The specification requires cartridge fuses rated 600V ac and less for control circuits, panelboards, and enclosed switches, along with spare-fuse cabinets. All fuses must be NEMA FU 1 current-limiting, nonrenewable cartridge fuses with 200 kAIC rating and must be obtained from a single manufacturer for each specific product or circuit. Required fuse types include: Type RK-1 and RK-5 (250-V, zero to 600-A); Type CC (600-V, zero to 30-A, fast acting); Type CD (600-V, 31 to 60-A, fast acting); Type J (600-V, zero to 600-A, time delay); Type L (600-V, 601 to 6000-A, time delay); and Type T (250-V, zero to 1200-A, very fast acting). All electrical components must be listed and labeled per NFPA 70 by a qualified testing agency. Fuse applications are specified by circuit type: Class L fast acting for service entrance and feeders, Class RK1 time delay for motor and other branch circuits, Class L time delay for large motors (601-4000A), Class J high speed for power electronics, and Class CC time delay for control transformer circuits. Maintenance material submittals require spare fuses equal to 10 percent of installed quantity for each size and type, minimum three of each. The specification includes detailed action submittals requiring product data, ambient temperature adjustment information, current-limitation curves, time-current coordination curves in PDF format, coordination charts, and fuse sizing for elevator applications. The spare-fuse cabinet must be a wall-mounted steel unit with gray baked enamel finish, piano-hinged door, key-coded cam lock, and labeled "SPARE FUSES" with adequate capacity for 15 percent spare margin.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Federal Bureau of Prisons MCA, LLC
ELECTRICAL SERVICE UPGRADES BATON ROUGE, LOUISIANA
UNICOR, FPI March 20, 2026
SECTION 262813 – FUSES, PAGE 1 OF 4
TECHNICAL SPECIFICATIONS
SECTION 262813
FUSES
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Cartridge fuses rated 600 V ac and less for use in the following:
a. Control circuits.
b. Panelboards.
c. Enclosed switches.
2. Spare-fuse cabinets.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for spare-fuse cabinets. Include the following for each fuse type indicated:
1. Ambient Temperature Adjustment Information: If ratings of fuses have been adjusted to accommodate ambient temperatures, provide list of fuses with adjusted ratings.
a. For each fuse having adjusted ratings, include location of fuse, original fuse rating, local ambient temperature, and adjusted fuse rating.
b. Provide manufacturer's technical data on which ambient temperature adjustment calculations are based.
2. Dimensions and manufacturer's technical data on features, performance, electrical characteristics, and ratings.
3. Current-limitation curves for fuses with current-limiting characteristics.
4. Time-current coordination curves (average melt) and current-limitation curves
(instantaneous peak let-through current) for each type and rating of fuse. Submit in PDF format.
5. Coordination charts and tables and related data.
Federal Bureau of Prisons MCA, LLC
UNICOR, FPI March 20, 2026
SECTION 262813 – FUSES, PAGE 2 OF 4
6. Fuse sizes for elevator feeders and elevator disconnect switches.
1.4 CLOSEOUT SUBMITTALS
A. Operation and Maintenance Data: For fuses to include in emergency, operation, and maintenance manuals. In addition to items specified in Section 017823 "Operation and
Maintenance Data," include the following:
1. Ambient temperature adjustment information.
2. Current-limitation curves for fuses with current-limiting characteristics.
3. Time-current coordination curves (average melt) and current-limitation curves
(instantaneous peak let-through current) for each type and rating of fuse used on the
Project. Submit in PDF format.
4. Coordination charts and tables and related data.
1.5 MAINTENANCE MATERIAL SUBMITTALS
A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.
1. Fuses: Equal to 10 percent of quantity installed for each size and type, but no fewer than three of each size and type.
1.6 FIELD CONDITIONS
A. Where ambient temperature to which fuses are directly exposed is less than 40 deg F or more than 100 deg F, apply manufacturer's ambient temperature adjustment factors to fuse ratings.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Source Limitations: Obtain fuses, for use within a specific product or circuit, from single source from single manufacturer.
2.2 CARTRIDGE FUSES
A. Characteristics: NEMA FU 1, current-limiting, nonrenewable cartridge fuses with voltage ratings consistent with circuit voltages.
1. Type RK-1: 250-V, zero- to 600-A rating, 200 kAIC.
2. Type RK-5: 250-V, zero- to 600-A rating, 200 kAIC.
3. Type CC: 600-V, zero- to 30-A rating, 200 kAIC, fast acting.
4. Type CD: 600-V, 31- to 60-A rating, 200 kAIC, fast acting.
5. Type J: 600-V, zero- to 600-A rating, 200 kAIC, time delay.
Federal Bureau of Prisons MCA, LLC
UNICOR, FPI March 20, 2026
SECTION 262813 – FUSES, PAGE 3 OF 4
6. Type L: 600-V, 601- to 6000-A rating, 200 kAIC, time delay.
7. Type T: 250-V, zero- to 1200-A rating, 200 kAIC, very fast acting.
B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
C. Comply with NEMA FU 1 for cartridge fuses.
D. Comply with NFPA 70.
E. Coordinate fuse ratings with utilization equipment nameplate limitations of maximum fuse size and with system short-circuit current levels.
2.3 SPARE-FUSE CABINET
A. Characteristics: Wall-mounted steel unit with full-length, recessed piano-hinged door and key-coded cam lock and pull.
1. Size: Adequate for storage of spare fuses specified with 15 percent spare capacity minimum.
2. Finish: Gray, baked enamel.
3. Identification: "SPARE FUSES" in 1-1/2-inch-high letters on exterior of door.
4. Fuse Pullers: For each size of fuse, where applicable and available, from fuse manufacturer.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine fuses before installation. Reject fuses that are moisture damaged or physically damaged.
B. Examine holders to receive fuses for compliance with installation tolerances and other conditions affecting performance, such as rejection features.
C. Examine utilization equipment nameplates and installation instructions. Install fuses of sizes and with characteristics appropriate for each piece of equipment.
D. Evaluate ambient temperatures to determine if fuse rating adjustment factors must be applied to fuse ratings.
E. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 FUSE APPLICATIONS
A. Cartridge Fuses:
Federal Bureau of Prisons MCA, LLC
UNICOR, FPI March 20, 2026
SECTION 262813 – FUSES, PAGE 4 OF 4
1. Service Entrance: Class L, fast acting.
2. Feeders: Class L, fast acting.
3. Motor Branch Circuits: Class RK1, time delay.
4. Large Motor Branch (601-4000 A): Class L, time delay.
5. Power Electronics Circuits: Class J, high speed.
6. Other Branch Circuits: Class RK1, time delay.
7. Control Transformer Circuits: Class CC, time delay, control transformer duty.
8. Provide open-fuse indicator fuses or fuse covers with open fuse indication.
3.3 INSTALLATION
A. Install fuses in fusible devices. Arrange fuses so rating information is readable without removing fuse.
B. Install spare-fuse cabinet(s) in location shown on the Drawings or as indicated in the field by
Owner.
3.4 IDENTIFICATION
A. Install labels complying with requirements for identification specified in Section 260553
"Identification for Electrical Systems" and indicating fuse replacement information inside of door of each fused switch and adjacent to each fuse block, socket, and holder.