P03 Sole Source BNOE 503-19-112 Repalce Steam System.pdf

PDF 135 KB Posted

Attached to
Z1DA--NRM | 503-19-112 Replace Steam System Project (VA-24-00009779) Federal contract opportunity
Solicitation number
36C24424R0001
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 4

About this file

This document is a Sole Source Justification related to a federal contract opportunity for the replacement of a steam system at the Altoona VA Medical Center.

The document lists several sole source manufacturers and products required for the project, including ball valves, fire alarm system, HVAC controls, and sprinkler heads. It states that no "equal" products will be considered. It also provides a list of "brand name or equal" products that are required, including pressure relief valves, hydronic pumps, condensate pumps, steam pressure reducing valves, and various steam traps. The project is numbered 503-19-112 and has a performance period of 720 calendar days.

The related federal contract opportunity is a Request for Proposal (RFP) for construction services to replace the steam system at the Altoona VAMC, with a magnitude of construction cost between $5,000,000 and $10,000,000. The solicitation will be issued as a tiered evaluation, considering Service Disabled Veteran Owned Small Businesses, Veteran Owned Small Businesses, and other small businesses before non-small businesses. A pre-bid conference and site visit are planned.

View the file

Other files for this federal contract opportunity

Other files attached to Z1DA--NRM | 503-19-112 Replace Steam System Project (VA-24-00009779), newest first.
File Type Posted
36C24424R0001 0004_1 10-23-24.pdf PDF
36C24424R0001 0004 10-23-24.pdf PDF
EXHIBIT D - Sample Transmittal Letter for Past Performance Evaluation 36C24424R0001 10-11-24.pdf PDF
SCHEDULE Line Item replace steam system w alternate 10-11-24.pdf PDF
36C24424R0001 0003 10-11-24.pdf PDF
36C24424R0001 0003_1.pdf PDF
EXHIBIT E - Past Performance Questionnaire 36C24424R0001 _ Replace Steam System 10-11-24.pdf PDF
36C24424R0001 0002 10-8-24.pdf PDF
Bid RFIs 12.6.23 - 503-19-112 Replace Steam Project.pdf PDF
Cast Iron Operational Alert VHA 121621.pdf PDF
VA Directive 1810.pdf PDF
Justification MPT-SAT 03-Trane Tracer Ensemble_Redacted.pdf PDF
36C24424R0001 0002_1 10-8-2024.pdf PDF
PN 503-19-112 100PCT ACM Specs and Survey.pdf PDF
PN 503-19-112 100PCT Drawings.pdf PDF
Justification-MPT-SAT 01-Apollo Conbraco Ball Valves_Redacted.pdf PDF
Justification MPT-SAT-02-Bettwy Systems_Redacted.pdf PDF
Two Valve Isolation Per VA Directive 1810 Appendix A.pdf PDF
Bid RFIs - 503-19-112 Replace Steam Project - Dec. 2023.pdf PDF
PN 503-19-112 100PCT Specifications.pdf PDF
General Decision Number PA20240002 08-16-2024.pdf PDF
Water Safety Plan Requirements 11.22.2021.pdf PDF
36C24424R0001_3.pdf PDF
36C24424R0001 0001 1-18-24.pdf PDF
Bid RFIs - 503-19-112 Replace Steam Project.pdf PDF
EXHIBIT B - Subcontractor Information and Consent Form 36C24424R0001 _ Replace Steam System.pdf PDF
EXHIBIT A - Past Performance Relevancy Questionnaire 36C24424R0001 _ Replace Steam System.pdf PDF
503-19-112 -CD- Drawings_Part3.pdf PDF
PM-Part808-405-6-Atch1-Limiting Sources Justification MPT-SAT 04 Viking Sprinkler Heads (s) 10-2-23_Redacted(s).pdf PDF
EXHIBIT D - Sample Transmittal Letter for Past Performance Evaluation 36C24424R0001 _ Replace Steam System.pdf PDF
503-19-112 -CD- Drawings_Part2.pdf PDF
36C24424R0001_1 11-16-23.pdf PDF
EXHIBIT E - Past Performance Questionnaire 36C24424R0001 _ Replace Steam System.pdf PDF
PM-Part808-405-6 Atch1 Limiting Sources Justification MPT-SAT 03-Trane Tracer Ensemble (s) 10-2-23_Redacted (s).pdf PDF
503-19-112 -CD- Drawings_Part1.pdf PDF
503-19-112 - CD - Specifications.pdf PDF
36C24424R0001 12-8-23.pdf PDF
36C24424R0001_2.docx DOCX document
PM-Part808-405-6 - Atch1MPT-SAT 01-Apollo Conbraco Ball Valves (s) 10-2-23_Redacted (s).pdf PDF
PM-Part808-405-6 Atch1 Limiting Sources Justification MPT-SAT-02-Bettwy Systems (s) 10-2-23_Redacted(s).pdf PDF
Show all 40

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

503-315

SOLE SOURCE

In accordance with VAAR clause 852.236-90, RESTRICTION ON SUBMISSION AND

USE OF EQUAL PRODUCTS (NOV 1986)

List of sole source manufacturers and referenced locations for Altoona James E.

VanZandt DEPARTMENT OF VETERANS AFFAIRS VA Medical Center project #503- 19-112 Replace Steam System Project. Contractor is required to use these sole source items without exception. Justifications are included in the bid package.

1. Ball valves shall be “Apollo Conbraco”.

2. Fire alarm system shall be “Honeywell Notifier”.

3. Fire alarm Installer shall be “Bettwy Systems”

4. HVAC controls shall be “Trane Tracer Ensemble”

5. Sprinkler heads shall be “Viking”

Notwithstanding the “Material and Workmanship” clause of this contract, FAR 52.236- 5(a), nor any other contractual provision, “equal” products will not be considered by the Department of Veterans Affairs and may not be used.

BRAND NAME OR EQUAL

Per FAR clause 52.211-6 – the following are basis of design and are required to be brand name or equal:

• 1-SV-BB15F-L. Watts F41 Series Pressure Relief Valves. Drawing M-601.

• 1-SV-BA10-M. Watts F41 Series Pressure Relief Valves Drawing M-601.

• 1-SV-BA10-L. Watts F41 Series Pressure Relief Valves Drawing M-601.

• 1-SV-BE01F-L. Watts F41 Series Pressure Relief Valves Drawing M-601.

• 1-HW-BB12A. Bell & Gossett Hydronic Pump Drawing M-601.

• 1-HW-BB12B. Bell & Gossett Hydronic Pump Drawing M-601.1-CP-BA10a.

Armstrong DPT 300 Series Steam Motive Duplex Condensate Pump with Integral Vented Receiver. Drawing M-601.

• 1-CP-BA10a. Armstrong DPT 300 Series Steam Motive Duplex Condensate Pump with Integral Vented Receiver. Drawing M-601.

• 1-CP-BA10b. Armstrong DPT 300 Series Steam Motive Duplex Condensate Pump with Integral Vented Receiver. Drawing M-601.

• 1-CP-BB12. Armstrong DPT 300 Series Steam Motive Duplex Condensate Pump with Integral Vented Receiver. Drawing M-601.

• 1-CP-BB15F. Armstrong DPT 300 Series Steam Motive Duplex Condensate Pump with Integral Vented Receiver. Drawing M-601.

• 1-CP-BC11. Armstrong DPT 300 Series Steam Motive Duplex Condensate Pump with Integral Vented Receiver. Drawing M-601.

• 1-CP-BE01F. Armstrong DPT 300 Series Steam Motive Duplex Condensate Pump with Integral Vented Receiver. Drawing M-601.

https://www.acquisition.gov/far/current/html/52_233_240.html#wp1113390 https://www.acquisition.gov/far/current/html/52_233_240.html#wp1113390

• 1-SPVR-BB15F-L-1/3. Armstrong Steam Pressure Reducing Valve. Drawing M- 601.

• 1-SPVR-BB15F-L-2/3. Armstrong Steam Pressure Reducing Valve. Drawing M- 601.

• 1-SPVR-BA10-M-1/3. Armstrong Steam Pressure Reducing Valve. Drawing M- 601.

• 1-SPVR-BA10-M-2/3. Armstrong Steam Pressure Reducing Valve. Drawing M- 601.

• 1-SPVR-BA10-L-1/3. Armstrong Steam Pressure Reducing Valve. Drawing M- 601.

• 1-SPVR-BA10-L-2/3. Armstrong Steam Pressure Reducing Valve. Drawing M- 601.

• 1-SPVR-BE01F-L-1/3. Armstrong Steam Pressure Reducing Valve. Drawing M- 601.

• 1-SPVR-BE01F-L-2/3. Armstrong Steam Pressure Reducing Valve. Drawing M- 601.

• LSD-1. Titus FL Series Lineal Slot Diffuser. Drawing M601

• SD-1. Titus FL Series Slot Diffuser. Drawing M601

• Armstrong International. Steameye Monitoring System. Specification 23 21 11 and Specification 23 22 13. Drawing M-701

• All marked 01-H Thermal Steam Humidifiers. Armstrong Model 90, Series 9000.

Drawing M-602.

• 1-ST-1. Armstrong IB-973 Steam Trap. Drawing M-602.

• 1-ST-1-RTUA. Armstrong AIC6 Steam Trap. Drawing M-602.

• 1-ST-1-RTUB. Armstrong AIC6 Steam Trap. Drawing M-602.

• 1-ST-2. Armstrong IB-973 Steam Trap. Drawing M-602.

• 1-ST-AC. Armstrong FT-ICS6 Steam Trap. Drawing M-602.

• 1-ST-AH1. Armstrong IB-973 Steam Trap. Drawing M-602.

• 1-ST-AH2. Armstrong AIC6 Steam Trap. Drawing M-602.

• 1-ST-AH4. Armstrong 1CS6 Steam Trap. Drawing M-602.

• 1-ST-AH-5. Armstrong IB-973 Steam Trap. Drawing M-602.

• 1-ST-AHU-3. Armstrong FT-AIC6 Steam Trap. Drawing M-602.

• 1-ST-AHU-11. Armstrong FT-AIC6 Steam Trap. Drawing M-602.

• 1-ST-AHU-12. Armstrong FT-AIC6 Steam Trap. Drawing M-602.

• 1-ST-DH1. Armstrong 310 Steam Trap. Drawing M-602.

• 1-ST-DH2. Armstrong IB-973 Steam Trap Drawing M-602.

• 1-ST-DWH-1. Armstrong FT-AIC6 Steam Trap. Drawing M-602.

• 1-ST-DWH-2. Armstrong FT-AIC6 Steam Trap. Drawing M-602.

• 1-ST-HX-1. Armstrong FT-AIC6 Steam Trap. Drawing M-602.

• 1-ST-HX-1F69. Armstrong CS6/8 Steam Trap. Drawing M-602.

• 1-ST-HX-2A. Armstrong FT-AIC6 Steam Trap. Drawing M-602.

• 1-ST-HX-2B. Armstrong FT-AIC6 Steam Trap. Drawing M-602.

• 1-ST-HX-3. Armstrong FT-AIC6 Steam Trap. Drawing M-602.

• 1-ST-K. Armstrong ICS4 Steam Trap. Drawing M-602.

• 1-ST-L-SP. Armstrong CS6/8 Steam Trap. Drawing M-602.

• 1-ST-LD. Armstrong CS6/8 Steam Trap. Drawing M-602.

• 1-ST-SPS. Armstrong CS6/8 Steam Trap. Drawing M-602.

• 1-ST-UH-1. Armstrong IB-973 Steam Trap. Drawing M-602.

• 1-ST-UH-2. Armstrong IB-973 Steam Trap. Drawing M-602.

• 1-ST-UH-3. Armstrong IB-973 Steam Trap. Drawing M-602.

• 2-ST-HX-1. Armstrong FT-ICS6 Steam Trap. Drawing M-602.

• 3-ST-B1. Armstrong 1CS6 Steam Trap. Drawing M-602.

• 3-ST-HX-1. Armstrong FT-1CS6 Steam Trap. Drawing M-602.

• 7-ST-HX-1. Armstrong FT-1CS4 Steam Trap. Drawing M-602.

• 32-ST-DWH-1. Armstrong 1CS6 Steam Trap. Drawing M-602.

• 32-ST-HX-1. Armstrong CS6/8 Steam Trap. Drawing M-602.

• 32-ST-HX-2. Armstrong CS6/8 Steam Trap. Drawing M-602.

• Procore Technologies, Inc. Specification 01 31 23 (2.1A) – Project Website.

• Electromagnetic Water Flow Sensor. Onicom F3500. Specification 23 09 23

(2.9E)

• CO2 Sensor. Veris CWE. Specification 23 09 23 (2.9N.2)

• Bi-Directional Through Wall Differential Pressure Sensor. TSI 80024.

Specification 23 09 23 (2.9.O)

• Magnetic Door Contact Switch. Interlogic 2500. Specification 23 09 23 (2.9P)

• Ari Flow Measuring Station. Ebtron GTx108-F. Specification 23 09 23 (2.9P)