN OUT
CLEAN OUT
HOSE BIBB, FAUCET HEAD, SHOWER HEAD
WATER HAMMER ARRESTOR (PLAN VIEW)
FE
CO
MA
MV
LA
LV
OA
IA
D
SS
SD
SD
TWR
DWS
DWR
TWS
SS
SCW
FCW
NO
O
N
NG
NG
FOD
FOS
FOR
FOV
PLUMBING PIPING SYMBOLS
DOMESTIC COLD WATER, COLD WATER
DOMESTIC HOT WATER, HOT WATER
DOMESTIC HOT WATER RETURN
MEDICAL AIR
MEDICAL VACUUM
LABORATORY AIR
LABORATORY VACUUM
ORAL EVACUATION
INDUSTRIAL AIR
DRAIN
VENT (SANITARY)
SOIL, WASTE, OR SANITARY SEWER
SANITARY SEWER, BELOW GRADE
STORM WATER
STORM WATER, BELOW GRADE
SOFTEN COLD WATER
FILTERED COLD WATER
DRINKING WATER SUPPLY
DRINKING WATER RETURN
TEMPERED WATER RETURN
TEMPERED WATER SUPPLY
NITROUS OXIDE
OXYGEN
NITROGEN
NATURAL GAS
NATURAL GAS, BELOW GRADE
FUEL OIL DISCHARGE
FUEL OIL SUPPLY
FUEL OIL VENT
FUEL OIL RETURN
REAGENT WATER
REAGENT WATER RETURN
CORROSION RESISTANT SANITARY SEWER
CORROSION RESISTANT VENT (SANITARY)
GREASE WASTE
NEW PIPING
EXISTING PIPING
PIPE TO BE DEMOLISHED
FIXTURE OR EQUIPMENT TO BE DEMOLISHED
AV
PLUMBING VALVE SYMBOLS
GENERIC VALVE (REF SPEC FOR TYPE)
GENERIC VALVE WITH 3/4" HOSE ADAPTER
CHECK VALVE
ANGLE GLOBE VALVE
BUTTERFLY VALVE
BALL VALVE
CONTROL VALVE
THREE-WAY CONTROL VALVE
PRESSURE REGULATING VALVE
AUTOMATIC FLOW CONTROL VALVE
PRESSURE RELIEF VALVE
MANUAL AIR VENT
TEST PLUG (PRESSURE/TEMPERATURE)
AUTOMATIC AIR VENT
THERMOSTATIC MIXING VALVE
IN LINE FILTER
RWR
RW
V CRP
SS CRP
GW
P-###
H4
H7
A
DETAIL NUMBER
DRAWING NUMBER WHERE SHOWN
SECTION LETTER
TYPICAL FIXTURE NUMBER
DRAWING NUMBER WHERE DRAWN
DRAWING SYMBOLS
NEW FIXTURE/EQUIPMENT (SHAPE VARIES, REF: SYMBOLS,
TAGS, & NOTES. SCHEDULED ITEMS ARE NEW UNO)
(E) EXISTING COMPONENT
(X) DEMOLISHED COMPONENT
26-SF 3
TYPICAL EQUIPMENT NUMBER
## GENERAL EQUIPMENT FURNISHED BY OTHERS; REF SHEET
01-P2 FOR CONNECTION SCHEDULE
DOUBLE-LINED VALVE
(REFER TO SPECS FOR TYPE)
PLUMBING GENERAL NOTES
A. PIPING IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN A FURRED
CHASE OR ABOVE THE CEILING. REF SPECIFICATION SECTION 22 05 11.
B. REFER TO ARCHITECTURAL CEILING PLANS FOR CEILING TYPES IN EACH
SPACE. MINIMUM 18"X18" ACCESS PANELS ARE REQUIRED IN HARD CEILINGS
FOR VALVES, TRAPS, DAMPERS, CLEANOUTS, CONTROLS, AND SO FORTH.
COORDINATE FINAL LOCATIONS IN THE FIELD FOR BEST ACCESS. REF
SPECIFICATION 08 31 13.
C. PROVIDE ACOUSTICAL SEALANT PER SPECIFICATION SECTION 07 92 00 AT
PIPE PENETRATIONS THROUGH SOUND RATED PARTITIONS.
D. SUBMIT COMPLETE CONSOLIDATED AND COORDINATED SHOP DRAWINGS
FOR NEW SYSTEMS, AND FOR EXISTING SYSTEMS THAT ARE IN THE SAME
AREAS. DO NOT INSTALL EQUIPMENT FOUNDATIONS, EQUIPMENT, OR PIPING
UNTIL COORDINATION/SHOP DRAWINGS HAVE BEEN APPROVED. REF
SPECIFICATION SECTIONS 01 33 23 AND 22 05 11.
PLUMBING ASCE 7-16 NONSTRUCTURAL SEISMIC
RESTRAINT AND ANCHORAGE NOTES
PROVIDE AND DESIGN SEISMIC BRACING FOR PLUMBING EQUIPMENT, PIPING
AND DUCTWORK IN ACCORDANCE WITH SPECIFICATION SECTION 13 05 41
SEISMIC RESTRAINT REQUIREMENTS FOR NONSTRUCTURAL COMPONENTS.
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\U se rs
\J D ez m an \D oc um en ts
\1 9.
_M
E C
H -P
LU
M
_R
_J D ez m an .rv t 4/
/2
1:
:3
P M
01-P1
PLUMBING ABBREVIATIONS,
SYMBOLS, & LEGENDS
RENOVATE 9TH FLOOR MENTAL
HEALTH
1111 EAST END BLVD, WILKES-BARRE, PA 18711
693-19-106
01 & 17
04/18/2023 MB RT
100% CONSTRUCTION
DOCUMENTS
VEG 19.25 DWG 1 of 24 F
IN
A L
D R
A W
IN
G
S U
B M
IT
T
A L
A
A/E ARCHITECT/ENGINEER
AD AREA DRAIN/ACCESS DOOR
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AG AIR GAP
AS AUTOMATIC SPRINKLER
ASD ADJUSTABLE SPEED DRIVES
ASD AUTOMATIC SPRINKLER DRAIN
ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATION,
AND AIR CONDITIONING ENGINEERS
ASME AMERICAN SOCIETY OF MECHANCIAL ENGINEERS
ASPE AMERICAN SOCIETY OF PLUMBING ENGINEERS
AV ACID VENT
AW ACID WASTE
B
BAS BUILDING AUTOMATION SYSTEM
BFP REDUCED PRESSURE BACKFLOW PREVENTER
BHP BREAK HORSEPOWER
BOD BASIS OF DESIGN
BSP BLACK STEEL PIPE
BT BATHTUB
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
C
CA COMPRESSED AIR
CFM CUBIC FEET PER MINUTE
CGA COMPRESSED GAS ASSOCATION
CI CAST IRON
CO CLEANOUT
CRP CORROSION RESISTANT PIPE
CS CLINICAL SINK
CV CONTROL VALVE
D
DCW DOMESTIC COLD WATER
DEMO DEMOLISH
DFU DRAINAGE FIXTURE UNITS
DHW DOMESTIC HOT WATER
DHWR DOMESTIC HOT WATER RETURN
DI DEIONIZED WATER
DIV DIVISION
DN DOWN
DOE DEPARTMENT OF ENERGY
DS DOWNSPOUT
DW DISHWASHER
DWG DRAWING
DWH DOMESTIC WATER HEATER
DWR DRINKING WATER RETURN
DWS DRINKING WATER SUPPLY
DWV DRAIN WASTE VENT
E
EL ELEVATION
EMCS ENERGY MANAGEMENT CONTROL SYSTEM
EPA ENVIRONMENTAL PROTECTION AGENCY
EPACT ENERGY POLICY ACT
ESC ESCUTCHEON
ESH EMERGENCY SHOWER
ET EXPANSION TANK
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EWS EYE WASH STATION
EWS/SH EYE WASH/DRENCH SHOWER
EX EXISTING
F
F FARENHEIT
FCO FLOOR CLEANOUT
FCW FILTERED COLD WATER
FD FLOOR DRAIN
FDC FIRE DEPARTMENT (HOSE) CONNECTION
FM FLOW METER
FOP FUEL OIL PUMP
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FOV FUEL OIL VENT
FS FLOOR SINK
FS FLOW SWITCH
FU FIXTURE UNITS
G
GAL GALLON
GCO GRADE CLEANOUT
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPR GAS PRESSURE REGULATOR
GRS GAS REGULATOR STATION
GT GREASE TRAP
GVTR GAS VENT THROUGH ROOF
GWB GYPSUM WALL BOARD
GWH GAS FIRED WATER HEATER
PLUMBING ABBREVIATIONS
H
HB HOSE BIB
HD HUB DRAIN
HP HORSEPOWER
HR HR
HS HAND SINK
HST HOT WATER STORAGE TANK (DOMESTIC)
HWB HOT WATER BOILER
HWCP HOT WATER CIRCULATING PUMP
HWP HOT WATER PUMP
HX HEAT EXCHANGER
HYD HYDRANT
I
ICW INDUSTRIAL COLD WATER
ID INSIDE DIAMETER
IE INVERT ELEVATION
IHW INDUSTRIAL HOT WATER
INV INVERT
IPC INTERNATIONAL PLUMBING CODE
IRW IRRIGATION WATER
IW INDIRECT WASTE
IWH INSTANTANEOUS WATER HEATER
IWR INDUSTRIAL WATER RETURN
IWS INDUSTRIAL WATER SUPPLY
K
KW KILOWATT
KWH KILOWATT-HOUR
L
LA LABORATORY AIR
LAV LAVATORY
LB POUND
LCW LABORATORY COLD WATER
LHW LABORATORY HOT WATER
LNG LIQUID NATURAL GAS
LOX LIQUID OXYGEN
LV LABORATORY VACUUM
LW LOW WATER
M
M METER
MA MEDICAL AIR
MAV MANUAL AIR VENT
MBH 1000 BTUH
MED MEDICAL
MER MECHANICAL EQUIPMENT ROOM
MFR MANUFACTURER
MH MANHOLE
MOU MEMORANDUM OF UNDERSTANDING
MSB MOP SERVICE BASIN
MV MEDICAL VACUUM
N
N2 NITROGEN
N2O NITROUS OXIDE
NC NORMALLY CLOSED
NG NATURAL GAS
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NOM NOMINAL
NPS NOMINAL PIPE SIZE
NPW NON POTABLE WATER
NTS NOT TO SCALE
O
O2 OXYGEN
OC ON CENTER
OD OUTSIDE DIAMETER
OFD OVERFLOW DRAIN
OH OVER HEAD
OR OPERATING ROOM
OVFL OVERFLOW
P
P&ID PROCESS & INSTRUMENTATION DIAGRAM
PB PUSH BUTTON
PD PRESSURE DROP OR DIFFERENCE
PDI PLUMBING AND DRAINAGE INSTITUTE
PG PRESSURE GAUGE
PH PHASE
PLBG PLUMBING
PLUM PLUMBING
PP PLUMBING PUMP
PPM PARTS PER MILLION
PRS PRESSURE REDUCING STATION
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH ABSOLUTE
PSIG POUNDS PER SQUARE INCH GAGE
PTRV PRESSURE TEMPERATURE RELIEF VALVE
PW POTABLE WATER
R
RD ROOF DRAIN
RDL ROOF DRAIN LEADER
REF REFERENCE OR REFER TO
RH ROOF HYDRANT
RL ROOF LEADER
RO REVERSE OSMOSIS WATER
RP RECIRCULATION PUMP
RPZA REDUCED PRESSURE BACKFLOW PREVENTION
ASSEMBLY
RW REAGENT WATER
RWL RAIN WATER LEADER
RWR REAGENT WATER RETURN
S
SAN SANITARY SEWER
SCFM STANDARD CUBIC FEET PER MINUTE
SCW SOFTENED COLD WATER
SDMH STORM DRAIN MANHOLE
SIM SIMILAR
SMACNA SHEET METAL AND AIR CONDITIONING
CONTRACTORS NATIONAL ASSOCATION
SMH SANITARY MANHOLE
SP SUMP PUMP
SPR SPRINKLER LINE
SQFT/SF SQUARE FEET
SS SANITARY SEWER
SST STAINLESS STEEL
ST STORAGE TANK
SW STORM WATER
T
TCV TEMPERATURE CONTROL VALVE
TD TEMPERATURE DIFFERENCE
TD TRENCH DRAIN
TDH TOTAL DYNAMIC HEAD
TEMP TEMPERATURE
TMV THERMOSTATIC MIXING VALVE
TP TRAP PRIMER
TSTAT THERMOSTAT
TWR TEMPERED WATER RETURN
TWS TEMPERED WATER SUPPLY
TYP TYPICAL
U
UF UNDER FLOOR
UNO UNLESS NOTED OTHERWISE
UR URINAL
V
V VENT
VAC VACUUM OR VOLTAGE (AC)
VB VACUUM BREAKER
VCO VACUUM CLEANER OUTLET
VP VACUUM PUMP
VS VENT STACK
VSD VARIABLE SPEED DRIVE
VTR VENT THROUGH ROOF
W
W WASTE
WC WATER CLOSET
WCO WALL CLEANOUT
WG WATER GAGE
WH WALL HYDRANT
WH WATER HEATER
WHA WATER HAMMER ARRESTER
WL WATER LINE
WM WATER METER
WPD WATER PRESSURE DROP
WS WASTE STACK
WSFU WATER SUPPLY FIXTURE UNITS
X
XP EXPLOSION PROOF
Y
YCO YARD CLEANOUT
YH YARD HYDRANT
0 100% CONSTRUCTION DOCUMENTS 04/18/2023
04/20/2023
A. FOR ALL SCHEDULED EQUIPMENT, PROVIDE BASIS OF DESIGN OR APPROVED
EQUAL. REFER TO SPECIFICATIONS SECTIONS 01 33 23 AND 22 05 11 FOR
FURTHER REQUIREMENTS.
REMARKS:
1. REFER ALSO TO SPECIFICATION
SECTIONS 22 40 00 AND 22 13 00.
2. FIXTURES SHALL BE ACCESSIBLE
UNO. REFER TO GENERAL AND
ARCH PLANS FOR REQUIREMENTS.
3. PROVIDE AN IN-LINE LEGIONELLA
FILTER.
REMARKS:
1. REFER ALSO TO SPECIFICATIONS
SECTIONS:
A. 22 11 23 FOR DCW & DHW
PUMPS.
B. 22 13 29 FOR SW PUMPS.
C. 22 14 29 FOR SUMP PUMPS.
REMARKS:
1. REFER ALSO TO SPECIFICATION
SECTION 22 33 00.
2. SET TO STAGE 2.
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\U se rs
\J D ez m an \D oc um en ts
\1 9.
_M
E C
H -P
LU
M
_R
_J D ez m an .rv t 4/
/2
1:
:3
P M
01-P2
EQUIPMENT & FIXTURE
SCHEDULES
RENOVATE 9TH FLOOR MENTAL
HEALTH
1111 EAST END BLVD, WILKES-BARRE, PA 18711
693-19-106
01 & 17
04/18/2023 MB RT
100% CONSTRUCTION
DOCUMENTS
VEG 19.25 DWG 2 of 24 F
IN
A L
D R
A W
IN
G
S U
B M
IT
T
A L
PLUMBING FIXTURE SCHEDULE
MARK DESCRIPTION
DCW
CONNECTION
(NPS)
DHW
CONNECTION
(NPS)
SS
CONNECTION
(NPS)
VENT
CONNECTION
(NPS) REMARKS
FD-B3 FLOOR DRAIN, 7" WITH SECONDARY STRAINER - - 3 1 1/2 1,2
FD-C3 FLOOR DRAIN, 6" FOR TILE FLOOR - - 3 1 1/2 1,2
FD-D3 FLOOR DRAIN, 6" FOR MEMBRANE FLOOR - - 3 1 1/2 1,2
FD-E4 FLOOR DRAIN, 12" WITH SEDIMENT BUCKET - - 4 2 1,2
FD-S3 FLOOR SINK, 12" SST WITH DOME STRAINER - - 3 2 1,2
P-101 WC, FLOOR MOUNT, FLUSH VALVE 1 - 4 2 1,2
P-103 WC, WALL MOUNT, FLUSH VALVE 1 - 4 2 1,2
P-408 LAV, SMALL WALL MOUNT, WRIST CONTROL, 4" CENTERS 1/2 1/2 1 1/2 1 1/2 1,2
P-417 LAVATORY 1/2 1/2 1 1/2 1 1/2 1,2
P-501 SERVICE SINK 1/2 1/2 1 1/2 1 1/2 1,2
P-502 MOP SERVICE SINK, FLOOR MOUNT 1/2 1/2 3 1 1/2 1,2
P-528 SINK, COUNTER MOUNT 1/2 1/2 1 1/2 1 1/2 1,2
P-808 WASHING MACHINE SUPPLY AND DRAIN UNIT 1/2 1/2 2 1.5 1,2
P-910
WC, LIGATURE RESISTANT, FLOOR MOUNT REAR OUTLET, REAR SPUD
CONCEALED SENSOR FLUSH VALVE
1 - 4 2 1,2
P-912
WC, LIGATURE RESISTANT, WALL MOUNT, BARIATRIC, REAR OUTLET,
REAR SPUD CONCEALED SENSOR FLUSH VALVE
1 - 4 2 1,2
P-930 LAV, LIGATURE RESISTANT, NON-ACCESSIBLE 1/2 1/2 1 1/2 1 1/2 1,2
P-935 1 COMPARTMENT, ANTI-LIGATURE, WHEELCHAIR 1/2 1/2 1 1/2 1 1/2 1,2
P-940 LIGATURE RESISTANT SHOWER BATH MIXING VALVE 3/4 3/4 3 1 1/2 1,2,3
P-941 BARIATRIC LIGATURE RESISTANT SHOWER BATH MIXING VALVE 3/4 3/4 3 1 1/2 1,2,3
PLUMBING PUMP (PP) SCHEDULE
MARK LOCATION
AREA AND/OR BLDG
SERVED SYSTEM PUMP TYPE FLUID GPM
HEAD
(FT WG)
FLUID
TEMP
(°F)
MIN %
EFF
ELECTRICAL/MOTOR DATA
BASIS OF DESIGN REMARKSHP VAC PH CONTROL
1-BP-1 C9-36 MECH 9TH FLOOR DCW END SUCTION
DOMESTIC
WATER
85 69.3 68 52.2 2 208 3 VARIABLE GRUNDFOS HYDRO MULTI-E 3 CRE 5-6 1
1-PP-1 C9-36 MECH 9TH FLOOR DCWR CANNED ROTOR
DOMESTIC
WATER
5 15.5 68 0 1/4 115 1 CONSTANT GRUNDFOS UPS 26-99 SFC 1
1-PP-2 C9-36 MECH 9TH FLOOR DHWR CANNED ROTOR
DOMESTIC
WATER
5 15.5 140 0 1/4 115 1 CONSTANT GRUNDFOS UPS 26-99 SFC 1
ELECTRIC WATER HEATER (EWH) SCHEDULE
MARK LOCATION TYPE
TOTAL
KW
CONNECTION
SIZE (IN)
DESIGN DHW
TEMP
(°F)
ELECTRICAL DATA
BASIS OF DESIGN OR
APPROVED EQUAL REMARKSVAC PH MCA MOCP
17-WH-1 BLDG 17 - UNDER SINK
POINT OF
USE
7.2 1/2 90 208 1 26 35 STIEBEL ELTRON DHC-E8 1,2
17-WH-2 BLDG 17 - UNDER SINK
POINT OF
USE
7.2 1/2 100 208 1 26 35 STIEBEL ELTRON DHC-E8 1
17-WH-3 BLDG 17 - UNDER SINK
POINT OF
USE
9 1/2 100 208 1 44 50 STIEBEL ELTRON DHC-E12 1,2
17-WH-4 BLDG 17 - UNDER SINK
POINT OF
USE
7.2 1/2 100 208 1 26 35 STIEBEL ELTRON DHC-E8 1,2
A. REFER TO 01-P1 FOR PLUMBING SYMBOLS, ABBREVIATIONS, AND GENERAL
NOTES.
B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE
VHA COR BEFORE PROCEEDING WITH WORK.
C. REFER TO I SHEET SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED
LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP
PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE
SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL
PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN
SHALL GOVERN.
D. REFER TO SPECIFICATIONS SECTIONS 01 00 00 AND 23 05 11 FOR SELECTIVE
DEMOLITION AND REPAIR REQUIREMENTS. PATCH OPENINGS REMAINING IN
EXISTING CONSTRUCTION FOLLOWING DEMOLITION OF PENETRATIONS NOT
REPLACED IN KIND. MATCH AESTHETICS AND LIFE SAFETY RATINGS OF THE
SURROUNDING CONSTRUCTION. ENGAGE LICENSED AND SITE-APPROVED
ROOFING CONTRACTOR TO PATCH AND SEAL WHERE ITEMS ARE REMOVED
THROUGH THE EXISTING ROOF. MAINTAIN EXISTING WARRANTIES.
E. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT
PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING
HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN
ACCORDANCE WITH THE SPECIFICATIONS.
F. REFER TO I SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.
G. PROVIDE SERVICE VALVES AT LIMITS OF DEMOLITION. CAP ENDS WHERE
NOT RECONNECTED IN NEW WORK. EXISTING SYSTEMS SHALL REMAIN IN
SERVICE FOLLOWING DEMOLITION. REFER TO 22 05 11 FOR DEAD END
REQUIREMENTS.
H. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:
a. DOMESTIC WATER
b. MED GAS
c. STORM DRAINAGE
d. VENTS
I. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:
a. SANITARY SEWER
A B C D E F G
F
-P
F
-P
4"ø SS OH
4" ø
S S
O H
4" ø S
S O H
4"ø SS OH
4" ø
S S
O H
4"ø SS OH
4" ø
S S
O H
2"ø SS OH
4" ø
S S
O H
4"ø SS OH
4"ø SS OH
4" ø
S S
O H
4"ø SS OH
4" ø
S S
O H4" ø S S O
H
2" ø
S S
O H
4"ø SS4"ø SS
2"ø SS
4"ø SS
2"ø SS OH 4"ø SS OH
4"ø SS OH
4" ø S
S O H
4" ø
S S
O H
4"ø SS
4" ø
S S
2 1/2"ø DHW
2 1/2"ø DCW
E-9
ELEVATOR
E-8
ELEVATOR
E-7
ELEVATOR
C8-81
OFFICE
C8-82
OFFICE
C8-83
OFFICE
C8-84
OFFICE
C8-72
OFFICE
C8-71
WAITINGC8-13A
RECEPTION
C8-69
SOILED UTILITY
C8-68
CLEAN STORAGE
C8-61
PATIENT EDUCATION
ST-1
STAIR
C8-14
ELEC
C8-15
MECH
C8-02
CLEAN STORAGE
C8-03
TECHNICIAN ROOM
C8-04
SOILED UTILITY
C8-05
SLEEP ROOM
C8-05A
BATH
C8-06A
BATH
C8-06
SLEEP ROOM
C8-07
BARIATRIC SLEEP
ROOM
C8-07A
BARIATRIC BATH
C8-08A
BATH
C8-08
SLEEP ROOM
C8-09
SLEEP LAB MGR
OFFICE
C8-100
CORRIDOR
C8-70
CORRIDOR
C8-12
NUTRITION
C8-16
JANITOR CLOSET
C8-17
ELECTRICAL
C8-11
TOILET
ST-5
STAIR
C8-21A
UTILITY
C8-21
UTILITY CORRIDOR
C8-24
TEMP NUTREATION
OFFICE
C8-24B
COPY
C8-23
CORRIDOR
C8-20
ELEVATOR LOBBY
C8-23A
KITCHENETTE
C8-23B
BREAK LOCKER
ROOM
C8-70D
ELECTRICAL
C8-18
TOILET
C8-19
TOILET
C8-10
CORRIDOR
C8-101
CORRIDOR
4" ø
S S
O H
C5
01-P23
2"ø DHW3"ø DCW
P la n N o rt h
T ru e N o rt h
BLDG 01
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
00KEYNOTES
KEY PLAN
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\U se rs
\J D ez m an \D oc um en ts
\1 9.
_M
E C
H -P
LU
M
_R
_J D ez m an .rv t 4/
/2
1:
:4
P M
01-P3
DEMOLITION PLAN - 8TH FLOOR
WEST
RENOVATE 9TH FLOOR MENTAL
HEALTH
1111 EAST END BLVD, WILKES-BARRE, PA 18711
693-19-106
04/18/2023 MB RT
100% CONSTRUCTION
DOCUMENTS
VEG 19.25 DWG 3 of 24 F
IN
A L
D R
A W
IN
G
S U
B M
IT
T
A L3/16" = 1'-0"
DEMOLITION PLAN - 8TH FLOOR WEST
F6
B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE
VHA COR BEFORE PROCEEDING WITH WORK.
C. REFER TO I SHEET SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED
LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP
PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE
SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL
PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN
SHALL GOVERN.
D. REFER TO SPECIFICATIONS SECTIONS 01 00 00 AND 23 05 11 FOR SELECTIVE
DEMOLITION AND REPAIR REQUIREMENTS. PATCH OPENINGS REMAINING IN
EXISTING CONSTRUCTION FOLLOWING DEMOLITION OF PENETRATIONS NOT
REPLACED IN KIND. MATCH AESTHETICS AND LIFE SAFETY RATINGS OF THE
SURROUNDING CONSTRUCTION. ENGAGE LICENSED AND SITE-APPROVED
ROOFING CONTRACTOR TO PATCH AND SEAL WHERE ITEMS ARE REMOVED
THROUGH THE EXISTING ROOF. MAINTAIN EXISTING WARRANTIES.
E. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT
PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING
HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN
ACCORDANCE WITH THE SPECIFICATIONS.
F. REFER TO I SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.
G. PROVIDE SERVICE VALVES AT LIMITS OF DEMOLITION. CAP ENDS WHERE
NOT RECONNECTED IN NEW WORK. EXISTING SYSTEMS SHALL REMAIN IN
SERVICE FOLLOWING DEMOLITION. REFER TO 22 05 11 FOR DEAD END
REQUIREMENTS.
H. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:
a. DOMESTIC WATER
b. MED GAS
c. STORM DRAINAGE
d. VENTS
I. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:
a. SANITARY SEWER
H J K L M N O P
F
-P
/F6 01-P3
F
-P
F
-P
2"ø SS OH
2"ø SS OH
4"ø SS OH
4"ø SS OH
4"ø SS OH
4" ø
S S
O H
4"ø SS OH
4" ø
S S
O H
4"ø SS OH
4"ø SS OH
4" ø
S S
O H
2" ø S
S O H
4" ø
S S
O H
4" ø
S S
O H
4"ø SS OH
4"ø SS OH 4"ø SS OH
4"ø SS OH
1 1/2"ø SS OH
1 1/2"ø SS OH
1 1/2"ø SS OH
3"ø DCW 2 1/2"ø DHW
E-5
ELEVATOR
E-6
ELEVATOR
E-4
ELEVATOR
E-3
ELEVATOR
E-2
ELEVATOR
E-1
ELEVATOR
C8-29
C8-51
GROUP ROOM
C8-30
VOLUNTARY
SERVICE STORAGE
C8-52
STORAGE
C8-28
C8-28A
TOILET
C8-27
OFFICE
C8-26
OFFICE
C8-25
OFFICE
C8-51A
TELEPHONE
C8-53
CORRIDOR
C8-26A
TOILET
C8-77
SOCIAL WORK ROOM
C8-54
CORRIDOR
C8-56
MECHANICAL ROOM
ST-3
STAIR
C8-55A C8-55
ELEC
C8-52B
CORRIDOR
C8-57
ASSOC CHIEF
C8-58
SECY
C8-59A
TOILET
C8-59B
TOILET
C8-59
WAITING ROOM
C8-54B
C8-54A
MECHANICAL ROOM
C8-78
CONFERENCE
C8-79
OFFICE
C8-80
OFFICE
C8-76
OFFICE
C8-75
OFFICE
C8-74
OFFICE
C8-73
OFFICE
C8-101
CORRIDOR
C8-52A
CORRIDOR
P la n N o rt h
T ru e N o rt h
BLDG 01
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
00KEYNOTES
KEY PLAN
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\U se rs
\J D ez m an \D oc um en ts
\1 9.
_M
E C
H -P
LU
M
_R
_J D ez m an .rv t 4/
/2
1:
:4
P M
01-P4
DEMOLITION PLAN - 8TH FLOOR
CENTER
RENOVATE 9TH FLOOR MENTAL
HEALTH
1111 EAST END BLVD, WILKES-BARRE, PA 18711
693-19-106
04/18/2023 MB RT
100% CONSTRUCTION
DOCUMENTS
VEG 19.25 DWG 4 of 24 F
IN
A L
D R
A W
IN
G
S U
B M
IT
T
A L3/16" = 1'-0"
DEMOLITION PLAN - 8TH FLOOR CENTER
F6
B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE
VHA COR BEFORE PROCEEDING WITH WORK.
C. REFER TO I SHEET SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED
LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP
PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE
SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL
PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN
SHALL GOVERN.
D. REFER TO SPECIFICATIONS SECTIONS 01 00 00 AND 23 05 11 FOR SELECTIVE
DEMOLITION AND REPAIR REQUIREMENTS. PATCH OPENINGS REMAINING IN
EXISTING CONSTRUCTION FOLLOWING DEMOLITION OF PENETRATIONS NOT
REPLACED IN KIND. MATCH AESTHETICS AND LIFE SAFETY RATINGS OF THE
SURROUNDING CONSTRUCTION. ENGAGE LICENSED AND SITE-APPROVED
ROOFING CONTRACTOR TO PATCH AND SEAL WHERE ITEMS ARE REMOVED
THROUGH THE EXISTING ROOF. MAINTAIN EXISTING WARRANTIES.
E. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT
PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING
HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN
ACCORDANCE WITH THE SPECIFICATIONS.
F. REFER TO I SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.
G. PROVIDE SERVICE VALVES AT LIMITS OF DEMOLITION. CAP ENDS WHERE
NOT RECONNECTED IN NEW WORK. EXISTING SYSTEMS SHALL REMAIN IN
SERVICE FOLLOWING DEMOLITION. REFER TO 22 05 11 FOR DEAD END
REQUIREMENTS.
H. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:
a. DOMESTIC WATER
b. MED GAS
c. STORM DRAINAGE
d. VENTS
I. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:
a. SANITARY SEWER
Q R S T U V
F
-P
F
-P
1 1/2"ø SS OH
1 1/2"ø SS OH
4" ø
S S
O H
C8-43B
TOILET
C8-43A
TOILET
C8-35
ST-2
STAIR
C8-42A
MECH
C8-42
ELEC
C8-40
GROUP ROOM C8-37A
OFFICE
C8-37
C8-38
EMPLOYEE FITNESS
C8-39
CORRIDOR
C8-36A
STORAGE
C8-38A
TOILET
C8-36
OFFICE
C8-45
TOILET
C8-41
CORRIDOR
C8-46
CORRIDOR
C8-49
OFFICE
C8-47A
HAC
C8-47
ELECTRICAL
C8-33
STORAGE
C8-32
STORAGE
C8-50A
TOILET
C8-50
C8-34
STORAGE
C8-30
VOLUNTARY
SERVICE STORAGE
C8-49A
OFFICE
C8-49B
MECHANICAL
C8-49C
ELECTRICAL
P la n N o rt h
T ru e N o rt h
BLDG 01
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
00KEYNOTES
KEY PLAN
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\U se rs
\J D ez m an \D oc um en ts
\1 9.
_M
E C
H -P
LU
M
_R
_J D ez m an .rv t 4/
/2
1:
:4
P M
01-P5
DEMOLITION PLAN - 8TH FLOOR
EAST
RENOVATE 9TH FLOOR MENTAL
HEALTH
1111 EAST END BLVD, WILKES-BARRE, PA 18711
693-19-106
04/18/2023 MB RT
100% CONSTRUCTION
DOCUMENTS
VEG 19.25 DWG 5 of 24 F
IN
A L
D R
A W
IN
G
S U
B M
IT
T
A L3/16" = 1'-0"
DEMOLITION PLAN - 8TH FLOOR EAST
F6
4" RWC
FD "B"
2"
3/4" H & CW DN.
3/4"
4" S & VENT UP
4" S & VTR
2" HW
4" CW
1/2" H & CW
2" SD "C"
2" SD "C"
2" SD "C"
4"
2"
1 1/2"
4" CW
2" HW
1 1/2"
2"
2" (RAC)
2" VENT UP
2" VENT UP
2"
2"
2"
3/4"
3/4"
1/2" RECIRC
1" CW
3/4"
3/4"
1/2"
1/2"
3/4"
2" SD "C"
3/4"1 1/2"
1/2"
1/2"
2" 1"
2" SD "C"
1/2"
2" SD "C"
2" SD "C"
1/2" HW & CW DN.
1 1/2" CW DN.
3/4" HW DN.
1 1/2"1"
1 1/2" CW &
1/2" HW DN.
SA-"B"
3/4" HW DN.
1 1/2" CW DN.
1 1/2"
1" 2"
1 1/2"
3/4" 1 1/2"
2"
1 1/2" 2"
1" 1"
1/2" H & CW
1 1/4"
1/2"
1/2" CW & HW DN.
1 1/4" CW
1/2" HW
1 1/4"
1/2" CW & HW DN.
1 1/4" CW DN.
3/4"
1 1/2"
SA-"B"
3/4" CW & HW DN.
1/2" CW & HW
DN.
1/2" CW & HW
DN.
2 1/2" H & CW UP FROM BELOW. CAP LINES
BELOW FLOOR IN CHASE.
2" STANDPIPE AND 2" WASTE BELOW
FLOOR
3/4" CW & HW
DN.
1 1/2" VENT UP
2" STAND PIPE 2" WASTE BELOW
FLOOR
3/4" CW & HW
DN.
1 1/4" CW & 1/2" HW
DN.
1/2" CW & HW DN.
1 1/4" CW & 1/2"
HW DN.
4" SAN DN. 2"
VENT UP
1 1/4" CW & 1/2" HW
DN.
1 1/4" CW & 1/2"
HW DN.
1 1/2" CW & 1/2" HW DN.
TO WC & LAV
3/4" CW TO HB
3/4" CW UP
2" W DN. 2" V UP
1 1/4" CW & 1/2"
HW DN.
1 1/2" CW & 1/2"
HW DN.
3/4" CW & HW DN.
A. REFER TO 01-P1 FOR PLUMBING SYMBOLS, ABBREVIATIONS, AND GENERAL
NOTES.
B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE
VHA COR BEFORE PROCEEDING WITH WORK.
C. REFER TO I SHEET SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED
LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP
PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE
SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL
PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN
SHALL GOVERN.
D. REFER TO SPECIFICATIONS SECTIONS 01 00 00 AND 23 05 11 FOR SELECTIVE
DEMOLITION AND REPAIR REQUIREMENTS. PATCH OPENINGS REMAINING IN
EXISTING CONSTRUCTION FOLLOWING DEMOLITION OF PENETRATIONS NOT
REPLACED IN KIND. MATCH AESTHETICS AND LIFE SAFETY RATINGS OF THE
SURROUNDING CONSTRUCTION. ENGAGE LICENSED AND SITE-APPROVED
ROOFING CONTRACTOR TO PATCH AND SEAL WHERE ITEMS ARE REMOVED
THROUGH THE EXISTING ROOF. MAINTAIN EXISTING WARRANTIES.
E. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT
PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING
HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN
ACCORDANCE WITH THE SPECIFICATIONS.
F. REFER TO I SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.
G. PROVIDE SERVICE VALVES AT LIMITS OF DEMOLITION. CAP ENDS WHERE
NOT RECONNECTED IN NEW WORK. EXISTING SYSTEMS SHALL REMAIN IN
SERVICE FOLLOWING DEMOLITION. REFER TO 22 05 11 FOR DEAD END
REQUIREMENTS.
H. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:
a. DOMESTIC WATER
b. MED GAS
c. STORM DRAINAGE
d. VENTS
I. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:
a. SANITARY SEWER
1 S&V 1
S&V 2 S&V 3 S&V 4
S&V 6
S&V 5
S&V 7
S&V 8
S&V 37
S&V 33
1 1
1 1
A B C D E F G
F
-P
F
-P
TYP
P la n N o rt h
T ru e N o rt h
BLDG 01
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
00KEYNOTES
KEY PLAN
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\U se rs
\J D ez m an \D oc um en ts
\1 9.
_M
E C
H -P
LU
M
_R
_J D ez m an .rv t 4/
/2
1:
:4
P M
01-P6
DEMOLITION PLAN - 9TH FLOOR
WEST
RENOVATE 9TH FLOOR MENTAL
HEALTH
1111 EAST END BLVD, WILKES-BARRE, PA 18711
693-19-106
04/18/2023 MB RT
100% CONSTRUCTION
DOCUMENTS
VEG 19.25 DWG 6 of 24 F
IN
A L
D R
A W
IN
G
S U
B M
IT
T
A L
1. RISER S+V NUMBERS REFER TO EXISTING SEWER AND VENT RISER TO
REMAIN.
2. EXISTING DOMESTIC HOT & COLD WATER RISER LOCATION TO REMAIN.
3. INTENT IS TO DEMOLISH PLUMBING SERVING THE 9TH FLOOR BACK TO
EXISTING RISERS.
3/16" = 1'-0"
DEMOLITION PLAN - 9TH FLOOR WEST
F6
2" SD "C"
2" SD "C"
1 1/2"
1 1/2"
2"
1"
1 1/2"
1 1/4"
1"
1/2"
3/4"
2"
3/4"
1 1/2"
2" 3/4"
SA-"B"
1"
1 1/2"
3/4"1 1/2"
2" SD "C"
3/4" HW & CW DN.
1 1/4" CW DN.
2" SD "C"
1 1/2"
1/2" H & CW DN.
1"3/4"
1 1/2"
1/2" H & CW DN.
1 1/2"
1 1/2"
4" LEADER NO. 1"
DN. 3088∅
3" CW & 2 1/2"
HW RISER
1 1/2" CW DN. 1 1/4" CW TP WC
1/2" HW DN. TO LAV
1 1/4" CW & 1/2" HW
DN.
1/2" HW & CW DN.
1" CW & 1/2" HW RISERS
1 1/2" CW & 3/4" HW
DN.
1 1/2" CW & 2" HW
RISERS
1/2" CW & HW DN.
1/2" CW & HW
DN.
1/2" CW & HW DN.
1 1/4" CW & 1/2" HW
DN.
3" CW & 2 1/2" HW RISER
5" MAIN HOT WATER
RISER
6" COLD WATER RISER
2" DRINKING WATER
RISER
6" COLD WATER TO HOT WATER
GENERATOR
S&V 10
S&V 9
S&V 11
S&V 12 S&V 16
S&V 17
S&V 20
1 1
2 2 2
H J K L M N O P
/F6 01-P6
F
-P
F
-P
F
-P
TYP
(E) 4"ø SS
(E) 2"ø V
S 231 V 23 1
A. REFER TO 01-P1 FOR PLUMBING SYMBOLS, ABBREVIATIONS, AND GENERAL
NOTES.
B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE
VHA COR BEFORE PROCEEDING WITH WORK.
C. REFER TO I SHEET SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED
LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP
PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE
SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL
PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN
SHALL GOVERN.
D. REFER TO SPECIFICATIONS SECTIONS 01 00 00 AND 23 05 11 FOR SELECTIVE
DEMOLITION AND REPAIR REQUIREMENTS. PATCH OPENINGS REMAINING IN
EXISTING CONSTRUCTION FOLLOWING DEMOLITION OF PENETRATIONS NOT
REPLACED IN KIND. MATCH AESTHETICS AND LIFE SAFETY RATINGS OF THE
SURROUNDING CONSTRUCTION. ENGAGE LICENSED AND SITE-APPROVED
ROOFING CONTRACTOR TO PATCH AND SEAL WHERE ITEMS ARE REMOVED
THROUGH THE EXISTING ROOF. MAINTAIN EXISTING WARRANTIES.
E. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT
PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING
HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN
ACCORDANCE WITH THE SPECIFICATIONS.
F. REFER TO I SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.
G. PROVIDE SERVICE VALVES AT LIMITS OF DEMOLITION. CAP ENDS WHERE
NOT RECONNECTED IN NEW WORK. EXISTING SYSTEMS SHALL REMAIN IN
SERVICE FOLLOWING DEMOLITION. REFER TO 22 05 11 FOR DEAD END
REQUIREMENTS.
H. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:
a. DOMESTIC WATER
b. MED GAS
c. STORM DRAINAGE
d. VENTS
I. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:
a. SANITARY SEWER
P la n N o rt h
T ru e N o rt h
BLDG 01
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
00KEYNOTES
KEY PLAN
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\U se rs
\J D ez m an \D oc um en ts
\1 9.
_M
E C
H -P
LU
M
_R
_J D ez m an .rv t 4/
/2
1:
:5
P M
01-P7
DEMOLITION PLAN - 9TH FLOOR
CENTER
RENOVATE 9TH FLOOR MENTAL
HEALTH
1111 EAST END BLVD, WILKES-BARRE, PA 18711
693-19-106
04/18/2023 MB RT
100% CONSTRUCTION
DOCUMENTS
VEG 19.25 DWG 7 of 24 F
IN
A L
D R
A W
IN
G
S U
B M
IT
T
A L3/16" = 1'-0"
DEMOLITION PLAN - 9TH FLOOR CENTER
F6
1. RISER S+V NUMBERS REFER TO EXISTING SEWER AND VENT RISER TO
REMAIN.
2. EXISTING DOMESTIC HOT & COLD WATER RISER LOCATION TO REMAIN.
3. DEMO (E) PLUMBING PIPES FROM MIXING STATION TO RISER TO ALLOW
FOR NEW PLUMBING INSTALLATION. CAP PIPES AT RISER
4. (E) HOT WATER MIXING STATION SHALL REMAIN FOR FUTURE USE.
5. INTENT IS TO DEMOLISH PLUMBING SERVING THE 9TH FLOOR BACK TO
EXISTING RISERS.
1"
1/2" H & CW DN.
1 1/2"1"
1 1/2"
FD-"B"
4" RD (700∅)
4" RD (440∅)
1/2" H & CW DN.
2" HW
3" CW
3/4" @ CLG. BELOW
4" RD (440∅)
3/4" CW TO HB
3/4" CW UP
3" CW & 2 1/2"
HW RISER
3" HW 4"
CW
S&V 18
S&V 29 S&V 27
S&V 26
S&V 31
1 1
Q R S T U V
F
-P
F
-P
TYP
S&V 25 1
A. REFER TO 01-P1 FOR PLUMBING SYMBOLS, ABBREVIATIONS, AND GENERAL
NOTES.
B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE
VHA COR BEFORE PROCEEDING WITH WORK.
C. REFER TO I SHEET SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED
LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP
PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE
SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL
PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN
SHALL GOVERN.
D. REFER TO SPECIFICATIONS SECTIONS 01 00 00 AND 23 05 11 FOR SELECTIVE
DEMOLITION AND REPAIR REQUIREMENTS. PATCH OPENINGS REMAINING IN
EXISTING CONSTRUCTION FOLLOWING DEMOLITION OF PENETRATIONS NOT
REPLACED IN KIND. MATCH AESTHETICS AND LIFE SAFETY RATINGS OF THE
SURROUNDING CONSTRUCTION. ENGAGE LICENSED AND SITE-APPROVED
ROOFING CONTRACTOR TO PATCH AND SEAL WHERE ITEMS ARE REMOVED
THROUGH THE EXISTING ROOF. MAINTAIN EXISTING WARRANTIES.
E. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT
PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING
HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN
ACCORDANCE WITH THE SPECIFICATIONS.
F. REFER TO I SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.
G. PROVIDE SERVICE VALVES AT LIMITS OF DEMOLITION. CAP ENDS WHERE
NOT RECONNECTED IN NEW WORK. EXISTING SYSTEMS SHALL REMAIN IN
SERVICE FOLLOWING DEMOLITION. REFER TO 22 05 11 FOR DEAD END
REQUIREMENTS.
H. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:
a. DOMESTIC WATER
b. MED GAS
c. STORM DRAINAGE
d. VENTS
I. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:
a. SANITARY SEWER
P la n N o rt h
T ru e N o rt h
BLDG 01
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
00KEYNOTES
KEY PLAN
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\U se rs
\J D ez m an \D oc um en ts
\1 9.
_M
E C
H -P
LU
M
_R
_J D ez m an .rv t 4/
/2
1:
:5
P M
01-P8
DEMOLITION PLAN - 9TH FLOOR
EAST
RENOVATE 9TH FLOOR MENTAL
HEALTH
1111 EAST END BLVD, WILKES-BARRE, PA 18711
693-19-106
04/18/2023 MB RT
100% CONSTRUCTION
DOCUMENTS
VEG 19.25 DWG 8 of 24 F
IN
A L
D R
A W
IN
G
S U
B M
IT
T
A L3/16" = 1'-0"
DEMOLITION PLAN - 9TH FLOOR EAST
F6
1. RISER S+V NUMBERS REFER TO EXISTING SEWER AND VENT RISER TO
REMAIN.
2. EXISTING DOMESTIC HOT & COLD WATER RISER LOCATION TO REMAIN.
3. DEMO (E) ROOF DRAINS AND STORM PIPES BACK TO RISER.
4. INTENT IS TO DEMOLISH PLUMBING SERVING THE 9TH FLOOR BACK TO
EXISTING RISERS.
W X Y Z
(E) 4"ø SS
(E
1/
2" ø
D C
W
(X)
17-DWH-E
(X) P-89
(X) P-1
(X) P-66
A. REFER TO 01-P1 FOR PLUMBING SYMBOLS, ABBREVIATIONS, AND GENERAL
NOTES.
B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE
VHA COR BEFORE PROCEEDING WITH WORK.
C. REFER TO I SHEET SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED
LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP
PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE
SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL
PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN
SHALL GOVERN.
D. REFER TO SPECIFICATIONS SECTIONS 01 00 00 AND 23 05 11 FOR SELECTIVE
DEMOLITION AND REPAIR REQUIREMENTS. PATCH OPENINGS REMAINING IN
EXISTING CONSTRUCTION FOLLOWING DEMOLITION OF PENETRATIONS NOT
REPLACED IN KIND. MATCH AESTHETICS AND LIFE SAFETY RATINGS OF THE
SURROUNDING CONSTRUCTION. ENGAGE LICENSED AND SITE-APPROVED
ROOFING CONTRACTOR TO PATCH AND SEAL WHERE ITEMS ARE REMOVED
THROUGH THE EXISTING ROOF. MAINTAIN EXISTING WARRANTIES.
E. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT
PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING
HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN
ACCORDANCE WITH THE SPECIFICATIONS.
F. REFER TO I SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.
G. PROVIDE SERVICE VALVES AT LIMITS OF DEMOLITION. CAP ENDS WHERE
NOT RECONNECTED IN NEW WORK. EXISTING SYSTEMS SHALL REMAIN IN
SERVICE FOLLOWING DEMOLITION. REFER TO 22 05 11 FOR DEAD END
REQUIREMENTS.
H. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:
a. DOMESTIC WATER
b. MED GAS
c. STORM DRAINAGE
d. VENTS
I. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:
a. SANITARY SEWER
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
00KEYNOTES
KEY PLAN
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\U se rs
\J D ez m an \D oc um en ts
\1 9.
_M
E C
H -P
LU
M
_R
_J D ez m an .rv t 4/
/2
1:
:5
P M
17-P9
DEMOLITION PLAN - WAREHOUSE RENOVATE 9TH FLOOR MENTAL
HEALTH
1111 EAST END BLVD, WILKES-BARRE, PA 18711
693-19-106
04/18/2023 MB RT
100% CONSTRUCTION
DOCUMENTS
VEG 19.25 DWG 9 of 24 F
IN
A L
D R
A W
IN
G
S U
B M
IT
T
A L3/16" = 1'-0"
DEMOLITION PLAN - WAREHOUSE
F6
1. DEMO PLUMBING VENT THRU ROOF. PROTECT AND REUSE OPENING FOR
NEW VENT.
2. DEMO PLUMBING FIXTURES, DRAINS, PIPING AND VENT IN HATCHED AREA
3. DEMO FLOOR CLEAN OUT.
4. TO EXISTING DOMESTIC COLD WATER SUPPLY.
P-912
P-912
P-910
P-502
P-912
P-910
2 1/2"ø DCW2 1/2"ø DCW
2"ø DHW
2 1/2"ø DCW
2"ø DHW
2 1/2"ø DCW
2"ø DHW
2" ø
D H
W
1/
2" ø
D C
W
2"ø DHW
2 1/2"ø DCW
2"ø DHW
2 1/2"ø DCW
2 1/2"ø DCW
2"ø DHW
2"ø DHW
2 1/2"ø DCW
3/ 4" ø D
C W
P-501
P-930
P-935
P-935
P-935 P-417
P-528
P-408
P-930
P-930
P-930
P-912
P-910
P-940P-940
P-941
P-941
P-940
P-101
A B C D E F G
F
-P
F
-P
2 1/2"ø DCW
2 1/2"ø DHW
P-941
P-941
C9-62
ELEC
C9-53
ELEC
C9-58
ELECTRICAL
E-7
ELEVATOR
E-8
ELEVATOR
E-9
ELEVATOR
C9-46
LINEN
C9-44A
TOILET
C9-52
SALLY PORT
C9-51
HAC
C9-41A
TOILET
C9-66A
TOILET
C9-68A
TOILET
C9-68
BARIATRIC
GERIATRIC
C9-69
OFFICE
C9-66
GERIATRIC
ST-5
STAIR
ST-1
STAIR
C9-63
ELEC
C9-71
GROUP THERAPY
C9-50
MEETING
C9-45
PATIENT STORAGE
C9-C07
CORRIDOR
C9-70
CLEAN UTILITY
C9-41
WOMEN'S
C9-49
WOMEN'S BARIATRIC
C9-49A
TOILET
C9-54
ELEVATOR LOBBY
C9-67A
TOILET
C9-65
MED
C9-47
OFFICE/ GROUP
ROOM
C9-47A
STORAGE
C9-44
WOMEN'S
C9-56
CLEAN STORAGE
C9-55
MECHANICAL
C9-60
CONFERENCE
C9-57
HAC
C9-59
PREFUNCTION/
COLLABORATION
C9-61
WORKSTATIONS
C9-43
WOMEN'S
C9-C06
CORRIDOR
C9-43A
TOILET
C9-42
STAFF TOILET
C9-40
MED
C9-C09
CORRIDOR
C9-C08
CORRIDOR
S3
LINEN CHUTE
C9-48
LAUNDRY
C9-64
NURSE'S STATION
C9-67
BARIATRIC
GERIATRIC
C9-72
DAY/TV
C9-72A
GERIATRIC DINING
C5
01-P23
SIM
4 1/2"ø DCW
A. REFER TO 01-P1 FOR PLUMBING SYMBOLS, ABBREVIATIONS, AND GENERAL
NOTES.
B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE
VHA COR BEFORE PROCEEDING WITH WORK.
C. REFER TO I-SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED
LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP
PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE
SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL
PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN
SHALL GOVERN.
D. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT
PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING
HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN
ACCORDANCE WITH THE SPECIFICATIONS.
E. REFER TO I SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.
F. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:
a. DOMESTIC WATER
b. MED GAS
c. STORM DRAINAGE
d. VENTS
G. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:
a. SANITARY SEWER
P la n N o rt h
T ru e N o rt h
BLDG 01
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
00KEYNOTES
KEY PLAN
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\U se rs
\J D ez m an \D oc um en ts
\1 9.
_M
E C
H -P
LU
M
_R
_J D ez m an .rv t 4/
/2
1:
:5
P M
01-P10
DOMESTIC WATER PLAN - 9TH
FLOOR WEST
RENOVATE 9TH FLOOR MENTAL
HEALTH
1111 EAST END BLVD, WILKES-BARRE, PA 18711
693-19-106
04/18/2023 MB RT
100% CONSTRUCTION
DOCUMENTS
VEG 19.25 DWG 10 of 24 F
IN
A L
D R
A W
IN
G
S U
B M
IT
T
A L3/16" = 1'-0"
DOMESTIC WATER PLAN - 9TH FLOOR WEST
F6
1. DCW TO NEW HUMIDIFIER. COORDINATE WITH MECHANICAL.
2. OFFSET DOMESTIC WATER RISERS TO WALL ABOVE 8TH FLOOR CEILING
AND RECONNECT TO EXISTING RISER.
3. PROVIDE CONTROLS COMPATIBLE WITH WATER MANAGEMENT
CONTROLLER.
4. PROVIDE AND CONNECT TO TRAP PRIMER CONTROLLER.
2"ø DHW
2 1/2"ø DCW
1/
2" ø
D C
W
2" ø
D H
W
2" ø
D H
W
3" ø
D C
W
2"ø DHW
3"ø DCW
1" ø
D C
W
1" ø
D H
W R
2" ø
D H
W
1/
2" ø
D C
W
1" ø
D C
W
1" ø
D H
W R
2 1/2"ø DCW
2"ø DHW
2 1/2"ø DCW
2"ø DHW
1" ø
D C
W
3/ 4" ø D
H W
2"ø DHW
2 1/2"ø DCW
2 1/2"ø DCW2 1/2"ø DCW
2"ø DHW
2 1/2"ø DCW
2"ø DHW
2 1/2"ø DCW
2"ø DHW
1" ø
D H
W
1" ø
D C
W
1" ø
D H
W R
P-910
P-912
P-528
P-910
P-910
P-528
P-417
P-930
P-930
P-408
P-930
P-930
P-101
P-940 P-940
H J K L M N O P
F
-P
/F6 01-P10
F
-P
F
-P
01-P23
F5
01-P23
F1
C9-35
NURSE'S LOUNGE
C9-35A
LOCKERS
ST-3
STAIR
C9-34
ELEC C9-34A
ELEC
E-4
ELEVATOR
C9-23
ELEVATOR LOBBY
E-5
ELEVATOR
E-6
ELEVATOR
C9-21
SALLY PORT
E-2
ELEVATOR
E-3
ELEVATORC9-30
ELEVATOR LOBBY
C9-28
SALLY PORT
C9-33
STAFF TOILET
C9-29
INTERVIEW
C9-31
TELECOM ROOM
C9-C04
CORRIDOR
C9-37
TEAMING/
COUNSELING
C9-32
MECHANICAL
C9-22
SERVING KITCHEN
C9-16
DINING/ ACTIVITIES
C9-19
ELEC
C9-38
EXAM/ INTAKE
C9-26
LOBBY
C9-39
HEAD NURSE
OFFICE
C9-27
NURSE'S STATION
C9-27A
NURSE'S
WORKROOM
C9-C05
CORRIDOR
C9-25
ANTE ROOM
C9-24
MEN'S
C9-C03
CORRIDOR
E-1
ELEVATOR
C9-20
MEN'S
C9-18
MEN'S
C9-17
GROUP THERAPY
C9-20A
TOILET
C9-18A
TOILET
C9-25B
SECLUSION ROOM
C9-24A
TOILET
C9-25A
TOILET
P-528
P-941
A. REFER TO 01-P1 FOR PLUMBING SYMBOLS, ABBREVIATIONS, AND GENERAL
NOTES.
B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE
VHA COR BEFORE PROCEEDING WITH WORK.
C. REFER TO I-SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED
LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP
PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE
SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL
PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN
SHALL GOVERN.
D. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT
PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING
HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN
ACCORDANCE WITH THE SPECIFICATIONS.
E. REFER TO I SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.
F. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:
a. DOMESTIC WATER
b. MED GAS
c. STORM DRAINAGE
d. VENTS
G. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:
a. SANITARY SEWER
P la n N o rt h
T ru e N o rt h
BLDG 01
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
00KEYNOTES
KEY PLAN
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\U se rs
\J D ez m an \D oc um en ts
\1 9.
_M
E C
H -P
LU
M
_R
_J D ez m an .rv t 4/
/2
1:
:0
P M
01-P11
DOMESTIC WATER PLAN - 9TH
FLOOR CENTER
RENOVATE 9TH FLOOR MENTAL
HEALTH
1111 EAST END BLVD, WILKES-BARRE, PA 18711
693-19-106
04/18/2023 MB RT
100% CONSTRUCTION
DOCUMENTS
VEG 19.25 DWG 11 of 24 F
IN
A L
D R
A W
IN
G
S U
B M
IT
T
A L3/16" = 1'-0"
DOMESTIC WATER PLAN - 9TH FLOOR CENTER
F6
1. OFFSET DOMESTIC WATER RISERS TO WALL ABOVE 8TH FLOOR CEILING
AND RECONNECT TO EXISTING RISER.
2. PROVIDE CONOTROLS COMPATIBLE WITH WATER MANAGEMENT
CONTROLLER.
3. PROVIDE DOMESTIC COLD WATER CONNECTIONS ABOVE COUNTER TOP
FOR COFFEE MAKER AND ICE MACHINE.
2"ø DHW
2 1/2"ø DCW
2"ø DHW
2 1/2"ø DCW
2"ø DHW
2 1/2"ø DCW
P-912 P-910
P-910
2 1/2"ø DCW
2"ø DHW
3/ 4" ø D
C W
1/
2" ø
D C
W
2" ø
D H
W
2 1/2"ø DCW
2"ø DHW
2 1/2"ø DCW
2"ø DHW
2 1/2"ø DCW
2"ø DHW
2 1/2"ø DCW
3"ø DCW
2"ø DHW
P-502
P-910
P-930
P-930
P-910
P-501
P-912
P-935 P-930
P-930
P-935
P-940P-940
P-941
P-940
P-941
Q R S T U V
F
-P
F
-P
C9-02
HAC
C9-04A
TOILET
C9-04
MEN'S
ST-2
STAIR
C9-09
ELEC
C9-11
QUIET ROOM
C9-C01
CORRIDOR
C9-13
SOILED UTILITY
C9-15A
TOILET
C9-15
MEN'S BARIATRIC
C9-14
MEN'S
C9-14A
TOILET
C9-12A
TOILET
C9-12
MEN'S
C9-08
MEN'S BARIATRIC
C9-08A
TOILET
C9-07
OFFICE
C9-05
TOILET
C9-03
GROUP
COUNSELING ROOM
C9-C02
CORRIDOR
C9-06
MECHANICAL
C9-06A
ELEC
C9-01
EAST SUNROOM
C9-10
LAUNDRY
C9-00
COURTYARD
S1
SHAFT
S2
SOILED LINEN
CHUTE
P-808 P-808
3/ 4" ø D
C W
1/2"ø DCW
A. REFER TO 01-P1 FOR PLUMBING SYMBOLS, ABBREVIATIONS, AND GENERAL
NOTES.
B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE
VHA COR BEFORE PROCEEDING WITH WORK.
C. REFER TO I-SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED
LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP
PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE
SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL
PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN
SHALL GOVERN.
D. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT
PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING
HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN
ACCORDANCE WITH THE SPECIFICATIONS.
E. REFER TO I SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.
F. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:
a. DOMESTIC WATER
b. MED GAS
c. STORM DRAINAGE
d. VENTS
G. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:
a. SANITARY SEWER
P la n N o rt h
T ru e N o rt h
BLDG 01
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
00KEYNOTES
KEY PLAN
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\U se rs
\J D ez m an \D oc um en ts
\1 9.
_M
E C
H -P
LU
M
_R
_J D ez m an .rv t 4/
/2
1:
:0
P M
01-P12
DOMESTIC WATER PLAN - 9TH
FLOOR EAST
RENOVATE 9TH FLOOR MENTAL
HEALTH
1111 EAST END BLVD, WILKES-BARRE, PA 18711
693-19-106
04/18/2023 MB RT
100% CONSTRUCTION
DOCUMENTS
VEG 19.25 DWG 12 of 24 F
IN
A L
D R
A W
IN
G
S U
B M
IT
T
A L3/16" = 1'-0"
DOMESTIC WATER PLAN - 9TH FLOOR EAST
F6
1. DCW TO NEW HUMIDIFIER.
2. OFFSET DOMESTIC WATER RISERS TO WALL ABOVE 8TH FLOOR CEILING
AND RECONNECT TO EXISTING RISER.
3. PROVIDE CONTROLS COMPATIBLE WITH WATER MANAGEMENT
CONTROLLER.
4. PROVIDE AND CONNECT TO TRAP PRIMER CONTROLLER.
1"ø DCW
3/ 4" ø D
C W
1 1/2"ø DCW
1/
2" ø
D C
W
P-103
P-103
P-103
W X Y Z
P-408 P-408
P-408
1"ø DCW
P-528
3/4"ø DCW
(E
1/
2" ø
D C
W
(E) 1 1/2"ø DCW
17-WH-1
17-WH-3
17-WH-217-WH-4
1/
2" ø
D C
W
L1-110
OFFICE
L1-109
OFFICE
L1-108
OFFICE
L1-107
OFFICE
L1-105
TOILET
L1-104
COPY/LOCKERS
L1-103
OPEN OFFICE
L1-102
SECRETARY
L1-111
CONFERENCE
L1-112
MECH
L1-100
STORAGE
L1-100H
OFFICE
L1-100G
TOILET
L1-100A
ELEC
L1-100J
LOADING DOCK
L1-102A
CLOSET
L1-100F
LOCKERS
L1-100E
TELECOM ROOM
L1-106
TOILET
L1-001
OXYGEN STORAGE
3/ 4" ø D
C W
A. REFER TO 01-P1 FOR PLUMBING SYMBOLS, ABBREVIATIONS, AND GENERAL
NOTES.
B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE
VHA COR BEFORE PROCEEDING WITH WORK.
C. REFER TO I-SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED
LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP
PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE
SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL
PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN
SHALL…