36C24122R0135 0005.docx

DOCX document 59 KB Posted

Attached to
Z2DA--405-13-104 | Inpatient Ward Renovation
Solicitation number
36C24122R0135
Issued by

About this file

This document contains responses to questions from potential offerors on a solicitation for inpatient ward renovation services. The solicitation is for project number 36C24122R0135 issued by the Department of Veterans Affairs to renovate wards at the VA Medical Center in White River Junction, Vermont. Key details include specifications for installing an approved nurse call system, quantities of sinks requiring asbestos abatement, clarification of flooring types and patching requirements, a list of smart bed data to integrate into electronic whiteboards, and sign-in sheets from pre-bid meetings. The responses aim to provide additional information to help offerors fully understand renovation requirements and prepare accurate proposals due by February 23, 2023.

View the file

Other files

File Type Posted
36C24122R0135 0016.docx DOCX document
36C24122R0135 0015.docx DOCX document
Fingerprint Request Form.pdf PDF
Sign-in Sheet 07-06-2023.pdf PDF
36C24122R0135 0014.docx DOCX document
36C24122R0135 0013.pdf PDF
Sign-in Sheet 06-01-2023.pdf PDF
Owners Equipment Schedule updated 6-20-2023.xlsx XLSX spreadsheet
36C24122R0135 0012.docx DOCX document
36C24122R0135 0011.docx DOCX document
S02 36C24122R0135 0010.pdf PDF
36C24122R0135 0009.pdf PDF
Wage Determination VT20230023 02-24-2023.pdf PDF
WRJ Campus Map Inpatient Ward Site Visit Meeting Location 03.21.2023.pdf PDF
36C24122R0135 0008.pdf PDF
36C24122R0135 0007.docx DOCX document
36C24122R0135 0006.docx DOCX document
VHA COVID-19 Operational Plan 1-27-2023.pdf PDF
Building 31 Abatement Diagrams REV-1 02072023.pdf PDF
Bldg 31 Exterior Elevations _ Building Sections.pdf PDF
Pre-bid site visit sign-in 01-24-2023.pdf PDF
Bldg 31 Basement Intended Route Debris Removal.pdf PDF
Revised Spec 117313 Patient Lifts 20230201.pdf PDF
36C24122R0135 0004.docx DOCX document
Original Building Ground _ 1st Floor Plan_Wall Types.pdf PDF
Pre-bid site visit sign-in 01-19-2023.pdf PDF
36C24122R0135 0003.pdf PDF
WRJ Campus Map Inpatient Ward Site Visit Meeting Location 1.24.2023.pdf PDF
Renovate Inpatient Ward Site Visit 1.12.2023.pdf PDF
36C24122R0135 0002.pdf PDF
WRJ Campus Map Inpatient Ward Site Visit Meeting Location 1.19.2023.pdf PDF
WRJ Campus Map Inpatient Ward Site Visit Meeting Location.pdf PDF
36C24122R0135 0001.docx DOCX document
36C24122R0135 Solicitation Final (1).pdf PDF
S02 Inpatient Drawings 09302022 Final Architectural Int Design.pdf PDF
S02 Inpatient Drawings 09302022 Final Plumb FirePro Mech Elec.pdf PDF
S02 EXHIBIT B Subcontractor Information and Consent Form.pdf PDF
S02 EXHIBIT A Project Information Sheet for Contractors.pdf PDF
VAMC-WRJ Building 31 Nursing Unit Renovation Project Manual Vol-1 09302022 Final.pdf PDF
VAMC-WRJ Building 31 Nursing Unit Renovation Project Manual Vol-2 09302022 Final.pdf PDF
VAAR 852.219-75 VA Notice of Limitations on Subcontracting_Certificate of Compliance for Services and Construction 02.docx DOCX document
S02 VHA Supplemental Contract Requirements for Combatting COVID-19.pdf PDF
S02 Inpatient Drawings 09302022 Final Gen LifeSafety Structural.pdf PDF
S02 EXHIBIT C Past Performance Questionnaire.pdf PDF
WD VT20220023 Building.pdf PDF
Show all 45

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

5. PROJECT NUMBER (if applicable)

CODE

7. ADMINISTERED BY

2. AMENDMENT/MODIFICATION NUMBER

CODE

6. ISSUED BY

8. NAME AND ADDRESS OF CONTRACTOR

4. REQUISITION/PURCHASE REQ. NUMBER

3. EFFECTIVE DATE

9A. AMENDMENT OF SOLICITATION NUMBER

9B. DATED

PAGE OF PAGES

10A. MODIFICATION OF CONTRACT/ORDER NUMBER

10B. DATED

BPA NO.

1. CONTRACT ID CODE

FACILITY CODE

CODE

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

E. IMPORTANT:

is extended,

(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.

12. ACCOUNTING AND APPROPRIATION DATA

(REV. 11/2016)

is required to sign this document and return ___________ copies to the issuing office.

is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.

15C. DATE SIGNED

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER

Contractor

16C. DATE SIGNED

14. DESCRIPTION OF AMENDMENT/MODIFICATION

16B. UNITED STATES OF AMERICA

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER

16A. NAME AND TITLE OF CONTRACTING OFFICER

15B. CONTRACTOR/OFFEROR

STANDARD FORM 30

PREVIOUS EDITION NOT USABLE

Prescribed by GSA - FAR (48 CFR) 53.243 (Type or print) (Type or print) (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

(Number, street, county, State and ZIP Code) (If other than Item 6) (Specify type of modification and authority) such as changes in paying office, appropriation date, etc.)

(If required)

(SEE ITEM 11)

(SEE ITEM 13)

(X)

CHECK

ONE

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

(Signature of person authorized to sign) (Signature of Contracting Officer) 02/08/2023 405-13-104 Department of Veterans Affairs

VAMC

Togus 1 VA Center Augusta ME 04330 Department of Veterans Affairs

VAMC

Togus 1 VA Center Augusta ME 04330 To all Offerors/Bidders

36C24122R0135 12-30-2022

X X X ** HOUR & DATE for Receipt of Offers is EXTENDED to:

X The purpose of this amendment is to provide additional RFI responses.

See attached RFI responses.

There is no change to the RFI deadline of 02-07-2023 and the proposal due date 0f 02-23-2023 at 13:00EST.

Stephen Slaby Contracting Officer RFI Questions Submitted with Answers 36C24122R0135 Amendment 0005 405-13-104 Renovate Inpatient Ward, White River Junction, VT Questions #1 - #57 Appear in earlier amendments Question# 58

SECTION: 27 52 23-12

G. Functional Components: As indicated on the drawings or as required to complete system.

1. Staff Consoles.

2. Patient and Staff Audio Stations: Standard.

3. Patient and Staff Audio Stations: Graphical.

4. Smart Bed Connectors.

5. Bed Side Rail Interface.

6. Call Switches.

7. Remote Audio Devices.

8. Corridor (Dome / Zone) Lights.

9. Room Control Boards (RCB).

10.Power over Ethernet (PoE) Switches.

11.Bed Interface Device (pillow speaker, bed and auxiliary input).

12.Electronic Whiteboard.

13.Configuration Software.

14.Physical Servers.

Please advise if VA will provide drawings that show which rooms will have Patient and Staff Audio Stations: Standard, versus Patient and Staff Audio Stations: Graphical

Answer: The bidder shall refer to “New Nurse Call Legend” on Drawing 31-E-601, “Navicare Nurse Call Schedule” on Drawing 31-E-607, and the various Power & Signal distribution plans including but not necessarily limited to enlarged room details on Drawings 31-EP-411 and 31-EP-412. No additional drawings shall be provided beyond those already included in the bidding documents. The successful nurse call bidder shall prepare fully detailed design & installation shop drawings and equipment catalogue and review the same with the Owner to confirm all aspects of the design.

Question# 59 Please confirm that the Room Control Board (RCB) should be the latest version (v3).

Answer: VA confirms that all hardware should be the latest version.

Question# 60 Please confirm intent of the Bed Interface Device will allow for all 3 inputs on one device versus multiple nurse devices to accomplish.

Answer: VA confirms intent of bed interface device will allow all 3 inputs on one device.

Question# 61

SECTION: 27 52 23-15

N. Electronic Whiteboard: Real-time dashboard, typically displayed on large central monitors, displaying Nurse Call System, patient and smart bed information.

1. Display: LAN-PC or smart LCD.

2. Data: Patient room number, patient name, patient notes, assigned patient risk protocol, assigned staff, nurse call type, call wait time, and staff presence.

Please confirm you want following smart bed data to be available on the Electronic Whiteboard:

1.Digital patient weight
2.Head of Bed Angle
3.Side Rail Position up/down
4.Patient Presence in bed
5.Brakes on / off
6.Bed Exit on / off

Answer: VA confirms that the smart bed data should include items 1-6 above on the electronic whiteboard.

Question# 62 Are there any additional requirements related to the Nurse Call System?

Answer: This project requires installation of a nurse call system that has been approved through VA's national Office of Information & Technology vetting and approval process. Bidders should only cost an approved nurse call system for installation with this project.

Question# 63 Are you able to provide a list of bidding contractors?

Answer: The VA has only a list of contractors who attended the site visits and does not know who all intends to bid this contract. Please see site visit sign-in sheets provided by amendments 02 and 03.

Question# 64 Will updated Asbestos drawings be provided?

Answer: Please see updated attached files: Building 31 Abatement Diagrams REV-1 02072023.

Question# 65 How high is the asbestos wall tile present on the 1st floor? What rooms is it present in? From the site visit, it appears that tile is present in rooms other than hallways and rooms not indicated on the drawings.

Answer: Please refer to attached revised Abatement Drawings (See 31-AS-105B). The ACM wall tile is throughout Level 1 all hallways, including hidden behind the sheet wall paneling, approximately 4ft up the walls. It is in each patient room bathrooms and shared bathrooms it runs floor to ceiling. Also, at each water fountain/sink there is wall tile for a back splash.

Question# 66 No abatement plan or notes were found for the basement. Are there any hazardous materials in the basement that will require abatement? If so, please provide information on such.

Answer: Please refer to Attached Abatement Diagrams (see 31-AS-105C). The basement level has limited abatement work to include areas that will be impacted by ground level and level-1 M-E-P utility service connections. The bidder shall refer to the M-E-P drawings to ascertain the scope..

Question# 67 Sheet AS-105 B abatement plan legend does not appear to be consistent with field conditions from the site visit specifically with the ceramic wall tile in rooms and corridors please review and confirm legend is correct.

Answer: Please refer to attached revised abatement drawings (See 31-AS-105B). All hallways, including hidden behind the sheet wall paneling, approximately 4ft up the walls. It is in each patient room bathrooms and shared bathrooms it runs floor to ceiling. Also, at each water fountain/sink there is wall tile for a back splash. Additionally Room 125 nurses breakroom/kitchenette has ceramic wall tile ceiling to floor.

Question# 68 Sheet AS-105 A abatement plan only indicates Floor tile mastic and HVAC Duct Caulking please confirm no wall tile to be abated and removed on ground floor. During site visit ceramic tile was noted in hallways and bathrooms.

Answer: Please refer to attached revised abatement drawings (See 31-AS-105A). AS-105 A was not accurate. Yes, there is ceramic wall tile in hallways approximately 4ft up wall, bathrooms and patient room bathrooms floor to ceiling, and at water fountains and sinks as backsplash. The intent on the Ground Floor is to abate only those areas that are disturbed by construction activities but not necessarily all areas of the Ground Floor.

Question# 69
1.Are As a follow-up to RFIs #48 and #49, and to ensure that we fully understand the flooring on the ground floor, please review the following questions in conjunction with the attached overlay of existing and proposed plans:
a.Bedrooms G-83, G-84, G-85 and G-86 have VCT flooring that will remain, per RFI #31. Toilets G-83A, G-84A, G-85A and G-86A are to receive new RS-1 flooring and toilets are to remain in place with the new sheet flooring cut around. There will be some slab areas left exposed when existing toilet walls are demolished that will need to be patched (highlighted in green on the attached sheet). Please confirm that we are to patch these areas with VCT. Please also acknowledge that even if we are able to find the exact VCT as the original, it will be very apparent that the flooring has been patched.
b.At G-81, G-81A, G-82 and G81B, there will be areas of slab exposed after demolition of walls that will need to be patched. We think your intent is that these areas are to be patched with VCT that matches adjacent floor areas (highlighted in green on the attached sheet). Please confirm. Please also acknowledge that even if we are able to find the exact VCT as the original, it will be very apparent that the flooring has been patched.
c.At G-77, the new floor finish will be epoxy. Should the epoxy extend under the door (highlighted in orange on the attached sheet)? If so, please acknowledge that the new epoxy will be visible in the corridor when the door is closed.

Answer:

a. Confirmed and acknowledge; however, the contractor shall make every reasonable attempt to match existing materials in all respects.

b. Confirmed and acknowledge; however, the contractor shall make every reasonable attempt to match existing materials in all respects.

c. Transition between finish materials under the center of the closed door. Match existing on the corridor side.

Question# 70 Will nurse call systems drawings be provided?

Answer: The bidder shall refer to “New Nurse Call Legend” on Drawing 31-E-601, “Navicare Nurse Call Schedule” on Drawing 31-E-607, and the various Power & Signal distribution plans including but not necessarily limited to enlarged room details on Drawings 31-EP-411 and 31-EP-412. No additional drawings shall be provided beyond those already included in the bidding documents. The successful nurse call bidder shall prepare fully detailed design & installation shop drawings and equipment catalogue and review the same with the Owner to confirm all aspects of the design.

Question# 71 What are the floor-to-floor elevations between Ground, Basement, First, Second and Roof? If you have a section through the building in the original drawings, that would be helpful.

Answer: PDFs of the original building exterior elevations and building sections are attached, 3 drawings total (Bldg 31 Exterior Elevations & Building Sections). Also refer to the original building structural drawings included in the bid documents.

Question# 72 For the exterior windows, please specify the following: Winter U value, visible light transmittance, solar heat gain coefficient and center-of-glass U value for the system.

Answer: Provide 1-inch insulated glass units with performance characteristics equal to or better than Vitro Architectural Glass, SolarBan 60 (2) Clear+Clear, Low E, Argon Filled. See also specification section 085113.2.1.E.

Question# 73 What are the floor-to-floor elevations between Ground, Basement, First, Second and Roof? If you have a section through the building in the original drawings, that would be helpful.

Answer: PDFs of the original building exterior elevations and building sections are attached, 3 drawings total. Also refer to the original building structural drawings included in the bid documents.

Question# 74 We have called and emailed the two contacts for Sure Hands and not received any response. Please provide a responsive contact.

Answer: The contacts have been notified that they need to respond in a timely manner.

Question# 75 Could you please clarify the quantities of sinks with undercoating. The provided asbestos drawings identify 77 sinks throughout the workspace with coatings, but the asbestos specifications calls out only 19. Could we clarify which is the correct quantity?

Answer: The bidders shall refer to the updated Abatement Diagrams. These include drawings 31-AS-105 Basement, 31-AS-105A Ground Floor, and 31-AS-105B First Floor, all being Revsion-1 dated 02/07/2023.

Question# 76 The BSASI Rep stated they will be including pricing for replacing and upgrading a number of existing cameras in their proposal. We do not find a requirement for this scope of work in the documents provided. When asked about this the BSASI Rep stated it was set forth by VAPD when they were originally assisting in designing the scope. Please clarify if these should be included in our proposal?

Answer: The replacement cameras and associated cabling shall be furnished and installed by BSA Security Integrators through the general contractor and the costs shall be carried by the general contractor as part of the contract for construction. No change to the head-end network equipment is anticipated. Existing cameras and cabling shall be removed by the contractor and the Owner shall have the right of first refusal. The contractor shall itemize, package, label and deliver to the Owner’s place of storage any materials that the Owner chooses to keep. The contractor shall dispose of rejected materials at the least costly legal disposal site. All work shall proceed in a manner consistent with the project phasing to ensure that all occupied spaces are appropriately covered at all times.

Question# 77 Reference specification 098400 for “Acoustic Room Components”. We cannot find these items depicted on the drawings. Where do these occur?

Answer: Tackable wall panels are indicated on elevation 4 on drawing 31-AS-401 and elevations 2 & 7 on drawing 31-AS-409; however, pursuant to the Owner’s request please use Carnegie Xorel fabric in lieu of the specified material. Fabric Color to be selected by the Owner from the manufacturer’s standard product line. There are no other “acoustic room components”.

Question# 78 Reference VHA Supplemental Contract Requirements for Combatting COVID-19, section 1.a, subsections 1) and 2). Since we now know that even though a person may be vaccinated they can still contract and transmit the virus, is this supplemental requirement still applicable to this project?

Answer: VHA Supplemental Contract Requirements for Combatting COVID-19 are hereby removed from this contract. Contractors will be required to comply with station/facility requirements.

Question# 79 Regarding infection control, please confirm that this project is Construction Type D and specify whether the spaces are Group 1 – “Lowest Risk” or higher classification. Refer to specification 013533-1.2.B.

Answer: This project is confirmed Construction Type D. Renovation work within one-hour fire rated construction barriers as described in Section 010000, 1.9, D., 2. are considered Group 1-Lowest Risk. Work outside the construction barrier may have higher risk levels and will vary based on specific location and use of the nearby spaces by VA.

Question# 80 Please issue the sign in sheet from the additional site visit that was held on Tuesday, January 24, 2023.

Answer: Sign-in sheet from the site visit on 1/24/2023 is attached. There were no attendees.

ATTACHMENTS

See attached document: Building 31 Abatement Diagrams REV-1 02072023.

See attached document: Bldg 31 Exterior Elevations _ Building Sections.

See attached document: Pre-bid site visit sign-in 01-24-2023.